GE (AF) NO 2 JODHPUR
GE (AF) NO 2 JODHPUR
REPAIR /MAINT OF GI EARTHING/CHEMICAL EARTHING PITS, SURGE PROTECTION DEVICE, LIGHTING ARRESTER AND ALLIED WORKS AND REPAIR/REPLACEMENT OF STREET LIGHTS,SECURITY LIGHTS AND ALLIED WORKS AT AF STN MANDORE UNDER AGE E/M ,GE (AF) NO 2 JODHPUR
2021_MES_464983_1
8268/E8
Open Tender
Civil Works
Item Rate
270 days
GE (AF) NO 2 JODHPUR
AS PER TENDER
6 documents required · 6 mandatory
₹500
GE (AF) NO 2 JODHPUR
₹40,000
Yes
12 Oct 2021
3 Aug 2021
1 Sept 2021
3 Aug 2021
30 Aug 2021
18 Aug 2021
Amount
M&L for maintaining the copper earth pits/ chemical earth pits/GI earth pits by carrying out the following steps to keep the earth pits as desired value as and when given by Engineer-In-Charge. Note:- a) M&L for carrying out salt water treatment to existing earth pits for improvement of earth result in terms of bringing down the resistance,by pouring salt water solution manually by the following methods. (i) Preperation of magnisum sulphate ,salt and water solution in ratio of 1000 ltr water and 30 kg magnisum sulphate in a bulk suitable container with the arrangement of bib tap and PVC 15 mm dia hose pipe of suitable length. (ii) Cleaning of earth pit chamber and bell mouth of funnel and water pipe. (iii) Pouring of salt water solution after stirring in to the earth pit through funnel approx- 20 lts in earth pit consicutively for 3 days. (iv) Carrying out testing of earth and recording of satisfactory result. b) The testing of earth pits and recording their results in a seperate resister in a presentable manner in every month and writing the result on the board and summary board at every month as specified and directed by Engr-In-Charge.The rate quoted by the contractor shall deemed to be included in the item for the tools for testing earth ,water, Magnisium shulphate and stationaries for earth test register maintained by contractor (c) The Annual Maint of earthing shall be done for 09 Months of 80 earthings.
Taking out old unserviceable GI/aluminium/copper earth strip of any size and type in any height and any location as directed by Engineer In charge.
S&F in repairs galvanized iron strip of size 32 x6 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed.
S&F in repairs copper strip of size 32 x6 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed.
S&F in repairs copper strip of size 20 x3 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed.
M & L for Refixing of existing serviceable copper / aluminium / GI strip with procelain insulator, fixing screws, aluminium cleats etc.(Procelain insulator measured separetly)duly straightened properly as directed by Engineer in charge.
M&L for carrying out brazing to existing earthing strip joint in between earthpit to test point after removing the nut bolt ,scraping the strip,preparing the hole and fix new copper bolt and nut the surface all as specified by Engr-in-charge Note - length of brazing 75mm minimum for jointing of strip.
Material and labour in repairs for electric Welding of existing GI strip of any size, any height (on roof/ on wall) at various places complete all as specified and directed by Engr in Charge.
M& L for porcelin insulater fixing on wall for supporting the copper strip at distance 45 cm including nut bolt drilling hole etc complete all as specified and directed by Engineer-in-charge.
M & L in repairs for GI funnel and wire mesh for earth pits complete all as specified & directed by Engr in Charge.
Material and labour for Test point terminal block in repairs as made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified & directed by Engr in Charge.
Taking down old broken and damaged earth pit chamber and M & L for construction of new earth pit chamber of size 700 X 700 X 450 mm of PCC 1:2:4 Type B-1 all as specified and directed by Engineer-in-charge.
M & L for PCC 1:2:4 with 20 mm grade aggregate including demolation of existing foundation all as specified and as directed by Engineer in charge.
Takig down old unserviceable GI/Copper earth plate from soft and hard soil from any location as directed by Engineer in charge.
Material & Labour in repairs for Earthing complete with galvanised earth plate electrode 60cm x 60cm x 6 mm thickness burried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and incl galvanised iron strip 32 x 6 mm by means of nuts & bolts, check nuts and washers of brass incl PCC pit of 1:2:4 type B-1, cover reinforced with XPM weight not less than 4 Kg/Sqm and 6mm dia bar handle,earth pit angle iron frame of size 25x25x3mm, excavation and earth work in any type of soil, charcoal dust, salt, light grade GI watering pipe 20mm dia with funnel and wire -mesh and medium grade GI protection pipe of 40mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical plate no 3 of MES SSR Part I 2009 connected board all as specified and testing on completion.(Note:- GI protection pipe and earth lead more than 7.5 RM shall be measure and paid separately)
Material & Labour in repairs for Earthing complete with copper earth plate electrode 60cm x 60cm x 3.15mm thickness burried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and incl copper strip 20x3mm by means of nuts & bolts, check nuts and washers of brass incl PCC pit of 1:2:4 type B-1, cover reinforced with XPM weight not less than 4 Kg/Sqm and 6mm dia bar handle,earth pit angle iron frame of size 25x25x3mm, excavation and earth work in any type of soil, charcoal dust, salt, light grade GI watering pipe 20mm dia with funnel and wire -mesh and medium grade GI protection pipe of 40mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical plate no 3 of MES SSR Part I 2009 connected board all as specified and testing on completion.(Note:- GI protection pipe and earth lead more than 7.5 RM shall be measure and paid separately)
Material & Labour in repairs for Chemical Earthing complete with copper earth plate electrode 90cm x 60cm x 5mm thickness burried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and incl copper strip 32x6mm by means of nuts & bolts, check nuts and washers of brass made of copper and connected to test point and earth dolly al as shown in electrical plate no 3 SSR part I 2009 ans specified or indicating including providing charcoal dust 1000 kgs ,common salt 500 kgs ,magnisum sulphate 150 kgs and all around the plate 15CM depth RCC 50 mm thick in cement and wide upto 650mm height in continuous layer ,balance pit will be filled with vegaetable soil upto groundlevel including excavation and earth work in any type of soil PCC (1:3;6) type C1 in chamber ,precast concrete (1:2:4) type B1,reinforced with welded steel wire fabric or XPM weight not less than 4 Kg/Sqm with cast iron frame ,funnel with wire mesh 40 mm bore light grade GI watering pipe all as specified and testing on completion.(Note:- the earth resistance should be less than one ohms and GI protection pipe and earth lead more than 7.5 RM shall be measure and paid separately)
Takig down old unserviceable air termination single pointed aluminium rod of 12 mm dia and 300 mm long.
M/L air termination single pointed aluminium rod of 12 mm dia and 300 mm long.
Supply & fixing in repairs of earthing improving Black fill compound (Conductolite) of 25 Kgs bag for improving earthing result by excavation till middle of the earthing plate both side and filled with Black Fill Compound (Conductolite) ,filling mixture of salt and charcoal 0.2 cum and magnisum sulphate 70 kgs around the earth electrode refilling the agriculture soil form non defence land and fixing the pit and watering the level complete for any type of earth electrode/earth strip making good as per the existing one before execavation all complete as specified and as directed. Make : ASHLOK Black Fill compound (Conductolite). Note:- Excavation, re-filling soil, removal surplus soil for shall be measured and paid under relavent item of this schedule.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 3 m in depth for taking out for repairs of eathing pits and getting out in hard / dense soil complete all as specified and as directed by the Engineer - in - Charge.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in hard/dense soil complete all as specified and as directed by the Engineer - in - Charge.
Removal of excavated material [soil] to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed by the Engineer - in - Charge.
S & F GI pipe 40 mm dia grade to be fixed in PCC foundation all as specified and as directed by Engineer in charge.
Comprehensive periodic maintenance and repair including commisssioning and renewal/replacement of defective parts of all existing fire protection system complete consisting of main fire control panel,smoke/heat detector/response indicator, MCPs to make 100% serviceability, including checking of fire detector, cleaning of detector by removing dust or dirt, cleaning of heavy greasy deposit if any, checking the connection of batteries, specific gravity of electrolyte, the alarm function of control and indicating equipment be checked by the operation of trigger device in each zone of the system installed many bldgs including reprogramming with software by authorized Technical Engineer of OEM i.e. M/S L & T Electrical & Automation(schrack-seconet) to keep the system fully functional for 24 x 7 complete all as specified and directed by the Engineer-in-Charge.
Supply and fixing in repairs detectors complying with and type certified to EN-45 Addressable type multi sensor with heat and smoke combination, mounting base, complete all as specified and directed.
Supply & Fixing in repairs of cable 1100 volt grade, PVC insulated, FRLS 2C X 2.5Sq mm multistranded copper conductor , fixed on wall/ceiling complete all as specified and directed.
Supply and laying in repair of GI pipes medium grade with fitting laid in trenches/wall /ground surface complete for the 20 mm sizes for eathing pits water connection complete all as specified and as directed.
Supply and fixing in repairs addressable electronic sounder cum strobe complete all as specified and directed.
Supply and fixing in repairs addressable manual call point resattable type complete all as specified and directed.
Supply and fixing in repairs fire alarm sounders/sirens electronic type horizantal two stage continous normal operation atleast 50 minutes with sound level 65 db to 120 db measured at 1.5 m with sound output variation of + 5 db 500 m range complete all as specified and directed.
Taking out unserviceable street light/Flood light from the site of any/size complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 60 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 72 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 90 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 100 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED Flood light fitting of 120 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection of make CG cat No-LFLN-120-CDL/60-M complete all as specified and directed .
S&F and testing in replacement of energy efficient LED Flood light fitting of 150 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection of make CG cat No-LFLN-150-CDL/60-M complete all as specified and directed .
S&F and testing in replacement of energy efficient LED Flood light fitting of 200 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection of make CG cat No-LFLN-200-CDL/60-M complete all as specified and directed .
M&L for disconnecting electric connection and dismantling U/S LED driver form led light fittings and fixed new driver 45 watt complete all as specified and as directed.
M&L for disconnecting electric connection and dismantling U/S LED driver form led light fittings and fixed new driver 60 watt complete all as specified and as directed.
M&L for disconnecting electric connection and dismantling U/S LED driver form led light fittings and fixed new driver 70/72 watt complete all as specified and as directed.
M&L for disconnecting electric connection and dismantling U/S LED driver form led light fittings and fixed new driver 90/100 watt complete all as specified and as directed.
M&L for repair of mechanism of highmast and rewinding of three phase high mast tower motor 440 volt AC 1HP 1425 RPM if burnt and incl dismantling form highmast transportation to workshop for rewinding with existing size of super enamlled copper wire replacing of gear,bearing bush ,greashing varnishing etc for running of rope at satisfactory level and reinstalation complete all as specified and as directed.
M & L for PVC insulated copper conductor 4 sqmm 10 core complete all as specified and as directed.
Supply and fixing in replacement of high mast panel with complete copper wiring ,ML contractor 4 pole AC3 18Amp 9 KW -03 Nos ,Timer 32 Amp , TPN MCB 63 Amp with complete busbar and including taking down old panel complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCCB in replacement of 63 Amps, 3/4 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
Supply and fixing MCCB in replacement of 125Amps, 3/4 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
Supply and fixing MCCB in replacement of 160Amps, 3/4 pole, 415 volts, 50 HZ, rupturing capacity 36KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
S & F in repair GI Bracket for mounting street light fittings made out of light grade 32mm GI pipe and have angle of 120 degree incl fixing arrangement complete all as specified and as directed by engr-in-charge.
Supply and fix single core PVC insulated FR cable with multi stranded copper conductor 1.5 sq mm cross sectional area 3 core ,1100 volts grade all as specified and as directed.
Supply and fixing in replacement of automatic street light switch using Nature switch for automatic switching of street light based on LUX level of natural light. The sensor (nature switch) along with suitable power contactor , MCB and support terminals should be encloused in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC juction box (sintex make) conorming to IP 54. The contactor, MCB and copper circuit should suitable enough to take 3 phase load of 5 KW, contactor rating 25-32 Amps per phase, MCB SP rating of 32 Amps (03 Nos)
S&F in replacement Building Security LED 45 Watt fixture made of pressure die cast housing with toughened glass and high power LEDs with option of secondary optic with IP65 protection ,commercial building including connection complete all as specified and directed by Engineer in Charge. Make - Crompton model No-LSTS-45-CDL-M
M&L in replacement for MCB single pole 6 Amps, 240 V complete all as specified and as directed.
M&L in replacement for MCB single pole and neutral 20 Amps, 240 V.
Supplying, Laying, Jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 3.5 core 25 sqmm laid in duct/ pipe including all electrical connection with required lugs and nuts, bolts complete incl taking down old cable all as specified and directed by Engr-in-Charge.
Supplying, Laying, Jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 3.5 core 35 sqmm laid in duct/ pipe including all electrical connection with required lugs and nuts, bolts complete incl taking down old cable all as specified and directed by Engr-in-Charge.
M&L HERITAGE LED Post Ideal to lit up parks, garden ways and heritage sites 20 Watts complete all as directed by Engr-in -Charge Make :Crompton cat pat no -LPTH-20-CDL or eqult Havells/Bajaj
Material and labour for painting with two coats of synthetic enameled paint on LT PCC pole upto 1.5 mtr above the GL in alternatively black and white strap of 30 cm each after scrapping/removing the existing paint and the preparation the surface of PCC LT pole complete.
L C ASSOCIATES
J AND T Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .