Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | S Balbir Singh L-1₹2.9 CrAccepted-AOC | ₹2.9 Cr | L-1 | Accepted-AOC Accepted being L-1 |
| 2 | L-2₹3.1 Cr+₹15.1 L (5.18%)Rejected-Finance | ₹3.1 Cr+₹15.1 L (5.18%) | L-2 | Rejected-Finance Not being L-1 |
| 3 | L-3₹3.2 Cr+₹24.5 L (8.41%)Rejected-Finance H NO 19 6 243 1 NGO S COLONY SHIV NAGAR NORTH BIDAR 585401 | BIDAR | KARNATAKA | 585401 | ₹3.2 Cr+₹24.5 L (8.41%) | L-3 | Rejected-Finance Not being L-1 |
| 4 | L-4₹3.3 Cr+₹39.2 L (13.5%)Rejected-Finance | ₹3.3 Cr+₹39.2 L (13.5%) | L-4 | Rejected-Finance Not being L-1 |
Tender Value
₹2.7 Cr
EMD Value
₹3.5 L
Closing Date
3 Mar 2020, 6:00 pmClosed
CE AF BANGALORE
Chief Engineer AF Bangalore No. 2 DC Area MES Road Yeshwantpur Post Bangalore 560022
73_801433/E8 AUGMENTATION OF WATER SUPPLY ALONGWITH ALLIED FACILITIES AT AF STATION, BIDAR
2020_MES_312261_1
73_801433/E8
Open Tender
Civil Works
Lump-sum
365 days
BIDAR, KARNATAKA
AS PER NIT
12 documents required · 12 mandatory
₹2,000
Yes
GE AF BIDAR
₹3.5 L
Yes
CE AF BANGALORE
11 May 2020
6 Jan 2020
4 Mar 2020
7 Jan 2020
3 Mar 2020
12 Feb 2020
7 Jan 2020 - 16 Jan 2020
17 Jan 2020
Amount
REVISED BOQ UPLOADED ON 06 Feb 2020
NOTE: Schedule ‘A’ Part-I to VIII are under Ser No. 3.00 to 10.00 are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lumpsum price worked out by the contractor for “Building or Structures” as listed in Schedule ‘A’ Part–I
Lumpsum price worked out by the contractor for “Internal water supply” as listed in Schedule ‘A’ Part–II
Lumpsum price worked out by the contractor for “Internal Electrification” as listed in Schedule ‘A’ Part–III
Lumpsum price worked out by the contractor for “Sewage disposal” as listed in Schedule ‘A’ Part–IV
Lumpsum price worked out by the contractor for “Fencing" as listed in Schedule ‘A’ Part–V
Lumpsum price worked out by the contractor for “Road” as listed in Schedule ‘A’ Part–VI
Lumpsum price worked out by the contractor for “External water supply” as listed in Schedule ‘A’ Part–VII
Lumpsum price worked out by the contractor for “External Electrification” as listed in Schedule ‘A’ Part–VIII
Total of Prepriced portion
SCHEDULE `A' PART - IX -Fittings, fixtures and Miscellaneous items is not prepriced by MES. Bidder shall insert their rates in Green filed under Col-6.
INTERNAL WATER SUPPLY Angle cock, cast copper alloy, fancy type, chromium plated, screwed down, high pressure, screwed both ends for iron pipe and fixed of bore of pipe 15mm complete all as specified and as directed.
INTERNAL ELECTRIFICATION Modular socket, multi purpose, 2 / 3 pin, 6 Amps, complete all as specified and as directed.
Modular socket, multi purpose, 2-in-1, 3 pin, 6 / 16 Amps complete all as specified and as directed.
Ceiling fan, 1200mm sweep, and connecting including provision of three way PVC connectors, 0.5 sqmm flexible three core multistranded copper conductor cable from ceiling rose or connector to fan including earthing and fixing arrangements and writing MES No.20mm height with synthetic enamel paint black complete all as specified and as directed.
Note:- Make shall be of Havells ES 50 Premium (5 star rated) or equivalent of makes as listed here-in-after.
Exhaust fan, heavy duty, 300mm sweep, 1400 RPM, with louvers, conforming to IS-2312-1967, AC single phase, 240 Volts, 50 Hz and connecting including provision of three way PVC connectors, 1 sqmm flexible three core multistranded copper conductor cable from ceiling rose or connector to fan including earthing and fixing arrangements and writing MES No.20mm height with synthetic enamel paint black complete all as specified and as directed. Make shall be of Havells Turbo Force SP or equivalent of makes as listed here-in-after.
LED Batten luminaire with and including tube / lamp, surface and wall mounted, 4 feet, isolated multistage CCCV driver, system wattage of 19/ 20 Watts, meets LED IS specifications, Class-1, SDCM<5, short circuit and over circuit protection, driver efficiency >85%, temperature range 0 to 50 degree centigrade, Safety Extra Low Voltage Safe level<60V DC as per IS-10322/IEC-60598 standard and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting with the following parameters,complete all as specified and as directed.
(a) Make:- Philips Cat No. BN021C LED 20S PSU CDL GR/Wipro TRIM NEO LL20-221-xxx65NE-3/ Havells No-ENDURALINEAR-NEO BS20W LED840 SPC WH or equivalent of makes as listed here-in-after.
(b) For all other mandatory requirements of LED fittings, please refer PS Clause No.51.5 on Sl Page No.193
LED security light fitting 20 W, high efficient with pressure die cast LM6 aluminium housing and has peanut lens optics specially designed for street lighting polycarbonate cover, giving a system efficiency at luminaire level of 100 lumens per watt with a life class of 50000 burning hours at L70, colour temperature is around 5700 k, the luminaire is IP-66 protected and an electronic driver of efficiency >85% compliant to IEC safety standards with a voltage variation range of 150 - 270 Volts, power factor > 0.95, THD < 20%, high and low protection alongwith surge protection of 3 KV including provision of necessary GI tubing medium grade 25mm bore of pipe 1.5 bent to shape with necessary clamps made out of mild steel, nuts and bolts etc., including two coats of synthetic enamel paint over a coat of red oxide primer on exposed steel surface for fixing the fitting to steel tubular poles etc complete all as specified and as directed.
(a) Make: Philips Cat No. BRP022 LED 20 CW MR S1 PSU GR/Crompton-LST-20-CDL/Havells-ENDURA PEARLS L20W LED757-SASYTOPC or equivalent of makes as listed here-in-after.
(b) For all other mandatory requirements of LED fittings, please refer PS Clause No.51.5 on Sl Page No.193
Recess mounted downlighter round with die-cast aluminium housing, voltage range 120-270 V, system wattage of 10 Watts, meets LED IS specifications, Class-1, SDCM<5, short circuit and over circuit protection, surge protection of 1.5 kW and including connecting up with including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire with the following parameters complete all as specified and as directed.
(a) Make: Philips Cat No. BBS170 1XDLED-5000 PSU WH/Wipro-LD71-111-SMS-65-xx/Havells-INTEGRAGRANDDLR 10W LED 830S or equivalent of makes as listed here-in-after.
(b) For all other mandatory requirements of LED fittings, please refer PS Clause No.51.5 on Sl Page No.193
MCB DB SPN 8 way, horizontal, double door, powder coated, 240 volts, AC, 50Hz, IP 43 protected, with provision for MCB SPN as incomer and DP / SP MCBs as outgoing with tinned copper bus bar, neutral link, earth link and connecting up complete all as specified and as directed.
MCB 6-32 Amps, SP, 240 Volts, 50 Hz, AC supply, "C" curve, with breaking capacity of 10 kA complete all as specified and as directed.
MCB 6-32 Amps, SPN, 240 Volts, 50 Hz, AC supply, "C" curve with breaking capacity of 10 kA complete all as specified and as directed.
SEWAGE DISPOSAL Pre-cast cement concrete block masonry with grade 'C' solid blocks exceeding 10cm in width having minimum compressive strength of 50 Kg/Sqcm as per IS 2185 (Part-I) 2005 and set in CM 1:4 complete all as specified and as directed.
Ductile iron pipe, of 100mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-7" class including push on joints with EPDM gaskets of standard length laid in trenches, and tested complete all as specified and as directed.
Note:- DI specials and Earthwork as required shall be measured and paid separately under relevant items.
Ductile iron pipe, of 100mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-7" class including push on joints with EPDM gaskets of standard length and fixed complete to walls and ceilings or laid in floors of bore of pipe complete all as specified and as directed.
Note:- DI specials and Earthwork as required shall be measured and paid separately under relevant items.
Ductile iron pipe, of 150mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-7" class including push on joints with EPDM gaskets of standard length laid in trenches, and tested complete all as specified and as directed.
Note:- Earthwork as required shall be measured and paid separately.
Ductile iron pipe, of 150mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-7" class including push on joints with EPDM gaskets of standard length and fixed complete to walls and ceilings or laid in floors of bore of pipe complete all as specified and as directed.
Note:- DI specials as required shall be measured and paid separately under relevant items.
Ductile iron pipe, of 200mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-9" class including push on joints with EPDM gaskets of standard length laid in trenches, and tested complete all as specified and as directed.
Note:- DI specials and Earthwork as required shall be measured and paid separately under relevant items.
Ductile iron pipe, of 200mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-9" class including push on joints with EPDM gaskets of standard length and fixed complete to walls and ceilings or laid in floors of bore of pipe complete all as specified and as directed.
Note:- DI specials as required shall be measured and paid separately under relevant items.
Ductile iron pipe, of 250mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-9" class including push on joints with EPDM gaskets of standard length laid in trenches, and tested complete all as specified and as directed.
Note:- DI specials and Earthwork as required shall be measured and paid separately under relevant items.
Ductile iron pipe, of 250mm nominal diameter, centrifugally cast (spun), ISI marked, spigot and socket joints of "K-9" class including push on joints with EPDM gaskets of standard length and fixed complete to walls and ceilings or laid in floors of bore of pipe complete all as specified and as directed.
Note:- DI specials as required shall be measured and paid separately under relevant items.
Ductile iron specials i.e bends (any type,radius and angle), tapers any type (straight, bend, increasing, decreasing or double socket etc), tee pieces, single branch, "Y" junction, double branch, tail piece, cross (all socket and spigot), collars, caps and plugs upto 300mm dia as required for laying pipes complete all as specified and as directed.
Cast iron air valves, flanged type with necessary gasket and nut bolts with double air outlets 100mm dia bore and fixing up in cast iron water supply mains conforming to IS-14845, complete all as specified and as directed. NOTE: DI specials as required shall be measured and paid separately under relevant items.
Cast iron air valves, flanged type with necessary gasket and nut bolts with double air outlets 50mm dia bore and fixing up in cast iron water supply mains conforming to IS-14845, complete all as specified and as directed. NOTE: DI specials as required shall be measured and paid separately under relevant items.
Cast iron Sluice valve, of class PN 1.6, both ends flanged conforming to IS-14846, with iron wheel head, brass spindle, bolts and nuts, making new flanged joints with 3mm thick rubber gaskets and fixed for bore of pipe 250mm complete all as specified and as directed
Cast iron Non-return valve, (Reflex valve) both ends flanged, of class PN 1.6, with necessary fixing arrangements such as fasteners, making new flanged joints with 3mm thick rubber gaskets, hinges, pins, ring, bolts and nuts etc and fixed for bore of pipe 100mm complete all as specified and as directed
Cast iron foot valve, including fittings such as flanges, leather washer, necessary fixing arrangements such as fasteners of suitable size such as nuts, bolts and washers, rubber packing / joining materials, etc and fixed for bore of pipe 100mm complete all as specified and as directed
Construction of valve chamber of size 1100mm x 1100mm x 900mm (inner dimension), with 150mm thick PCC foundation 1:4:8 type D2, PCC block masonry 200mm thick built in CM 1:6, 15mm thick internal and external plaster in CM 1:4, external plaster to a depth of 150mm below ground level as also the valve chamber floor, MS sheet cover of size 800mm x 800mm, 3.00mm thick including flat iron framework of FI 25mm x 4mm alround the frame and diagonal bracing, base frame of angle iron 40mm x 40mm x 6mm, and 100mm thick PCC coping of 1:2:4, type B1, using 20mm graded aggregate with FI hinge, nuts, bolts, locking arrangement, handles etc, lock 7 lever of approved make with duplicate keys, and painting steel surfaces with one coat of red oxide primer and two coats of synthetic enamel black paint complete including necessary excavation in any type of strata and removal of surplus soil to a distance not exceeding 50m, complete all as specified and as directed.
Supply, installation, testing and commissioning including perfect aligning and proper levelling of surface pump electrically driven horizontal / vertical end suction centrifugal type, confirming to IS 12469.1988, with bronze impeller, bronze working parts and stainless steel shaft (EN-8) mounted on heavy duty bearing suitable for continuous operation of rated capacity for 440Volts, 3 phase, 50 Hz AC supply 30 m head, 2840 LPM discharge, 1450RPM, The pump set shall be coupled to electical motor with 'F' class insulation squirrel cage induction motor working 3 phase, 415 Volts, AC both pump and motor mounted on common base frame with suitable medium grade GI pipe for suction pipe, delivery pipe of required length alongwith rigid foundation, nuts, bolts with coupling guards and anti-vibration pads including suitable fully automatic star delta starter as per manufacturer approval including provn. of dial type pressure gauge with stopcock, priming funnel and all other accessories recommended by manufacturer complete all as specified and directed.
Supply, installation, testing and commissioning of three phase, 10 HP monoblock pump set, suction 80mm, delivery 65mm pump with Cast Iron impleller C-40 Shaft, TEFC motor, IP-44, F class insulation all as per manufacturer specification fixed on common base plate with suitable foundation bolts and nuts, grouted in and including PCC platformm 1:2:4, type B2, using 40mm graded stone aggregate, medium grade 80mm dia bore GI pipe for suction and 65mm dia bore GI pipe for delivery of required length duly flanged and jointed with gasket and nuts bolts etc. Suitable cast iron foot valve, non-return valve 65mm-01 No and heavy duty gate valve 65mm- 1 No including necessary fully automatic star delta starter as per manufaturer approval, suction pipe, foot valve and Non-return valve complete all as specified and directed.
Supply only CHLORINE TEST KIT with coloured sample and test tubes complete all as specified and directed.
Supply only PH TEST KIT with coloured sample (range 6.0 to 7.0) or phenol red (range 6.8 to 8.4) and test tubes complete all as specified and directed.
Supply only IRON TEST KIT and test tubes with necessary fitments and testing solution in rexine finish box complete all as specified and directed.
INTERNAL ELECTRIFICATION AND EXTERNAL ELECTRIFICATION Earthing complete with galvanised iron earth plate electrode 600mm X 600mm X 6mm thick, with and including earthing of 4mm dia GI wire protected by 15mm dia GI pipe light grade upto a length of 7.5m. The plate shall be buried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level, connected to earth lead as described here-in-before by means of bolts, nuts, washers and checknuts made out of galvanised iron or mild steel, earthing lead protected by as described here-in-before and connected to main switch board or main control board or electric pole all as shown on electrical plate No.3 of MES Sch Part-I including necessary earth work and excavation in any type of soil, plain cement concrete 1:3:6, type C1 chamber, reinforced cement concrete cover slab with locking arrangement and handle of 10mm dia MS round bars 450mm long, 1:2:4 type B1, 50mm thick with 8mm dia TMT bars at 140mm centre to centre both ways, GI pipe of bore 20mm medium grade for watering with funnel, wiremesh, salt, charcoal, lugs including testing complete all as specified and as directed.
Wiring with three runs of single core 16 sqmm FRLS PVC insulated multistranded copper conductor unsheathed cable, 1100 volts grade, conforming to IS-694, drawn through and including PVC flexible conduit with conduit accessories of suitable dia, necessary copper lugs, nuts, bolts and washers and connecting between outgoing starter and motor terminal box complete all as specified and as directed.
Note:- Three runs of 16 sqmm cable and one run of conduit will be measured as one length.
Wiring with 3 core 1.5 sqmm FRLS PVC insulated copper conductor sheathed cable, 1100 volts grade, conforming to IS-694, drawn through steel tubular pole and connecting with junction box and street light fittings complete all as specified and as directed.
Loop in-loop out junction box(street light box) with non metallic FRP junction box suitable of size 350mmx250mmx150mm with connector 4 way and including one MCB 6 Amps, 230V alongwith 2Nos'C' clamps and back clamp madeup of 20x3mm flat iron and fixing on pole with necessary nut bolts, washers 2 Nos cable gland, lugs as required complete all as specified and as directed. Make: Sintex model GSJB3525
Cable route indicator of PCC 1:2:4, type B1, using 20mm graded stone aggregate duly finished smooth including necessary formwork of size 350mm x 200mm x 200mm with slanting top duly embossed 'HT CABLE' or 'HT LOOP’ and placed on PCC foundation 1:4:8, type D2 using 40mm graded aggregate,150 mm thick and 100mm projecting all round the cable route indicator including necessary earthwork complete all as specified and as directed.
LED Street light fitting, energy saving and environment friendly, long life, 45 W, CRI >=80, CT >=5700 K, made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 65/66 protection and impact resistance not less than IK-07 complete with integrated type, high efficiency electronic driver, built-in surge supressor / SPD of 10 KV or more and high brightness LEDs, luminaire efficacy >110 lumen/Watt, power factor >/ 0.90, operating range - 140 to 270 V, 50 Hz complete including suitable medium grade GI pipe for fixing arrangement complete all as specified and as directed.
(a) Make: Crompton Greaves Freedom+ series Cat No. LSTS - 45 - CDL-I /Havells ENDURA PEARL NEO SL 45W LED 757 SASYTOPC/Wipro skyline LED LR-2-451-xxx-57-xx or equivalent of makes as listed here-in-after.
(b) For all other mandatory requirements of LED fittings, please refer PS Clause No.51.5 on Sl Page No.193
Earthing complete with galvanised iron earth plate electrode 600mm X 600mm X 6mm thick, with and including earthing of 32mm x 6mm GI strip protected by 40mm dia GI pipe light grade upto a length of 7.5m. The plate shall be buried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level, connected to earth lead as described here-in-before by means of bolts, nuts, washers and checknuts made out of galvanised iron or mild steel, earthing lead protected by as described here-in-before and connected to main switch board or main control board or electric pole all as shown on electrical plate No.3 of MES Sch Part-I including necessary earth work and excavation in any type of soil, plain cement concrete 1:3:6, type C1 chamber, reinforced cement concrete cover slab with locking arrangement and handle of 10mm dia MS round bars 450mm long, 1:2:4 type B1, 50mm thick with 8mm dia TMT bars at 140mm centre to centre both ways, GI pipe of bore 20mm medium grade for watering with funnel, wiremesh, salt, charcoal, lugs including testing complete all as specified and as directed.
Supply, install, testing and commissioning of advanced encapsulated compound based maintenance free, pipe-in-pipe technology Zinc & Allcy coated earthing system conforming to IS - 3043 ( Code of practice for Earthing ) with the help of Zinc coated (80-100 microns ) and Alloy coated ( 200 - 250 microns ) Gl pipes, one bag BFC (Back Fill Compound = Electrodite or any similar compound) incl required excavation & earthwork complete with the following nomenclatures and technical requirements.
(a) Nomenclatures
(i) MATERIAL Zinc & Alloy coated Gl pipes
(ii) LENGTH 2000 mm
(iii) DIA OF OUTER PIPE 76.20 mm
(iv) DIA OF INNER PIPE 41.90 mm
(v) THICKNESS OF OUTER PIPE 2.5 mm
(vi)THICKNESS OF INNER PIPE 3.2 mm
(vii) BFC One Bag ( 25 Kg Capacity )
(b) Notes:-
(i) All the above given dimensions may vary +/- 0.1mm.
(ii) The annular space between the Gl Pipes shall be filled up with crystalline conductive compound (CCC). It must be machine pressed in the pipes
(iii) BFC should be eco-friendly and must not contain environmentally hazardous material / metal and must have ROHS Certification from NABL accredited Lab. The quantity of BFC indicated above is generally for normal / good soils.In case the soil resistivity is high, the quantity of BFC shall be increased and cost of the same is deemed to be included in the unit rates quoted.
(iv) The rate quoted is also deemed to include for provision of concrete pit in PCC (1.3 6), type C1, using 20mm graded stone aggregate, precast cover slab of RCC 1:2:4, type B1, using 20mm graded stone aggregate of size 540mm x 540mm x 50mm thick with one handle for its lifting made out of 8 mm dia MS round bar and reinforced with 8mm dia TMT bars 150mm centre to centre bothways and also Gl strip 32 X 6 mm for connection or earthing with equipment to be earthed viz. Generator body / neutral etc.
Supply, install, test and commissioning of step down transformer outdoor type suitable for plinth mounting complete with standard accessories or fittings suitable for HT 11 kV/415 volts (at no load), AC, 3 phase, 50 cycles, 4 wire, capacity 100 kVA, double copper wound, oil immersed, C R GO core type, naturally cooled, built-up with class "A" insulation conforming to IS-1180 (Part-I) 2014 including amendments as on the date of receipt of tender with following requirements.
(a) Continuous rating : 100 kVA
(b) No load voltage ratio : 11kV / 415 V
(c) Tapping on HV : +2.5% to -5% in steps of 2.5% for variation of HV
(d) Phase and frequency : 3 Phase & 50 Hz
(e) Vector group : Dyn-11
(f) Cooling : ONAN
(g) Type : Outdoor
(h) Terminal arrangement :
(i) HV side : Quadfurcating cable box with 03 Nos bushing type terminals for connecting HT XLPE cable and 01 No for earthing.
(ii) LV side : Quadfurcating cable box with 05 Nos compression glands for PVC cable, 01 No additional neutral terminal will be brought out separately for earthing purpose.
(j) First filling of new and unused transformer oil conformimg to IS-335-1993 (fourth revision) shall be marked, filtered and tested upto 60 kV per minute instantaneous dielectric strength at 2.5mm air gap between testing electrodes.
(k) Fittings
(i) Externally Hand Operated Off - Circuit tap switch with position indicator and locking arrangement device.
(ii) Conservator with oil gauge, filling hole with plug and drain hole with plug.
(iii) Undercarriage with four plain rollers.
(iv) Oil - Filling hole cum air release plug.
(v) Drain valve cum sampling valve.
(vi) TOP Filter valve with plug.
(vii) Rating plate with diagram plate.
(viii) Lifting lugs for transformer.
(ix) Lifting lugs for core.
(x) Earthing terminals.
(xi) Thermometer Pockets.
(xii) Silica Breather.
(xiii) Explosion Vent.
(xiv) 150mm Oil temperature indicator.
(xv) 150mm Winding temperature indicator .
(xvii) OCTC(Off circuit Tap Changer)
Note: Cost of PCC foundation for transformer as per IE rules shall deemed to be included in the quoted rate. .
Design, fabrication, supply, installation, testing and commissioning of factory made feeder pillar box, outdoor type, of suitable dimension made up of CRCA sheet 3mm thick, with front and rear opening hinged door shutters, four side slanting roof duly projected, with locking arrangement, weather, dust and vermin proof, epoxy powder coated, to minimum IP-55 protection class of IS-2147, pedestal mounted, LT 500 volts, 3 Phase, 4 wire, 50 cycles, including cable galleries, interconnecting bus-bar connection / linkage, suitable for housing and including provision of the following switch gears including all pre-wiring with PVC copper conductor cable of suitable size, nuts, bolts and washers and in accordance with IS-13947 (Part-I) 1993 & IS-8623 and all as specified and directed by Engineer-in-Charge.
(a) Copper bus bar with rating 200 Amps 3 phase and neutral with PVC insulat sleeves with standard colour code duly mounted on bakelike / DMC insulators with terminal switch - 01 Set
(b) MCCB 4 pole, 415 Volts, 200 Amps, 35 kA - 01 No (Incoming)
(e) LED type pilot indicator lamps RYB phases with backup fuse, Set of three - 01 No.(Incoming)
(f) CT (100/5A) - 01 Set of 03 (Incoming)
(g) MCCB 4 pole, 415 Volts, 100 Amps, 25 kA - 03 Nos (Outgoing)
(h) MCB SPN, 240 Volts, (0-32 Amps), 10 kA - 03 Nos (Outgoing)
(j) Timer switches 20 Amps, 230 Volts, single phase - 01 No for street light (Outgoing)
(k) Change over switch 200 Amps - 01 No
(l) The LT panel board shall be mounted on angle iron framing 50mm x 50mm x 6mm and legs of 500mm length duly embedded in platform made out of PCC 1:3:6, type B1, using 25mm graded stone aggregate with a projection of 1m alround the means of panel board.
Note:- The design of the feeder pillar box shall be got approved from GE.
Supply, install, testing and commissioning of silent type Diesel Engine Generating Set , water cooled, 415 Volts, 100 kVA, 3 Phase, 4 wire, 0.80 power factor, 50 Hz, 1500 RPM self excited, self regulated brushless AC generator installed including acoustic enclosure suitable for ambient condition of Bidar and conforming to condition under IS 4722, 10001 , 10002, 13364, BS 5514, 2613, 5000 and shall include alternator, diesel engine, AMF panel, relay panel and civil works complete complete all as specified and as directed.
Note:- For full details of description of items and specifications please refer under PS Clause No. 51.12 and 51.13 on Sl Page No.196 to 201. Bidders are advised to read the description alongwith particular specifications before inserting their rates.
Mr Madhusudhan Kotarki
ramesh construction co
M/s RL Pareek
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .