Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.6 LAccepted-AOC | ₹24.6 L Quoted ₹25.5 L | L1 | Accepted-AOC Accepted as L1 bidder |
| 2 | L2₹25.9 LRejected-Finance SHIBNAGAR COLLEGE ROAD EXTN AGARTALA TRIPURA WEST | AGARTALA | WEST TRIPURA | TRIPURA | ₹25.9 L | L2 | Rejected-Finance Quoted rate higher than L1 bidder |
Tender Value
₹21.2 L
EMD Value
₹42,481
Closing Date
3 Feb 2026, 5:00 pmClosed
EXECUTIVE ENGINEER, IE DIVISION, AMBASSA
JAWHARNAGAR, AMBASSA, DHALAI TRIPURA
PROVIDING EI AT DOUBLE STORIED CMO OFFICE BUILDING AT KHOWAI DISTRICT, KHOWAI TRIPURA
2026_CEPWD_69610_1
85/EE-IED/AMB/2025-26
Open Tender
Electrical Works
60 days
KHOWAI
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
₹42,481
Yes
3 Mar 2026
27 Jan 2026
4 Feb 2026
27 Jan 2026
3 Feb 2026
27 Jan 2026
Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvc insulated Copper conductor cable (FR) in pvc casing and capping complete with 6/10 amps modular type switch, cover plate, surface modular switch board including connection etc as required:- (As Per TSR 2021, S.L No.201)
Short point:-
Medium point:-
Long point:-
Providing and fixing of 3 pin 6/10 amps plug point with modular type 6/10 amps switch and socket including connection with 2x1.5 sq. mm PVC insulated Copper conductor cable (FR) on surface modular switch board, earthing the 3rd pin etc. as required:-(As Per TSR 2021,S.L No.203)
Providing and fixing of 3/6 pin 16/20 amps plug point with modular type 16/20 amps switch and socket including connection with 2x2.5 sq. mm PVC insulated Copper conductor cable(FR) on surface modular switch board, earthing the 3rd pin etc. as required:-(As Per TSR 2021, S.L No.204)
Wiring for Circuit/Sub-main wiring with the following sizes PVC insulated copper conductor cable (FR) in PVC casing capping etc. as required. (As Per TSR 2021, S.L No.205):-
2 x 1.5 sq.mm.
2 x 2.5 sq.mm
2 x 4 sq.mm
2 x 6 sq.mm
4 x 10 sq.mm
4 x 16 sq.mm
4 x 35 sq.mm
Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required:- (As per TSR-2021, Sl. No.503)
1 x 1.5 sq.mm.
1 x 2.5 sq.mm.
1 x 4 sq.mm.
1 X 6 sq mm.
1 X 10 sq mm
Supplying and fixing of the following electrical accessories including necessary connection etc. as required.(As per TSR-2021, Sl. No.604)
Ding dong call bell.
32 amps DP kit kat switch:-
Supplying and fixing of the following electrical accessories including necessary connection etc. as required.(As Per TSR 2021, S.L No.609)
5 step fan regulator (2M):-
20/25 amps single phase motor starter switch (2M):-
6/10 amps one way SP switch (1M) :-
Earthing with Copper earth plate 600 mm x 600 mm x 3 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12"x 12" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required:-(As Per TSR 2021, S.L No.703)
Supply and fixing of 25mm x 3mm Copper on walls/ floor of the building for horizontal/ vertical network including necessary spacers and porcelain insulators at regular intervals. (As Per TSR 2021, S.L No.714)
Supplying, Installation of Lighting Arrestor, ESE Lightning conductor LAP CX-040 with GI mast 5.00 mtrs long with base plate 250x 250x3 mm, Bakelite Insulator, Mounting Accessories, (Stay wire-15.00 mtrs + Pin fasten -08 Hook/ Ring Fastener-3 nos, U clamp-3 nos), Lighting Counter, Test Link, Earthing(Copper Rod 3 mtrs, 25kg chemical, Polyplastic cover) and 15 m long 70 sq. mm single core flexible copper cable:-( As per F.LOC-1/57/EE-IED/AMB/2024-25/3432-40.)
Supplying and fixing of powder coated sheet steel enclosure on surface/ recess, suitable for 240/415 volts MCB/Isolator/RCCB (SP/ SPN/ DP/ TP/ TPN/FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connection as required.(As Per TSR 2021,S.L No.1208)
2 way SPN MCB DB (single door):-
(2+10) / 12 way SPN MCB DB (double door):-
4 way horizontal TPN MCB DB (Double door):-
6 way horizontal TPN MCB DB (Double door):-
Supplying & fixing of following ratings MCB B/C curve having breaking capacity 10 KA in the existing MCB DB including connection as required:-(As Per TSR 2021, S.L No.1215)
6 to 32 amps SP MCB:-
6 to 32 amps DP MCB:-
Supplying & installation of isolators of following ratings in the existing MCB DB including connection etc as required:-(As Per TSR 2021, S.L No.1217)
40 amps DP isolator:-
Supplying, installation, testing & commissioning of powder coated prewired panel board suitable for 415 volts TP MCCB as incomer & outgoing including busbar & connection as required of the following ratings & sizes:-(TSR (IE)2021 SL.No.1210)
4 way TP MCCB outgoing & TP MCCB incomer upto 400 amps:-
Supplying, installation, testing & commissioning of powder coated prewired digital meter module complete with ammeter, voltmeter, phase indicator lamp, control fuses, CTs, in the existing panel board including connection etc. as required:-(TSR (IE)2021 SL.No.1212)
Supplying, installation, testing & commissioning of powder coated side cable module (1 pair) in the existing panel board including connection etc. as required suitable for the following sizes and ratings:-(TSR (IE)2021 SL.No.1213)
4/6 way outgoing and incomer upto 400 amps :-
Supplying & installation of TP/FP MCCB of following ratings in the existing MCCB enclosure/ panel board including connection etc as required (Ics=100% of Icu with adjustable settings):-(TSR (IE)2021 SL.No.1219)
200 amps FP MCCB, Breaking capacity 36KA (Thermal Magnetic) :-
16 to 100 amps FP MCCB, Breaking capacity 16/18KA (Thermal Magnetic):-
Supplying and installation of changeover switch of following ratings with enclosure including necessary connection etc. as required:-(As Per TSR 2021, S.L No.1204)
200 amps FP on load change over switch (Front handle with enclosure):-
Supplying and installation of Bus bar chamber of the following ratings and sizes made of steel sheet enclosure with all accessories including necessary connection etc. as required:-(As Per TSR 2021, S.L No.1201)
100 amps 415 volts four strip Copper busbar chamber 6 ways of size (610mmx410mmx120mm):-
Supplying and installation of fuse unit kitkat/HRC/HBC of the following ratings in existing main switch/panel board including necessary connection etc as required:-(As Per TSR 2021,S.L No.1203)
200/250 amps kitkat porcelain fuse unit with base(rewireable):-
Supplying & installation of Surge Protection Device (SPD) of following ratings in the existing Panels/MCB DBs including necessay connections etc as required:-(TSR (IE)2021 SL.No.1216)
Surge Protection Device (SPD, withdrawable) (Type-2) with Imax 70 KA (3P+N) :-
Catridge for Surge Protection Device (SPD) (Type-2) with Imax 70 KA (1P+N/3P+N) :-
Supplying and fixing of following luminaries complete with necesaary accessories and connection etc. as required (Commercial lighting fixtures with 50,000 burning hours):- (As Per TSR 2021, S.L No.1101)
Surface mounted box type batten suitable for single 18/20 watt integrated LED tube lamp (without lamp):-
Surface mounted box type batten suitable for double 18/20 watt integrated LED tube lamp (without lamp):-
Supplying and fixing of following LED Tubes, retrofit bulbs/lamps for LED luminaries including necessary connection etc. as required:- (As Per TSR 2021, S.L No.1103)
18/20 watt LED tube with integral driver and polycarbonate diffuser (50000 burning hours and minimum lumen output of 100lm/watt):-
14 watt LED retrofit lamp with polycarbonate body and aluminium heatsink :-
Supplying and fixing of following surface/recess mounted LED luminaries in powder coated die cast housing complete with high efficiency polycarbonate diffuser and necessary connection etc. as required (with 50000 burning hours and minimum lumen output of 100 lm/watt):-(As Per TSR 2021, S.L No.1101)
Surface mounted round/Square shaped 18/20 watt LED downlight with integral driver and high quality polycarbonate diffuser:-
Supplying and fixing of following luminaries complete with necesaary accessories and connection etc. as required (Commercial lighting fixtures with 50,000 burning hours):- (As Per TSR 2021, S.L No.1001)
Bulk head fittings with frosted/clear glass suitable for GLS or retrofit CFL/LED (without lamp) : -
Supplying & fixing of 1200 mm sweep white color AC ceiling fan capacitor type double ball bearing complete with 300 mm down rod,canopies,shackles, 3nos blades, including wiring the down rod with 2x1.5 sqmm PVC insulated Copper conductor cable(FR) (ISI marked, BEE 1 star/minimum service value 4.0 m3/min/W) : - (As Per TSR 2021, S.L No.802)
Supplying & installation of 225/230 mm sweep metalic body exhaust fan including connection etc as required:-(As Per TSR 2021, S.L No.816)
Supplying & installation of shutter for 230/300 mm sweep metalic body exhaust fan in the existing hole as required:-(As Per TSR 2021, S.L No.821)
Making different sizes of hole in the wall for fixing of exhaust fan including finishing the same with cement plastering and painting etc as required:(As Per TSR 2021, S.L No.831)
Supplying and fixing of following outdoor LED luminaries in powder coated die cast housing complete with heat resistant tempered glass/diffuser including necessary connection etc. as required (50000 burning hours and minimum lumen output of 100 lm/watt):-(As Per TSR 2021, S.L No.1102)
60 watt LED street light fixture with integral driver and secondary lens (IP 66):-
Supplying and laying of following sizes XLPE insulated PVC sheathed Aluminium conductor Un-armoured cable including necessary connection etc as required.(As Per TSR 2021, S.L No.1302)
3 core 4 Sq mm
Drawing of armoured/un-armoured cable with proper saddeling etc as required:-(As Per TSR 2021, S.L No.1511)
Supplying & fixing of G.I. pipe (medium gauge) bracket fabricated at suitable angle for fixing of outdoor light on wall/ RCC base with necessary MS clamp, nut, bolt etc as required:-(As Per TSR 2021, S.L No.1501)
40 mm dia
Supplying and fixing of MS frame made of (25 x 25 x 5)mm MS angle with necessary support by (40 x 6)mm MS flat and 10 mm thick boiled plywood on top, grouted on wall with 4 nos leg(25 x 25 x 5 mm MS angle 20 cm long) finished with red oxide and 2 coat synthetic enamel paint including necessary cc work, mending the damages & painting etc as required:-(As Per TSR 2021, S.L No.1502)
Supplying of 25 cm long ‘L’ hook made with 40mm x 6mm MS flat and fixing with necessary fasten nuts including finishing, painting etc as required. (As per TSR-2021 Sl.No.1508)
Supplying, installation, testing and commissioning of following ratings true online double conversion UPS with IGBT based rectifier and inbuilt isolation transformer, 50/60Hz (Auto sensing) frequency, P.F range 0.95-0.99, voltage regulation +/-1%, Pure sine wave form, total harmonic distortion < 5% with full load, Noise level 50db at 1m, LED indication for Normal mode/Load on battery/Load on bypass/System fault, Audible alarm for Mains failure, low battery, Overload, fault and Bypass mode complete with necessary battery bank, M.S Rack for mounting battery bank, Battery inter link cables and all other necessary accessories including connections etc. as required:- (As per rate analysis)
5kVA, 240 VDC1Ph input/1Ph output Online UPS with 20 nos of 12V, 65Ah SMF VRLA Battery bank with (for 2hrs Backup) etc.as required:-
3 kVA, 72 VDC , 1Ph input/1Ph output Online UPS with 6 nos of 12V, 100 Ah Battery bank (for 2hrs Backup) etc. as required:-
Supplying and fixing of thermoplastic cable junction box with connectors suitable for following sizes cable : -(As Per TSR 2021, S.L No.1405)
1.5 sqmm - 4 sqmm Cable:-
Supplying and fixing of Copper terminal ends (LUGS) - long barrel of following sizes: -(As Per TSR 2021, S.L No.1402)
Supplying and installation of secure zone 4 kg ABC powder fire Extinguisher gross weight 6.38 kg, empty weight 2.38 kg, can height 372 mm, diameter 150 mm, discharge time minimum 13 seconds , discharge mechanism - squeeze grip type range minimum 2 meters applicable on class A,B,C and electrically started fire, A rating- 2A, raring-55B, can contrast- mig welded,valve construction- forging & machining, external coating of can..epoxy polyester powder coating, sheet metal thickness. 1.60mm, conforms to BIS standards, 5 years warranty(make. ceasefire/secure/fireshield) (Rate as per agreement no 74/EE/IED/AMB/2020-21):-
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_70839.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.35 MB
DNIeT85.pdf
Tender Documents • 2.62 MB
BOQ_70839.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid