| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.9 LAccepted-AOC 59 NEW MARKET CLOCK TOWER DEHRADUN UK PIN 248001 | DEHRADUN | UTTARAKHAND | 248001 | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹21.6 L+₹14,212 (0.66%)Rejected-Finance 1170 BENGALI MOHALLA NEAR PRABHAKAR HOSPITAL AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹29.8 L+₹8.4 L (39.1%)Rejected-Finance 255 VILLAGE UGRA POST OFFICE BARA AMBALA HARAYANA PIN 134003 | AMBALA | AMBALA | HARYANA | 134003 | L3 | Rejected-Finance Other than lowest bidder |
| Sl No | Description | Qty | Unit | M/s badrinath Traders L1 | u and v engineers and consultants L3 | The Rahul Vig L2 |
|---|---|---|---|---|---|---|
| 1.00 | Cleaning of tanks after desludging from sewage tanks (Stilling chamber-01 No,Bar & screen Chamber-01 No ,Oil & grease Chamer-01 No,Equilisation Tank-01 No, treated water tank -01 No, Chlorine Contact Tank-01 No, Tube Settler Tank -01 No, Sludge Holding Tank -01 No ) at Stp Plants of capacity 1.5 MLD to 3.0 MLD etc shall be carried out with water and chemical as applicable and complete white wash from inside after cleaning the tanks and dates of cleaning shall be marked on tank etc complete all as specified and directed.
Note:- 1.Rates for Dewatering and desludging of tanks including T&P and safetly equipments all as directed by Engr-in-Charge is included in above item.
2.Cleaning of each tank will be measured and paid seperately.
. | 32 | Each Job | 5,000 ₹1,60,000 | 1,000 ₹32,000 Lowest | 3,000 ₹96,000 |
| 2.00 | Material & labour carrying out the Tests of treated water from NABL approved lab every month and maintain the record of treated sewage at Each STP Plant as per frequency :-
(i) PH Valve
(ii) TSS
(iii) BOD
(iv) COD
(v) Oil & Grease
(vi) FC Min
(vii) Nitrate CN
Note:- Test report for each month should be submiited at the end of month by contractor .otherwise penalty of Rs. 2000/- per month will be imposed. | 8 | Each | 2,000 ₹16,000 Lowest | 4,000 ₹32,000 | 2,000 ₹16,000 Lowest |
| 3.00 | Taking out Non clog submersible sewage pumping set from eqilisation tank at STP (after and including dewatering of well) of 7.5/10 HP capacity by lifting and dismantling the same for assessing and carrying out the repair/serving and replacement of unserviceable parts with new parts as listed in subsequent items and making good in running condition with balancing, reassembling and lowering the same in well & fixing on the foundation making connections and testing complete all as specified & directed.
Note:- (a) The replaced parts of pump shall be measured & paid separately here-in-after as supply only. (b) Dewatering of well upto max 500 mtr distance from well shall be included in the quoted rate of item. | 6 | Each Job | 2,000 ₹12,000 | 12,000 ₹72,000 | 1,250 ₹7,500 Lowest |
| 4.00 | Rewinding of motor 7.5/10 HP non clog submersible sewage pumping set with suitable size and proper guage of winding wire using best quality of insulation material including all connected items complete all as specified & directed. | 4 | Each Job | 5,500 ₹22,000 Lowest | 12,000 ₹48,000 | 10,000 ₹40,000 |
| 5.00 | Material and labour in replacement CI impeller with guide bush suitable for 7.5/10 HP Non clog submersible sewage pumping set complete all as specified & directed. | 4 | Each | 1,000 ₹4,000 Lowest | 2,700 ₹10,800 | 1,000 ₹4,000 Lowest |
| 6.00 | All as per Srl Item No. 5.00 above but lubricated upper/lower bearing for non clog submersible pump set 7.5/10 HP complete all as specified & directed. Make : NBC/SKF | 4 | Each | 1,000 ₹4,000 Lowest | 4,000 ₹16,000 | 1,000 ₹4,000 Lowest |
| 7.00 | All as per Srl Item No. 5.00 above but pump shaft suitable for non clog submersible pump set 7.5/10 HP complete all as specified & directed. | 4 | Each | 1,000 ₹4,000 Lowest | 2,000 ₹8,000 | 1,000 ₹4,000 Lowest |
| 8.00 | Material & labour for dismentiling centrifugal induction motor from foundation and transport to work shop for rewinding after taking out burnt winding wire from motor of capacity 20 HP three phase , rewinding with copper wire of suitable gauge or as per existing gauge complete including all required insulation material and transport back to site after testing and commisioning complete all as specified & directed.
Make of wire: Finolex/Plaza/Havells.
Note :
a) The Motor testing will be done before installation on No load for any unbalance load and should be free from vibration and if found unsatisfactory no payment will be done to contractor for defected motor.
b) Necessary thimbles, lugs, insulation tape, nut bolts and all items required for installation of motor at site will be included in the rate quoted by the contractor. No extra payment will be done to contractor. | 6 | Each | 10,000 ₹60,000 Lowest | 21,000 ₹1,26,000 | 10,000 ₹60,000 Lowest |
| 9.00 | All as per Srl Item No. 8.00 here in before but of capacity upto 10 HP. | 4 | Each | 7,500 ₹30,000 Lowest | 9,000 ₹36,000 | 8,000 ₹32,000 |
| 10.00 | All as per Srl Item No. 8.00 here in before but of capacity 7.5/5 HP. | 4 | Each | 5,500 ₹22,000 Lowest | 8,000 ₹32,000 | 7,000 ₹28,000 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
30 Jul 2025, 6:00 pmClosed
GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
PREVENTIVE MAINT OF STP INSTALLATION AT SECTOR A B AND C UNDER GE UTILITY AMBALA CANTT
2025_MES_717904_1
CA NO GE U AMB 43 OF 2025-26
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹70,000
19 Aug 2025
1 Jul 2025
1 Aug 2025
1 Jul 2025
30 Jul 2025
16 Jul 2025
1 Jul 2025 - 8 Jul 2025
Amount
Cleaning of tanks after desludging from sewage tanks (Stilling chamber-01 No,Bar & screen Chamber-01 No ,Oil & grease Chamer-01 No,Equilisation Tank-01 No, treated water tank -01 No, Chlorine Contact Tank-01 No, Tube Settler Tank -01 No, Sludge Holding Tank -01 No ) at Stp Plants of capacity 1.5 MLD to 3.0 MLD etc shall be carried out with water and chemical as applicable and complete white wash from inside after cleaning the tanks and dates of cleaning shall be marked on tank etc complete all as specified and directed. Note:- 1.Rates for Dewatering and desludging of tanks including T&P and safetly equipments all as directed by Engr-in-Charge is included in above item. 2.Cleaning of each tank will be measured and paid seperately. .
Material & labour carrying out the Tests of treated water from NABL approved lab every month and maintain the record of treated sewage at Each STP Plant as per frequency :- (i) PH Valve (ii) TSS (iii) BOD (iv) COD (v) Oil & Grease (vi) FC Min (vii) Nitrate CN Note:- Test report for each month should be submiited at the end of month by contractor .otherwise penalty of Rs. 2000/- per month will be imposed.
Taking out Non clog submersible sewage pumping set from eqilisation tank at STP (after and including dewatering of well) of 7.5/10 HP capacity by lifting and dismantling the same for assessing and carrying out the repair/serving and replacement of unserviceable parts with new parts as listed in subsequent items and making good in running condition with balancing, reassembling and lowering the same in well & fixing on the foundation making connections and testing complete all as specified & directed. Note:- (a) The replaced parts of pump shall be measured & paid separately here-in-after as supply only. (b) Dewatering of well upto max 500 mtr distance from well shall be included in the quoted rate of item.
Rewinding of motor 7.5/10 HP non clog submersible sewage pumping set with suitable size and proper guage of winding wire using best quality of insulation material including all connected items complete all as specified & directed.
Material and labour in replacement CI impeller with guide bush suitable for 7.5/10 HP Non clog submersible sewage pumping set complete all as specified & directed.
All as per Srl Item No. 5.00 above but lubricated upper/lower bearing for non clog submersible pump set 7.5/10 HP complete all as specified & directed. Make : NBC/SKF
All as per Srl Item No. 5.00 above but pump shaft suitable for non clog submersible pump set 7.5/10 HP complete all as specified & directed.
Material & labour for dismentiling centrifugal induction motor from foundation and transport to work shop for rewinding after taking out burnt winding wire from motor of capacity 20 HP three phase , rewinding with copper wire of suitable gauge or as per existing gauge complete including all required insulation material and transport back to site after testing and commisioning complete all as specified & directed. Make of wire: Finolex/Plaza/Havells. Note : a) The Motor testing will be done before installation on No load for any unbalance load and should be free from vibration and if found unsatisfactory no payment will be done to contractor for defected motor. b) Necessary thimbles, lugs, insulation tape, nut bolts and all items required for installation of motor at site will be included in the rate quoted by the contractor. No extra payment will be done to contractor.
All as per Srl Item No. 8.00 here in before but of capacity upto 10 HP.
All as per Srl Item No. 8.00 here in before but of capacity 7.5/5 HP.
All as per Srl Item No. 8.00 here in before but of capacity upto 1.5 HP.
Supply & topup in replacement suitable compressor oil in air blower of make Everest Model No N5125 at STP complete all as specified & directed.
Supply and fixing in replacement of front & rear bearing suitable for 20 HP motor as per existing cat part and make complete all as specified & directed. Make-SKF/NBC. Note: a) The rate of dismantling and refixing of motor from pump with complete accessories are quoted in the same item. b) The alingnment of shaft should be checked during installation of motor with pump in all respect. The contractor will be bear the cost of repair in case of failure of motor occurs due to misalingment and no extra payemnt will be paid to contractor.
All as per Srl Item No. 13.00 here in before but of capacity upto 10 HP.
All as per Srl Item No. 13.00 here in before but of capacity 7.5/5 HP.
All as per Srl Item No. 13.00 here in before but of capacity upto 1.5 HP.
Maintenance and repair to leakage/blockage of water supply MS/CI/DI pipe line of 80 mm to 200 dia size including necessary excavation required for taking out burning out lead joint or damaged rubber ring/hole from position and making the disturbed surfaces as per existing surface after replacing new spun yarn and lead joint or Tyton joint or necessary fitting required as per site properly including welding work and making the pipe line leak proof completely to the entire satisfaction of Engineer-in-Charge complete all as specified & directed. Note:- Excavation and earth work shall be included in quoted rate.
Supply only chemicals PAC (Sodium Hypo chloride) required to achieve disired parameter of treated water and required spares for operation of the plant, at least one month requirement of the materials required shall be kept at site at a time etc complete all as specified & directed.
Supply only chemicals PE (Poly Electrolite) required to achieve disired parameter of treated water and required spares for operation of the plant, at least one month requirement of the materials required shall be kept at site at a time etc complete all as specified & directed.
Supply & fix in replacement DWPE Dosing tank of capacity 1000 ltr complete all as specified & directed.
Supply & fix in replacement DWPE Dosing tank of capacity 200 ltr complete all as specified & directed.
Supply & fix in replacement auto desludge valve 80 mm dia for STP plants complete all as specified & directed.
Repair of unserviceable electronic dosing pump of cap 0-6 IPH,pressure 3 kg/sq cm including replacement of U/S parts of pump to make it functional complete all as specified & directed. Note:- Spare Parts are included in above item.
Repair of unserviceable sludge feed pump screw type discharge 4 meter cube/ HR and 8 mtr head including replacement of U/S parts of pump to make it functional complete all as specified & directed. Note:- Spare Parts are included in above item.
Taking out damaged SGW sewage pipe and supply and laying Ductile iron pipe of 200mm bore, S/S,Class K-9 , including rubber gasket(tyton) joints, nut, bolts & washers ISI marked including excavation earth work complete all as specified & directed.
Taking out damaged SGW sewage pipe and supply and laying Ductile iron pipe of 150 mm bore, S/S,Class K-9 , including rubber gasket(tyton) joints, nut, bolts & washers ISI marked including excavation earth work complete all as specified & directed.
Supply and fix in replacement of CI foot valve 200 mm nominal bore ISI marked complete including dewatering of tanks for replacement , gasket nuts, washers etc complete all as specified & directed.
Supply and fix in replacement of CI air release valve 200 mm nominal bore ISI marked complete including gasket nuts, washers etc complete all as specified & directed.
Supply and fixing in replacement of stop valve cast copper alloy of 40 mm complete all as specified & directed.
Supply and fixing in replacement of stop valve cast copper alloy of 25 mm complete all as specified & directed.
Supply & fix in replacement Butter Fly Valve lever operated conforming to IS 13095 of size upto 150 mm dia PN 1.0, connected with two end flanges suitable for connecting with Pipe , nut-bolts etc with flanges nut - bolts etc complete all as specified & directed.
All as per Srl Item No. 31.00 above here in before but 125 mm dia.
All as per Srl Item No. 31.00 above here in before but 100 mm dia.
All as per Srl Item No. 31.00 above here in before but 80 mm dia.
All as per Srl Item No. 31.00 above here in before but 50 mm dia.
All as per Srl Item No. 31.00 above here in before but 40 mm dia.
Supply fix and testing in replacement of Non Return Valve 150 mm dia PN 1.0, connected with two end flanges suitable for connecting with Pipe, nut-bolts etc with flanges nut - bolts etc complete all as specified & directed.
All as per Srl Item No. 37.00 above here in before but 125 mm dia.
All as per Srl Item No. 37.00 above here in before but 100 mm dia.
All as per Srl Item No. 37.00 above here in before but 50 mm dia.
Supply & fix in replacement Sluice Valve with spindle and check nut conforming to IS 14846 of size upto 200 mm dia PN 1.0, connected with two end flanges suitable for connecting with Pipe , nut-bolts etc with flanges nut - bolts etc complete all as specified & directed.
All as per Srl Item No. 41.00 above here in before but 150 mm dia.
Supply, fixing in replacement & testing on wall or laid under floor GI pipe 40 mm medium grade ISI marked with all fittings including earth work complete all as specified & directed.
All as per Srl Item No. 43.00 here in before but of 25 mm bore.
Supply and fix in replacement PVC insulated aluminium cable round of size 10 Sqmm 3 core complete all as specified & directed.
Supply and fix in replacement PVC insulated submersible copper cable flat/round of size 6 Sqmm 3 core complete all as specified & directed.
Supply and fix in replacement PVC insulated copper cable flat/round of size 1.5 Sqmm 4 core complete all as specified & directed.
Excavation in trenches n.exc 1.5 m wide and in depth and getting out in soft/loose soil for laying cables, errection of poles complete all as specified & directed.
Removing excavated materials (soil) n.exc 50m and depositing where directed at at level not exceeding above the starting point complete all as specified & directed.
Returning filling in including spreading levelling, watering and well raming in layers n.exc 25 cm complete all as specified & directed.
Sand cushioning/sand covering for underground cable protection complete all as specified & directed.
Supply and laying double walled corrugated (DWC) HDPE duct pipe of 50mm dia conforming to IS, approved colour complete with fittings for cable protection complete all as specified & directed.
All as per Srl Item No. 52.00 here in before above but 80mm dia.
Taking down/out unserviceable UG cables of any cross sectional area and connections including Bricks, GI Pipes, etc of any descriptions, laid in trenches and/or fixing with walls/poles including segregating of serviceable materials viz Bricks, cables, GI Pipes etc complete all as specified & directed.
Supply & Fixing or Passing through pipe, XLPE insulated, Armoured, Electric power UG cable (Heavy duty) with aluminium conductor, 1100 volts grade, nominal cross sectional area 10 sqmm 2 core including cable gland, terminal lug etc and testing complete all as specified & directed.
All as per Srl Item No. 55.00 here in before above, but nominal cross sectional area 16 sqmm 4 Core .
All as per Srl Item No. 55.00 here in before above, but nominal cross sectional area 70 sqmm 3.5 Core .
All as per Srl Item No. 55.00 here in before above, but nominal cross sectional area 95 sqmm 3.5 Core .
Material & labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 3.15 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, connected to galvanised means of GI strip 32x6 mm and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion complete all as specified & directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance ismore than 2Ώ the earthing will be redone at no extra cost.
Material & labour for cable three core PVC insulated, PVC sheathed multi stranded copper conductor size 2.5 Sqmm 3 core for connection junction box to security light/bollard light complete all as specified & directed.
Taking down worn out , unserviceable and Supply & Fixing Thermo plastic cable Junction box 3 phase with MCB SP 10A suitable for Cable IP 65 Protection with metric knockout for cable entry including MS clamp fixed on pole with clamp nuts,bolts etc complete all as specified & directed.
Supply and fixing in replacement warm type LED Integral decorative type bollard 12 watt IP 65 protection, class I with operating voltage range 120 to 270 V complete all as specified & directed.
Supply & fix in replacement of flat/V belt/coupling coupled with air blower motor or pump motor set as per existing complete all as specified & directed.
Material & labour in replacement of unserviceable wire connectors of size 10-16 sqmm in LT panels complete all as specified & directed.
Material & labour in replacement of unserviceable LED indicator lamp in LT panels as per existing size complete all as specified and directed.
Supply & fix in replacement LED driver suitable for 45W LED street light complete all as specified & directed.
Supply & fix in replacement LED 70 W Street Light with all fixing arrangment complete all as specified & directed.
Material & labour in replacement of the unserviceable contactor 3 pole of AC3 rating of 200 Amp or as per existing rating and 415V coil rating complete with all new wiring including thimbles and lugs,nuts and screws complete all as specified & directed.
Material & labour in replacement of the unserviceable contactor 3 pole of AC3 rating upto 60 Amp or as per existing rating and 220 V/415V coil rating complete with all new wiring including thimbles and lugs,nuts and screws complete all as specified & directed.
Material and labour against replacement of worn out / defective thermal overload relay with range 28-42 Amps 415 V, 50 Hz, complete all as specified & directed.
Material and labour against replacement of worn out / defective single phase preventor suitable upto 40 HP motor star- delta starter 415 V, 50 Hz complete all as specified & directed.
Material and labour against replacement fully automatic star-delta starter for submersible pump set of capacity 30 HP , 415 V , with relay range 30-50 amps 50 Hz 3 Phase ,with single phase protection complete all as specified & directed.
Material & labour for atending any type pump/motor/LT panels/DGs/Starters complaint at pump houses and boosters and rectify the same, rates are also included for replcement of thimbles any type and any size with nut-bolts and cable jointing with tap, gland packing, greasing in pumps/valves with all connected items complete all as specified & directed. Note: Complaint should be rectify within 06 Hrs otherwise a penalty of 250 Rs per day will be imposed.
Material & labour in replacement of MCCB 4P , 35 KA breaking capacity, 160/200 Amp, 50 Hz adjustable thermal and magnectic type with thimbles and nut-bolts complete all as specified and directed.
Material & labour in replacement of MCCB 4P , 16 KA breaking capacity, 100 Amp, 50 Hz adjustable thermal and magnectic type with thimbles and nut-bolts complete all as specified and directed.
Material & labour in replacement of MCCB 4P , 10/16 KA breaking capacity, 63 Amp, 50 Hz adjustable thermal and magnectic type with thimbles and nut-bolts complete all as specified and directed.
Material & labour in replacement of MCB TP 63 Amp including suitable size of connectors complete all as specified and directed.
Material & labour in replacement of MCB TP 32 Amp including suitable size of connectors complete all as specified and directed.
Greasing/Oiling of blowers capacity 20/30 Hp with grease gun and necessary T&P for greasing/oiling of pump set/blower at STP installation complete all as specified & directed.
Greasing/Oiling of blowers/pumps/motors capacity 10 Hp to 40 Hp with grease gun and necessary T&P for greasing/oiling of pump set/blower at STP installation complete all as specified & directed.
Painting of blowers/Motors/pumps of capacity 10 to 40 Hp with spray coated painting and necessary T&P for painting of pump set/blower at STP installation complete all as specified & directed.
Taking down existing blower of capacity 450 m3/hr ,2050 RPM from the existing position after disconnecting all electrical connections and transportation to workshop for repair of unserviceable parts complete and removing defective parts , repair the air blower throughly including machine work and reassembling the air blower and commisioning testing complete on full load complete all as specified and directed.
Material & labour for removing the filer media of different sizes from the carbon filter / MS Dual media filter of size 2300/ 2500 mm dia and 1600 to 1800 mm height and Cleaning of dual media filter, sand 16/ 32 filter media beds, Activated carbon filter media, fine silex in filters, coarse silex in filters, 6-2 crushed gravels,20-12 pebbles in filter beds, 40-25 pebbles in filter beds and wash by bleaching powder and cleaning of existing pipe holes after refilling and topup of filter media as per existing capacity of media filters in each Tank complete all as specified and directed. Note for item No 85 to 94 :- 1. Defective media shall be replace by the contractor and cost of the same shall be paid unde respective item. 2. All filter media should be supplied from STP manufacturing company. 3. Contractor have to produce original purchase vouchers from STP manufacturing company for payment purpose.
Material & labour Cleaning of internal wall of MS Activated carbon filter / MS Dual media filter of size 2300/2500 mm dia and 1600 to 1800 mm height for removing the filter media by brushing with nylon brush and using bleaching powder and cleaning of existing pipe holes after refilling of existing useable filter media complete all as specified and directed.
Material & labour for replacing Anthracite in dual media filter as per existing complete all as specified and directed.
Material & labour for replacing filtering sand 16/32 filter media beds as per existing complete all as specified and directed.
Taking out defective carbon media, Supply and Laying Activated carbon filter media as per existing for carbon filters complete all as specified and directed.
Material & labour for replacing fine silex in filters as per existing complete all as specified and directed.
Material & labour for replacing coarse silex in filters as per existing complete all as specified and directed.
Taking out defective coarse gravel, supply and laying 6-2 crushed gravels in filter bed as per existing complete all as specified and directed.
Taking out defective pebbles, Supply and Laying 20-12 pebbles in filter beds as per existing complete all as specified and directed.
Taking out defective pebbles, Supply and Laying 40-25 pebbles in filter beds complete as per existing all as specified and directed.
Complete removal of the wild grass/ vegetation from surrounding area of STP installations area and making the surface clear and plain and spraying roundup chemical on the same clean area as directed after removing and depositing the same at a distance not less than 50 mtr away from the site complete all as specified and directed. Note:- 1. T&P machinary will be provided by the contractor.2.Cleaning should be done regularly as directed by Engr-in-Charge. 3.Contractor have to pay recovery of Rs 500/- per day for non Cleaned area.
Supply & fix in replacement air filter suitable for existing vertical type blower of capacities 425 m3/hr complete all as specified & directed.
Note:- Amount of credit of Rs. 56642.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in pdf form which will be deducted offline while acceptance of tender.
The Rahul Vig (BID ID -3370434)
u and v engineers and consultants (BID ID -3375937)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .