Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹9.2 L
EMD Value
₹18,479
Closing Date
30 Dec 2025, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX
Construction of Proposed Double Storeyed Veterinary Hospital Building at Hawal Opposite Islamia College Srinagar B.W.O Electric Part
2025_PWDJK_298423_1
NIT No.228/2025-26 Dt/17/12/2025
Open Tender
Electrical Works
Percentage
Hawal Srinagar
Please refer Tender documents.
4 documents required · 4 mandatory
₹600
Yes
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹18,479
17 Dec 2025
17 Dec 2025
31 Dec 2025
17 Dec 2025
30 Dec 2025
17 Dec 2025
Wiring for Light point/Exhaust fan point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable in existing surface/recessed Conduits (Including Cost of Conduit) laid in slabs with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Livia)/ eq. Make & shall be approved before execution of work.
Wiring for Ceiling fan point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable in surface/recessed Conduits(Including Cost of Conduit)(Havells/Polycab/Anchor Make) with 01 No. of 6 Amp Modular Switch,, Modular Plate,Cover in front and suitable GI box etc ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Livia) / eq. Make & shall be approved before execution of work.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required,ISO/IEC Certified of Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Livia) / eq. Make & shall be approved before execution of work.
Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Including Cost of Conduit)(Havells/Polycab/Anchor / eq. Make to be approved by EIC)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Livia) / eq. Make to be approved by EIC & shall be approved before execution of work.
Wiring for 6Amp Plug(Computer Point) with (P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Including Cost of Conduit)(Havells/Polycab/Anchor / eq. Make to be approved by EIC)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings), ISO/IEC Certified Havells(Crab-Tree)/ Legrand(Myris)/Anchor Rooma Plus/ Schneider(Livia) / eq. Make to be approved by EIC & shall be approved before execution of work.
Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLS PVC insulated copper conductor, single core Cable in surface/Recessed medium class PVC conduit (Including Cost of Conduit)(Havells/Polycab/Anchor / eq. Make to be approved by EIC) & shall be approved before execution of work.
2x10 sq.mm+ 1x6 sq.mm (P+N+E) for Power point Sub main in One run from Main Panel to Distribution Boards.
2x6 sq.mm+ 1x6 sq.mm (P+N+E) for Lighting/Inverter/AC Point Sub main in One run from Main Panel to Distribution Boards.
2x2.5 sq.mm+ 1x2.5 sq.mm (P+N+E) for Lighting/Inverter Circuit in One run from switch boards to Distribution Boards.
Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/ABB /Schneider / eq. Make to be approved by EIC)
Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/ABB/Schneider / eq. Make to be approved by EIC)
Supplying and Fixing of MCB 8-Way (4+24) horizontal typed , sheet steel, Double Door Distribution Board, TPN 240V/415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ ABB /Schneider / eq. Make to be approved by EIC)
ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER ROD EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value.Supply,Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 20mm Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through suitable DWC High Density Poly ethylene Pipe having Corrugation complete job.
Supply/Installation/Testing and Commissioning of 18W + LED Surface Mounted Panel light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of /H.G/Jaguar/Bajaj / eq. Make to be approved by EIC & Shall be approved.
Providing & Fixing of IK08 IP-66 protected high power LED 50 Watt flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 Im/wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL/ third party lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR:-High Power LED Flood Light Minimum lumen output 6200 Im of Havells/Crompton/HG / eq. Make to be approved by EIC as approved and to be installed on outside block including S/F of suitable size of Gyser bolt.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of two years reckoned from date of successful commissioning /handing over of site to intending department.
Supply/Installation/Testing and Commissioning of BLDC 1200 mm sweep, ceiling fan with 03 No. blades, 30 cm long down rod, 02 No. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havells/Polycab/Orient / eq. Make to be approved by EIC.(5-Star)
Supply/Installation/Testing and Commissioning of 225-250mm Shutter Typed,320 Cu.m/Hr.AC 220-240 Volts, 50 Hz Exhaust fan made out of ABS Plastic Material with inbuilt thermo cut-off Protection and Noise Level not exceeding 37dB o including connection etc USHA/Havells/Polycab/Orient / eq. Make to be approved by EIC.
Supply/Laying of 25/32mm Dia PVC Conduit of Anchor/Ravinder/Polypack/Finolex / eq. Make to be approved by EIC with other accessories like bends,etc complete to be laid in wall for downs and finishing the surface to its original shape by cement mortar plastering/Wall Putty/Tile with same Colour/Paint etc.
Design/Supply/ installation/testing and commissioning of CPRI Approved (IS/IEC:61439) panel Wall / floor mounted) compartmentalized , 415 volts TPN MCCB Mian Distribution panels ,fabricated out of sheet steel of 16 gauge dust protected, painted incl earth terminal with all necessary accessories as required for panel with internal wiring of panel .The Panel is to provided and fitted with following adjustable type controlling /Protection switch gear devices Normal Incoming 160 Amp TPN MCCB with breaking capacity of 36 KAwith extended thimbles of Legrand/Siemens/ ABB/Havells /LK make = 1 no 200 Amp TPN Bus bar Al Strips = 1 Set Volt meter =1 no, Ammeter = 1 no , CT coils for Am meter 300 /5A = 1 set ,phase indicators =1set Generator Incomer 100 Amp Four Pole Change over switch of Havells/Siemens/ ABB /Schinder /L&T make = 1 no 100 Amp TPN Bus bar Al Strips = 1 Set,phase indicators =1set & 100 Amp TPN Bus bar Al Strips = 1 Set Outgoing . (1) 63 Amps DP MCB MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. Make to be approved by EIC = 02 No for normal heating sub main (2) 40 Amps DP MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. Make to be approved by EIC = 02 No for Sub main lighting/invertor (3) 32 Amps DP MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. Make to be approved by EIC = 02 No for Sub main invertor (4) 100 Amp MCCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T / eq. Make to be approved by EIC = 01 No for X-Ray Bypass Change Over Switch: 3-Phase, Four Pole 100 Amp,415V Ac,50Hz offload Manual Changeover Switch side handle in enclosure Havells/L &T/ABB Make including S/F/Crimping of Suitable Size of thimbles for connections as per site requirement for bypassing 10 KVA AVR. as approved. The Panel manufacturing unit should be CPRI Registered and the Contractor has to submit the test certificate of main switch gear and Drawing of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards) is to approved by Engineer Incharge before manufacturing
Supply/Installation/Testing & Commissioning of 10KVA Single -Phase SERVO control VOLTAGE Stabilizer of COPPER wound of Chinar/Cosco/AE/Equivalent Make as Approved ISI/1SO/IEC certified for smooth functioning/constant voltage supply having Technical Specifications : Input voltage 90-260 volts(P-N) & output voltage 220 volts ±2% Buck Boost Transformer Copper wound 99.9% ,OIL Immersed COOLING OIL, High cut/Low Cut /Time delay/Over Cut through Micro Control and Spike Protection complete job & having protection of 63Amp DP from output side Complete job.(For Lighting Only)
P/F of sheet steel Kiosk/Canopy suitable to house 10KVA servo stabilizer of capacities fabricated out of 16 SWG M.S sheet having front door with locking arrangements and duly powder coated.
Supply/Laying/Testing and Commissioning of 3.5 Core 70 mm sq. Al armored XLPE Insulated,PVC cable Havells/Polycab/RR Kabel/Paramount / eq. Make to be approved by EIC. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping.
Supply/Laying/Testing and Commissioning of 3.5 Core 10 mm sq. Al armored XLPE Insulated,PVC cable Havells/Polycab/RR Kabel/Paramount / eq. Make to be approved by EIC. Including Supply/Laying of HDPE Pipe of suitable dia ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping. (from Panel to X-Ray Room)
Supply/Fixing/Testing and Commissioning of 100Amp , 4 pole, (TPN) 440 V, C* Curve 10K, complete with connections Steel Enclosure (L&T/Siemens/ Legrand/ABB/ Schneider / eq. Make to be approved by EIC) (for X-Ray Room)
Supply/Laying/Connecting of 6SWG copper solid wire with cotton cover as required in one run fitted with of brass nut bolt & spring washer up to MAIN Control PANEL through PVC Conduit complete job. (for X-Ray Room) for earthing.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.04 MB
BOQ_967305.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .