Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance FLAT NO 5 IIND FLOOR IIIRD B 2 NEHRU NAGAR GHAZIABAD UP 201001 | GHAZIABAD | GHAZIABAD | UTTAR PRADESH | 201001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Rejected-Technical | Rejected-Technical Technocommercially non responsive bid |
Tender Value
Refer Docs
EMD Value
₹1.5 Cr
Closing Date
24 Oct 2024, 3:30 pmClosed
Superintending EngineerCANDP1
CANDP Office PTCUL Vidyut Bhawan Dehradun Uttarakhand
Construction of 220 KV GIS Substation Banbasa Tanakpur
2024_PTCU1_75027_1
PTCUL/CandP-I/SS-10/2024-25
Open Tender
Electrical Works
914 days
Banbasa Tanakpur
Please refer Tender documents.
3 documents required · 3 mandatory
₹29,500
Yes
MD PTCUL
₹1.5 Cr
Yes
Dehradun
29 Oct 2024
20 Sept 2024
25 Oct 2024
20 Sept 2024
24 Oct 2024
12 Oct 2024
4 Oct 2024
Amount
Construction of 220/33 KV GIS Substation Banbasa,Tanakpur
Part-A (Supply of Material )
Transformer
50MVA, 220/33kV, Three phase transformer including Bushing, first filling of oil, Fibre Optic Temperature Measurement System and complete with all associated accessories.
Nitrogen Injection Fire Prevention & extingusihing system for above transformer.
Online DGA, Multigas type for above transformer.
Oil Storage Tank (15KL)
Oil sampling Bottle 2 ltr.
630KVA, 33/0.433kV, three phase transformer including bushing, accessories and first filling of oil.
245kV GIS Equipments
245kV, SF-6 gas insulated Transformer Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, two bus-bar disconnectors one with grounding switch and one without grounding switch, one disconnector with safety grounding switch, high speed fault acting earth switch, surge arrestors (216kV), SF6 gas monitoring system for complete bay, LCC, SF6 ducts and SF6/Air Interface to connect 220/33kV, 50MVA transformer and accessories with GIS etc. to complete transformer bay module.
245kV, SF6 gas insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, two bus-bar disconnectors one with grounding switch and one without grounding switch, line disconnector with safety grounding switch, high speed fault acting earth switch, SF6 gas monitoring system for complete bay, LCC, SF6 ducts and SF6/Air interface and accessories with GIS etc. to complete feeder bay module.
245kV, SF6 gas insulated, metal enclosed Bus Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus-bar set shall be complete with voltage transformer complete with safety grounding switch.
245kV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, two disconnectors with safety grounding switches, SF6 gas monitoring system for complete bay, LCC etc.
245kV AIS Equipments
245 kV CVT Single ph.
Junction box for above 245kV CVT
216kV Lightning Arrester with counter and leakage meter
245 kV BPI
Miscellaneous Materials (Insulators Strings / Disc Insulators, Hardware fittings, Conductor, 4" IPS Aluminium Tube, Cable Trays, Bay MB, Clamps, Connector including equipments connectors and all accessories etc.
36kV GIS Equipments
36kV, SF6 gas insulated Feeder Bay Module / Panel each comprising of SF6 gas insulated Circuit Breaker, Current Transformers, Potential Transformers, Lightning Arresters, two bus-bar disconnectors one with grounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, control & protection along with associated equipment. Cable termination and accessories with GIS etc. for 33 KV outgoing line Feeder Bay Module.
36kV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, two numbers of disconnectors with earthing switch, SF6 gas monitoring system for complete bay, control & protection along with associated equipment. etc.
36kV, SF6 gas insulated Transformer Bay Module each comprising of SF6 gas insulated circuit breaker, current transformer, Lightning Arresters, two bus-bar disconnectors one with grounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, with cable termination, control & protection along with associated equipments.
36kV, 3-phase or single phase encapsulated unit, SF6 gas insulated, metal enclosed Bus-Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of cirucit breaker bay module. Each bus-bar set shall be complete with voltage transformers with safety grounging switch.
36kV, SF6 gas insulated Feeder Bay Module / Panel each comprising of SF6 gas insulated circuit breaker, current transformers, Potential Transformers, Lightning Arresters, two bus-bar disconnectors one with grounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, Cable termination and accessories with GIS etc. suitable for 630KVA 33/0.433kV Station Transformer, control units, control and protection along with associated equipment.
36kV AIS Equipments
33kV BPI
30kV Lightning Arrester
33kV Air Break Switch
Miscellaneous Materials (Insulators Strings / Disc Insulators, Hardware fittings, Conductor, 4" IPS Aluminium Tube, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc.
Complete substation automation system including hardware and software for the substation & remote control stations alongwith associated equipments as per Technical Specifications.
Bay Control Units
220kV System
33kV System
220 KV Control and Relay panel
Circuit Breaker Control Panel
With Auto Reclose
With out Auto Reclose
Line Protection Panel (Main 1+Main 2)
Bus Bar Protection Panel
220kV bus bar protection panel for Main-1 and Main-2
Transformer Protection Panel
PLCC for 220KV Line feeder
Line Traps
2000A, 0.5/1 mH, 40 kA
Coupling device ( Phase to Phase )
HF Cable
Carrier Equipment
for Speech + Protection 1 & 2
for Speech + Data
Protection Coupler
Time Synchronisation Equipment (GPS Clock)
Online Monitoring, Data Acquisitionand ABT Analysis System
ABT meters 0.2s Cl with TCPIP, Optical Communication Port (ABT Meters are the part of C&R Panel. The rates of same may be included in the rates of C&R Panel). The quantity mentioned here for Supply & Erection is for indication purpose only.
DCU & Accessories
Industrial Grade Network Switch -8 Port, unmanaged
UPS 2 KVA online with 30 Min back up on 100% load
Workstation: Application & Database server
Database - Microsoft SQL Server 2016 STANDARD Edition (Latest) / ORACLE (Latest)
MS office - Standard edition (Latest)
MacAfee Virus Scan Enterprise Desktop Edition (Latest) - Per Year
Local Energy Monitoring Software - Professional edition
LAN cable (average one roll per S/S 300 Meters) Cat-06
PVC conduit Pipe - 3/4" ISI Mark
Enclosure for LAN Switch
4G/5G Data enable SIM
Cable 4 Core 2.5 Sq. mm Copper, Armored
SDH/MUX EQUIPMENT
Steel Cabinet with all internal wiring/terminations/MDF and arrangement for dual 48/50V Power supply input
SDH (STM-4 upgradable upto STM-16)/MUX base 19" equipment rack (incl. front cover, cable tray, common cards such as redundant CPU) with arrangement for dual input power supply.
OLTE - 4 Port STM-1 (155 Mbps) Card excluding SFPs
SFP module to support upto 50 km
SFP module to support upto 100 km
Optical Amplifier/Booster equipment
OFC Patch Cords - (Set of 12 Nos.)
Ethernet over SDH (STM-4 upgradable upto STM-16) transport card (with eight 10/100/1000BaseT interfaces)
Minimum 8 Port E1 interface card
Minimum 8 Port 4w E&M Interface card
Minimum 12 Port FXO interface card
Minimum 10 Port FXS interface card
Minimum 4 Port programmable data interface card
Integrated Teleprotection card (4 Commands each)
Engineering Order Wire Phone
Optical Fibre Cable for above OPGW communication
Testing & Maintenance Equipment
Meggar 5 KV (Motorized)
Meggar 15 KV (Motorized)
Automatic capacitor and Tan Delta measuring kit
Thermal Imaging Camera
Digital Multi meter
Leakage tester (Tong type)
Signal generator
Micro-ohm meter
Gapless zinc oxide LA tester
Oil BDV Kit 0-100 KV
SF-6 Gas Evacuating and refilling Plant
Gas Leakge Monitor
Circuit Breaker Analyser
Portable Partial discharge monitoring system
Dew Point Meter
Battery Earth Fault Locator
Primary Injection Set 1000 Amp
Relay Test Kit
Gas Mask
D-Spanner set (Insulated)
Ring-Spanner set (Insulated)
Torque wrench set
Insulating gloves
Helmets
Hydralic Ladder battery operated (Rechrgeable) upto 300KG Capacity and 10 Meters Height
Spliced ladders 5mtr.
Spliced ladders 10mtr.
Spliced ladders 20mtr.
Polyamide or Braided white nylon rope -12 mm
Polyamide or Braided white nylon rope -14 mm
Polyamide or Braided white nylon rope -20 mm
Earth resistance tester
Rubber mat in Control room, Battery Room & LT Panel Room etc. as per Site requirements
Shock treatment chart & artificial respiratory system
First-aid box complete with first filling of required medicines, instruments and tools
Danger / Man on line / Break-Down boards of appropriate size
Rain coat, Gum boot and Safety Harness Belt with adequate straps
Air-conditioner
Split AC (capacity-2T) Max. Star rating
Ventillation system for 220kV GIS Hall
Miscellaneous items
Air Curtain for Control Room Building
Interactive Screen for Control Room Building
LT Switchboard
415V Main Switchboard (MSB)
415V ACDB
220V DCDB
48V DCDB
Batteries
Battery charger system
220V, 100Amps Float Cum Boost Charger
48V, 60Amps Float Cum Boost Charger
250kVA, 440V DG set alongwith AMF control panel
Fire Prevention & Extinguishing System
Fire Detection and Alarm System for 220 kV & 33 kV GIS hall, Control Room Building
45 Ltr. Foam type
CO2 Type Fire Extinguisher 9 kgs
ABC type 10 kgs.
CO2 Type Fire Extinguisher 4.5 kgs
Mechanical Foam Type Fire Extinguisher 9 Ltrs
6 Fire bucket with stand
Sand drum (half size) filled with sand
Illumination sytem
33kV GIS Room / Control Room / Store Room / Offices llumination (LED Type Lights)
Switchyard lighting (LED Type Lights) with mounting accessories
Solar light system for street light (LED Type Lights) with Pole and other mounting accessories
LED Lights for 220kV GIS, High Bay type 170 Watts
1.1kV Aromoured Power Cables (AL) and Aromoured Control Cables (Copper) alongwith multidiameter moulded cable sealing, Lugs, Glands and straight joints, etc.
Power cables Aluminium (XLPE)
3.5Cx300 Sq.mm
Power cable Aluminium (PVC)
3.5Cx70Sq.mm
3.5Cx35Sq.mm
4Cx16 Sq.mm
4Cx6 Sq.mm
Control cable Copper (PVC)
2Cx2.5Sq.mm
4Cx2.5Sq.mm
6Cx2.5Sq.mm
10Cx2.5Sq.mm
33kV Power Cable and accessories
33kV XLPE Copper Power Cables for connecting Transformer to 33kV GIS of size 1 X 630 sq.mm.
33KV Indoor termination suitable for 630 sq.mm. cable
33KV Outdoor termination suitable for 630 sq.mm. cable
33kV XLPE Copper Power Cable for Auxiliary Transformer of size 1 X 185 sq.mm.
33kV Indoor Termination suitable for 185 sq.mm. cable
33kV Outdoor Termination suitable for 185 sq.mm. cable
Grounding/Earthing system
40mm MS rod for earthmat
40mm MS 03 meter electrodes
40mm 3 meter deep driven pipe electrode (treated pit)
MS/GS Flats 75x12
MS/GS Flats 50x6
GS shield Wire
Steel structure
Lattice structure
Pipe structure
EOT Crane
EOT Crane for 220KV GIS Room
Moveable ladder of suitable capacity for 220 KV, 33 KV GIS Room
Mandatory spares as per List indicated in Section "Mandatory spares" of Technical Specifications for following items
220/33kV Transformer
245kV GIS CB
245kV VT GIS Type (3 Nos)
245kV CT GIS Type (3 Nos)
245kV Isolators & ES GIS Type
216kV Surge Arrestor (3 Nos)
245kV Outdoor Termination Kit (SF6 to Air Type) (3Nos.)
llumination system
Optic fibre cable
Fire fighting
Battery
Battery charger
Relay & Protection panels
Substation Automation
LT Switchgear
Common Spares, maintenance
DG Set
245 KV CVT Outdoor Type (3 Nos.)
33kV Indoor Termination (3Nos.)
33kV Outdoor Termination (3Nos.)
Description of Work / Item(s)
Amount
Construction of 220/33 KV GIS Substation Banbasa',Tanakpur
Part-B (Erection of Material )
Transformer
50MVA, 220/33kV, Three phase transformer including Bushing, first filling of oil, Fibre Optic Temperature Measurement System and complete with all associated accessories.
Nitrogen Injection Fire Prevention & extingusihing system for above transformer.
Online DGA, Multigas type for above transformer.
Oil Storage Tank (15KL)
630KVA, 33/0.433kV, three phase transformer including bushing, accessories and first filling of oil.
245kV GIS Equipments
245kV, SF-6 gas insulated Transformer Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, two bus-bar disconnectors one with grounding switch and one without grounding switch, one disconnector with safety grounding switch, high speed fault acting earth switch, surge arrestors (216kV), SF6 gas monitoring system for complete bay, LCC, SF6 ducts and SF6/Air Interface to connect 220/33kV, 50MVA transformer and accessories with GIS etc. to complete transformer bay module.
245kV, SF6 gas insulated Feeder Bay Module each comprising of SF6 gas insulated Circuit Breaker, Current Transformer, two bus-bar disconnectors one with grounding switch and one without grounding switch, line disconnector with safety grounding switch, high speed fault acting earth switch, SF6 gas monitoring system for complete bay, LCC, SF6 ducts and SF6/Air interface and accessories with GIS etc. to complete feeder bay module.
245kV, SF6 gas insulated, metal enclosed Bus Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus-bar set shall be complete with voltage transformer complete with safety grounding switch.
245kV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, two disconnectors with safety grounding switches, SF6 gas monitoring system for complete bay, LCC etc.
245kV AIS Equipments
245 kV CVT Single ph.
Junction box for above 245kV CVT
216kV Lightning Arrester with counter and leakage meter
245 kV BPI
Miscellaneous Materials (Insulators Strings / Disc Insulators, Hardware fittings, Conductor, 4" IPS Aluminium Tube, Cable Trays, Bay MB, Clamps, Connector including equipments connectors and all accessories etc.
36kV GIS Equipments
36kV, SF6 gas insulated Feeder Bay Module / Panel each comprising of SF6 gas insulated Circuit Breaker, Current Transformers, Potential Transformers, Lightning Arresters, two bus-bar disconnectors one with grounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, control & protection along with associated equipment. Cable termination and accessories with GIS etc. for 33 KV outgoing line Feeder Bay Module.
36kV, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, two numbers of disconnectors with earthing switch, SF6 gas monitoring system for complete bay, control & protection along with associated equipment. etc.
36kV, SF6 gas insulated Transformer Bay Module each comprising of SF6 gas insulated circuit breaker, current transformer, Lightning Arresters, two bus-bar disconnectors one with grounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, with cable termination, control & protection along with associated equipments.
36kV, 3-phase or single phase encapsulated unit, SF6 gas insulated, metal enclosed Bus-Bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of cirucit breaker bay module. Each bus-bar set shall be complete with voltage transformers with safety grounging switch.
36kV, SF6 gas insulated Feeder Bay Module / Panel each comprising of SF6 gas insulated circuit breaker, current transformers, Potential Transformers, Lightning Arresters, two bus-bar disconnectors one with grounding switch & one without grounding switch, SF6 gas monitoring system for complete bay, Cable termination and accessories with GIS etc. suitable for 630KVA 33/0.433kV Station Transformer, control units, control and protection along with associated equipment.
36kV AIS Equipments
33kV BPI
30kV Lightning Arrester
33kV Air Break Switch
Miscellaneous Materials (Insulators Strings / Disc Insulators, Hardware fittings, Conductor, 4" IPS Aluminium Tube, Cable Trays, Clamps, Connector including equipments connectors and all accessories etc.
Complete substation automation system including hardware and software for the substation & remote control stations alongwith associated equipments as per Technical Specifications.
Bay Control Units
220kV System
33kV System
220 KV Control and Relay panel
Circuit Breaker Control Panel
With Auto Reclose
With out Auto Reclose
Line Protection Panel (Main 1+Main 2)
Bus Bar Protection Panel
220kV bus bar protection panel for Main-1 and Main-2
Transformer Protection Panel
PLCC for 220KV Line feeder
Line Traps
2000A, 0.5/1 mH, 40 kA
Coupling device ( Phase to Phase )
HF Cable
Carrier Equipment
for Speech + Protection 1 & 2
for Speech + Data
Protection Coupler
Time Synchronisation Equipment (GPS Clock)
Online Monitoring, Data Acquisitionand ABT Analysis System
ABT meters 0.2s Cl with TCPIP, Optical Communication Port (ABT Meters are the part of C&R Panel. The rates of same may be included in the rates of C&R Panel). The quantity mentioned here for Supply & Erection is for indication purpose only.
DCU & Accessories
Industrial Grade Network Switch -8 Port, unmanaged
UPS 2 KVA online with 30 Min back up on 100% load
Workstation: Application & Database server
Database - Microsoft SQL Server 2016 STANDARD Edition (Latest) / ORACLE (Latest)
MS office - Standard edition (Latest)
MacAfee Virus Scan Enterprise Desktop Edition (Latest) - Per Year
Local Energy Monitoring Software - Professional edition
LAN cable (average one roll per S/S 300 Meters) Cat-06
PVC conduit Pipe - 3/4" ISI Mark
Enclosure for LAN Switch
4G/5G Data enable SIM
Integration of station metering system with centrlized data system including all hardware and software required.
Cable 4 Core 2.5 Sq. mm Copper, Armored
SDH/MUX EQUIPMENT
Steel Cabinet with all internal wiring/terminations/MDF and arrangement for dual 48/50V Power supply input
SDH (STM-4 upgradable upto STM-16)/MUX base 19" equipment rack (incl. front cover, cable tray, common cards such as redundant CPU) with arrangement for dual input power supply.
OLTE - 4 Port STM-1 (155 Mbps) Card excluding SFPs
SFP module to support upto 50 km
SFP module to support upto 100 km
Optical Amplifier/Booster equipment
OFC Patch Cords - (Set of 12 Nos.)
Ethernet over SDH (STM-4 upgradable upto STM-16) transport card (with eight 10/100/1000BaseT interfaces)
Minimum 8 Port E1 interface card
Minimum 8 Port 4w E&M Interface card
Minimum 12 Port FXO interface card
Minimum 10 Port FXS interface card
Minimum 4 Port programmable data interface card
Integrated Teleprotection card (4 Commands each)
Engineering Order Wire Phone
Optical Fibre Cable for above OPGW communication
Air-conditioner
Split AC (capacity-2T) Max. Star rating
Ventillation system for 220kV GIS Hall
Miscellaneous items
Air Curtain for Control Room Building
Interactive Screen for Control Room Building
LT Switchboard
415V Main Switchboard (MSB)
415V ACDB
220V DCDB
48V DCDB
Batteries
Battery charger system
220V, 100Amps Float Cum Boost Charger
48V, 60Amps Float Cum Boost Charger
250kVA, 440V DG set alongwith AMF control panel
Fire Prevention & Extinguishing System
Fire Detection and Alarm System for 220 kV & 33 kV GIS hall, Control Room Building
ABC type 10 kgs.
CO2 Type Fire Extinguisher 4.5 kgs
6 Fire bucket with stand
Sand drum (half size) filled with sand
Illumination sytem
33kV GIS Room / Control Room / Store Room / Offices llumination (LED Type Lights)
Switchyard lighting (LED Type Lights) with mounting accessories
Solar light system for street light (LED Type Lights) with Pole and other mounting accessories
LED Lights for 220kV GIS, High Bay type 170 Watts
1.1kV Aromoured Power Cables (AL) and Aromoured Control Cables (Copper) alongwith multidiameter moulded cable sealing, Lugs, Glands and straight joints, etc.
Power cables Aluminium (XLPE)
3.5Cx300 Sq.mm
Power cable Aluminium (PVC)
3.5Cx70Sq.mm
3.5Cx35Sq.mm
4Cx16 Sq.mm
4Cx6 Sq.mm
Control cable Copper (PVC)
2Cx2.5Sq.mm
4Cx2.5Sq.mm
6Cx2.5Sq.mm
10Cx2.5Sq.mm
33kV Power Cable and accessories
33kV XLPE Copper Power Cables for connecting Transformer to 33kV GIS of size 1 X 630 sq.mm.
33KV Indoor termination suitable for 630 sq.mm. cable
33KV Outdoor termination suitable for 630 sq.mm. cable
33kV XLPE Copper Power Cable for Auxiliary Transformer of size 1 X 185 sq.mm.
33kV Indoor Termination suitable for 185 sq.mm. cable
33kV Outdoor Termination suitable for 185 sq.mm. cable
Grounding/Earthing system
40mm MS rod for earthmat
40mm MS 03 meter electrodes
40mm 3 meter deep driven pipe electrode (treated pit)
MS/GS Flats 75x12
MS/GS Flats 50x6
GS shield Wire
Steel structure
Lattice structure
Pipe structure
EOT Crane
EOT Crane for 220KV GIS Room
Support for Operation and Maintenance (O&M) of substation, Trouble shooting and familiarization of PTCUL staff with installed system for a period of Six (06) Months by deplyoing adequate number (Minimum 02) of qualified persons round the clock.
Description of Work / Item(s)
Amount
Construction of 220/33 KV GIS Substation Banbasa,Tanakpur
Part-A(Civil Work)
Construction of Substation and Development Work
Buildings
Construction of 220 KV GIS Control cum Relay Room and Cable Vault (Plinth area to be measured) Ground Floor (Minimum Ceiling height-4.50 M)
(i) Control cum Relay Room (Minimum Ceiling height-4.50 M)
(ii) Cable Vault (Minimum room height 2.40 M )
Construction of 220 KV GIS Hall and Cable Vault (Plinth area to be measured)
(i) 220 KV GIS Hall (Minimum Ceiling height-9.00 M)
(ii) Cable Vault (Minimum room height 2.40 M )
Construction of control room cum administrative building (Minimum Ceiling height-4.50 M)
Construction of 33 KV GIS Hall (Plinth area to be measured) Ground Floor (Minimum Ceiling height-4.50 M)
(i) 33 KV GIS Hall (Minimun Ceiling height- 4.50 M)
(ii) Cable Vault (Minimum Room height- 2.4M)
Construction of store shed (Plinth area to be measured) (Minimum Ceiling height-4.20 M)
Security Guard Room (Minimum Ceiling Height- 2.90 M)
Construction of Erector-hostel Building (D/S) (Minimum Ceiling Height- 3.20 M)
Landscaping of substation land, Plantation and lawn development around substation buildings including providing & installation of flower pots in substation builidngs, providing & fixing of sign boards in switch yard & substation buildings and flex boards as directed & approved by Engineer-in-charge.
Establishment of temporary PTCUL site cum transit office at site including all necessary arrangement as directed by Engineer incharge.
Part-B
Construction of foundation of following structures including excavation and back filling of earth, CC/RCC works, reinforcement , supply & Fixing foundation bolts & painting the foundation etc. complete along with P/F of solar lights as directed & approved by Engineer-in-charge complete in all respect.
145 KV Gantry Column foundation
CVT foundation
LA foundation
Foundations for Bus Duct support structure.
Foundations for BPI
Foundation for Lightening Mast
Plinth for 50 MVA 220/33KV Single Phase Transformers
Plinth for 630KVA Transformer
DG set plinth
Bushing foundations
Oil storage tank plinth
Burnt Oil Sump Pit Tank
Nitrogen Injection Fire Prevention cum Extinguishing System Foundation
RCC Cable trenches with trench covers (all Sections) including all type of crossing and all metallic work to support cables and trench covers including painting and proper numbering.
600 mm size trench with minimum depth 600 mm
1050 mm size trench with minimum depth 600 mm
600 mm size trench with minimum depth 1000 mm
1050 mm size trench with minimum depth 1000 mm
Buried cable Trenches for 33 KV XLPE Cable for Transformer LV to 33 KV GIS.
RCC Fire Protection Walls including paint.
Cement concrete roads including all type of crossings including supply and fixing of solar lights along the road side.
5.00 metre wide
3.80 metre wide
1.20 metre wide
Security (Chain link) Fencing 3.6 m high along with Gate.
Security (Chain link) Fencing 3.6 m high.
Gate (5.0M wide)
Storm water drainage including culverts & chambers.
AC junction box for Switchyard lighting
Switch yard turfing and antiweed treatment including leveling and dressing of area, PCC and gravels
Construction of tubewell with a minimum discharge capacity of 100 lpm (or decided by Engineer -incharge) with KSB make submersible pumping set with L&T make panel board. also including construction of pump house building, including connecting pipe lines, valves etc. complete with one spare pumping set and panel board and one no. chain pulley block 2.0 MT capacity INDEF make etc. with RCC overhead water storage tank 30 KL capacity with staging of 12.0 meter. (NOTE:- Overhead water storage tank to be constructed at a place suitable for supply water to all the buildings with gravity at appropriate pressure)
Constrution of ground water recharge pit of approved depth, installation of pipes for collecting storm runoff from roof of substation buildings & of substation land for rain harvesting process as per specifications of CPWD rain harvesting manual and as directed & approved by Engineer-in-charge.
Land development including necessary cutting /filling and construction of all retaining walls for complete switch yard area maintaining required terraces levels, approach road, culverts.
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. (2.31)
Carriage of Earth by mechanical transport including loading, unloading and stacking up to 5.0 KM lead (DSR No. 1.1.2)
Filling with available fly ash and earth (excluding rock) in trenches or embankment in layers (each layer should not exceed 15 cm), with intermediate layer of compacted earth (soil density of 98%) after every four layers of compacted depth of fly ash, sides & top layer of filling shall be done with earth having total minimum compacted thickness 30 cm or as decided by Engineer-in-charge, including compacting each layer by rolling/ramming and watering, all complete as per drawing and direction of Engineer in charge. (D.S.R. No. 2.38)
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.( DSR No. 2.25 (a))
Excavation work in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50m. Ordinary Rock. (DSR No. 2.7.1)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed.m, as directed by Engineer-in-charge. Ordinary Rock (DSR No. 2.9.1)
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. Ordinary Rock (DSR No. 2.26.2)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) (DSR No. 4.1.3)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:4:8 ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) (DSR No. 4.1.8)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.2)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.3)
Reinforced cement concrete work in walls ( any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.2.2)
Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15 degree landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) (DSR 5.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footing, bases of columns, etc. for mass concrete. (DSR No. 5.9.1)
Centering and shuttering including strutting, propping etc. and removal of form for : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. (DSR No. 5.9.2)
Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landing, balconies and access platform(DSR 5.9.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts. (DSR No. 5.9.6)
Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide (DSR No. 5.9.16.1)
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Cold twisted bars (DSR No. 5.22.3)
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR No. 7.1.1)
Coursed rubble masonry (second sort) with hard stone in foundation and plinth with : Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR No. 7.6.1)
Dry Random rubble masonry (first sort) with hard stone in foundation and plinth (DSR No. 7.1.1 Based item)
Stone tile (polished) work for wall lining over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and cement slurry @ 3.3 kg/sqm including pointing in white cement complete.8mm thick Granite of any colour and shade. (DSR No. 8.9.1.2)
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works (DSR No. 10.25.2)
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes. 110 mm diameter (DSR No. 12.41.2)
Supplying and stacking at site. 90 mm to 45 mm size stone aggregate. (DSR No. 16.3.1)
Supplying and stacking at site. 63 mm to 45 mm size stone aggregate. (DSR No. 16.3.2)
Laying spreading and compacting stone aggregate of specified sizes to WBM specifications including spreading in uniform thickness, hand picking , rolling with 3 wheeled road / vibratory roller 8-10 tonne in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate watering and compacting to the required density. (DSR No. 16.4)
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 300 mm dia. R.C.C. pipe (DSR No. 19.6.4)
Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 450 mm dia RCC pipes.(DSR No. 19.35.1)
Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 600 mm dia RCC pipes.(DSR No. 19.35.2)
Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 1200 mm dia RCC pipes.(DSR No. 19.35.5)
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade- Area of slab over 0.50 sqm (DSR No. 8.2.2.2)
Engraving letters in hard stone (DSR No. 16.21)
Part-C
Construction of Residences and Development Work
Residences
03 No. Type IV (G/F) residence (3x125=375.00)
04 No.Type III (G/F) residence (4x79=316.00)
04 No. Type III (F/F) residence (4x79=316.00)
08 No Type II (G/F) residence (8x57.70=461.60)
08 No. Type II (F/F) residence (8x 57.70=461.60)
Landscaping of residential area, Plantation and lawn development around residence buildings as directed & approved by Engineer-in-charge.
Part-D
Cement concrete roads including all type of crossings, parapet walls/railings, supplying & fixing of solar street lights along the road with foundation as directed & approved by Engineer-in-charge. Complete in all respect.
3.80 metre wide
1.20 metre wide
Security Fencing 1.5 m high along with Gate as directed & approved by Engineer-in-charge. Complete in all respect.
Security Fencing 1.5 m high
Gate (5.0 m wide)
Storm water drainage including culverts, chambers, etc. as directed & approved by Engieer-in-charge. Size of drain shall be decided by Engineer-in-charge. Complete in all respect.
Construction of Water supply mains including necessary pedestals for support as directed & approved by Engieer-in-charge. Complete in all respect.
Construction of Boundary Wall
Land development including necessary cutting /filling and construction of all retaining walls for complete area maintaining required terraces levels, approach road, culverts. as directed & approved by Engineer-in-charge.
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. (2.31)
Carriage of Earth by mechanical transport including loading, unloading and stacking up to 5.0 KM lead (DSR No. 1.1.2)
Filling with available fly ash and earth (excluding rock) in trenches or embankment in layers (each layer should not exceed 15 cm), with intermediate layer of compacted earth (soil density of 98%) after every four layers of compacted depth of fly ash, sides & top layer of filling shall be done with earth having total minimum compacted thickness 30 cm or as decided by Engineer-in-charge, including compacting each layer by rolling/ramming and watering, all complete as per drawing and direction of Engineer in charge. (D.S.R. No. 2.38)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed.m, as directed by Engineer-in-charge. Ordinary Rock (DSR No. 2.7.1)
Excavation work in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50m. Ordinary Rock. (DSR No. 2.9.1)
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. Ordinary Rock (DSR No. 2.26.1)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) (DSR No. 4.1.3)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:4:8 ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) (DSR No. 4.1.8)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.2)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). (DSR No. 5.1.3)
Reinforced cement concrete work in walls ( any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). (DSR No. 5.2.2)
Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15 degree landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement. 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) (DSR 5.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footing, bases of columns, etc. for mass concrete. (DSR No. 5.9.1)
Centering and shuttering including strutting, propping etc. and removal of form for : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. (DSR No. 5.9.2)
Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landing, balconies and access platform(DSR 5.9.3)
Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts. (DSR No. 5.9.6)
Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide (DSR No. 5.9.16.1)
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Cold twisted bars (DSR No. 5.22.3)
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR No. 7.1.1)
Coursed rubble masonry (second sort) with hard stone in foundation and plinth with : Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR No. 7.6.1)
Dry Random rubble masonry (first sort) with hard stone in foundation and plinth (DSR No. 7.1.1 Based item)
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works (DSR No. 10.25.2)
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes. 110 mm diameter (DSR No. 12.41.2)
Supplying and stacking at site. 90 mm to 45 mm size stone aggregate. (DSR No. 16.3.1)
Supplying and stacking at site. 63 mm to 45 mm size stone aggregate. (DSR No. 16.3.2)
Laying spreading and compacting stone aggregate of specified sizes to WBM specifications including spreading in uniform thickness, hand picking , rolling with 3 wheeled road / vibratory roller 8-10 tonne in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate watering and compacting to the required density. (DSR No. 16.4)
Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 450 mm dia RCC pipes.(DSR No. 19.35.1)
Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 600 mm dia RCC pipes.(DSR No. 19.35.2)
Lettering with black Japan paint of approved brand and manufacture (DSR No13.71)
Description of Work / Item(s)
Amount
Total Part-A (Supply) from BoQ1 sheet WITHOUT GST
Total Part-B (Erection) from BoQ2 sheet WITHOUT GST
Total Part-C (Civil) from BoQ3 sheet WITHOUT GST
Add GST* Amount on (Total of Part-A + Total of Part-B + Total of Part-C) above
Shyama Power India Limited (BID ID -339913)
JSP Projects Pvt Ltd (BID ID -341266)
JSP Projects Pvt Ltd (BID ID -341266)
Shyama Power India Limited (BID ID -339913)
JSP Projects Pvt Ltd (BID ID -341266)
Shyama Power India Limited (BID ID -339913)
JSP Projects Pvt Ltd (BID ID -341266)
Shyama Power India Limited (BID ID -339913)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid