Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.3 LAccepted-AOC 901 GH 83 SECTOR 20 PANCHKULA 134116 | PANCHKULA | HARYANA | 134116 | ₹18.3 L Quoted ₹18.4 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹20.0 L+₹1.6 L (8.87%)Rejected-Finance 154 GANDHI MARKET AMBALA CANTT HARYANA 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | ₹20.0 L+₹1.6 L (8.87%) | L2 | Rejected-Finance Being not lowest |
| 3 | Not Admitted-Finance | - | - | Not Admitted-Finance Price Bid not complied |
| 4 | Not Admitted-Finance 34 B A HOUSE NO 253 3 SECTOR C KALERHARI CHURCH ROAD AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | - | - | Not Admitted-Finance Price Bid not complied |
Tender Value
Refer Docs
EMD Value
₹48,000
Closing Date
22 Dec 2020, 6:00 pmClosed
Lt Col Sidhartha Singhal
GE (P) Dappar
Outsourcing for manning and operation of central AC plants at Mil stn Dappar under GE (P) Dappar
2020_MES_394154_1
GE (P) DPR-31/2020-21
Open Tender
Miscellaneous Services
Supply
330 days
GE (P) Dappar
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE (P) Dappar
₹48,000
Yes
5 Jan 2021
10 Nov 2020
24 Dec 2020
10 Nov 2020
22 Dec 2020
8 Dec 2020
10 Nov 2020 - 8 Dec 2020
Amount
Ousourcing for maintenance & operation of chilled water central AC plant 3 x 39 TR -03 Nos and 01 No stand by) and manning and operation of Diesel Generator set of 200 KVA installed at plant with connected panels by employing one technically qualified SKILLED AC operator , comprising the components detailed below round the clock daily in 03 shifts of 08 hrs including sunday and holiday. The team detailed at AC plant shall be for:- (a) Smooth functioning of entire AC plant and to maintain the specific temprature between 15 to 25 Degree Cetigrate and RH 65 + 5% all as specified and directed. (i) Hermatically sealed receprocal type compressor including meter etc-03 Nos complete. (ii) Shell & tube condensers. (iii) AHU unit at destance of approx 125 meter from plant room with heating and cooling coil and blower motors. (iv) Mono block pump set for circulation of chilled water for AHU. (v) Chiller for chilled water system capacity 39 TR = 03 Nos. (vi) Mono block pumping set for condenser water circulation. (vii) Electric control panel cubical type in plant room. (viii) Control valve such as expension valve. Thermostar, Humidistat, Solenoid, Valve, Hand shut of valve, antifreeze thermostate and anciliaries such as gauges etc installed in each chiller units. (ix) Ducting for supply air with grills, diffusers and fire dampers/smoke detector, fire protection alarm in plant room. (x) Coolinjg tower FRP induced draft couter flow single shell 78 TR capacity with axial flow fan of cast aluminium including electric motor 3 phase 415 volts, 2 HP capacity with water make up PVC tank 2000 Ltr capacity = 01 No. (xi) Electric control microprocesser based control panel. (xii) Mono block pump sets for Hot water generator. (xiii) Humiditifier. (xv) Condensor, chiller and hot water pipe line with control valve complete. (xvi) Pan type humiditer made out of SS sheet = 02 Nos. (xvii) Condenser, chiller and hot water pipe line complete with control valve. (xviii) Servo voltage stablizer cap 200 KVA 3 phase 415 V, 50 Hz = 01 Nos. (xix) Voltage stabilizer cpaicity 200 watt = 01 Nos. (xx) Recording and maintaining of log sheets of the installation as specified and driected by Engr-in-Charge. (xxi) Prevention maintenance of all equipments as specified. (xxii) Proper mainteance of installaiton including bldg, toilet, garden and light. Note:- 1. The item rate also including normal maint of AC plant cleaning of cooling coils, rectification of gas leakage including minor nuts, belts, V-belts. 2. Area of installation with be kept clean. 3. Diesel required to run the Diesel Generator Set shall be issued under Schedule 'B'.
as per item No 1.00 above but, EPF as notified by the Govt (as per notes given in this schedule)
as per item No 1.00 above but, EDLI as notified by the Govt/ as applicable
as per item No 1.00 above but Administration Charges on EPF (Employer contribution) as notified by the Govt (as per notes given in this schedule) (as per notes given in this schedule)
as per item No 1.00 above but, ESIC as notified by the Govt/as applicable (as per notes given in this schedule)
as per item No 1.00 above but, Bonus as notified by the Govt (as per notes given in this schedule)
as per item No 1.00 above but, Overhead and Profit (as per notes given in this schedule)
as per item No 1.00 above but, GST as notified by the Govt (as per notes given in this schedule)
as per item No 1.00 above but, LWC as notified by the Govt (as per notes given in this schedule)
Ousourcing for maintenance & operation of chilled water central AC plant 3 x 30 TR -03 Nos (Working 02 Nos and 01 No stand by) and manning and operation of Diesel Generator set of 250 KVA installed at plant with connected panels and two DG sets of 50 KVA capacity at 4 x Amn Shed by employing one technically qualified SKILLED AC operator in each shift of 08 (Eight) hrs each for 3 (Three shifts) round the clock daily including sunday and holidays comprising of the following equipments. (a) Smooth functioning of entire AC plant and to maintain the specific temprature between 15 to 25 Degree Cetigrate and RH 65 + 5% all as specified and directed. (i) Hermatically sealed receprocal type compressor including meter etc-03 Nos complete. (ii) Shell & tube condensers. (iii) AHU unit at destance of approx 125 meter from plant room with heating and cooling coil and blower motors. (iv) Mono block pump set for circulation of chilled water for AHU. (v) Chiller for chilled water system capacity 30 TR = 03 Nos. (vi) Mono block pumping set for condenser water circulation. (vii) Electric control panel cubical type in plant room. (viii) Control valve such as expension valve. Thermostar, Humidistat, Solenoid, Valve, Hand shut of valve, antifreeze thermostate and anciliaries such as gauges etc installed in each chiller units. (ix) Ducting for supply air with grills, diffusers and fire dampers/smoke detector, fire protection alarm in plant room. (x) Coolinjg tower FRP induced draft couter flow single shell 78 TR capacity with axial flow fan of cast aluminium including electric motor 3 phase 415 volts, 2 HP capacity with water make up PVC tank 2000 Ltr capacity = 01 No. (xi) Electric control microprocesser based control panel. (xii) Mono block pump sets for Hot water generator. (xiii) Humiditifier. (xv) Condensor, chiller and hot water pipe line with control valve complete. (xvi) Pan type humiditer made out of SS sheet = 02 Nos. (xvii) Condenser, chiller and hot water pipe line complete with control valve. (xviii) Servo voltage stablizer cap 200 KVA 3 phase 415 V, 50 Hz = 01 Nos. (xix) Voltage stabilizer cpaicity 200 watt = 01 Nos. (xx) Recording and maintaining of log sheets of the installation as specified and driected by Engr-in-Charge. (xxi) Prevention maintenance of all equipments as specified. (xxii) Proper mainteance of installaiton including bldg, toilet, garden and light. Note:- 1. The item rate also including normal maint of AC plant cleaning of cooling coils, rectification of gas leakage including minor nuts, belts, V-belts. 2. Area of installation with be kept clean. 3. Diesel required to run the Diesel Generator Set shall be issued under Schedule 'B'.
as per item No 2.00 above but, EPF as notified by the Govt (as per notes given in this schedule)
as per item No 2.00 above but, EDLI as notified by the Govt/ as applicable
as per item No 2.00 above but Administration Charges on EPF (Employer contribution) as notified by the Govt (as per notes given in this schedule) (as per notes given in this schedule)
as per item No 2.00 above but, ESIC as notified by the Govt/as applicable (as per notes given in this schedule)
as per item No 2.00 above but, Bonus as notified by the Govt (as per notes given in this schedule)
as per item No 2.00 above but, Overhead and Profit (as per notes given in this schedule)
as per item No 2.00 above but, GST as notified by the Govt (as per notes given in this schedule)
as per item No 2.00 above but, LWC as notified by the Govt (as per notes given in this schedule)
NOTES - FINANCIAL EVALUATION CRITERIA :- The provision of statutory laws relating to Minimum wages as per Code of wages 2019 including social security such as EPF and ESI shall be strictly adhered by the contractor and the quoted rate shall deemed to include these factors. Following rates of minimum wages, statutory provision and contractor profit & overhead charges shall be deemed to have been considered during financial evaluation :- (a) Minimum wages :- As per as latest notification issued by Government of India/State Government/Local body whichever is higher as on bid submission end date. (b) ESI (Insurance cover) @ 3.25% on minimum wage. In case monthly (26 days) minimum wage are exceeding Rupees twenty one thousand (Rs 21,000/-), ESI shall be exempted. (c) EPF (Employees provident fund) @ 12.00% on minimum wage. In case monthly (26 days) minimum wage are exceeding Rupees fifteen thousand (Rs 15,000/-) EPF shall be calculated for amount Rupees fifteen thousand (Rs 15,000/-) only. (d) EDLI @ 0.5% on total amount. (e) Administration Charges @ 0.5% on total amount. (f) Minimum Bonus applicable is @ 8.33%. (g) Labour cess @ 1% on total amount. (h) GST applicable is @ 18% on total amount. (j) The bidder shall have to be consider their profit and overhead charge on above provision. In case bidder considers Nil profit and overhead charge, the bidder shall be treated as a unresponsive and his offer shall be consider as a non bonafide bid. (k) Any quoted rate against the Sch Item as detailed above which corresponds to/works out to lower than the correspondening prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on the bid submission end date. If the Contractor's Profit quoted is equal to zero, the bid will be treated as non-bonafide.
Work done amount will only be paid to the Contractor only after he/she will submit a valid and authentic document in support of having paid the requisite amount of bonus to the workmen i.e. proof of payment. Monthly e banking statement stating payment done to the employees shall be furnished by contractor to the Engineer-in-Charge and the same shall be kept in record duly verified by Engineer-in-Charge alongwith monthly e-banking statement of employed employee EPF account stating monthly deposit of EPF & ESI by the contractor.
Operator shall be well qualified and should be adequately experienced as under :- (a). SKILLED Tradesman - Diploma Holder with 3 years experience or ITI with 5 years experience. (b). SEMI SKILLED Tradesman - class 12th pass with 5 years expeience. (c). Helper - UNSKILLED workmen shall have experience of minimum 3 years in the relevant trade.
In case the operator is found without proper uniform/dress as mentioned earlier, a penalty of Rs 100/- per day per operator shall be charged.
Payment to the worker shall be made on or before 07th day of every month, as per attendance register.
The contractor will submit the employee details as specified in PS of his Contract to the Engineer-in-Charge regarding each person to be employed by him under this contract within seven days from the date of commencement failing which the recovery of Rs 100/- per person per day shall be made from the contractor upto maximum of 15 days. After that the worker shall not be allowed to attend the installations and the contractor shall replace the person immediately otherwise further period shall be treated as absent and recovery shall be made as per P.S clause 71A of this Contract.
If the Accepting Officer finds the labours employed by the Contractor as not competent for the job, the same will be intimated to the Contractor on the 15th day of the same month. Contractor has to replace the respective labour before or on the last day of the month otherwise further period shall be treated as absent and recovery shall be made as per P.S clause 71A of this Contract.
The installations shall be manned and operated on all days as indicated in Schedule ‘A’. In case, the operator of the contractor found missing and / or the installation is found running unattended, during the check of installation by any officer, a penalty of Rs 420/- per shift per operator and or Rs 55/- per hour per operator per installation shall be make from the contractor. In addition to above the manning charges of that shift/period shall also not be paid to the contractor. No claim whatsoever shall be entertained from the contractor on his account.
All tools and machinery required for routine works, preventive maintenance etc. (for example such as pliers, cutter, screw drivers, spanner set, blower, drill machine, crimping tool, megger, earth tester, pipe wrench, tripod, safety equipment‟s etc.) shall be provided by the contractor cost of which is deemed to be included in the quoted rate.
The staff will ensure wearing respective work masks, safety gloves and belts as and when required cost of which is deemed to be included in the quoted rate.
Agency should provide Police Verification & Character Certificate of the manpower. The clearance of the local police with regards the antecedents of the persons deployed by it will be obtained by the agency before deployment of the personnel.
Any extra labour of any nature if required, at any time for attending any type of minor or major repair/break down shall be deployed by the contractor at his own cost for which nothing extra shall be payable.
Cost of conveyance for carrying and for filling of diesel from MES Yard to the installation for running of DG Sets is deemed to be included in the quoted rate.
Log sheets shall be prepared and kept on record in a binded folder covered with leather clad hard cover, all pages serially machine numbered cost of which is deemed to be included in the quoted rate.
After the approval of Operator the Contractor is required to submit at his own cost the cloth bound IDENTITY CARD duly affixed with a Passport size Photograph of Operators and one spare Photograph (both attested by the Contractor) to the Engineer-in-Charge, for his Countersignature. One copy of the Photograph shall be retained by the Department. Any Operator not in possession of requisite IDENTITY CARD shall not be allowed to handle the Installation.
Weekly "off " as per Lobour act to be given to the Operator& reliever to be Provided by the Contractor at no Extra Cost.
M&L for opening of condenser cover of both sides including disconnecting of water pipe line for inlet and outlet of the condenser of each plant. Removing scale/sludge precipitated in the copper tube by push and pull method with iron rod connected with steel wire brush of suitable size as per condenser copper tube size at the entire length of condenser and scraping down the sludge precipitated inside the tube. Closing both side of condenser and circulating the descaling solution, supplied in sealed containers, by 1 HP mono block pump set after mixing it in water in ratio of 1:5 in all tubes of three condenser of each plant through the circulating pump and allow to hold it for 30 minutes for chemical reaction. Opening the condenser from both sides and clean with iron rod connected with nylon brush of suitable size as per condenser copper tube size at the entire length of condenser ensuring that descaling process has been complete; then closing the condenser at both ends and circulating clean water in all the tubes of three condensers of each plant and draining out the same. These processess have to be continued till the tubes are of scales to the complete satisfaction of Engr-in-Charge including fixing new gasket for both ends of the three condensers of each plant, tighten with new nut end bolts. The job also includes Material and labour for making leak proof refrigerent system by vaccumising with in 7.6 mm HG carried out using N-2 gas and maintaining for three hours; at the end of this period vaccum should be maintained for 24 hours complete all as specified and directed by Engr-in-Charge for AC plants of 3X39 TR & 3 x 30 TR capacity. Note :- (a) Supplying the chemical solution for descaling solution for descaling is included in the unit rate quoted. (b) Strength of descaling solution shall be measured with pH paper and if the strength is less than 30%, then the descaling has to be done again by the contractor at his own cost to achieve the desired level of pH and nothing shall be payable extra on this account.
Supply ( in company sealed cylinders of any capacity) and charging refrigerent gas R-22 for filling in 3 x 39 TR & 3 x 30 TR AC compressor as per requirment complete all as specified and directed by Engr-in-Charge. Note: If the recharged refrigerent gas is leaked within 45 days of running of AC plant, the contractor shall recharge gas (including supply) without any extra cost to department.
M&L for topping up/charging compressor oil non freezing type in factory sealed containers in compressor units complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement 'V' Belt as per sample of existing specifications complete all as specified and directed by Engr-in-Charge. Make: Fenner/ Dunlop.
(i) S&F V Belts of size B-71 complete all as specified.directed by Engr-in-Charge.
(ii) S&F of V Belts of size B-78 complete all as specified.directed by Engr-in-Charge.
M&L for disconnecting, dismantling, taking down burnt out motor from its base and transporting the motor to the Contractor's workshop and back, refixing, testing on full load, commissioning the repaired motor after carrying out the foowing repairs - (i) opening the side covers and removing the rotor and cutting/ removing the burnt coils / winding from stator, (ii) Cleaning the slots carefully, (iii) Rewinding the stator using super enamelled copper conductor wire with same size, number of coils, number of turns / coils as per data acquired from the old burnt motor, including varnishing of two coats, drying using electric furnace, (iv) Testing the coils for there continuity and no current passing through the stator core, (v) Dynamic testing of the rotor and alignment of the main shaft and ensure that no imbalance vibtrations, (vi) Re-assembling the rotor and connecting the end terminals to the terminal plate of the motor, closing the ends with side covers. (vii) Testing and commissioing the electric motor connecting to the electric supply to its full load by connecting the compressor, (viii) Renewal of Bolts, nuts and washers for motors of following size - Note :- Parts renewed i.e Ball bearing shall be measured and paid separately. However filling of grease and oiling extra shall be deemed to be included in Unit rates.
Dismantling existing Monoblock pump with motor 3 HP to 14.75 HP, 3 Phase, 415 Volts, servicing of pump and motor by opening of pump, machining of pump shaft, renewal of gaskets, gland packing, Gun metal bushes, greasing of bearing complete all as specified. Note:- Ball bearing renewed and motor winding shall only be measured and paid separately.
Removing of Alpha filters from their positions and laying out the filters at site for refixing after cleaning them including cleaning of AHU cooling coil using chemical with brass brush in-order to remove all type of sludge/dust precipitated on the coil and filter without any damage to the copper cooling coil and then washing the cooling coil with fresh water and then air blowing the same to the complete satisfaction of Engr-in-Charge. Cooling coil drain water line shall be clean, if any type of obstacle is there in the flow of water, iron body of the AHU inside and outside shall be scrapped down and rubbed out with sand paper including applying one coat primer over a coat of synthetic enamel paint including part of duct portion in the AHU all to the complete satisfaction of Engr-in-Charge.
M&L for Repair to compressor of 3x30 TR AC plant by carrying out following -
(a) Dismantling, taking down of compressor 30 TR. Make : VOLTAS from foundation and opening by unscrewing for locating the of fault and transportation from AC plant to local market Ambala/ Chandigarh and back. Re-fixing in original state after carrying out necessary repairs and testing commissoning on load all as specified and directed.
(b) Replacement of suction and discharge reeds - 01 set (08 Nos)
(c) Replacement of suction & discharge valves-01 set
(d) Replacement of piston and ring- 04 Nos.
(e) Replacement of gudgeon pin-01 set
(f) Replacement of gasket set- 01 set
(g) Replacement of shaft seal assembly-03 set
(h) Replacemet of compressor oil-15 liters
(I) Replacement of 'O' ring -01 set
(j) Replacement of worn out main bearing as per sample- 01 No Note: Replacement include supply and fix of new part and taking down old and unserviceable part
M&L for Repair to compressor of 3x39 TR AC plant by carrying out following -
(a) Dismantling, taking down of scroll compressor 3x39 TR make : Bluestar from foundation and opening by unscrewing for locating the of fault and transportation from AC plant to local market Ambala/ Chandigarh and back. Re-fixing in original state after carrying out necessary repairs and testing commissoning on load all as specified and directed.
(b) Replacement of suction and discharge reeds - 01 set (08 Nos)
(c) Replacement of suction & discharge valves-01 set
(d) Replacement of piston and ring- 04 Nos.
(e) Replacement of gudgeon pin-01 set
(f) Replacement of gasket set- 01 set
(g) Replacement of shaft seal assembly-03 set
(h) Replacemet of compressor oil-15 liters
(I) Replacement of 'O' ring -01 set
(j) Replacement of worn out main bearing as per sample- 01 No (Note: Replacement include supply and fix of new part and taking down old and unserviceable part).
M&L for Pressure testing of entire system of AC plant comprising of three set of condenser, compressor and circulating system with CO2/Nitrogen gas and retain the gas in the system for three days. After three days checking the system to check for any leakage or reduction in the scale of pressure. If any leakage(s) is (are) found, it(they) shall be located and arrested by soldering or by taking an appropriate measure(s) to stop the leakage permenantly.
Cleaning the cooling tower by scraping with wire brush, washing powder and other solvent by removing the deposited impurities such as silt, dust particles mud/sand inside the dome and around the fins, on wiremesh, main shaft, etc and other connected items all as specified and directed by Engineer-in-Charge.
Servicing and maintenance of Rapid cool cap 63 KW Hot water generator (total- 1 Nos) complete by opening the existing assy and draining out complete water including cleaning of the connected components like container, checking of serviceability of heating element, pressure gauge, etc. and reassembling and testing the same after replacemen of unserviceable spares all as specified and as directed. NOTE - Spares to be replaced will be measured and paid separately under the relavant items of this schedule.
Supply only heating element of 2 K Watt
Supply only timer and other connected accessories.-01set
Supply only thermostat - 01No
Taking out the defective dehumidification pump set alongwith motor from the AHU ( CSU Type) by disconnecting electrically and mechanically, shifting to civil workshop, dismantling the same to remove burnt out windings and defective parts, rewinding the motor with super enemelled copper winding wire including all insulating materials all as per existing, varnishing,drying etc complete and replacing the bearings,bushes as per existing size replacing the pump impeller, reassembling the same shifting to original site, reconnecting electrically and mechanically and testing for proper working complete all as specified and directed for the 0.50 HP 230 volts SP 2780 RPM.
Taking out Hot water generator pump set alongwith motor by disconnecting electrically and mechanically, shifting to civil workshop, dismantling the same to remove burnt out windings and defective parts, rewinding the motor with super enemelled copper winding wire including all insulating materials all as per existing, varnishing,drying etc complete and replacing the bearings,bushes as per existing size replacing the pump impeller, reassembling the same shifting to original site, reconnecting electrically and mechanically and testing for proper working complete all as specified and directed for the 2 HP 230 volts complete all as directed by Engr-in-charge.
Supply & fix water pressure gauge 0-150 Kg/sq cm suitable for fixing with 100 mm dia water circulating inlet & out let pipe by means of proper welding and connection with checking the running water pressure as per specification all as directed by engineer in charge. Make H Guru or equivalent of approved make complete all as specified and directed.
M&L for replacement of water temp gauge dial type 0-120 degree F make H Guru or equivalent of approved make complete all as specified and directed
Supply & fix CT coil rating 200/5 amps, 415 volts of existing specification and make including taking down complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement ON/OFF Push button switch with two push buttons of existing specification complete all as specified and directed by Engr-in-Charge. Make:L&T/GE/SIEMENS.
Repair to pre- filter, pleated EU4/G4 type, GI frame, media-non wooen synthetic media + alluminium jalli, efficiency 90% down to 10 Micron size 590mm x 590mm x 50mm for central AC plant AHU in case of worn out U/S filter component at the descreation of Engr-in-Charge, tendered will replace the said filter with new one without any price adjustment complete all as specified and directed by Engr-in-Charge.
Repair to pre filter, pleated EU4/G4 type, GI frame, media-non wooen synthetic media + alluminium jalli, efficiency 90% down to 10 Micron size 590mm x 290mm x 50mm for central AC plant AHU in case of worn out U/S filter component at the descreation of Engr-in-Charge, tendered will replace the said filter with new one without any price adjustment complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement Electronic sensor suitable for 39 TR compressor unit (for chiller & condenser unit) of existing specifications and make complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of microprocessor elactronic control card chiller PCB suitable for 39 TR Scroll chiller Cat part No EACOZ0060 of existing specifications and make complete all as specified and directed by Engr-in-Charge.
S&F (in repairs) thermostatic expansion valve of 3x39 TR working on R-22( Ecofriendly) suitable for 1x39 TR AC plant ( Make - Blue Star) including collecting the refrigerent in the empty cylinders arranged by Contractor at his own resources by any means , cutting, welding, brazing, renewal of gasket, nuts, bolts and washers etc. complete all as specified and directed.by Engr-in-Charge.
S&F (in repairs) thermostatic expansion valve of 3x30 TR working on R-22( Ecofriendly) suitable for 1x30 TR AC plant ( Make - Voltas ) including collecting the refrigerent in the empty cylinders arranged by Contractor at his own resources by any means , cutting, welding, brazing, renewal of gasket, nuts, bolts and washers etc. complete all as specified and directed.by Engr-in-Charge.
Renewal of High pressure and low pressure control (HP&LP) switch suitable for water Cooled central type AC unit as per sample complete all as specified and directed.by Engr-in-Charge.
Supply and fix in repair Thermometer 0-60 Degree centrigrade suitable for fixing with 100 mm dia water circulating pipe by means of proper welding and connection with checking the running water temperature as per specification all as directed.by Engr-in-Charge.
M&L for digital type electronic temperature meter sensing the temperature from in side the user room and display on outside the AHU including wiring for sensing cable in case and copping, complete all as specified and directed.
Supply and fix in repair suction pressure sensor suitable for 3x 39 TR AC plant Make: Blue star,
Supply and fix in repair suction pressure sensor suitable for 3x 30 TR AC plant Make: Voltas
Supply and fix in repair discharge pressure sensor suitable for3x 39 TR AC plant Make: Blue star,
Supply and fix in repair discharge pressure sensor suitable for3x 30TR AC plant Make: Voltas
Supply and fix in repair oil pressure sensor suitable for 3x 30 TR AC plant Make: Blue star,
Supply and fix in repair oil pressure sensor suitable for 3x 39 TR AC plant Make: Voltas
S&F air flow switch suitable for Central/ package type AC plants complete all as specified.
S&Fanti freeze switch suitable for Central/ package type AC plants complete all as specified.
M&L for replacement of water flow switch type, IPS industrial pressure switch complete all as specified and directed. make : INDFOSS or equivalent as approved.
S&F in repair single phase preventer 230 Volts. Make : L&T/Siemens/Minilec/Havells/ABB/C&S
M&L PVC eliminator from colling tower of capacity 3x39 TR complete all as specified and directed by Engr-in-Charge.
M&L PVC eliminator from colling tower of capacity 3x30 TR complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement air release valve of gun metal 15 mm dia of existing specification and make complete all as specified and as directed by Engr-in-Charge.
Supply and fix in replacement butterfly valve with handle made out of brass/gun metal of 80 mm dia of existing specification and make complete all as specified and as directed by Engr-in-Charge. Make : LEADER/SANT
Supply and fix in replacement butterfly valve with handle made out of brass/gun metal of 50 mm dia of existing specification and make complete all as specified and as directed by Engr-in-Charge. Make : LEADER/SANT
Supply and fix in replacement dryer for liquid line 5/8'' Sutaible for 39 TR compressor complete all as specified and as directed by Engr-in-Charge. Make : DANFOSS/Elofic
Supply and fix Gate valve 40mm dia made of gun metal including taking down old complete all as specified and directed by Engr-in-Charge Make:- LEADER/Sant
Supply and fix in replacement solinoid coil suitable for 3x30 TR compressor complete all as specified and directed by Engr-in-Charge. Make : Alcho/Danfoss or as per existing.
Supply and fix in replacement solinoid coil suitable for 3x39TR compressor complete all as specified and directed by Engr-in-Charge. Make : Alcho/Danfoss or as per existing.
S&F MNX32 type power Contactor, 3 pole, 415 V, 50Hz, with auxulary Contact 2 NO+2NC suitable for Non-Inductive or Slightly Inductive ,Resistive Load (AC1- 40 Amps rating with the existing complete all as specified.
S&F MNX12.5 type power Contactor, 3 pole, 415 V, 50Hz, with auxulary Contact 2 NO+2NC suitable for Non-Inductive or Slightly Inductive ,Resistive Load (AC1- 40 Amps rating with the existing complete all as specified.
S&F replacement by fixing of control Voltage contactor mechanical interlocks horizontal mounted & configuration 415 V, 50HZ, AC 1NO+1NC suitable for water cooled chiller Control penal AC Coil controler make :- Siemens/L&T, all as specified and directed by engineer in charge.
Supply and fix in repair 3 pole power contactor rated current AC1 32A and AC3 32 A with auxiliary contact block, 3 phase 415 volts, with coil voltage 220 volts complete all as directed. Make : Siemens/L&T/Schenider/Legrand/ABB/C&S
Supply and fix in replacement contactor MNX-18A-3phase, 415volts, 50Hz, AC of existing specification complete all as specified and as directed by Engr-in-Charge. Make : L & T Cat no CS94100 or equivalent in GE/SIEMENS/
Supply and fixing front mounting add-on-aux control block MNX/MCX 9-80, MCX 01-23 CS 94114 of L&T or eq
Supply and fixing motor protection circuit braker (MPCB) rotary type with over load + short corcuit protection rating 13 Amps cat No ST419140000 of L&T or eq
Supply and fix in repair Over load relay Typ MN-2 range 9 Amp to 15 Amp complete all as directed. Make L&T or equivalent/Siemens/Schenider/Legrand/ABB/C&S
Supply and fix in repair Over load relay Typ MN-2 range 3 Amp to 5 Amp complete all as directed. Make L&T or equivalent/Siemens/Schenider/Legrand/ABB/C&S
Supply and fix in replacement thermal magnetic adjustable type thermal magnetic adjustable type MCCB 63 Amps, FP, 25 KA, 415 volts including 2 sets of OEM provided extenders and separators and making all connections complete all as directed. Make L&T/Seimens/ ABB/Schenider
Supply and fix in replacement thermal magnetic adjustable type MCCB 160 Amps, FP, 25 KA, 415 volts including 2 sets of OEM provided extenders and separators and making all connections complete all as directed. Make L&T/Seimens/ ABB/Schenider
Supply and fix in replacement thermal magnetic adjustable type MCCB 200 Amps, FP, 36 KA, 415 volts including 2 sets of OEM provided extenders and separators and making all connections complete all as directed. Make L&T/Seimens/ ABB/Schenider
S & F MCB TPN 32 Amps, 415 volts 'C' Curve 10 KA, including connection with suitable size copper lugs complete fixed in repair all as directed. Make :- Legrand/ABB/Schneider/L&T
Supply and fix in repair MCB TPN 63 Amps , C curve complete all as directed. Make: ABB/Legrand/L&T
Supply and fix in repair MCB TPN 6-32 Amps , C curve complete all as directed. Make: ABB/Legrand/L&T
Supply and fix in repair MCB TP 6-32 Amps , C curve complete all as directed. Make: ABB/Legrand/L&T
Material and labour replacement ammeter 0-200 Amps rectangle shape of size 96qmm, 3phase, 50 Hz AC suitable for AMF panel complete all as specified and directed by Engr-in-Charge. : Make : AE /L&T
Material and labour replacement ammeter 0-300 Amps rectangle shape of size 96 x96qmm, 3phase, 50 Hz AC suitable for AMF panel complete all as specified and directed by Engr-in-Charge. : Make : AE /L&T
Supply and fix in replacement Volt meter 0-500 volt, rectangle of size 96x 96 qmm 3 phase 440 volt, 50 Hz AC of existing specification and make complete all as specified and as directed by Engr-in-Charge. Make : AE/L&T/SEIMENS
Supply & fix CT coil rating 200/5 amps, 415 volts of existing specification and make including taking down complete all as specified and directed by Engr-in-Charge.
Supply & Fix rubber Hoses (tgl 13880 4) of 200 KVA DG Set all as specified and directed. Make: Cat No F6.013.13.0.00Kiloskar or equivalent in Elofic/Bosch
Supply & Fix rubber Hoses FOR MAIN AIR of 200 KVA DG Set all as specified and directed. Make: Cat No F6. 680.06.0.00 , Kiloskar or equivalent in Elofic/Bosch
S&F Hose (for 200 KVA young RA) of 200 KVA DG Set all as specified and directed Cat No F6.150.03.0.000
Replacement of LFL Sensor (Low Fuel Lever) Cat No 6H.192.14.0.00
Material and labour repair to self starter 24Volt of 200 KVA DG set as rewinding by using new supper enamelled copper wire of existing size, design and weight and replacement of bush & other unserviceable parts as required including taking down and transportation for repairs & re-fixing in original stae after duly repaired as a perfect working condition to the entire satisfaction of Engineer-in-Charge. Complete all as specified and as directed by Engineer-in-Charge.
Supply only fuel oil filter NO48.999.20.0.00Wih its gasket. Make: Kiloskar or equivalent in Elofic/Bosch.
Supply only Air filter inner & outer NO-F6729.03.00,F6729.05.0.00. with its gasket Kirloskar or equivalent in Elofic/Bosch.
Replacement of defective/detoriated lead Acid batteries withnew 24V, 32 Ah maintenance free batteries complete with SMPS Charger Make:Cummins Cat No AX1013235 or equivalent in EXIDE/ SF
Esha Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .