Loading…
Loading…
Tender Value
₹39.5 Cr
EMD Value
₹39.5 L
Closing Date
24 Jul 2026, 6:30 pm
Similar tender results from the same govt authority in the past 3 years.
Vice President, (P), GUDC Ltd., Gandhinagar
Bavla UGD-II under SJMMSVY : Working Survey, Soil Investigation, Design and Construction of Underground Drainage Project with 14.00 MLD Sewerage Treatment Plant Work Including Providing, Supplying, Lowering Laying, Jointing, Testing & Commissioning of Rising Main and Gravity Main Pipes for Sewer Collecting System, Construction of Sewage Pumping Station (SPS), Supplying, Erecting, Testing & Commissioning of Pumping Machineries, Road Restoration, Electrical Work Etc. With Operation & Maintenance With All Allied Works for 02-[Two] Years for UGD work and 07-[Seven] Years for STP Including 03-[Three] Years Defect Liability Period For Bavla Under Ground Drainage with Sewerage Treatment Plant, Tal: - Bavla, Dist.: Ahmedabad, Gujarat” Under SJMMSVY
317301
GUDC/PROJECTS/SJMMSVY/UGD-II/Bavla UGD-II
Open
Civil Works
Gandhinagar
3 documents required · 3 mandatory
₹28,320
GUDC Ltd., Gandhinagar
₹39.5 L
24 Jun 2026
24 Jun 2026
24 Jun 2026
24 Jul 2026
24 Jun 2026
SUMMARY (SCHEDULE-B)
Schedule No. Name of work
Schedule-B-1 SEWER COLLECTING SYSTEM
Schedule-B-2 HOUSE CONNECTION
Schedule-B-3 RISING MAIN NETWORK
Schedule-B-4 ELECTRO-MECHNAICAL WORKS AT VARIOUS PUMPING STATION
Schedule-B-5 PUMPING STATION AT PAKSHI BHAVAN
Schedule-B-6 SCREEN CHAMBER AT PAKSHI BHAVAN PS
Schedule-B-7 PUMP HOUSE
Schedule-B-8 CONSTRUCTION OF CC ROAD
Schedule-B-9 TEMPORARY ROAD RESTORATION AND PAVER BLOCK/KOTA STONE
Schedule-B-10 STP (14 MLD)
Total of Schedule-B
Schedule-C-1 02-YEARS OF OPERATION AND MAINTENANCE
Schedule-C-2 07-YEARS OF OPERATION AND MAINTENANCE FOR STP
Total Project Cost In Rs.
I/We am/ are willing to carry out the work at ………………………………… above/ below /at par percent
(should be written in figures and words),
the estimated rates mentioned above. Now amount of my/our tender works out as under.
* Estimated Amount * Estimated Amount
Put To Tender Put To Tender
Rupees In Word………………………………………………. Rupees In Word……………………………………………….
SEWER COLLECTING SYSTEM
Item Description Unit Qty Rate Amount
Providing and supplying lSl Standard R.C.C. pipes in standard lengths of following class and
diameter suitable for either collar joints or rubber ring joints including all taxes, insurance,
transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance
to departmental stores, stacking etc. complete. for following dia. Note : One collar should
be supplied with each full length plain ended RCC pipe, cost included in rates below. One
rubber ring should be supplied with each full length socketed pipe, cost included in rates
below. Class NP3 Test Pressure, 0.7 Kg / Sq.m. - 250 mm Pipe Dia.
2 300 mm Pipe Dia. Rmt 3,118.00 755.00
3 350 mm Pipe Dia. Rmt 122.00 879.00
4 400 mm Pipe Dia. Rmt 143.00 1,150.00
5 450 mm Pipe Dia. Rmt 1,483.00 1,361.00
6 600 mm Pipe Dia. Rmt 572.00 1,946.00
Frame & Cover Manufacture, supply & Delivery at store or at site of work precast FRC
ROUND FRAME & ROUND COVER - MSB Frame & cover suitable to drainage M.H. and as per
type design & Drawing including cost of reinforcement M.S.
Angles or Flat, curing mold work etc.
Clear Opening : 560 mm dia
7 Cover Size : 710 mm dia No. 491.00 1,850.00
Cover Thickness : 100 mm
Frame Size : 865 mm dia
Frame Thickness : 175 mm
> Frame & Cover
Providing and constructing Sewer manholes, scraper manholes and unit house connection
chamber, as per the type design in brick masonary in C. M. 1:3 and outside plastering in C.
M. 1:3 necessary coping in R.C.C.M. 200 fixing C. I. steps and fixing manhole frame and
covers (But excluding supply of manhole frame and covers) over manholes and house
connection chambers and fixing Manhole covers (but excluding supplying of manhole
8 covers) over scraper manhole etc. complete, providing and fixing safety chain wherever No. 239.00 14,005.85
necessary as per the stipulations in the type desing complete (excl. excavation).
Manhole type "A" Circular type having inside diameter of 1200 mm for depth up to 1.5 m
depth (for 150 mm to 500 mm dia sewer) Manhole type "A" as above but up to 1.0 M depth.
9 Extra depth beyond 1 .0 M but up to 1 .5 M depth for "A" type manhole above. Rmt 44.70 7,622.20
Manhole type "B" circular type having inside diameter of minimum 1500 mm and for depth
10 from 1.5 M to 4.0 M (for 150 mm to 600 mm dia sewers) Manhole type "B" as above but up No. 152.00 24,283.40
to 1.5 M depth.
11 Extra depth beyond 1 .5 M but up to 4.0 M depth for type B manhole above. Rmt 109.20 14,159.95
SEWER COLLECTING SYSTEM
Item Description Unit Qty Rate Amount
Providing, fixing and constructing of pre-cast RCC M-40 grade circular manholes with
internal dia 1.2m and up to specified depth having pre-cast RCC M-40 grade circular
manhole cover frame (ID 0.56m, OD 0.92m), conical piece (top ID 0.56m, bottom ID
1.2m,vertical height 1.005m, wall thickness 125mm), and circular rings of required heights
(ID 1.2m, height 150/225/300/600/900mm, wall thickness 125mm) below conical piece as
per required depth of manhole and having steel reinforcement in Conical piece @ not less
than 80 kg per cum of concrete, including cast-in-situ PCC M-10 grade (1:3:6) foundation of
1.825m dia and 150mm thickness, PCC M15 grade circular wall ID 1.125m, wall thickness
200mm, height equal to ID of sewer pipe + one wall thickness of pipe + 50 mm (to flush the
manhole frame with road top, height of wall can be increased but not more than 100mm),
PCC M15 grade benching and channel portion and up to top level of sewer pipe etc
complete with curing compaction and form work, supplying and fixing heavy duty SFRC
manhole cover as per IS 12592 (Part I and II), supplying and fixing plastic encapsulated
12 CI/MS footsteps / SFRC footsteps, including cost of shuttering, steel reinforcement, testing No. 559.00 17,800.00
for water tightness etc complete in all respect as per drawing, as per specification and the
direction of the Engineer. Note:- Excavation of earth work and road cutting for manhole will
be measured and paid separately.
Pre-cast RCC M-40 grade circular manhole conical piece with inbuilt cover and frame (height
1.005), cast-in-situ PCC M-10 grade foundation, PCC M15 grade circular wall ID 1.125m, wall
thickness 200mm, wall height equal to ID of sewer pipe + one wall thickness of pipe +
mm, PCC M15 grade benching and channel portion. Depth of manhole shall be measured
from top of manhole cover upto lowest invert of pipe. (Depth includes in the item = height
of Conical piece + ID of Sewer pipe + 1 Wall thickness of pipe + increased height of wall (if
Providing and fixing pre-cast RCC M-40 grade circular ring of ID 1.2m, wall thickness 125mm,
13 height 150/225/300/600/900mm for constructing extra depth of manhole beyond depth Rmt 104.30 7,810.00
mentioned in item no-12 as per drawing.
Providing, fixing and constructing of pre-cast RCC M-40 grade circular manholes with
internal dia 1.5m and up to specified depth having pre-cast RCC M-40 grade circular
manhole cover frame (ID 0.56m, OD 0.92m), conical piece (top ID 0.56m, bottom ID 1.5m,
vertical height 1.305m, wall thickness 125mm), and circular rings of required heights (ID
1.5m, height 150/225/300/600/900/1200 mm, wall thickness 125mm) below conical piece
as per required depth of manhole and having steel reinforcement in conical piece @ not less
than 80 kg per cum of concrete, including cast-in-situ PCC M-10 grade (1:3:6) foundation of
2.125m dia and 150mm thickness, PCC M15 grade circular wall ID 1.425 m, wall thickness
200mm, height equal to ID of sewer pipe + one wall thickness of pipe + 50 mm (to flush the
manhole frame with road top, height of wall can be increased but not more than 100mm),
PCC M15 grade benching and channel portion and up to top level of sewer pipe etc
complete with curing compaction and form work, supplying and fixing heavy duty SFRC
manhole cover as per IS 12592 (Part I and II), supplying and fixing plastic encapsulated
14 CI/MS footsteps / SFRC footsteps, including cost of shuttering, steel reinforcement, testing No. 358.00 23,900.00
for water tightness etc complete in all respect as per drawing, as per specification and the
direction of the Engineer. Note:- Excavation of earth work and road cutting for manhole will
be measured and paid separately.
Pre-cast RCC M-40 grade circular manhole conical piece with inbuilt cover and frame (height
1.305), cast-in-situ PCC M-10 grade foundation, PCC M15 grade circular wall ID 1.425m, wall
thickness 200mm, wall height equal to ID of sewer pipe + one wall thickness of pipe +
mm, PCC M15 grade benching and channel portion. Depth of manhole shall be measured
from top of manhole cover upto lowest invert of pipe. (Depth includes in the item = height
of Conical piece + ID of Sewer pipe + 1 Wall thickness of pipe + increased height of wall (if
Providing and fixing pre-cast RCC M-40 grade circular ring of ID 1.5m, wall thickness 125mm,
15 height 150/225/300/600/900/1200mm for constructing extra depth of manhole beyond Rmt 442.80 9,220.00
depth mentioned in item no-14 as per drawing.
SEWER COLLECTING SYSTEM
Item Description Unit Qty Rate Amount
Providing and cast in situ C.C. in grade M-30 proportions of ingredients as per mix design by
weigh batching using granite, quartzite trap metal of size 12 mm to 20 mm and or 6 mm to
12 mm including scaffolding centering formwork, needle vibrated consolidation, curing and
hydraulic testing etc. complete (excluding cost of reinforcement) with centering and
shutteringldeshuttering etc. comp. up to 6 meter height ldepth Av. G.L.for all water
retaining structures Flat bottom slab/floor slab/slab with shuttering
For Inspection Chamber
17 Vertical Wall Above 15 cm and up to 20 cm Cu.M. 431.20 9,673.80
Supplying, cutting, bending, binding, and placing in position steel as per plan and design and
as per ISS 2502 including cost of steel and binding wire for reservior/structures only
18 including lift up to 6 mt. height or depth below G. L. for all diameters. DO - Thermo MT 45.76 84,189.20
Mechanically Treated (TMT) Bars Fe-415 Grade for all diameters.
Providing and fixing intermediate vertically placed removable cast iron jail (minimum
opening 50 mm) fixed in RCC grooves (75 mm bearing on all sides) in the drain walls for
arresting floating debris placed at 60 m c/c in straight reach and at junctions and bends
provided with RCC Cover for cleaning.
Providing and fixing cast iron steps of size 500mm x 150mm x 22.5mm and painting with
two coats of Anti-corrosive paint etc. complete.
Providmg and constructing vertical drop arrangement of 0.6 m and more height as required
including providing and jointing special such as double T. Bend required stoneware pipe
21 fixed in m-100 C. C. at required level as type design culling. jointing and filleting as per No. 152.00 2,477.10
specification etc. complete.
Vertical drop arrangement as above up to 0.6 m height.
22 Extra over item No.4 above for additional drop beyond 0.6 m Rmt 110.00 2,214.90
Excavation for pipe line trenches for water supply, sewerage line, manhole etc. all with
shoring and struting if required as per required gradient and line including safety provisions
using site rails and stacking excavated stuff including up to all required lead cleaning the site
23 etc. complete for all lifts and strata as specified. Cu.M. 40,141.10 102.35
0.0 m to 1.5 m depth
In all sorts of soil & soft murrum
24 In hard murrum, boulders incl. macadam road Cu.M. 9,752.70 155.25
25 In soft rock and/or masonry in CM or L M or Lime Concrete. Cu.M. 7,234.35 187.45
In hard rock and I or in C. C. 1:2:4 or RCC with blasting, breaking, chiseling, or by
chiseling/breaking only.
27 1.50 m to 3.0 m depth In all sorts of soil & soft murrum Cu.M. 6,923.82 112.70
28 In hard murrum, boulders incl. macadam road Cu.M. 1,819.94 170.20
29 In soft rock and/or masonry in CM or L M or Lime Concrete. Cu.M. 1,641.97 205.85
In hard rock and I or in C. C. 1:2:4 or RCC with blasting, breaking, chiseling, or by
chiseling/breaking only.
31 3.00 m to 4.50 m depth In all sorts of soil & soft murrum Cu.M. 589.00 118.45
32 In hard murrum, boulders incl. macadam road Cu.M. 148.00 177.10
33 In soft rock and/or masonry in CM or L M or Lime Concrete. Cu.M. 148.00 215.05
In hard rock and I or in C. C. 1:2:4 or RCC with blasting, breaking, chiseling, or by
chiseling/breaking only.
Dewatering In all sorts of soil and soft murrum, hard Murrum and boulders, Soft Rock, Hard
35 Rock, upto 1.5 mt. depth from G.L. Cu.M. 9,758.00 31.05
1.50mt to 3.00 mt depth
Lowering , Laying and jointing R.C.C. pipes in C.M.1:1 1/2 of following diameter in proper
position, grade and alignment as directed by Engineer-in-charge including conveyance from
37 store to site of work,labour giving hydraulic testing as per ISI Code. Rmt 17,207.00 111.55
250 mm Pipe Dia
38 300 mm Pipe Dia. Rmt 3,118.00 136.85
39 350 mm Pipe Dia. Rmt 122.00 152.95
40 400 mm Pipe Dia. Rmt 143.00 178.25
41 450 mm Pipe Dia. Rmt 1,483.00 196.65
42 600 mm Pipe Dia. Rmt 572.00 262.20
Refilling the pipeline trenches incl. ramming, watering, consolidating desposal of surplus
43 stuff as directed within a radius of 3 km. Cu.M. 50,970.25 25.30
SEWER COLLECTING SYSTEM
Item Description Unit Qty Rate Amount
Providing and casting in situ mass cement concrete in Gradde M-10(approx correspondence
to propotion 1:3:6) using granite quartizite trap metal of size 12mm to 25mm incl.
consolidation curing etc. complete. (For Pipe Bedding) With Form Work
Add for restoration of infrastructures like Kharkuwa. Electncal Line, Telephone cables all
45 types. water lines. gas line. septic tanks. etc. Kharkuwa Repairing No. 125.00 2,103.35
Providing bedding incl. ramming, watering, levelling, consolidating etc. Complete as per
47 standard and instruction of enqineer incharqe. (As above with required quality Sand brought Cu.M. 3,282.00 378.35
from outside inclduinq all lead)
Suppliying, spreading, and consolidation by tamping of graded Hand broken stone
48 aggregate 40 mm to 63 mm size. Including all lead and lift. For Pipe Bedding Cu.M. 1,639.00 806.00
Loosen. de-silt and thoroughly clean and remove debris and objects such as boulders, bricks
elc. bacteriological slimes, roots, encrustations, grease, carbonated deposits, etc from the
49 sewer line including disposal of silt I debris I malba I ObJeCts etc. by super suction machine. Rmt 4,900.00 999.35
300mm dia.& below
50 350mm dia. Sewer line Rmt 2,100.00 1,248.90
Removing of existing pipeline incl. removal of specials, valves jointing material including
carting and stacking of removed material from site of work to the department store as
directed excl. excavation and refilling.
100 mm Dia D .I./ C. I. S. & S. Spun Pipes
52 150 mm Dia D.I./ C. I. S. & S. Spun Pipes Rmt 95.00 35.65
53 200 mm Dia D.I./ C. I. S. & S. Spun Pipes Rmt 75.00 48.30
54 250 mm Dia D.I./ C. I. S. & S. Spun Pipes Rmt 60.00 64.40
55 300 mm Dia D.I./ C. I. S. & S. Spun Pipes Rmt 45.00 80.50
56 300 mm Dia RCC/ Pre-stressed concrete Pipes Rmt 1,300.00 70.15
57 350 mm Dia RCC/ Pre-stressed concrete Pipes Rmt 670.00 80.50
58 90 mm Dia P. V. C./ HDPEI GRP Pipes Rmt 1,490.00 5.75
59 110 mm Dia P. V. C./ HDPEI GRP Pipes Rmt 870.00 5.75
60 140 mm Dia P. V. C./ HDPEI GRP Pipes Rmt 565.00 5.75
61 160 mm Dia P. V. C./ HDPEI GRP Pipes Rmt 340.00 6.90
62 180 mm Dia P. V. C./ HDPEI GRP Pipes Rmt 205.00 9.20
63 200 mm Dia P. V. C./ HDPEI GRP Pipes Rmt 98.00 11.50
Labour charges for repairing of leakage in Cl/DI pipeline for following diameter at different
places including necessary excavation manually or by machinery, removing mud,
dewatering, cleaning of pipe and leakage portion and repairing by Inserting lead wool
64 including tools required for inserting lead wool, hiring charges of excavators, Hydra/Crane. No. 260.00 1,135.05
dewatenng set, fuel. operator, cost of lead wool etc complete (including all material but
excluding cost of pipe)
100 mm Dia D .I./ C. I. S. & S. Spun Pipes
65 150 mm Dia D.I./ C. I. S. & S. Spun Pipes No. 95.00 1,537.55
66 200 mm Dia D.I./ C. I. S. & S. Spun Pipes No. 75.00 1,909.00
67 250 mm Dia D.I./ C. I. S. & S. Spun Pipes No. 60.00 2,794.50
68 300 mm Dia D.I./ C. I. S. & S. Spun Pipes No. 45.00 3,119.95
Labour charges for repairing of leakage in PVC pipeline of foiling diameter at different places
including necessary excavation manually or by mechanise excavation. dewatering removing
of mud, cleaning of pipe and leakage portion, cutting the pipeline & removing piece of pipe
69 from trench with inclussive of mechanical devices JCB. Hydra/Crain if necessary & labours No. 1,490.00 963.70
required with providing material such couplers. solution etc. comp. (incl. all material but
Exclu. cost of pipe) 90 mm Dia P. V. C.
Total Amount (In Rs.) =
Total Amount (In Rs.) =
HOUSE CONNECTION
Item Description Unit Qty Rate Amount
Providing and supplying of Class SN8 Structured Wall
polyethelene Piping systems (Pipe with online/offline
coupler and elastomeric sealing ring) with non-smooth
External Annular Corrugated and Smooth Internal
Surfaces (Double Wall) for non pressure underground
Sewerage & Drainage application as per EN:13476-3
including all local and central taxes, transportation,
freight charges, octroi, inspection charges. loading,
unloading, conveyance to the departmental stores etc.
complele.(ID Dia)
Corrugated DWC HDPE pipes (non-pressure pipes)
Manufacture, supply and delivery of Chemical fabricated
RCC Precast chambers (For House Connection) with top
cover as per specification and drawing for sizes as
mentioned below. The delivery of chambers with clamps,
nuts. bolts and locking arrangement (without lock) is to
be made to sites any where in Gujarat. The rates includes
all taxes. loading, carting, unloading, stacking, including
all taxes. 60 x 60 x 90 cm deep (Suitable to 60 to 300 mm
House Connection Chamber of Size 0.60 x 0.60 x
Excavation for pipe line trenches incl. all safety provisions
using site rails and stacking excavated stuff up to a lead of
90 mts. cleaning the site etc. complete for lifts and strata
0.0 m to 1.5 m depth
In all sorts of soil & soft murrum
Lowering, laying and jointing of class SN 8 structured wall
( External Annular Corrugated & Smooth Internal surface)
Polyethylene Piping and fittings with the help of coupler (
on line I off line ) attached with one end of pipes, sliding
over the elastomeric sealing rubber ring placed on the
specified valley of the corrugation at the spigot end,
lowering the same into the trench at all level, laying on
the lower bedding (constructed at bottom of trenches) at
prescribed gradient, depth & alignment ,testing the water
tightness of the joints, ensuring the continuity tests of
specified pipe segments etc. complete as per
drawing,specifications & detailed engineering, including
carriage of pipes & fittings from site stacks to the place of
laying etc. as per direction of Engineer-in-charge. 100mm
Refilling the pipeline trenches including ramming,
watering, consolidating disposal of surplus stuff as
directed within a radius of 3 km
Total Amount (In Rs.) =
Total Amount (In Rs.) =
Rising Main Network
Item Description Unit Qty Rate Amount
Providing and supplying D. I. K-9 grade pipes for following nominal bore diameter with
internal cement mortar lining including all taxes, insurance, transportation, freight
charges, octroi, inspection charges. loading, unloading, conveyance to departmental
stores, stacking etc. complete. For sewerage project cement mortor lining shall be
with sulphate resistance cement
Manufacture, Supply & Delivery of Ductile Iron Flange socket spigot bends, tees,
reducers or any other specials as per BS-EN-545/1995 Class-A series K12 suitable for
use with D.I. Pipes manufactured as per IS:8329/1994delivery of specials is to be made
to site of works any where in Gujarat including all taxes, loading, unloading, carting,
stacking, insurance, inspection charges, octroi etc. complete. Specials 80 to 300mm
7 Specials Above 350mm dia Kg. 4,421.00 151.00
Providing and supplying ISI mark CI D/F Sluice Valves/ Scour Valve as per IS:14846
(Latest Edition) of following class and diameter including all taxes, insurance,
transportation, freight charges, octroi, inspection charges, loading, unloading,
conveyance to departmental stores, stacking etc. complete. A9) P.N.1.6 with hand
wheel/cap operated (PD type short body)
Supply, installation, testing & commissioning of flange ends Expansion Bellow as per
EJMA standards of overall length of minimum 300 mm, designed for 15 mm axial
compression and 5 mm axial extension with tie rods etc. of following MOC & pressure
MOC: Bellows: SA 240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr.
B; Flanges: IS 2062 Gr. B (Drilling as per IS 1538 /IS 6392 ) & Limit Rods & Nuts: CS - IS
Size- NB 200mm, Width- 300mm
11 Size- 300mm, Width- 300mm Nos. 6.00 10,800.00
Providing and supplying C. I Air valves of approved make & quality of following class
and diameter including all taxes, insurance, transportation, freight charges, octroi,
inspection charges, loading, unloading, conveyance to departmental stores, stacking
etc. complete. air valve Double Acting (DS2) type 50mm dia
Erection of airvalve riser by installing new M.S pipe of 6mm thick and 3.2mt length
with necessary fittings such as flange of appropriate size,nut bolts and embeded the
pipe in RCC M: 15 with offset of 10 cm around pipe with necessary steel etc complete
Dia of Air Valve 50mm& MS Pipe
16 Dia of Air Valve 80mm& MS Pipe Rmt 3.00 5,002.50
17 Dia of Air Valve 100mm& MS Pipe Rmt 13.00 6,374.45
Excavation for pipe line trenches for water supply, sewerage line, manhole etc. all
with shoring and struting if required as per required gradient and line including safety
provisions using site rails and stacking excavated stuff including up to all required lead
cleaning the site etc. complete for all lifts and strata as specified.
0.0 to 1.5 mt depth. In all sorts of soil and soft murrum
19 In hard murrum, boulders incl. macadam road. Cum 2,652.38 155.25
20 In soft rock and/or masonary in CM or LM or Lime Concrete. Cum 1,591.43 187.45
In hard rock and/or in C.C. 1:2:4 or R.C.C. with blasting and chiselling or by chiselling
22 1.5 to 3.0 mt depth. In all sorts of soil and soft murrum Cum 222.90 112.70
23 In hard murrum, boulders incl. macadam road. Cum 111.45 170.20
24 In soft rock and/or masonary in CM or LM or Lime Concrete. Cum 66.87 205.85
Rising Main Network
Item Description Unit Qty Rate Amount
In hard rock and/or in C.C. 1:2:4 or R.C.C. with blasting and chiselling or by
chiselling/breaking only.
Lowering, laying and jointing C. I. S & S Spun pipes suitable for Tyton joints / Mortar
lined D. I. Pipes of various classes with CI / MS specials of following diameters in
26 proper position, grade and alignment as directed by Engineer-in-charge including Rmt 680.00 113.85
hydraulictesting etc. complete
Lowering, laying and jointing in position following C. I. / D/F Reflux valves, Butterfly
valves, Sluice valves including cost of all labour, jointing material, including nut bolts
and giving satisfactory hydraulic testing, etc. complete. 200mm dia
Construction of valves chambers in brick or bela stone masonry, locally available in C.
M. 1:6. Foundation concrete 150 mm thick in C. C. 1:4:8 of trap metal size 25 mm to
40 mm thick, inside cement plaster in C. M. 1:3 and cement pointing outside in C. M.
1:3 and top cover of precast RCC slab 100 mm thick (with key hole in two parts, each
with handles or MS Bar etc. complete as given size) Upto 1 Mt. depth from G. L. to
pipe invert level incl. complete civil works but excl. cost of excavation and refilling,
with cast in situ RCC slab in one single piece with fixing of CI-MH Frame and cover
(excl. cost of CI-MH Frame and cover) with 23 mm thick brick masonry wall in C.M.1:6
Valve chamber of Size
Size of chamber 0.90 m x 0.90 m and 1.0 mt. deep for Air Valve
With precast slab in two parts 15 cm
34 For 1 mt extra Depth Rmt 4.00 5,150.85
Providing and casting in situ C.C. in grade M-20 (proportions as per mix design or as
per table-9 of IS456 2000 in masses by weigh batching ) using granite, quartzite trap
metal of size 6 mm to 20 mm for RCC work, including scaffolding centering, formwork,
needle vibrated consolidation, curing complete up to 6 meter depth or height
(excluding cost of reinforcement and neat finishing) with centering and
shuttering/deshuttering etc. complete for structure other than water retaining (Below
G.L). Footing for column or foundation (with form work) Thrust Block
Supplying, cutting, bending, binding, and placing in position steel as per plan and
design and as per ISS 2502 including cost of steel and binding wire for
36 reservior/structures only including lift up to 6 mt. height or depth below G. L. for all MT 33.80 84,189.20
diameters. DO - Thermo Mechanically Treated (TMT) Bars Fe-415 Grade for all
Providing bedding incl. ramming, watering, levelling, consolidating etc. Complete as
37 per standard and instruction of engineer incharge As above with Murrum brought Cum 730.61 202.40
from outside inclduing all lead
Refilling the pipeline trenches including ramming, watering, consolidation, disposal of
38 surplus stuff as directed within a radius of 3 KM Cum 9,476.00 25.30
Drilling of Horizontal bore hole for water main pipeline under the Railway / Road
tracks in all strata with required length including fixing of M.S.(or as specified by
Railway / Road authority) casing pipe of suitable size and Thickness. Rate includes the
cost of Drilling of bore hole , Casing pipe & welding pushing etc complete but
excluding the cost of water main, valves and other items. Entire work should be as per
Approved Drawing and as per instruction of Railway / Road authority for Following
diameter of Bore hole. for MS pipe Horizontal Drilling-300:& MS Casing Pipe-250
40 Horizontal Drilling-600:& MS Casing Pipe-500 thick:8 Rmt 45.00 9,166.00
Total Amount (In Rs.) =
Total Amount (In Rs.) =
Electro-Mechnaical works at Various Pumping Station
Item Description Unit Qty Rate Amount
Sewage Non Clog, End Suction Type Vertical Centrifugal Pump :-
Supply, installation, testing & commissioning of non clog seweage vertically mounted end suction type vertical centrifugal
pump set of required capapcity & head with suitable TEFC squirrel cage foot mounted induction motor (with minimum IE-3
efficiency class), working on three phase 50 Hz ± 3%, 415 V ± 10% AC supply, 1500 RPM synchronous speed including suitable
1 provision of extended shaft of 2 meters length to couple with motor along with base frame, coupling with guard, foundation Set. 2.00 1,12,885.00
bolts, strainer etc. complete set as per relevant IS & following M.O.C: Casing: 1.5 to 2% Ni. CI; Impeller & wearing ring: SS /
CF8M, Shaft with sleeve: SS & Base frame: CI; Guide Pipe: SS.
PUMP Required (For 1 DWF) :- 30 HP (1 Working AND 1 Stand By)
2 PUMP Required (For 2 DWF) :- 60 HP (1 Working AND 1 Stand By) Set. 2.00 1,76,331.00
3 PUMP Required (For 1 DWF) :- 100 HP (1 Working AND 1 Stand By) Set. 2.00 2,67,794.00
4 PUMP Required (For 2 DWF) :- 170 HP (1 Working AND 1 Stand By) Set. 2.00 6,59,184.00
5 PUMP Required (For 1 DWF) :- 10 HP (1 Working AND 1 Stand By) Set. 2.00 87,342.00
6 PUMP Required (For 2 DWF) :- 20 HP (1 Working AND 1 Stand By) Set. 2.00 87,342.00
Supply, installation, testing & commissioning of horizontal split casing centrifugal pump motor set of specified duty
parameters & guaranteed efficiency of following MOC with specified capacity, horizontal foot mounted TEFC squirrel cage
induction motor (with minimum IE-3 efficiency class), working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%, rated
7 speed 1450 RPM along with fabricated MS base frame, coupling, coupling guard, foundation bolts etc. as per relevant IS. Set. 2.00 2,42,624.00
M.O.C.: Impeller & Wearing Rings: Bronze LTB II IS: 318, Casing: CI FG 260 IS: 210 , Shaft: SS 410, Shaft Sleeve: Bronze LTB II IS:
318 or SS 410, Mechanical Seal (Above 30 kW), Base Frame: MS.
PUMP Required (For 1 DWF) :- 34 KW (1 Working AND 1 Stand By)
8 PUMP Required (For 2 DWF) :- 62 KW (1 Working AND 1 Stand By) Set. 2.00 4,42,432.00
PRESSURE GAUGE:
Design, Supply, Installation, Testing, Commissioning of Bourdon Type Pressure Gauge, ±1% accuracy, Direct
bottom 1/2" NPT (M) process connection, IP 67, Glycerine filled, SS304 Case with Bayonet Type Bezel, SS316 L
9 Bourdon Tube, SS 316 Movement material, Aluminium dial with black graduation on white background, Micro No. 16.00 1,029.00
Zero adjustable pointer, neoprene gasket, Blow out disc, shatter proof glass, SS tag plate etc as per IS
Range : 0 - 6 kg / sq.cm.
FLOW METER: Full Bore Electromagnetic Flow Meter- Inbuilt Battery Power operated
Design, Supply, Installation, Testing, Commissioning of Full Bore Electromagnetic flow meter with factory
calibration, Inbuilt Battery Power Operated, flanged connection, Flow sensor, Indicator, transmitter and
totaliser with all accessories viz. surge arrestor, associated cables, cabinets, hardwares, etc complete as per
following specifications:
I :- Flow Meter/ Sensor:
DC pulsed type, IP 68 Protection, Flanged process connection as per IS 1538 or equivalent standard, SS304/
Metallic Alloy Flow Tube, SS316/ SS 316 L/ Hastelloy Sensor, SS316/ Hastelloy Grounding Ring/ Inbuilt
Grounding Electrode, Neoprene/Polyurethane/ Hard Rubber/ Rilsan lining, SS304/ Die Cast Aluminium/
Carbon steel with Anticorrosive Paint Coil Housing with Junction Box, CS flanges.
10 II :- Flow Transmitter/ Converter ( Remote Field Mounted): No. 1.00 2,10,688.00
Microprocessor based, Modular design, 2 line LCD for indication of actual flow rate, forward, reverse, sum
totaliser display, ±0.5% accuracy at 0.3 to 4 m/sec velocity, one scalable pulse/ one status, one Modbus output,
one GPRS/ GSM output, IP 67 protection, Die cast aluminium/ polycarbonate/ SS316 with Anticorrosive Paint/
PU finish with glass window enclosure, Inbuilt EEPROM and Data Logger, 20 meters cable length for sensor to
transmitter communication, Minimum 5 years battery lifetime, 3.6 VDC Non
Rechargeable Lithium-thionyl chloride/ Ni-Cd high power batteries, Hourly Basis Worldwide transmission of
measured data and events via e‐mail and SMS by integrated GSM/GPRS modem, Reliable data storage facility
through integrated SD card etc alongwith wall mounted/ stand mounted cabinet.
Full Bore Electromagnetic Flow Meter (Inbuilt Battery Power Operated)- PN
300 mm Nominal Bore (At header)
11 400 mm Nominal Bore (At header) No. 1.00 2,78,633.00
12 450 mm Nominal Bore (At header) No. 1.00 2,94,706.00
13 200 mm Nominal Bore (At header) No. 1.00 1,43,211.00
EXPANSION BELLOWS:
Supply, installation, testing & commissioning of flange ends Expansion Bellow as per EJMA standards of overall
length of minimum 300 mm, designed for 15 mm axial compression and 5 mm axial extension with tie rods etc.
14 of following MOC & pressure ratings. No. 8.00 10,200.00
MOC: Bellows: SA 240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B
(Drilling as per IS 1538 / IS 6392 ) & Limit Rods & Nuts: CS - IS
Ultrasonic Type Level Transmitter with Integral Display :
Design, Supply, Installation, Testing and Commissioning of NOn Contact Ultrasonic Type Level Transmitter
Sensor with Head Mounted Transmitter:
The sensor should be non contact type, field mounting type, housing shall have minimum IP65 protection, PP/
17 PVC Sensor MOC, Microprocessor based indicator with LED / LCD digital display,panel/ wall mounting type, No. 4.00 59,723.00
power supply shall be 110- 240 Vac or 15 to 36 Vdc, 50 Hz ± 10 %.
Accesories: Mounting bracket, nut, bolts etc as per system requirement and Hook up diagram of the
Level Transmitter shall be suitable for following Range.
iii) 0 to 15 Meter
C.I. D/F VALVES: SLUICE VALVE:
Providing and supplying ISI mark CI D/F Sluice Valves as per IS:14846 (Latest Edition) of following class and
diameter including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading,
unloading, conveyance to departmental stores, stacking etc. complete..
PN-1.6 With hand wheel /cap operated (PD type short body) Size:300 mm (delivery side)
19 Size: 200 mm (delivery side) No. 4.00 10,295.00
Electro-Mechnaical works at Various Pumping Station
Item Description Unit Qty Rate Amount
Lowering, laying and jointing in position following C. I. / D/F Reflux valves, Butterfly
20 valves, Sluice valves and Air valves including cost of all labour, jointing material, No. 12.00 1,312.15
including nut bolts and giving satisfactory hydraulic testing, etc. complete Size 300 mm
Supply, installation, painting, testing & commissioning of non-slam, spring action, flanged Dual plate check
22 valve confirming to API 594 & 598 PN 1.0 with C.I. body, spring steel spring, S.S. seating with all carbon steel No. 12.00 35,045.00
hardware’s and other accessories as per data sheet and specification.
Size: 300 mm NB-Manually operated (on delivery side)
23 Size: 200 mm NB-Manually operated (on delivery side) No. 4.00 15,929.00
Lowering, laying and jointing in position following C. I. / D/F Reflux valves, Butterfly valves, Sluice valves and
Air valves including cost of all labour, jointing material, including nut bolts and giving satisfactory hydraulic
24 testing, etc. complete. Sluice valves, Butterfly Valves, Reflux Valves No. 12.00 1,312.15
Size: 300 mm NB-Manually operated (on delivery side)
25 Size: 200 mm NB-Manually operated (on delivery side) No. 4.00 853.30
Providing and supplying C. I. Air valves of approved make & quality of following class and diameter including
26 all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading, No. 1.00 3,660.00
conveyance to departmental stores, stacking etc. complete.
Air valves double acting (DS 2) Size: 80 mm NB - PN
Lowering, laying and jointing in position following C. I. / D/F Reflux valves, Butterfly
30 valves, Sluice valves and Air valves including cost of all labour, jointing material, No. 1.00 472.65
including nut bolts and giving satisfactory hydraulic testing, etc. complete Size 80 mm
Manufacture, Supply & Delivery of Electric Resistance Welded (Up to 400mm)/Submerged Arc Welded(Above
400mm) M.S.Pipe having beveled ends plate or coil conforming to IS-3589-2001 or its latest revision/
34 ammendment for following thickness outside diameter at site anywhere in Gujarat State including all taxes, Rmt 150.00 3,106.00
insurance, transportation, freight charges, octroi, inspection charges, loading, unloading conveyance to
Departmental stores, stacking etc. all complete.
Size:323.9 mm NB-5.6 mm thick (on Delivery side)-As per site requirement
35 Size: 219.1 mm NB-6.3 mm thick (on Delivery side)-As per site requirement Rmt 50.00 2,337.00
Lowering, laying, Jointing & welding in position to correct line & level M.S. Pipe with outer gunniting & inside
lining/Epoxy painting on pedestal or chairs upon prepared formation or prepared bedding in trenches the
36 rates include conveyance from store to site of work loading, unloading, joint plastering, hydrotesting Rmt 150.00 341.55
Size:323.9 mm NB-5.6 mm thick
37 Size: 219.1 mm NB-6.3 mm thick Rmt 50.00 248.40
Providing, S.I.T.C of Structure Steel at site of work with freight, loading, unloading carting, etc. including all
taxes and duties complete such as joints, channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates,
Chequered plates (below 10mm thickness) etc. required for support structure of Elecrto- Mechanical
equipments etc. for support on floor / wall / beam / brackets etc. as per tender and IS.
Supplying and erecting, commissioning and testing of Diesel Generating set confirming to IS:4722:1968 & BS:5514 having
continuous rating ,3phase, 415 volts, 50 cycles A.C. supply comprising of a totally enclosed air/water cooled diesel
engine with multi-cylinders developing suitable BHP not lessthan following capacity at 1500 RPM with 10% overload for
one hour in 24 hours with standard accessories like fly wheel, lubricating oil cooler, "A" class governor, heavy duty fuel
wheel and lubricating oil filter, oil bath air filler, lubricating oil pressure gauge, end exhaust manifold, standard set of
tools with adjustable spanners, screw drivers, cylinder head to cover, joint cylinder head to exhaust, element lube oil
filter, 12/24 volts electric starting equipment complete with standard heavy duty battery, dynamo, cut-outs, ammeter,
necessary wiring, pressure gauge, starter etc and heavy duty Residential type exhaust silencer (WithDEF
System) and vertical hot air duct both
logged with asbestos rope, save oil trays, exhaust piping of required length, standard wall/floor mounted fuel with level
indicator and piping and drip proof alternator, self excited, self regulated, screen protected, with excitation system,
capable of delivering the rated system output at 415 volts, 3 phase, 0.8 PF, 50 Hz, 4 wire, running at 1500 RPM, conforming
to IS-4722-1968 with voltage regulation +/-5% of rated voltage from no load to full load. Both the engine and alternator
fitted on a common fabricated steel base plate with antivibration mounting engine and alternator both connected to each
39 other by flexible flange coupling and with floor/wall mounted control panel box comprising of voltmeter ammeter, No. 1.00 26,14,761.90
selector switches, ACB/MCCB/MCB of adequate capacity,
indicator lamps duly wired with HRC fuses. The alternator & control panel shall be connected with provided suitable
capacity armoured cable and complete with Acoustic enclosure (canopy) made out of 16 SWG CRCA Sheet, sound
absorbing material Rockwool of 64 density & 100 mm thick conforming to IS:8183/PU Foam of 40 Density - at least 40 mm.
The resin bonded rockwool covered from inside the canopy by perforated sheet with 3/4 mm holes, sound level not more
than 75 dB at a distance of 1 mtr, as per PVCT norms. .DGset should have inbuilt fuel tank capacity of minimum
hrs of continous running capacity on full load. Erection, commissioning and satisfactory testing as per requirement with
first filling of fuel (minimum up to the 80% of fuel tank capacity), oil, etc. with guarantee / Warrantee of complete system
for Two years. & with obtaining all necessary certificate from Electrical Inspector. The Capacity and Ratings of DG sets
are as below. (Aspernew CPCB4+ Emission norms Engine With - Turbo Charger, EGR(Exhaust Gas Recirculation), CRS
(Common Rail Fuel System), DOC (Diesel Oxidation Catalyst), SCR (Selective Catalytic Reduction), Integrated wiring
harness connected to ECU .) (S)Continuous rating of 320 KVA, BHP not less than 375 BHP
Electro-Mechnaical works at Various Pumping Station
Item Description Unit Qty Rate Amount
Providing & erecting approved make AMF control panel suitable for following size of 3 phase, 415 V., 50 cycles, A.C. diesel
generating set complete of scope as detailed below:
1) Power module: A pair of electromechanically interlocked contactors (for mains & generator) Overload relay for generator
contactor Neutral contactor for mains and generator Power socket for connections.
2) Control and metering module: Line voltage monitor. Generator voltage monitor Ammeter 3 items attempt start facility. Air
circuit breakers/MCB/MCCB of suitable rating for auto/manual operation. Auto/manual switch. Emergency stop push buttons.
Manual start push button. frequency meter. Engine hour meter. Two earthing studs.3) Protection module: The engine
shutdown in the unlikely event of Low lube oil pressure High cylinder head temperature. V belt failure.
4) Indicators with alarm Load on generator.
5) Indicators Load on mains Engine fails to start . Emergency stop battery charger.
The AMF Panel of following capacity
(E) AMF Control Panel for 300KVA / 320KVA 3 phase DG Set
Auto transformer starter suitable for local & remote pump control application consisting of Auto Transformer (vacuum
impregnated, air cooled having three (3) tappings at 50%, 65% and 80%), incomer MCCB / MPCB, overload relay and
contactors as per Type II coordination including digital MFM with RS 485 communication port, analogue type ammeter with
41 selector switch, run hour meter, required protective relays & control accessories. No. 2.00 24,276.00
A. T. S. from 21 to 30 HP
DOL / Star Delta starter suitable for local & remote pump control application consisting of MPCB, overload relay and
contactors as per Type II coordination including digital voltmeter, analogue ammeter with selector switch, run hour meter,
required protective relays & control accessories.
PUMP Required (For 1 DWF) :- Discharge-75 m³/hr, (1250 LPM) ,(2 Sets) of 10 HP, 28 Head
47 PUMP Required (For 2 DWF) :- Discharge-150 m³/hr, (2500 LPM) ,(2 Sets) of 20 HP, 28 Head No. 2.00 13,771.00
LV POWER CONTROL CENTER (PCC)
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed, dust & vermin proof, indoor
type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for base frame / channel / gland plates, 2.0 mm for
load bearing members / doors & 1.6 mm for internal partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable
for operation on 3 Phase, 4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with instrumentation compartments
accomodating meters, aux / protective relays, LED type indicating lamps & control MCBs as per IS: 13947, current & voltage
transformers as per IS: 2705, air insulated electrolitic grade Aluminum / Copper bus bar for three phase & neutral system, GI
earth bus for entire length, power / control wiring using 1100 V grade, FRLS insulated copper conductor wires conforming to
IS: 694 & 8130, equipment fittings, horizontally running busbar compartment height of minimum 300 mm, incoming &
ougoing cable connections for 1100 V grade, Aluminium / Copper conductor XLPE / PVC insulated & PVC sheathed armoured
cable. LVDB shall have required incomming / bus coupler / outgoing modules of following type & ratings.
Above 80A, upto & including 250A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism,
current limiting type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB
module, when used as Outgoing(s), shall have enclosure dimensions- 400 (H) x 600 (W) x 600 (D) & following technical
(A) 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics =100% of Icu), Microprocessor release
Above 80A, upto & including 250A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism,
current limiting type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB
module, when used as Outgoing(s), shall have enclosure
dimensions- 1800(H) x 600(W) x 600 (D) & following technical features:1.13k) 4 Pole, MCCB with Breaking Capacity of Icu=36
KA at 415V (Ics =100% of Icu), TM release
Above 16A, upto & including 80A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism,
current limiting type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB
50 module, when used as Incommer / Bus Coupler, shall have enclosure dimensions- 1800(H) x 500(W) x 600 (D) & following No. 2.00 18,130.00
technical features: 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics =100% of Icu), TM release
Supply, installaton, testing & commissioning LV APFC panel consisting of required capacitor banks for continuous duty to
improve P.F. 0.85 to 0.99 in required steps enclosed in dust & vermin proof compartment, indoor type, fabricated from CRCA
sheet steel with minimum thickness of 3 mm for base frame / channel / gland plates, 2.0 mm for load bearing members /
doors & 1.6 mm for internal partitions, minimum degree of protection - IP 42, busbar chamber, required size of Al bus bar /
terminals, minimum 10 stage APFC relay, metering, indicating lamps, push buttons complete as per IS: 16636-2017 with latest
ammendment & detailed technical specification and data sheet as under.
Up to 50 KVAR capacity: APFC panel consisting following items.
a) 125 A, 50 kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle
b) 0-125 A range analogue ammeter of 96 x 96 mm size
51 with selector switch No. 3.00 1,38,383.00
c) 3 nos. 125 / 5A, 10 VA CL-1.0 cast resin type current transformer
d) Suitable rating MCCB / MCB &Contactors for each capacitor bank
e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil, internally delta connected with
built in internal
fuses complete with discharge resistances & terminal cover) of approoved make in required steps with well suited detuned
reactor is placed in
series with each capacitor step. (e.g. 50 KVAR capacity will be provided in steps of 2 nos x 5 KVAR, 2 nos x 7.5KVAR & 2 nos
x12.5 KVAR). (f) Enclosure
dimensions: 1600 (H) x 1150 (W) x 600 (D)
Electro-Mechnaical works at Various Pumping Station
Item Description Unit Qty Rate Amount
Above 50 & up to 100 KVAR: APFC panel consisting following items. a) 250 A, 50 kA for 1sec. TP, TM based MCCB with
spreader terminals & rotary handle b) 0-250 A range analogue ammeter of 96 x 96 mm size with selector switch c) 3nos. 250 /
5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable rating of MCCB / MCB & Contactors for each capacitor bank e)
Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil, internally delta connected with
built in internal fuses complete with discharge resistances & terminal cover) of approved make in required steps with well
suited detuned reactor is placed in series with each capacitor step. ( e.g. 100 KVAR capacity will be provided in steps of 2 nos x
5 KVAR, 2 nos x 10KVAR, 2 nos x 15 KVAR & 2 nos x 20 KVAR) f) Enclosre dimensions: 2100 (H) x 1150 (W) x 600 (D)
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip
/ round wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps /
in existing cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to
IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes:
3 Core x 50 Sqmm
54 3.5 Core x 120 Sqmm Rmt 80.00 423.00
55 3 Core x 16.0 Sqmm Rmt 50.00 91.00
57 3 Core x 4 Sqmm Rmt 40.00 61.00
58 3 Core x 6.0 Sqmm Rmt 40.00 70.00
59 3.5 Core x 70 Sqmm Rmt 50.00 287.00
Providing and erecting Pipe type earthing with 40mm dia 2.5mtr long 'B' grade G.I. pipe with necessary coupling buch buried in
61 specially prepared earth pit & G.I. earthwire of 8SWG erected & connected as directed (For panel) No. 7.00 816.28
Supply & laying GI ladder type cable trays with side channels of size - 75 x 15 x 15 mm / 100 x 15 x 15 mm & rungs of size -
x15 x 15 mm spaced at 250 mm apart, fabricated from 2 mm thick sheet steel in standard length of 2.5 meter, duly hot dipped
62 galvanized after fabrication as per IS 2629-1989/ IS 4759-1984 including accessories such as coupler plates/ fish plates, bends, Rmt 120.00 388.00
tees, reducers, elbows, covers and electro-galvanized hardware etc, erected on existing support as per specification and
instruction of Engineer-in-charge.
300(W) x 75(H) x 2.0 mm Thick
Float/ Displacer Type Level Switch
Design, Supply, Installation, Testing and Commissioning of Top mounted Displacer Type level switches with 2 nos SPDT
contacts of Micro switch rated 5 A, potential free power supply, Material of wetted parts shall be SS 316 and the material of
accessories shall be SS. IP 65 or equivalent degree of protection for enclosure, suitable for sump, ESR, tank, vessels and
66 underground reservoirs. The top mounted level switches shall be supplied with still tubes to suit the requirement. No. 8.00 12,802.00
. Accessories like name plate, mating flange, gaskets, fasteners, bolts & nuts, etc. shall be supplied with the Level Switch
of following Range.
a) 0 to 5 Meter
INTERNAL WIRING:-
Providing and erecting mains with 1.1 kV grade, FRLS PVC insulated, ISI-marked stranded copper conductor wires, laid in
suitable conduits, concealed or flush-mounted on walls/ceilings. The work shall include 1.5 sq.mm FRLS PVC insulated
67 stranded copper conductor of green colour for earth continuity, complete for the following sizes, as specified Rmt 3800.00 82.06
(A) With medium class Rigid PVC pipe and accessories
SITC of Main wiring with 3 wire 1.5 sq. mm as per tender specification / IS
SITC of Main wiring with 3 wire 2.5 sq. mm as per tender specification / IS
Point wiring for independent plug, comprising mains wiring of the specified size with 1.5 sq.mm (green) earth wire, both ISI-
marked, 1.1 kV grade, FRLS PVC insulated, multi-strand copper conductors, laid in suitable conduits, for a run up to 10 m. The
work shall include supply and installation of ISI-marked 3-pin / 5-pin socket and Tissino-type switch, complete with proper
69 earth continuity connection, mounted on metal / PVC / wooden box and covered with 3 mm thick PC (polycarbonate) / acrylic / No. 120.00 310.60
laminated sheet, complete in all respects.
[A] For 6amp plug and 6amp switch with 2-1.5 sq.mm Cu.Mains from nearby switchboard/db board upto 6 mt.
(a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete
[B]6/16A Plug and 16amp switch with 2-2.5sq.mm Cu. Mains from mcb d b boards.
70 (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling No. 120.00 489.47
LED LIGHT FIXTURES:
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with
housing used as a heat sink shall be made of thick sheet Steel conforming to IS:513 / CRCA / aluminium die cast powder coated
and high U.V. & corrosion resistance with diffuser with company mark / name 160 V to 270 V, Power Factor more than 0.95,
71 THD < 15%, CCT 3000 K to 6500 K, Luminaire efficacy > 85 lumens / watt, LED LED driver efficiency > 85 % ( fitting required LM- No. 50.00 370.26
79 & LM-80 Certificates ) ( NOTE: Below description have shown ranges of Wattage capacity of LED fittings. The Engineer in
charge may select any wattage capacity between the ranges shown. ) (A) Tube Light with integral driver
(iv) 22-24 Watts, Surge - 2KV,IP-20, conventional 4 feet Cat-lll
Supplying and erecting LED lamps with following wattage capacity of 220 to 240 voltage, minimum 15000 burning hours life,
500 V inbuilt-surge protection, Polycarbonate diffuser, mounting suitable for E14 / E27 / B22 lamp holders, pf >=
72 (A) LED Lamps integral type, with PC diffuser suitable LAMP holder. No. 60.00 111.00
(ii) 5 to 8 watts Cat-III
SAFETY ACCESSORIES:
Supplying & erecting carbon dioxide (CO₂) fire extinguisher user of following capacity with necessary clamps made from 50 ×
mm M.S. flat with nut & bolts grouted in wall complete.
[B] For 5.5 / 6.5 KG Capacity
Electro-Mechnaical works at Various Pumping Station
Item Description Unit Qty Rate Amount
Supplying standard First AID box with antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage,
74 medicated ready to use bandage (Band-aid), adhesive tape for medicinal user, scissors, anti-septic solution (Savlon or similar) No. 12.00 297.00
etc. (All above contents shall be of standard makes).
Providing and fixing printed instruction chart both in English and Gujarati and duly framed with front glasses, for treatment of
person suffering from Electric shock with minimum 50" diagonally size.
Supplying FIRE bucket round bottom of 9 litres capacity made out of 24 gauge G.I. sheet with extra handle at bottom duly
76 painted white inside and Red outside with FIRE mark, filled with dry-sand and kept on existing stand provided or hung on wall No. 8.00 212.00
providing and erecting Fully Automatic Emergency Light working on 220/250Volts 50C/s. AC supply complete with BATTERY of
6volts, 18watts Lamps Magnetic relay&Battery charging circuit, and extra output socket, to provide sufficient light
continuously for about 4hours including lampsEmergency Light immediately comes to on by providing bright light when main
electric supply fails suddenly. And it is all automatic,controlled by a magnetic relay. It is portable too, can be placed at any
convenient point.
a) Tube emergency light 2feet,20watt ,10AH
Supplying rubber matting of following thickness as per IS:15652/IEC 61111 (b)4mm
Providing pair of rubber handgloves suitable for working on 11 KV/22 KV supply. (b)4mm
Total Amount (In Rs.) =
Total Amount (In Rs.) =
PUMPING STATION AT PAKSHI BHAVAN
Item Description Unit Qty Rate Amount
Sinking single circular well of internal diameter and thickness of steining as specified
up to the level as specified in all sorts of soi l including hard murrum, boulders and all
strata type & strata up to the level as per drawing by dredging, dewatering, drop
chiselling with necessary kentiedge and with mechanical means as may be necessary
1 for this type of work including all labour. plant machinery etc. complete. Zero level to Rmt 3.00 1,03,129.99
be considered from cutting edge level. Including all labour charges with Dewatering
but Excluding cost of Cutting Edge & Well steining For 12.0 mt dia well, internal incl.
Dewatering 1. 0 to 3 mt depth
Providing fabricating and placing cutting edge and curbs as per design MT
and drawing manufactured from structural steel or M.S. plate confirming to
4 ISS 226-1962 incl. Riveting, welding etc. complete. incl. m.s.bars, anchor MT 4.71 1,01,124.10
bolts and structural steel etc complete.
Providing and casting in situ mass cement concrete in grade M-10 (approx.
corresp. to prop. 1:3:6) using granite quartzite trap metal of size 12 mm to
mm incl. consolidation curing etc. complete. with Formwork.
Providing and cast in situ C.C. in grade M-25proportions of ingredients as
per mix design by weigh batching using granite, quartzite trap metal of size
12 mm to 20 mm and or 6 mm to 12 mm including scaffolding centering
6 formwork, needle vibrated consolidation, curing and hydraulic testing etc. Cum 49.12 9,288.55
complete (excluding cost of reinforcement) up to 6 meter height /depth Av.
G.L.for all water retaining structures a. Slab
7 Beams Cum 13.76 9,599.05
8 Vertical walls ( above 25 cm) Cum 141.63 9,126.40
9 Column Cum 2.21 10,574.25
Supplying, cutting, bending, binding, and placing in position steel as per plan and
design and as per ISS 2502 including cost of steel and binding wire for
10 reservior/structures only including lift up to 6 mt. height or depth below G. L. for all MT 31.01 84,189.20
diameters. Do-Thermo mechanically treated (TMT)bars Fe-415 grade for all diameters.
Brick work using common burnt clay buildings brick having crushing strength not less
than 35kg/sq.cm. in foundation and plinth in CM 1:6 ( 1 Cement: 6 Fine Sand) Extra for
brick in super structure above plinth level up to floor two level A) Modular
Providing and laying polished Kota stone slab flooring over 20mm (Average) thick base
of cement mortar 1:6 (1-cement : 6-coarse sand) or L.M. 1.1.5 (1-Lime putty :1.5 -
12 coarse sand) laid over and jointed with grey cement slurry mixed with pigment to Sqm 115.74 992.66
match the shade of slab including rubbing and polishing etc. complete. (A) 25mm thick
Providing 15mm thick cement plaster in single coat on fair side Brick/Concrete wall for
13 interior plastering upto floor two level finished even and smooth in : 1) Cement Mortar Sqm 551.57 188.42
1:3 ( 1cement : 3 sand )
Providing 20 mm thick cement plaster in single coat on single or half brick wall for
14 interior plastering upto floor two level finished even and smooth in : 1) Cement Sqm 147.84 217.94
Mortar 1:3 ( 1cement : 3 sand )
20mm thick sand faced cement plaster on wall upto hight 10 meters above ground
level consisting of 12mm thick backing coat of CM 1:3 ( 1 cement : 3 sand ) and 8mm
thick finishing coat of CM 1:1 ( 1 cement : 1 sand ) etc complete
White washing with lime on wall surfaces( two coats) to give an even shade including
16 thoroghly brooming the surface to remove all dirt, mortar drops and other foreign Sqm 699.40 12.41
Finishing wall with water proofing cement paint on wall surfaces (two coats) to give an
approved brand and manufactures and of required shape even shade after throughly
17 brushing the surface to remove all dirts, and remains of loose powdered material. Sqm 172.55 57.44
PUMPING STATION AT PAKSHI BHAVAN
Item Description Unit Qty Rate Amount
Providing and fixing copper lightning arrestor incl. copper strip and earthing plate etc.
complete (incl. cost of excavation for earthing plate etc.
Providing and fixing rolling shutters of approved make made of 80mm wide MS Laths
inter locked together through their entire length and jointed together at the ends by
end lokes mounted on specially designed pipe shaft with bracket plates, guide
channels and arrangements for inside and outside locking with push pull operation
complete excluding the cost of hood cover and spring A) shutters having width
Providing and fixing 35 mm thick shutters for Doors, windows and clearstory windows
20 including blackenamelled M.S. butt hinges with necessary screws. (A) Indian teak Sqm 3.60 3,656.67
wood. (i) Fully Panelled.
Providing and fixing 50 cm wide M.S. Ladder fabricated from M.S. Flats 10 mm x 75 mm
with 20 mm dia steel bar steps in double rows, @ 30 cm C/C. The include stays of
mm x 50 mm flats fixed at 3 meter C/C with welding anchoring and 3 coats anticorrsive
paint. M.S. Ladder(Without safety cage)
Providing an fixing 25 mm x 5.2 mm MS railing with three horizontal rows and posts of
angle iron of size 65 mm x 65 mm x 8 mm RCC 150 mm and 1.15 meter height and
placed at 1.85 mt / c/c including painting two coats and anchorage in CC etc complete
Providing and fixing depth gauge painted on TW plank 25 mm / MS plate 4 mm thick
float, level indicator sliding wire on standard pullies incl. necessary arrangement to
prevent the swinging etc. complete with calibration up to 5 mt height.
Providing, installing & commissioning Lifting Device including all electrical cable
connection complete: Chain pulley block 3 tonne capacity
Purchasing & supplying at site of works, with Railway freight, loading, unloading,
25 carting, etc. complete such as joints, channels, angles, iron rails, etc. Angles 10mm & MT 1.00 72,916.00
above thick For EOT Crane
Labour charges for lowering laying, erecting, fixing, various size of M. S. section such as
26 joints channel, angles plates etc. complete. do - with fabrication. MT 1.00 13,069.75
Single Girder EOT Crane: Supply, installation, testing & commissioning single girder
type fully electrically operated EOT crane with electrically operated hoist, class II duty,
geared travelling trolley with seven meter lift complete with long travel rail track (40
mm sq. bar), moving or cross girder, all three motions electrically operated by suitable
27 rating motor IP 54, control panel & down pendant control block, brake, safety device, Nos 1.00 5,54,250.00
cables form motor to starter panel & other required accessories & tested as per IS
Specifications.
3 T, Span-9 m - 12 m, Long travel-12 m, Lift-6 m - 10 m.
Total Amount (In Rs.) =
Total Amount (In Rs.) =
SCREEN CHAMBER AT PAKSHI BHAVAN PS
Item Description Unit Qty Rate Amount
Sinking single well of internal Area and thickness of steining as specified up to the
level as specified in all sorts of soil including hard murrum, boulders and all strata type
& strata up to the level as per drawing by dredging, dewatering, drop chiselling with
necessary kentiedge and with mechanical means as may be necessary for this type of
work including all labour. plant machinery etc. complete. Zero level to be considered
from cutting edge level. Including all labour charges with Dewatering but Excluding
cost of Cutting Edge & Well steining For Screen Chamber 1. 0 to 3 mt depth
2 2. Beyond 3 mt up to 6 mt depth Rmt 3.00 4,340.78
3 3. Beyond 6 mt to 9 mt depth Rmt 2.40 4,654.43
Providing fabricating and placing cutting edge and curbs as per design MT and drawing
manufactured from structural steel or M.S. plate confirming to ISS 226-1962 incl.
Riveting, welding etc. complete. incl. m.s.bars, anchor
bolts and structural steel etc complete.
Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4)
(proportions as per mix design or as per Table 9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work,
including scaffolding centering, form work, needle vibrated consolidation, curing
comp. up to 6 meter depth or height (excluding cost of reinforcement and neat
finishing) with centering and shuttering/deshuttering etc. comp. for structure for
other than water retaining. Screen Chamber
Providing and cast in situ C.C. in grade M-25 proportions of ingredients as per mix
design by weigh batching using granite, quartzite trap metal of size 12 mm to 20 mm
and or 6 mm to 12 mm including scaffolding centering formwork, needle vibrated
consolidation, curing and hydraulic testing etc. complete (excluding cost of
reinforcement) with centering and shuttering/deshuttering etc. comp. up to 6 meter
height /depth Av. G.L.for all water retaining structures
a) Base slab Screen Chamber
7 b) Vertical Wall Screen Chamber cum 22.31 9,126.40
Supplying, cutting, bending, binding, and placing in position steel as per plan and
design and as per ISS 2502 including cost of steel and binding wire for
8 reservior/structures only including lift up to 6 mt. height or depth below G. L. for all MT 3.35 84,189.20
diameters. Do-Thermo mechanically treated (TMT)bars Fe-415 grade for all diameters.
Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior
9 plastering upto floor two level and finished even and smooth in (iii) Cement mortar Sq.mt. 68.80 103.40
1:6 (1-cement:6-sand) Inside Plaster Screen chamber
Providing and fixing 50 cm wide M.S. Ladder fabricated from M.S. Flats 10 mm x
mm with 20 mm dia steel bar steps in double rows, @ 30 cm C/C. The include stays of
10 mm x 50 mm flats fixed at 3 meter C/C with welding anchoring and 3 coats
anticorrosive paint.
Providing Screening arrangement in Screen chamber, fixing of screen for screening.
Top cover for screen chamber with locking arrangment M.S. bar cover to be provided
Total Amount (In Rs.) =
Total Amount (In Rs.) =
Item Description Unit Qty Rate Amount
Designing (aesthetically) and constructing R.C.C frame
structure of pump room with positive suction / Negative
Upto 6.00 M (Plinth Level to Top slab Beam bottom)
1. Minimum 15 % opening for ventilation should
be provided. Sq.M
2. Pump room rolling shutter, door and windows t.
of aluminium section and window grill of iron
should be provided (Included in Cost).
3. Plinth level of Pump house should be min.1
meter above GL.
4.Cost does not include foundation for pumping
Total Amount (In Rs.) =
Total Amount (In Rs.) =
Construction of CC Road
Item Description Unit Qty Rate Amount
Rolling and consolidation of soling including filling in depression
1 which occurduring the process, with powerroler 8 tonne to 12 Sqmt 19,723.20 22.36
Providing and laying cement concrete 1:3:6 (1-Cement : 3- coarse
sand : 6- hand broken stone aggregates 40 mmnominal size) and
curing complete excluding cost of formwork in (A) Foundation
Providing and laying in position Ready Mixed M-200 grade
concrete for reinforced cement conctere work , using cement
content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in
transit mixer for a lead up to 10 kms having continuous agitated
mixer, manufactured as per mix design of specified grade for
reinforced cement concrete work including pumping of R.M.C.
from transit mixer to site of laying, excluding the cost of
centering shuttering finishing and reinforcement including cost of
admixtures in recommended proportions as per IS: 9103 to
accelerate/ retard setting of concrete, improve workability
without impairing strength and durability as per direction of the
Engineer - in - charge. Without Fly Ash (Min cement level as per
latest IS 456 shall be maintained)
Total Amount (In Rs.) =
Total Amount (In Rs.) =
Temporary Road Restoration and Paver Block/Kota Stone
Item Description Unit Qty Rate Amount
Providing WBM surface using 45 to 63 mm size machine
crused BT metal of 150mm compacted thickness in two
layer using 20% screening 11.20mm 0.16 cum and
cum stone dust as filler including watering and
consolidation of WBM with vibrator roller
Providing and fixing pre-cast Rubber Dye / steel Dye inter
locking concrete block 60mm thick with grade of concrete
M300 pnumatic compressed / vibrated mechanically and
as per approved design Confirming to IS 15658 :
including 35 mm Sand layer for levelling and filling the
joint with sand in proper line and level as per guidlines of
IRC : SP 63-2018 etc. Complete.
Providing and laying polished Kota stone slab flooring over
20mm (Average) thick base of cement mortar 1:6 (1-
3 cement : 6-coarse sand) or L.M. 1.1.5 laid over and jointed Sqmt 16,506.00 1,096.33
with grey cement slurry including rubbing and polishing
etc. complete. (B) 30 mm thick
Total Amount (In Rs.) =
Total Amount (In Rs.) =
Item Description Unit Qty Rate Amount
Design, supply, construction, installation, testing and
commissioning of 14.00 MLD Capacity sewage treatment plant
based on Open Technology with Biological Nutrient Removal
(BNR) with MCC panel room, DG set and all civil, electrical,
mechanical, piping and instrumentation works with three
months trial run including but not limited to;
a) Connecting the existing rising main with all fittings up to the
b) Internal roads of 4.5m
c) 33% green zone
d) Providing compound wall and
e) Discharge effluent pipe up to 500 m.
All other Constitions and General Technical Specification are as
Total Amount (In Rs.) =
Total Amount (In Rs.) =
02-YEARS OF OPERATION AND MAINTENANCE
Item Description Unit Qty Rate Amount
Comprehensive Operation and maintenance of the various
components of Under ground Drainage scheme undertaken in this
tender mainly sewer collecting network, pumping station, Rising
Main pipeline, pumping machinery & Electrical works & other works
as a whole including:
1) Breakdown Maintenance or Emergency Maintenance,
2) Day to day Maintenance,
3) Preventive or Periodic Maintenance,
1 4) Major Maintenance (or Special repairs and replacement including Year 1.00 14,09,625.94
Training to O & M staff of Municipality.
The rate shall also include all consumables and deployment of
Manpower but excluding electric power (The electrical bill for power
shall be paid by the municipality).
The O & M work shall be carried out as per detailed specifications in
the tender & maintaining the record for the same.
For 1st year O&M
2 For 2nd year O&M Year 1.00 14,09,625.94
Total Amount (In Rs.) =
Total Amount (In Rs.) =
07-YEARS OF OPERATION AND MAINTENANCE FOR STP
Item Description Unit Qty Rate Amount
Operation and Maintenance of the various components of
Upgraded 14 MLD Sewage Treatment Plant based on extended
aeration system as per NGT Norms and other Under Ground
Drainage Work as a whole incluiding,
1) Breakdown Maintenance or Emergency Maintenance,
2) Day to day Maintenance,
3) Preventive or Periodic Maintenance,
4) Major Maintenance (or) Special repairs and replacement
including Training to O & M staff of Municipality. The rate shall
also include cost against fixed charges, consumables flow
1 dependent charges, maintenance repair charges, replacement Year 1.00 22,76,466.70
charges, miscellaneous charges and deployment of manpower
but excluning electric power. all the components executed
under this tender mainly pimping machinery, pumping station.
Rising Main, including estabilishment charges and all materials
on repairing of pipe line and other civil works and pumping
machinery. The O & M work shall be carried out as per detailed
specificstions in the tender & maintaining the record for O & M.
2 For 2nd Year Year 1.00 23,90,290.04
3 For 3rd Year Year 1.00 25,09,804.54
4 For 4th Year Year 1.00 26,35,294.76
5 For 5th Year Year 1.00 27,67,059.50
6 For 6th Year Year 1.00 29,05,412.48
7 For 7th Year Year 1.00 30,50,683.10
Total Amount (In Rs.) =
Total Amount (In Rs.) =
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01_SBD_GUDC_Works_Tech_Bavla_UGD-II.pdf
02_Vol-I-B_SBD_GUDC_Works_GCC_Bavla_UGD-II.pdf
03_Vol-II-A-Part-1_Extent_of_Works_STP_UGD.pdf
04_Vol-II-A-Part-2_Gen_Tech_And_Process_Require_STP.pdf
05_Vol-II-A-Part-3_ITC_Mod_STP.pdf
06_Vol-II-B-Part-1_TS for Civil Work STP.pdf
07_Vol-II-B-Part-2_TS for Mechanical Work STP.pdf
08_Vol-II-B-Part-3_TS for E and I Work STP.pdf
09_Vol-II-C-Part-1_Func_Guran_of_the_Plant_Mod_STP.pdf
10_Vol-II-C-Part-2_Data sheet for Process and Civil_STP.pdf
11_Vol-II-C-Part-3_Data sheet for Mechanical_STP.pdf
12_Vol-II-C-Part-4_Data sheet Electrical_STP.pdf
13_Vol-II-C-Part-5_Data sheet Instrumentation_STP.pdf
14_Vol-II-C-Part-6_Data_sheet_UGD.pdf
15_Vol-II-D_Part-1_Item_Tech_Spec_Civil.pdf
16_Vol-II-D_Part-2_Tech Spec - E and M.pdf
17_Vol-II-General_Part-1_Gen_Tech_Spec_Civil_R_and_B.pdf
18_Vol-II-General_Part-2_Gen_Tech_Spec_Electrical.pdf
19_Vol-III_SBD_GUDC_Works_Price_Bid_Bavla_UGD-II.pdf
20_Vol-III_Bavla_UGD-II_STP_Schedule-B_Final.pdf