Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹55.7 LAccepted-AOC SCO 26 SEC 30 KURUKSHETRA 136118 | KURUKSHETRA | HARYANA | 136118 | ₹55.7 L | L1 | Accepted-AOC AOC |
| 2 | L2₹59.0 L+₹3.3 L (5.95%)Rejected-Finance C 311 IIND FLOOR RAMPHAL CHOWK PALAM EXTENSION SOUTH WEST DELHI DELHI 110077 | SOUTH WEST DELHI | DELHI | 110077 | ₹59.0 L+₹3.3 L (5.95%) | L2 | Rejected-Finance Highest |
| 3 | Rejected-Technical | - | - | Rejected-Technical Rejected |
Tender Value
₹66.7 L
EMD Value
₹1.3 L
Closing Date
2 Jun 2022, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Divn. PWD B and R Br. Ambala Cantt.
Const. of ATC and Passenger Terminal building at Civil Aerodrome Pinjore, Panchkula. (Pdg. VRV/VRF AC System Only).
2022_HRY_222822_1
PWD/Elect-KNL/Elect-AMB/110269
Open Tender
Construction Works
Works
120 days
Ambala Cantt.
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
₹1.3 L
Yes
11 Jul 2022
20 May 2022
3 Jun 2022
20 May 2022
2 Jun 2022
20 May 2022
Amount
Earthing Earthing with tinned copper earth plate 00mmx600mmx3mm thick each 9267including accessories and providing masonry enclosures with cover platehaving locking arrangement and watering pipe etc. (but without charcoal orcoke and salt) etc. complete as required. HSR No. 24.1.4
Extra for charcoal or coke and salt for G. I. plate or copper plate earthelectrode. HSR No. 24.1.5
Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for metre connections etc. as required with all labour and material HSR No. 24.1.8
Providing and fixing 25 mm x 5mm copper strip on surface or in recess for metre connections etc. as required with all labour and material HSR No. 24.1.10
AIR SIDE WORKS Factory fabricated Duct-GI duct Supply, installation, and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. as per approved drawings and specifications of following sheet thickness complete as required and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to make Collors/bends/plenums/suit pieces Only 0.63mm (24 gauge) GSS HSR No. 25.7
0.8mm (22 gauge) GSS HSR No. 25.7.1
(Make: Eco Duct/Zeco,Pioneer Airtech (Sheet Make: Tata, Sail,Jindal) EQUIPMENT VRV/VRF Supply, installation, testing and commissioning of Variable Refrigerant Flow modular type air-conditioning system suitable for Cooling & Heating both by multiple scroll/DC Twin rotary compressor controlled by individual inverters for each compressor complete with indoor and outdoor units with individual wired and wireless /wired remote controller for indoor units and centralized controller, interconnecting refrigerant piping, full charge of refrigerant gas (R-410A) & oil, control cabling and fittings etc. as per details given in specifications and having following items. The out door units shall be suitable for 3 phase 4 wire system, 415V + 10 %, 50 Hz AC supply and indoor shall be suitable for Single phase 220-240V, 50 Hz AC supply. Outdoor Units Supply, installation, testing & commissioning of Modular type outdoor units equipped with highly efficient multiple scroll compressors fully inverter controlled (individual inverter for each compressor) i.e. changes its speed in accordance to the variation in cooling loads, special heat exchanger, low noise condenser fan, auto check function for connection error, auto address setting and capacity as mentioned below including all hardware & accessories & including full charging of R-410A refrigerant gas complete i/c powder coating complete as per specifications. The units should be with necessary weather protection coating. The coating should be done before bringing the units to site. Out door units shall be provided with MS stand of suitable size duly painted with corrosion resistant paint suitable for outdoor application. Including supply, installation, testing and commissioning of centralized remote control system for monitoring the parameters of entire system from a centralized location. All the units shall be provided with built-in microprocessor control panel, for automatic operation and capacity control. All compressor shall have inverter technology i.e. outdoor units shall have all inverter based compressor. All Bidders has to submit the test certificates along with the delivery of VRF/VRV Units at site. A draft Format of the same need to be submitted along with in the Technical Bid Variable refrigerant flow modular type air- conditioning system suitable for Cooling/Heating by inverter driven capacity control compressor Outdoor unit having minimum COP at 50% Load to be >=5.5and at 100% Load to be 3.9 - 3% maximum (To crosscheck COP original data sheet to be provided from OEM) Insurance of Units ,Unloading at site, placement of Outdoor Units on the foundation,stands, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned VRF/VRV by OEM. Note: The civil foundations reqd shall be made by the tenderer 28 HP
Supply, installation, testing and commissioning of below mentioned capacity Ductable/Casettes type Indoor air conditioners complete with fan and fan motor, inter connecting it with refrigerant piping, insulation , cabling, earthing, necessary galvanized steel supports etc. as per specification and drawing. The cooling coil shall be made of seamless copper tube. The tube shall be hydraulically or mechanically expanded and tested for 21 Kg/cm2. Indoor units shall have a wired remote control. They shall be operated through from the wired remote control from the respective locations. Corded Remotes are seperately payable. The Drain pump as a standard accessory and shall be included in the price of units Ductable Acs 8 Tr
Four Way Cassette Acs along with its Grill Panel 1.6 TR
Providing and fixing of Corded remote controls with cord for ductable/Cassette Acs
Providing and fixing of Cordless Remotes
Centralized Controller Providing, Fixing & Running Centralized Controller (capable of at least to control 64 indoor units) for all VRV/VRF /AHU Indoor /Outdoor Units and Must Be Compatible with BMS Make: Toshiba,MitisubishiElectric,Daikin,O'General,Samsung,Voltas
Refnet / T / Y- Joints Supply Installation, Testing and commissioning of fittings Ref Net / T / Y-joints etc as per specifications. Make: Toshiba,MitisubishiElectric,Daikin,O'General,Samsung,Voltas
Refrigerant Piping Supply and Installation of Interconnecting Refrigerant Piping (Make : Rajco,Mandev,Totaline,Hariom) of various sizes as required for the full functionality of the VRF /VRV system etc. complete in all respects duly insulated with Class 'O'closed cell nitrile rubber as per specifications of the manufacturer. the contractor shall submit a detailed drawing approved by the manufacturer showing the piping sizes & layout to be followed at the site with the tender document. the contractor shall also get the drawings showing outdoor units in connection with indoor units approved from the HVAC consultant in original from and then the head office of the manufacturer with a certificate stating that the piping layout is as per company specifications for full functioning of the system. (Insulation Make: K-Flex,Armacell,Aerofoam) 41.3 mm OD (insulation = 19mm)
38.2 mm OD (insulation = 19mm)
34.9 mm OD (insulation = 19mm)
31.8 mm OD (insulation = 19mm)
28.6 mm OD (insulation = 19mm)
25.4 mm OD (insulation = 19mm)
22.2 mm OD (insulation = 19mm)
19.1 mm OD (insulation = 13 mm)
15.9 mm OD (insulation = 13 mm)
12.7 mm OD (insulation = 13 mm)
9.5 mm OD (insulation = 13mm)
6.4 mm OD (insulation = 13 mm)
Nitrile Insulation Supplying , installation, testing & commissioning of external thermal insulation on ducts with closed cell elastomeric nitrile rubber insulation of thickness 13 mm with density 40-60 Kg/m3 ,ANTI MICROBIAL/ANTI FUNGAL,Class 'O' material AS PER BS476 PART6&7 ASTM E 84. The product shall have temperature range of –40oC to 105oC.as per specifications and approved shop drawings Armacell/K-Flex/Aerofoam
Accoustic Lining Supply, Installation, Testing and Commissioning of Acoustic lining inside ducts/plenum using open cell nitrile rubber foam having microban anti-microbial/ anti fungal product protection and of 160-180 kg / m³ density as per ASTM D3575, class 1 ratingn As per BS476,PART-7, cut to required sizes and to be stuck to the inside of duct surfaces with adhesive as approved by the manufacturer. (Rubber based solvent) 10 mm thickness accosound Board Armacell/K-Flex/Aerofoam
Supplying, fixing testing commissioning of supply air diffusers (Round/Square) of powder coated aluminium complete as rquired. Make:Tristar/Caryaire/Ravistar/Pineair
Dampers Supplying, fixing testing commissioning of Al. volume control compete as required. Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
Supply, installation, testing & commissioning of CBRI approved Fire duct Dampers for at least 90 min fire rating as per UL555:1955 Specifications without Sleeve
Supply, installation, testing & commissioning of Spring Return Actuator and Control Panel Complete with Heat Sensors , Complete Control wiring and Limit switch,4NM/7NM/9NM,(24VAC/220VAC)
Supplying, fixing testing commissioning of Aluminium supply air collar damper Make:Tristar/Caryaire/Ravistar/Pineair
Bird Screen Louver Supply, Installation, Testing and Commissioning of extruded aluminium louvres with frame bird screeen 50 mm pre-filter with frame, mounting arrangement etc. as per specifications and drawings. Make:Tristar/Caryaire/Ravistar/Pineair
Condensate Drain Piping: Providing Hard PVC (10KG/CM2) pipes of various sizes for condensed water drainage from Indoor unit to nearest disposal point in toilet/ outside rain water harvesting system as approved by architect/consultant/Client All necessary civil works like cutting & chasing of walls/floor/ glass etc. and make them good thereof 40 MM dia with 6mm Class O Nitrile Insulation
32 MM dia with 6mm Class O Nitrile Insulation
25 MM dia with 6mm Class O Nitrile Insulation Make : Diplast/Polypack/Astral
Power & Control Works Supplying and laying of following 1100 volt grade PVC insulated sheathed copper conductor armoured cables in trenches, on walls clamped to wall with suitable clamps, saddles, and fixing bolts, or laying in ground including cost of digging brick and sand protection, and including jointing / connecting / terminating, testing and commissioning : 4C x 35 Sq. mm Aluminium(armoured) Conductor
4C x 16Sq. mm Copper (armoured) Conductor
4C x 10Sq. mm Copper (armoured) Conductor
4C x 6Sq. mm Copper (armoured) Conductor Make : Havell's,Eko,Finolex,Polycab
For Indoor Units, Providing & fixing of electrical supply Flexible Cabling of 4 core x 2.5 sq. mm copper in suitable conduits between IDU & Room DB. Make : Havell's,Eko,Finolex,Polycab
Control Cabling Providing & fixing control cum transmission wiring/ Control Cabling of 2 core x 1.5sq. mm copper in suitable conduits between indoor and out door unit & indoor unit & its remote controller.
Providing & fixing control cum transmission wiring/ Control Cabling of 4 core x 1.5sq. mm copper in for Actuator/Motor , Fire Dampers & between IDU & Room DB.etc. Make : Havell's,Eko,Finolex,Polycab
Cable Tray Providing and fixing of perforated type cable tray made out of GI SHEET & HOT DIP GALVANISED for Running Copper Refrigerant Piping of of Following Sizes including nut bolts G.I Thread rods Complete in all Respect 50mm(H) x 450mm(W) x50 mm(H) and 2.0 mm Thick
50mm(H) x 300mm(W) x 50 mm(H) and 1.5 mm Thick
50mm(H) x 150mm(W) x 50 mm.(H) and 1.5 mm Thick
Main Electrical Panel (CPRI Approved) for VRV/VRF System (Panel 1) Supply,Installation,Testing and Commissioning Electrical Main Panel weather Proof outdoor Type Powder Coated Made out of TATA/SAIL/ESSAR/JINDAL/Reputed make sheet having thickness 2.0 mm for load bearing surfaces & 1.6 mm Non bearing surfaces duly processsed powder coated having Siemens grey colour or as approved by client or department (Outdoor Type with weatherproof canopy design)as per following specifications complete in all respect . Note : Manufacturer should have atleat CPRI Approval of 70 K INCOMING SUPPLY 320-400A ,3Pole MCCB,50 KA with Microprocessor release adjustable type.The MCCB shall be double break & the ICS=100% ICU = 1nos (for VRV unit 48 HP combination) Make : Schneider/ Siemens/ABB Auto Phase Sequence section ATS400 Amps for using with each section of VRV 28 HP for Auto Phase sequence with SPP alongwith On delay and required equipment for correction of Sequence. Make of ATS : Socomec/HPL/Schnieder/L&T Metering Section Multi function Digital meter with RS485 Port (Class 1.0) with Paramenters V, Amp, Frequency = 1No. Make : Schneider / Secure / Siemens/ABB/Elmeasure/L&T Control MCB SP C Curve= 3nos Make : Schneider/ Siemens/ABB CT's 400/5 = 3nos Make: AE/Essma/Newtek/Selec Indication Lamps LED Type RYB = 3nos Make : ABB/ Schneider/ Siemens/L&T/Reputed Outgoing Feeder for 28 HP VRV Units - 5nos (3W+2S) 63A ,3Pole MCCB,36 KA with Thermal magenetic release adjustable type.The MCCB shall be double break & the ICS=100% ICU = 5nos (for VRV unit 28 HP combination) Make : Schneider/ Siemens/ABB Spreader Link with phase Barriers = 5 sets Make : Schneider/ Siemens/ABB Rotary Mechanism = 5nos Make : L&T/ Schneider/ Siemens/ABB ELCB 63 Amps 4pole 300 MA= 5nos Make : Schneider/ Siemens/ABB Multi function Meter EM 64xx 1.0 RS or equavalent for EMS/BMS compatibilty Make: Schnieder/Nippen/HPL=5nos INDICATING LAMPS LED Type Make : ABB/ Schneider/ Siemens/L&T/Reputed for on postion for each section=5nos Control MCB SP C Curve for control Make : Schneider/ Siemens/ABB CT's 60/5 Make: AE/Essma/Newtek/Selec=5 sets Panel Fabrication of Powder Coated Enclosure made out of TATA/SAIL/ESSAAR/JINDAL/Reputed make CRCA sheet having 2 mm for load bearing surfaces & 1.6 mm for non load bearing surfaces ,duly processsed powder coated having Siemens grey colour. (Outdoor Type with weatherproof canopy design) Assembly charges of Aluminium Bus Bar 500A TPN Electrolite grade E91 having cross section 1X100X10mm for Phase & 100X5/50x10 mm for Neutral & Current carring capacity 1 A/Sq. mm2. inclusive of Insulators, colour coded Heat shrinkable Insulation sleeve (RYBN) Assembly of Hardware (PVC Channels/MCB Channels/Fibre-Glass/Gaskits/nuts/Bolts/washers/ Terminal blocks, etc) Complete Wiring inclusive of control wiring, power wiring, Aluminium Solid connections/interconnections including insulators, thimbles,etc Unloading at site, placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel.Materials for Wiring, Buttons, Tie Sticker Panel Make : Adlec/Siemens/Tricolite/Unitech Power System/Vrindavan Electricals
Main Electrical Panel (CPRI Approved) for VRV/VRF System (Panel 2) Supply,Installation,Testing and Commissioning Electrical Main Panel weather Proof outdoor Type Powder Coated Made out of TATA/SAIL/ESSAR/JINDAL/Reputed make sheet having thickness 2.0 mm for load bearing surfaces & 1.6 mm Non bearing surfaces duly processed powder coated having Siemens grey colour or as approved by client or department (Outdoor Type with weatherproof canopy design)as per following specifications complete in all respect . Note : Manufacturer should have atleat CPRI Approval of 70 K INCOMING SUPPLY 250A ,3Pole MCCB,50 KA with Microprocessor release adjustable type.The MCCB shall be double break & the ICS=100% ICU = 1nos (for VRV unit 48 HP combination) Make : Schneider/ Siemens/ABB Auto Phase Sequence section ATS250 Amps for using with each section of VRV 48 HP for Auto Phase sequence with SPP alongwith On delay and required equipment for correction of Sequence. Make of ATS : Socomec/HPL/Schnieder/L&T Metering Section Multi function Digital meter with RS485 Port (Class 1.0) with Paramenters V, Amp, Frequency = 1No. Make : Schneider / Secure / Siemens/ABB/Elmeasure/L&T Control MCB SP C Curve= 3nos Make : Schneider/ Siemens/ABB CT's 400/5 = 3nos Make: AE/Essma/Newtek/Selec Indication Lamps LED Type RYB = 3nos Make : ABB/ Schneider/ Siemens/L&T/Reputed Outgoing Feeder for 20 HP VRV Units - 4 nos (2W+2S) 40A ,3Pole MCCB,36 KA with Thermal magenetic release adjustable type.The MCCB shall be double break & the ICS=100% ICU = 4nos (for VRV unit 28 HP combination) Make : Schneider/ Siemens/ABB Spreader Link with phase Barriers = 4 sets Make : Schneider/ Siemens/ABB Rotary Mechanism = 4nos Make : L&T/ Schneider/ Siemens/ABB ELCB 40 Amps 4pole 300 MA= 4nos Make : Schneider/ Siemens/ABB Multi function Meter EM 64xx 1.0 RS or equavalent for EMS/BMS compatibilty Make: Schnieder/Nippen/HPL=4nos INDICATING LAMPS LED Type Make : ABB/ Schneider/ Siemens/L&T/Reputed for on postion for each section=4nos Control MCB SP C Curve for control Make : Schneider/ Siemens/ABB CT's 60/5 Make: AE/Essma/Newtek/Selec=4 sets Fabrication of Powder Coated Enclosure made out of TATA/SAIL/ESSAAR/JINDAL/Reputed make CRCA sheet having 2 mm for load bearing surfaces & 1.6 mm for non load bearing surfaces ,duly processsed powder coated having Siemens grey colour. (Outdoor Type with weatherproof canopy design) Assembly charges of Aluminium Bus Bar 500A TPN Electrolite grade E91 having cross section 1X100X10mm for Phase & 100X5/50x10 mm for Neutral & Current carring capacity 1 A/Sq. mm2. inclusive of Insulators, colour coded Heat shrinkable Insulation sleeve (RYBN) Assembly of Hardware (PVC Channels/MCB Channels/Fibre-Glass/Gaskits/nuts/Bolts/washers/ Terminal blocks, etc) Complete Wiring inclusive of control wiring, power wiring, Aluminium Solid connections/interconnections including insulators, thimbles,etc Unloading at site, placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel.Materials for Wiring, Buttons, Tie Sticker Panel Make : Adlec/Siemens/Tricolite/Unitech Power System/Vrindavan Electricals
Earthing Supplying, laying (saddling on slabs walls/ columns and connecting the following continuous earth conductors. Note: Any joint in the GI earth conductor shall be made by the process of brazing. GI 8 SWG wire earthing complete with thimbles etc
P/F of Fire retardant canvas connections between Fan & initial duct piece.
1st Year - Comprehensive maintenance& Operation cost (after free warranty period only) @ 4% on Original work done amount
2nd Year - Comprehensive maintenance& Operation cost @ 4.5% on Original work done amount
3rd Year - Comprehensive maintenance& Operation cost @ 5% on Original work done amount
4th Year - Comprehensive maintenance& Operationcost @ 5.50% on Original work done amount
5th Year - Comprehensive maintenance& Operationcost @ 6% on Original work done amount
Pacific Engineers
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .