Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 CrAccepted-AOC UDAYAVANI BUILDING UDAYAVANI ROAD PRESS CORNER MANIPAL 576104 UDUPI D KARNATAKA | UDUPI | KARNATAKA | 576104 | ₹8.5 Cr Quoted ₹8.8 Cr | L1 | Accepted-AOC NOA ISSUED |
| 2 | L2₹9.3 Cr+₹51.3 L (5.84%)Rejected-AOC DOOR NO 5 155B KOTHARATHU BUILDING NEAR ALPHA PALIATIVE CARE VENGANELLUR CHEKKAKKARA THRISSUR KERALA 680586 | THRISSUR | KERALA | 680586 | ₹9.3 Cr+₹51.3 L (5.84%) | L2 | Rejected-AOC L2 BIDDER |
Tender Value
₹8.5 Cr
EMD Value
₹16.9 L
Closing Date
29 Feb 2024, 3:00 pmClosed
Deputy Chief Engineer, EC, Pbvr
O/o Deputy Chief Engineer, Electrical Circle, Perumbavoor
Development of Distribution infrastructure at Eranakulam District (Electrical Circle, Perumbavoor) of Kerala State under RDSS scheme for Construction/Reconductoring of HT and LT lines with ABC, covered conductor and Raccoon conductor.
2024_KSEB_644427_1
KSEB/EC-PBVR/RDSS4/23-24 dtd 12.01.2024
Open Tender
Electrical Works
Turn-key
365 days
Location details attached in tender document
Please refer Tender documents.
10 documents required · 10 mandatory
₹11,800
Yes
₹16.9 L
Yes
O/o Deputy Chief Engineer, Ele.Circle, Pbvr
1 Sept 2024
15 Jan 2024
4 Mar 2024
16 Jan 2024
29 Feb 2024
24 Jan 2024
23 Jan 2024
Replacement of old/frayed conductor-Reconductoring of 11kV OH line with HT ABC 3x150 + 1x120 sq.mm (Insulated Messenger)
Aerial Bunched Cable HT 3x150 + 1x120 sq.mm (Insulated Messenger)
Pole PSC 9 M
A pole 11 m
A pole 12 m
Anchoring /Dead end Clamp Assembly for HT AB Cables up to 150 sq.mm
Suspension Clamp Assembly for HT AB Cables up to 150 sq.mm
Stainless Steel Strap 20mmX0.7mm along with Stainless steel Buckles [20.5 mm x 1.5 mm; thickness 1.2 mm] as per requirement
MVT Kit For HT ABC- 1 set = 3 Nos
Heat Shrinkable Termination Kit (3 Nos) for 150 Sq.mm Three phase Aerial Bunched Cable
Channel cross arm GI 75 x 40 x 6mm 2.4 m with GI- Clamp Bolt & Nut with washers
Lightning Arrester 9 kV,10 KA (Station class) Composite Polymer Housing 1 set = 3 nos with LA Supporting plate GI of size 500x300x3MM
CROSS ARM GI CHANNEL 2 LINE (2 Line Channel Cross Arm) with Clamp, Bolt & Nut and washers
CROSS ARM GI CHANNEL 4 LINE (4 Line Channel Cross Arm) with Clamp Bolt & Nut and washers
Composite type polymeric PIN INSULATOR 415V
SHACKLE INSULATOR 415V (WITH STRAP BOLT& NUT)
GI Stay Set includes ( HT) 1. Stay Insulator Porcelain 11k V - 2 Nos 2. Anchor Plate 200 x 200 x 8 mm GI (HT Stay Plate GI) 3. STAY TIGHTNER HT 4. Stay Wire 7/8 (7/3.15mm) GI (HT Stay Wire) 5. Stay Rod (Anchor Rod) GI 20 mm dia (HT Stay Rod) 6. Helically formed Guy-Grip HT 7. Thimble GI 75 mm x 22 mm x 40 mm ,1.5 mm Thickness (For HT and LT) 8. Stay clamp (GI ) etc as required as per technical specification, approved drawings and scope of work.
G.I.WIRE. 4MM (8 SWG)
GI Pipe Earthing set includes 1. Pipe GI 40 mm dia - 2.5 m Length( Earth Pipe) 2. Earth Chamber (RCC) With RCC Covering Slab as per approved drawing. 3. Earth Connector 95 Sqmm 4. Crimping Socket Palm Type 50 Sq.mm -Al(Cable Lug) 5. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. etc as required as per technical specification, approved drawings and scope of work.
Bolt & Nut (GI ) with washers of various sizes as per requirement
RDSS sign Board as per approved spec
Provision for new ABC-New 11kV line using ABC 3x150 + 1x120 sqmm cable
Aerial Bunched Cable HT 3x150 + 1x120 sq.mm (Insulated Messenger)
Pole PSC 9 M
A pole 11 m
A pole 12 m
A pole 13 m
Anchoring /Dead end Clamp Assembly for HT AB Cables up to 150 sq.mm
Suspension Clamp Assembly for HT AB Cables up to 150 sq.mm
Stainless Steel Strap [20 mm x 0.7 mm] with adeqaute no. of Stainless steel Buckles [20.5 mm x 1.5 mm; thickness 1.2 mm]
MVT Kit For HT ABC- 1 set = 3 Nos
Heat Shrinkable Termination Kit (3 Nos) for 150 Sq.mm Three phase Aerial Bunched Cable
Channel cross arm GI 75 x 40 x 6mm 2.4 m with GI- Clamp Bolt & Nut with washers
Lightning Arrester 9 kV,10 KA (Station class) Composite Polymer Housing 1 set = 3 nos with LA Supporting plate GI of size 500x300x3MM
Air Break Switch (AB Switch) 11kV 400 A , Composite Polymer Housing
GI WIRE 6MM DIA 4 SWG
GI Stay Set includes 1. Stay Insulator Porcelain 11k V - 2 Nos 2. Anchor Plate 200 x 200 x 8 mm GI (HT Stay Plate GI) 3. STAY TIGHTNER HT 4. Stay Wire 7/8 (7/3.15mm) GI (HT Stay Wire) 5. Stay Rod (Anchor Rod) GI 20 mm dia (HT Stay Rod) 6. Helically formed Guy-Grip HT 7. Thimble GI 75 mm x 22 mm x 40 mm ,1.5 mm Thickness (For HT and LT) 8. Stay clamp (GI ) etc as required as per technical specification, approved drawings and scope of work.
G.I.WIRE. 4MM (8 SWG)
GI Pipe Earthing set includes 1. Pipe GI 40 mm dia - 2.5 m Length( Earth Pipe) 2. Earth Chamber (RCC) With RCC Covering Slab 3. Earth Connector 95 Sqmm 4. Crimping Socket Palm Type 50 Sq.mm -Al(Cable Lug) 5. Stainless Steel starp and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. etc as required as per technical specification, approved drawings and scope of work.
Bolt & Nut (GI ) with washers of various sizes as per requirement
RDSS Sign Board as per standard
Replacement of old/frayed conductor-Reconductoring of 11kV line with ACSR Raccoon
Conductor ACSR Racoon
Pole PSC 9 M
A pole 11 m
11 kV Composite Polymeric Disc Insulator with Hardware Fittings and GI Cleat etc.
11 kV COMPOSITE POLYMERIC PIN INSULATOR(with PIN)
11 kV V cross arm with GI Clamps, Bolt & Nuts with washers
Pole Top Bracket -F Type GI -11 kV
Knee bracing for HT Cantiliver cross arm
Channel cross arm GI 75x40x6mm 1.8M- with GI- Clamp Bolt & Nut with washers
Air Break Switch (AB Switch) 11kV 400 A , Composite Polymer Housing
GI WIRE 6MM DIA 4 SWG
Channel cross arm GI 75 x 40 x 6mm 2.4 m with GI- Clamp Bolt & Nut with washers
LT 2 pin channel cross arm with GI- Clamp Bolt & Nut with washers
LT 4 pin channel cross arm with GI- Clamp Bolt & Nut with washers
Composite type polymeric PIN INSULATOR 415V (withPIN)
SHACKLE INSULATOR 415V (WITH STRAP BOLT&NUT)
GI Stay Set includes ( HT) 1. Stay Insulator Porcelain 11k V - 2 Nos 2. Anchor Plate 200 x 200 x 8 mm GI (HT Stay Plate GI) 3. STAY TIGHTNER HT 4. Stay Wire 7/8 (7/3.15mm) GI (HT Stay Wire) 5. Stay Rod (Anchor Rod) GI 20 mm dia (HT Stay Rod) 6. Helically formed Guy-Grip HT 7. Thimble GI 75 mm x 22 mm x 40 mm ,1.5 mm Thickness (For HT and LT) 8. Stay clamp (GI ) etc as required as per technical specification, approved drawings and scope of work.
GI WIRE (4 mm DIA 8 SWG)
GI Pipe Earthing set includes 1. Pipe GI 40 mm dia - 2.5 m Length( Earth Pipe) 2. Earth Chamber (RCC) With RCC Covering Slab as per approved drawing. 3. Earth Connector 95 Sqmm 4. Crimping Socket Palm Type 50 Sq.mm -Al(Cable Lug) 5. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. etc as required as per technical specification, approved drawings and scope of work.
Coil Earth set includes 1. Earthing Coil GI 115 Turns 50 mm internal Dia 2. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. 3. Ferrules 5 SQ.MM - GI etc as required as per technical specification, approved drawings and scope of work.
Bolt & Nut (GI ) with washers of various sizes as per requirement
RDSS sign Board as per approved spec
Replacement of old/frayed conductor-Reconductoring of 11kV line using AAAC 99 sqmm Covered conductor
Covered conductor HT AAAC 99 sqmm conforming to EN 50397 - 1 2020
PSC Pole 9m
A pole 11 m
11 kV COMPOSITE POLYMERIC PIN INSULATOR
11 kV V cross arm with GI clamps Bolt & Nut with washers
Pole Top Bracket -F Type GI -11 kV
Disc insulator 11 kV composite polymeric
Hardware fittings ( Tension clamp assembly) for HT covered conductor suitable for 99 Sqmm
Mid span joint set for HT covered conductor suitable for 99 Sqmm - 1 set = 3 nos
Single core outdoor termination kit for HT covered conductor suitable for 99 Sqmm 1 set = 3 nos
Insulated piercing connector set for covered conductor HTsuitable for 99 Sqmm ( Bare to Covered conductor & Covered conductor to Covered conductor)
Helical UV plastic tie
Lightning Arrester 9 kV,10 KA (Station class) Composite Polymer Housing 1 set = 3 nos with LA Supporting plate GI of size 500x300x3MM
Channel cross arm GI 75x40x6mm 1.8M- with GI- Clamp Bolt & Nut with washers
CROSS ARM GI CHANNEL 2 LINE (2 Line Channel Cross Arm) with Clamp, Bolt & Nut and washers
CROSS ARM GI CHANNEL 4 LINE (4 Line Channel Cross Arm) with Clamp Bolt & Nut and washers
G.I.WIRE. 4MM (8 SWG)
GI Pipe Earthing set includes 1. Pipe GI 40 mm dia - 2.5 m Length( Earth Pipe) 2. Earth Chamber (RCC) With RCC Covering Slab 3. Earth Connector 95 Sqmm 4. Crimping Socket Palm Type 50 Sq.mm -Al(Cable Lug) 5. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. etc as required as per technical specification, approved drawings and scope of work.
Coil Earth set includes 1. Earthing Coil GI 115 Turns 50 mm internal Dia 2. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. 3. Ferrules 5 Sq.mm - GI etc as required as per technical specification, approved drawings and scope of work.
GI Stay Set includes ( HT) 1. Stay Insulator Porcelain 11k V - 2 Nos 2. Anchor Plate 200 x 200 x 8 mm GI (HT Stay Plate GI) 3. STAY TIGHTNER HT 4. Stay Wire 7/8 (7/3.15mm) GI (HT Stay Wire) 5. Stay Rod (Anchor Rod) GI 20 mm dia (HT Stay Rod) 6. Helically formed Guy-Grip HT 7. Thimble GI 75 mm x 22 mm x 40 mm ,1.5 mm Thickness (For HT and LT) 8. Stay clamp (GI ) etc as required as per technical specification, approved drawings and scope of work.
Bolt & Nut (GI ) with washers of various sizes as per requirement
RDSS sign Board as per approved spec
Replacement of old/frayed conductors Reconductoring of LT Line with ABC 3x95+1x70+1x16 sqmm with insulated messenger
Aerial Bunched Cable LT 3x95 + 1x70 + 1x16 sq.mm (Insulated Messenger)
Pole PSC 8 M
Pole PSC 9 M
A Pole 11 M
Suspension Clamp Assembly suitable for insulated messenger of sizes 70 sq.mm, 50 sqmm & 35 Sqmm.
Anchoring /Dead end Clamp Assembly suitable for insulated messenger of sizes 70 sq.mm, 50 sqmm & 35 Sqmm.
Stainless Steel Strap 20mmX0.7mm along with Stainless steel Buckles [20.5 mm x 1.5 mm; thickness 1.2 mm] shall also be supplied as per requirement
Pre-insulated Bi metallic lug for 95 sqmm with brass nut and bolt
Pre-insulated Bi metallic lug for 70 Sqmm with brass nut and bolt
Pre-insulated Bi metallic lug for 50 Sqmm with brass nut and bolt
Pre-insulated Bi metallic lug for 16 Sqmm with brass nut and bolt
1.1 kV 1C X 25 sqmm unarmoured PVC Al Cable
Distribution Box for service connection
Satellite connector for service connection Main:16sqmm to 95sqmm,Tap:2.5 sqmm to 35sqmm(4 way)
Insulation Piercing Connector ( IPC Connector): For ABC to Distribution box & other service connection Main 16 sq mm to 95 sq mm; Tap 4 sq.mm to 35 sq.mm
Insulation Piercing Connector (IPC Connector): For ABC to ABC/Bare Main 16 sq mm to 95 sq mm; Tap 16 sq.mm to 95 sq.mm
Insulation Piercing Connector ( IPC Connector): For ABC to service connection/street light/Earthing Main 16 sq mm to 95 sq mm; Tap 1.5 sq.mm to 10 sq.mm
11 kV Composite Polymeric Disc Insulator with Hardware Fittings and GI Cleat etc.
11 kV COMPOSITE POLYMERIC PIN INSULATOR
11 kV V cross arm with GI Clamps, Bolt & Nuts with washers
Pole Top Bracket -F Type GI -11 kV
Channel cross arm GI 75x40x6mm 1.8M- with GI- Clamp Bolt & Nut with washers
GI Stay Set includes (LT) 1. Stay Insulator Porcelain 11 k V - 1 No 2. Anchor Plate 200 x 200 x 6 mm GI (LT Stay Plate GI) 3. STAY TIGHTNER LT 4. Stay Wire 7/8 (7/3.15mm) GI (HT Stay Wire) 5. Stay Rod (Anchor Rod) GI 16 mm dia (LT Stay Rod) 6. Helically formed Guy-Grip LT 7. Thimble GI 75 mm x 22 mm x 40 mm ,1.5 mm Thickness (For HT and LT) 8. Stay clamp (GI ) etc as required as per technical specification, approved drawings and scope of work.
GI Stay Set includes ( HT) 1. Stay Insulator Porcelain 11 k V - 2 Nos 2. Anchor Plate 200 x 200 x 8 mm GI (HT Stay Plate GI) 3. STAY TIGHTNER HT 4. Stay Wire 7/8 (7/3.15mm) GI (HT Stay Wire) 5. Stay Rod (Anchor Rod) GI 20 mm dia (HT Stay Rod) 6. Helically formed Guy-Grip LT 7. Thimble GI 75 mm x 22 mm x 40 mm ,1.5 mm Thickness (For HT and LT) 8. Stay clamp (GI ) etc as required as per technical specification, approved drawings and scope of work.
G.I.WIRE. 4MM (8 SWG)
Coil Earth set includes 1. Earthing Coil GI 115 Turns 50 mm internal Dia 2. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. 3. Ferrules 5 SQ.MM - GI etc as required as per technical specification, approved drawings and scope of work.
GI Pipe Earthing set includes 1. Pipe GI 40 mm dia -2.5 m Length( Earth Pipe) 2. Earth Chamber (RCC) With RCC Covering Slab 3. Earth Connector 95 Sqmm 4. Crimping Socket Palm Type 50 Sq.mm -Al(Cable Lug) 5. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. etc as required as per technical specification, approved drawings and scope of work.
RDSS Sign Board as per approved spec
Conversion of LT Sph line to 3 Ph line with ABC using 3x95+1x70+1x16sqmm (insulated messenger)
Aerial Bunched Cable LT 3x95 + 1x70 + 1x16 sq.mm (Insulated Messenger)
Pole PSC 8 M
Pole PSC 9 M
A Pole 11 M
Suspension Clamp Assembly suitable for insulated messenger of sizes 70 sq.mm, 50 sqmm & 35 Sqmm.
Anchoring /Dead end Clamp Assembly suitable for insulated messenger of sizes 70 sq.mm, 50 sqmm & 35 Sqmm.
Stainless Steel Strap 20mmX0.7mm along with Stainless steel Buckles [20.5 mm x 1.5 mm; thickness 1.2 mm] shall also be supplied as per requirement
Pre-insulated Bi metallic lug for 95 sqmm with brass bolt & nut
Pre-insulated Bi metallic lug for 70 Sqmm with brass bolt & nut
Pre-insulated Bi metallic lug for 16 Sqmm with brass bolt & nut
1.1 kV 1C X 25 sqmm unarmoured PVC Al Cable
Distribution Box for service connection
Satellite connector for service connection Main:16sqmm to 95sqmm,Tap:2.5 sqmm to 35sqmm(4 way)
Insulation Piercing Connector ( IPC Connector): For ABC to Distributio box & other service connection Main 16 sq mm to 95 sq mm; Tap 4 sq.mm to 35 sq.mm
Insulation Piercing Connector (IPC Connector): For ABC to ABC/Bare Main 16 sq mm to 95 sq mm; Tap 16 sq.mm to 95 sq.mm
Insulation Piercing Connector ( IPC Connector): For ABC to service connection/street light/Earthing Main 16 sq mm to 95 sq mm; Tap 1.5 sq.mm to 10 sq.mm
11 kV Composite Polymeric Disc Insulator with Hardware Fittings and GI Cleat etc.
11 kV COMPOSITE POLYMERIC PIN INSULATOR
11 kV V cross arm with GI Clamps, Bolt & Nuts with washers
Pole Top Bracket -F Type GI -11 kV
GI Stay Set includes ( LT) 1. Stay Insulator Porcelain 11 k V - 1 No 2. Anchor Plate 200 x 200 x 6 mm GI (LT Stay Plate GI) 3. STAY TIGHTNER LT 4. Stay Wire 7/8 (7/3.15mm) GI (HT Stay Wire) 5. Stay Rod (Anchor Rod) GI 16 mm dia (LT Stay Rod) 6. Helically formed Guy-Grip LT 7. Thimble GI 75 mm x 22 mm x 40 mm ,1.5 mm Thickness (For HT and LT) 8. Stay clamp (GI ) etc as required as per technical specification, approved drawings and scope of work.
G.I.WIRE. 4MM (8 SWG)
Coil Earth set includes 1. Earthing Coil GI 115 Turns 50 mm internal Dia 2. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. 3. Ferrules 5 SQ.MM - GI etc as required as per technical specification, approved drawings and scope of work.
GI Pipe Earthing set includes 1. Pipe GI 40 mm dia -2.5 m Length( Earth Pipe) 2. Earth Chamber (RCC) With RCC Covering Slab 3. Earth Connector 95 Sqmm 4. Crimping Socket Palm Type 50 Sq.mm -Al(Cable Lug) 5. Stainless Steel strap and Buckle Slot width 10.5 mm x 1.5 mm,Thickness 1.2 mm. etc as required as per technical specification, approved drawings and scope of work.
RDSS Sign Board as per approved spec
Description of Work / Item(s)
Replacement of old/frayed conductor-Reconductoring of 11kV OH line with HT ABC 3x150 + 1x120 sq.mm (Insulated Messenger)
Survey of line using GPS, route alignment and , preparation of survey report and uploading in the web portal after approval of project manager.
Insertion of one HT PSC pole in existing OH line including digging & backfilling pit in all classes of soil, fitting cross arm , insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing.
Insertion of one HT 'A' type pole in existing OH line including digging & backfilling pit in all classes of soil , fitting cross arm, insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing (excluding provision of earthing).
Providing concrete muffing for A pole of size 0.45x0.45x1.5m (0.5 m above GL and 1m below GL). Excavation 0.45x0.45x1m, concrete (1:3:6, 20mm) 0.45x0.45x1.5m, Plastering (1:3) 12mm 0.45x0.45mx5 sides
Fitting and providing one HT Stay for 11kV pole - excavation of stay pit in all classes of soil and back filling including erection of complete stay set along with with GI stay wire ( 7/3.15 mm dia), binding of stay wire, providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings etc. .
Dismantling (without damage) 11 kV line (Three conductors) /LT line including dismantling cross arm, insulators, disc, spacers, disconnecting jumper connection etc & disconnection of service connection where ever necessary and rolling the conductor and stacking the materials and then transporting safely to the KSEBL store and stacking the same with proper documentation as directed by KSEBL.
Stringing of 11 kV Aerial bunched cable of size 3 x 150 + 1 x 120 sqmm with insulated Messenger through existing poles/ newly inserted pole providing loop where ever necessay and tieing the cables using UV plastic tie -Heavy Duty of Length as per standard( including cost of plastic tie).The work also includes 1.Touching clearance where ever necessary 2. Erection of Anchoring clamp / suspension clamp 3. Installation of MVT and its terminal connections where ever necessary 4.Straightening of poles wherever necessary 5. Re erection of dismantled LT lines and all associated materials ( including street light fittings) / re connection of dismantled service connections whereever necessary etc
Doing one cable end termination on HT ABC of sizes Up to 3x150+1x120 sqmm
Erection of 11kV LA set ( 3 Nos) with supporting plates and giving all connections etc including cost of earth strip- GI ( 25 x 3mm) and its drawal.
Providing one Earth using GI earth pipe of size 40mm dia,2.5 m length including digging separate pit (0.45X0.45X2.5 m) at standard distance (1.5m) away from the pole/structure in all classes of soil and backfilling the pit with Bentonite powder and other accessories for improving earth resistance and providing earth chamber with covering slab complete.(includes the cost of adeqaute earth enhancing compound- Bentonite powder etc)
Provision for new ABC-New 11kV line using ABC 3x150 + 1x120 sqmm cable
Survey of line using GPS, route alignment and , preparation of survey report and uploading in the web portal after approval of project manager.
Fitting and erecting one HT PSC Single Pole in position, fitting cross arm if needed, digging and back filling pit in all classes of soil (as per standards), drawing sufficient length of GI earthing leads to the ground for earthing etc.(excluding provision of earthing)
Fitting and erecting one HT 'A' type Single Pole in position, fitting cross arm if needed, digging and back filling pit inall classes ofsoil (as per standards), drawing sufficient length of GI earthing leads to the ground for earthing (excluding provision of earthing)
Providing concrete muffing of size 0.45x0.45x1.5m (0.5 m above GL and 1m below GL). Excavation 0.45x0.45x1m, concrete (1:3:6, 20mm) 0.45x0.45x1.5m, Plastering (1:3) 12mm 0.45x0.45mx5 sides
Fitting and erecting one HT Double Pole Structure using PSC pole in position including fitting channel cross arms, digging and back filling pit in all classes of soil, drawing sufficient length of GI earthing leads through all cross arms to the ground for earthing (excluding provision of earthing).
Fitting and providing one HT Stay for 11kV pole - excavation of stay pit in all classes of soil and back filling including erection of complete stay set along with with GI stay wire ( 7/3.15 mm dia), binding of stay wire, providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings etc. .
Fitting and providing one HT Fly stay for 11kV pole using HT PSC pole, drawing sufficient length of GI earth leads to the ground for earthing including excavation of stay pit in all classes of soil and back filling, erection of complete stay set along with GI stay wire ( 7/3.15 mm dia), binding of stay wire, providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings etc. .
Fitting and providing one Strut using HT PSC pole using proper size of strut clamp ( GI) including digging and back filling pit in all classes of soil. The Cost includes cost of Strut clamp also.
Stringing of 11 kV Aerial bunched cable of size 3 x 150 + 1 x 120 sqmm with insulated Messenger through existing poles/ newly inserted pole providing loop where ever necessay and tieing the cables using UV plastic tie -Heavy Duty of Length as per standard ( including cost of plastic tie)). The work also includes 1. Touching clearance where ever necessary 2. Erection of Anchoring clamp / suspension clamp 3. Installation of MVT and its terminal connections where ever necessary 4. Pole numbering as per standards etc
Doing one cable end termination on HT ABC of sizes Up to 3x150+1x120 sqmm
Fitting one set AB switch on existing DP, giving connection and drawing sufficient length of GI earthing leads to the ground for earthing, excluding provision of earthing.
Erection of 11kV LA set ( 3 Nos) with supporting plates and giving all connections etc including cost of earth strip- GI ( 25 x 3mm) and its drawal.
Providing one Earth using GI earth pipe of size 40mm dia,2.5 m length including digging separate pit (0.45X0.45X2.5 m) at standard distance (1.5m) away from the pole/structure in all classes of soil and backfilling the pit with Bentonite powder and other accessories for improving earth resistance and providing earth chamber with covering slab complete.(includes the cost of adeqaute earth enhancing compound- Bentonite powder etc)
Replacement of old/frayed conductor-Reconductoring of 11kV line with ACSR Raccoon
Survey of line using GPS, route alignment and , preparation of survey report and uploading in the web portal after approval of project manager.
Insertion of one HT PSC pole in existing OH line including digging & backfilling pit in all classes of soil, fitting cross arm, insulators, binding etc, drawing sufficient length of GI earth leads to the ground for earthing.
Insertion of one HT 'A' type pole in existing OH line including digging & backfilling pit in all classes of soil , fitting cross arm, insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing.
Providing concrete muffing for A pole of size 0.45x0. 45x1.5m (0.5m above GL and 1m below GL). Excavation 0.45x0.45x1m, concrete (1:3:6, 20mm) 0.45x0.45x1.5m, Plastering (1:3) 12mm 0.45x0.45mx5sides
Fitting and erecting one HT Double Pole Structure using PSC pole in position including fitting channel cross arms, digging and back filling pit in all classes of soil, drawing sufficient length of GI earthing leads through all cross arms to the ground for earthing (excluding provision of earthing).
Fitting and providing one HT Stay for 11kV pole - excavation of stay pit in all classes of soil and back filling including erection of complete stay set along with with GI stay wire ( 7/3.15 mm dia), binding of stay wire, by providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings etc. .
Dismantling (without damage) 11 kV line (Three conductors) /LT line including dismantling cross arm, insulators, disc, spacers, disconnecting jumper connection etc & disconnection of service connection where ever necessary & rolling the conductor and stacking the materials and then transporting safely to the KSEBL store and stacking the same with proper documentation as directed by KSEBL.
Stringing of 11kV line with ACSR Raccoon (Three conductors) after fitting insulators (Hellically formed distribution top tie shall be used for binding conductor with pin insulators) , providing disc sets at cut points and giving jumper connections including touching clearance wherever necessary including cut point works. The work also included re erection of dismantled LT lines and all associated materials ( including street light fittings) / re connection of dismantled service connections where ever necessary. Straightening of poles wherever necessary shall also form part of the work.
Fitting one set AB switch on existing DP, giving connection and drawing sufficient length of GI earthing leads to the ground for earthing, excluding provision of earthing.
Providing one Earth using GI earth pipe of size 40mm dia, 2.5 m length including digging separate pit (0.45X0.45X2.5 m) at standard distance (1.5m) away from the pole/structure in all classes of soil and backfilling the pit with Bentonite powder and other accessories for improving earth resistance and providing earth chamber with covering slab complete.(includes the cost of adeqaute earth enhancing compound- Bentonite powder etc)
Providing one Coil Earth using No.8 GI-earth wire (50mm dia, 115 turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in ordinary soil & backfilling.
Fitting one Additional 75x40mm, 1.8m Channel cross arm in existing single pole incl. conveyance of materials.
Fitting one Additional 2.4m/3m Channel cross arm (100x50x6mm), in existing 11kV DP incl. conveyance of materials.
Replacement of old/frayed conductor-Reconductoring of 11kV line using AAAC 99 sqmm Covered conductor
Survey of line using GPS, route alignment and , preparation of survey report and uploading in the web portal after approval of project manager.
Insertion of one HT PSC pole in existing OH line including digging & backfilling pit in all classes of soil, fitting cross arm, insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing.
Insertion of one HT 'A' type pole in existing OH line including digging & backfilling pit in all classes of soil , fitting cross arm, insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing.
Providing concrete muffing for A pole of size 0.45x0. 45x1.5m (0.5m above GL and 1m below GL). Excavation 0.45x0.45x1m, concrete (1:3:6, 20mm) 0.45x0.45x1.5m, Plastering (1:3) 12mm 0.45x0.45mx5sides
Fitting and providing one HT Stay for 11kV pole - excavation of stay pit in all classes of soil and back filling including erection of complete stay set along with with GI stay wire ( 7/3.15 mm dia), binding of stay wire, by providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings etc. .
Fitting and providing one HT Fly stay for 11kV pole using HT PSC pole, drawing sufficient length of GI earth leads to the ground for earthing including excavation of stay pit in all classes of soil and back filling, erection of complete stay set along with GI stay wire ( 7/3.15 mm dia), binding of stay wire, providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings etc. .
Dismantling (without damage) 11 kV line (Three conductors) /LT line including dismantling cross arm, insulators, disc, spacers, disconnecting jumper connection etc & disconnection of service connection where ever necessary & rolling the conductor and stacking the materials and then transporting safely to the KSEBL store and stacking the same with proper documentation as directed by KSEBL.
Stringing of 11 kV line with Covered conductor HT 99 sqmm conforming to EN 50397 - 1 2020 (3 conductors) after fitting insulators, binding conductors to pin insulators using helical UV plastic tie suitable for any neck dia, fixing disc insulators and anchoring with anchoring clamps including cut point works.The works also includes 1. Touching clearance where ever necessary 2. Doing straight joint on HT covered conductor 99 Sqmm using the mid span jointing kit as per specification. 3. Doing one cable end termination on HT covered conductor 99 Sqmm using the cable jointing kit as per specification. 4. Re erection of dismantled LT lines and all associated materials ( including street light fittings) / re connection of dismantled service connections whereever necessary. 5. Straightening of poles wherever necessary. 6. Installation of Insulation piercing connector ( Bare to Covered conductor & Covered conductor to Covered conductor) for branching suitable for HT Covered conductor 99 Sqmm etc
Erection of 11kV LA set ( 3 Nos) with supporting plates and giving all connections etc including cost of earth strip - GI ( 25 x 3mm) and its drawal.
Providing one Coil Earth using No.8 GI-earth wire (50mm dia, 115 turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure all classes of soil& backfilling.
Providing one Earth using GI earth pipe of size 40mm dia,2.5 m length including digging separate pit (0.45X0.45X2.5 m) at standard distance (1.5m) away from the pole/structure in all classes of soil and backfilling the pit with Bentonite powder and other accessories for improving earth resistance and providing earth chamber with covering slab complete.(includes the cost of adeqaute earth enhancing compound- Bentonite powder etc)
Replacement of old/frayed conductors Reconductoring of LT Line with ABC 3x95+1x70+1x16 sqmm with insulated messenger
Survey of line using GPS, route alignment and , preparation of survey report and uploading in the web portal after approval of project manager.
Dismantling (without damage) 11 kV/LT - Single /three phase OH line conductor by dismantling cross arms, insulators, spacers , jumper connections etc and stacking the conductors in rolls properly including the conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL.The work also includes dismantling of branch circuit, service connection, street light etc
Single phase Two wire
Single phase Three wire
Three phase Four wire
Three phase Five wire
Insertion of one LT PSC pole in existing Single/three phase OH line including digging & back filling pit in all classes of soil, binding etc. drawing sufficient length of GI earth leads to the ground for earthing.
Insertion of one HT PSC pole in existing OH line including digging & backfilling pit in all classes of soil, fitting cross arm , insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing.
Insertion of one HT 'A' type pole in existing OH line including digging & backfilling pit in all classes of soil , fitting cross arm, insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing (excluding provision of earthing).
Providing concrete muffing for A pole of size 0.45x0.45x1.5m (0.5 m above GL and 1m below GL). Excavation 0.45x0.45x1m, concrete (1:3:6, 20mm) 0.45x0.45x1.5m, Plastering (1:3) 12mm 0.45x0.45mx5 sides
Renewal of existing damaged/old LT PSC/RCC/teak wood Pole with new PSC pole in place including excavation, erection of new pole, backfilling pit and refitting of all items etc . Conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL is also form part of the work.
Renewal of existing damaged/old 11kV PSC/RCC/ Teak wood Pole with new PSC pole in place including excavation, erection of new pole, backfilling pit and refitting of all items , drawing sufficient length of GI earth leads to the ground for earthing. etc complete including the conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL.
Erection of complete LT stay set along with excavation of stay pit in all classes of soil with GI stay wire ( 7/3.15 mm dia), binding of stay wire, providing guy stay insulator ( 1 No) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings and backfilling etc.
Renewal of existing damaged/old LT stay with complete stay set along with excavation of stay pit in all classes of soil with GI stay wire (7/3.15 mm dia), binding of stay wire, by providing guy stay insulator (1 No) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings & backfilling of pit, dismantling, refitting of all items in place including the conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL.
Fitting and providing one HT Stay for 11kV pole - excavation of stay pit in all classes of soil and back filling including erection of complete stay set along with with GI stay wire ( 7/3.15 mm dia), binding of stay wire, providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings etc. .
Renewal of existing damaged/old 11kV Stay with complete stay set along with excavation of stay pit in classes of soil with GI stay wire ( 7/3.15 mm dia), binding of stay wire, providing guy stay insulator ( 2 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings & backfilling of pit, dismantling, refitting of all items in place including the conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL.
Drawing, Testing and commissioning of LT AB cable. Stringing of 1.1 kV Aerial bunched cable with insulated Messenger through existing/renewed poles including erection of tension clamp for dead ends, suspension clamps , installation of IPCs of various types and satellite connectors where ever necessary. The work also includes the following 1. Touching clearance where ever necessary . 2. UV plastic tie for binding the conductors ( Including cost of plastic tie) 3. Providing end caps ( Including cost of end caps) 4. Installation of pre insulated mid span joints of sizes 16 sqmm, 35Sq.mm, 50 Sqmm,70 sqmm & 95 sqmm as per field requirement( Including cost of pre insulated mid span joints). 5. Reconnection of service connection, branch circuit lines, street light & re erection of dismantled 11kV lines where ever necessary 6. Straightening of poles where ever necessary. 7. Installation of pre insulated bi metallic lugs at transformer points & other fuse points etc.
3 x 95 + 1 x 70+1x 16 sqmm with insulated Messenger
Fitting of one No. pole top service connection box of standard size - up to 4 way (3 phase connection -4 Nos or 1 Ph connection - 12 Nos ) using ss strap/B&N of suitable size in to the PSC/A poles at the standard height including giving connections
Providing one Coil Earth using No.8 GI-earth wire (50mm dia, 115 turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in all classes soil & backfilling.
Providing one Earth using GI earth pipe of size 40mm dia,2.5 m length including digging separate pit (0.45X0.45X2.5 m) at standard distance (1.5m) away from the pole/structure in all classes of soil and backfilling the pit with Bentonite powder and other accessories for improving earth resistance and providing earth chamber with covering slab complete.(includes the cost of adeqaute earth enhancing compound- Bentonite powder etc)
Transferring of LT Threephase line to HT Poles
Conversion of LT Sph line to 3 Ph line with ABC using 3x95+1x70+1x16sqmm (insulated messenger)
Survey of line using GPS, route alignment and , preparation of survey report and uploading in the web portal after approval of project manager.
Dismantling (without damage) 11 kV/LT Single /three phase OH line conductor by dismantling cross arms, insulators, spacers, jumper connections etc and stacking the conductors in rolls properly including the conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL.The work also includes dismantling of branch circuit, service connection, street light etc
Single phase Two wire
Single phase Three wire
Insertion of one LT PSC pole in existing three phase OH line including digging & back filling pit in all classes of soil, binding etc. drawing sufficient length of GI earth leads to the ground for earthing.
Insertion of one HT PSC pole in existing OH line including digging & backfilling pit in all classes of soil, fitting cross arm , insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing.
Insertion of one HT 'A' type pole in existing OH line including digging & backfilling pit in all classes of soil , fitting cross arm, insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing (excluding provision of earthing).
Providing concrete muffing for A pole of size 0.45x0.45x1.5m (0.5 m above GL and 1m below GL). Excavation 0.45x0.45x1m, concrete (1:3:6, 20mm) 0.45x0.45x1.5m, Plastering (1:3) 12mm 0.45x0.45mx5 sides
Renewal of existing damaged/old LT PSC/RCC/teak wood Pole with new PSC pole in place including excavation, erection of new pole, backfilling pit and refitting of all items etc . Conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL is also form part of the work.
Renewal of existing damaged/old LT stay with complete stay set along with excavation of stay pit in all classes of soil with GI stay wire ( 7/3.15 mm dia), binding of stay wire, by providing guy stay insulator ( 1 No) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings & backfilling of pit, dismantling, refitting of all items in place including the conveyance of the taken back materials to KSEBL store and stacking the same with proper documentation as directed by KSEBL.
Erection of complete LT stay set along with excavation of stay pit in all classes of soil with GI stay wire ( 7/3.15 mm dia), binding of stay wire, by providing guy stay insulator ( 1 Nos) and .2 cum concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips ( 1:3:6) as per technical specification, approved drawings and backfilling etc.
Drawing, Testing and commissioning of LT AB cable. Stringing of 1.1 kV Aerial bunched cable with insulated Messenger through existing/renewed poles, erection of tension clamp for dead ends, suspension clamps , installation of IPCs of various types and satellite connectors where ever necessary. The work also includes the following 1. Touching clearance where ever necessary . 2. UV plastic tie for binding the conductors ( Including cost of plastic tie) 3. Providing end caps ( Including cost of end caps) 4. Installation of pre insulated mid span joints of sizes 16 sqmm, 35Sq.mm, 50 Sqmm,70 sqmm & 95 sqmm as per field requirement( Including cost of pre insulated mid span joints). 5. Reconnection of service connection, branch circuit lines, street light & re erection of dismantled 11kV lines where ever necessary 6. Straightening of poles where ever necessary. 7. Installation of pre insulated bi metallic lugs at transformer points & other fuse points etc.
3 x 95 + 1 x 70+1x 16 sqmm with insulated Messenger
Fitting of one No. pole top service connection box of standard size - up to 4 way (3 phase connection -4 Nos or 1 Ph connection - 12 Nos ) using ss strap/B&N of suitable size in to the PSC/A poles at the standard height including giving connections
Providing one Coil Earth using No.8 GI-earth wire (50mm dia, 115 turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in all classes soil & backfilling.
Providing one Earth using GI earth pipe of size 40mm dia,2.5 m length including digging separate pit (0.45X0.45X2.5 m) at standard distance (1.5m) away from the pole/structure in all classes of soil and backfilling the pit with Bentonite powder and other accessories for improving earth resistance and providing earth chamber with covering slab complete.(includes the cost of adeqaute earth enhancing compound- Bentonite powder etc)
Description of Work / Item(s)
Amount
TOTAL BOQ1 (Materials( Total Ex-work price of Materials + Total Transportation cost ) excluding GST.)
TOTAL BOQ2 (Installation / Erection Charges (Excluding GST)
TOTAL AMOUNT [1+2] (Excluding GST)
Discount offerred by Bidder(If any)
BOQ 3: TOTAL excluding GST [3 - 4]
Grand Total including GST (5+ GST Amount of BOQ1+GST Amount of BOQ2 )
ITHAL ENGINEERING GROUPS
Manipal Energy & Infratech Limited
ITHAL ENGINEERING GROUPS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .