| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.0 LAccepted-AOC THEERTHAM NADUVILEMURI PADANILAM POST NOORANAD ALAPPUZHA DIST KERALA 690529 | ALAPPUZHA | KERALA | 690529 | ₹37.0 L Quoted ₹37.9 L | L1 | Accepted-AOC Awarded contract being lowest |
| 2 | L2₹42.6 LRejected-AOC | ₹42.6 L | L2 | Rejected-AOC Rejected not being lowest |
| Sl No | Description | Qty | Unit | Green Ray Enterprises L1 | ELSOL ENGINEERS L2 |
|---|---|---|---|---|---|
| 1.00 | Material and labour for servicing of 2 Nos 2 HP booster pumps, 230V by checking functionality, abnormality, cleaning, proper alignment of fan covers, tightening nut bolts including scrapping of rust and painting on pumps, 20 ltrs expansion tank complete all as specified and as directed. | 1 | Each Job | 16,000 ₹16,000 | 14,700 ₹14,700 |
| 2.00 | Supply & Fix in replacement of single phase computerized alternating twin pump controller suitable to operate 2 Nos 2 HP booster pumps alternatively with following features,
a) short circuit protection,
b) overload protection,
c) low voltage protection,
d) dry run protection,
e) 1 inch graphic display showing voltage, current, Auto/manual mode, pressure switch high/low
f) Both pumps bypass toggle switches,
g) Inbuilt timers for ON time/OFF time.
complete all as specified and interconnected with fioat switch/pressure switch, making electrical connections and testing at site including taking down unserivecable panel | 1 | Each | 34,000 ₹34,000 | 18,900 ₹18,900 |
| 3.00 | Supply & Fix in replacement of float switch with counter weight to interconnect with booster pump for safety of dry run complete all as specified and as directed. | 1 | Each | 800 ₹800 | 900 ₹900 |
| 4.00 | Supply & Fix in replacement of pressure switch (regulation range 2-14 bar, diff range 0.7 to 4 bar) including taking down unserivceable complete all as specified and as directed. | 1 | Each | 2,500 ₹2,500 | 2,540 ₹2,540 |
| 5.00 | Supply & Fix in replacement liquid filled pressure gauge (0-10 bar/0-150 Psi ) including taking down unserviceable complete all as specified and as directed. | 1 | Each | 2,300 ₹2,300 | 2,390 ₹2,390 |
| 6.00 | Material and labour for 3 phase centrifugal monoblock pumpset foundation alignment upto 10 HP capacity including disconnection of pumpset electrical connections/suction and delivery pipes,removing of pumpset from foundations, removing of rusted/broken foundation bolts by dismantling of PCC/RCC and making good of foundation by observing with water level indicator/ mercury level indicator maintaining asthetic view and re-fixing pumpset with new foundation bolts on re- aligned foundation and testing at site complete all as specified and as directed. | 15 | Each Job | 2,800 ₹42,000 | 4,300 ₹64,500 |
| 7.00 | All as per item No. 6 here-in-before but of capacity single phase, 1 HP pumpsets. | 35 | Each Job | 1,700 ₹59,500 | 3,600 ₹1.3 L |
| 8.00 | Supply & Fix in replacement of powder coated metal safety guards of min size 300mmx200mmx220mm complete all as specified and as directed. | 25 | Each | 1,900 ₹47,500 | 3,200 ₹80,000 |
| 9.00 | Supply & Fix in replacement of dry run protection relay (current based) with adjustable current setting, single phase, 240V compatible with MU2P single phase DOL starter and testing with pump dry run complete all as specified and as directed by Engr-in-charge.
Make : L&T (i-AD) or equivalent in siemens/C&S
Note : The relay should trip the supply min 3 times of dry run condition inpresence of JE/AGE, otherwsie contractor has to ensure its functionality without extra cost. | 24 | Each | 1,650 ₹39,600 | 2,100 ₹50,400 |
| 10.00 | Supply & Fix in replacement of single phase preventer & dry run protection relay (current based) with adjustable current setting, three phase, 4l5V compatible with MK1/MU/MUG three phase starters and testing with pump dry run complete all as specified and as directed.
Make : L&T (i-ADS) or equivalent in siemens/C&S
Note : The relay should trip the supply min 3 times of dry run condition inpresence of JE/AGE, otherwsie contractor has to ensure its functionality without extra cost. | 15 | Each | 2,600 ₹39,000 | 3,200 ₹48,000 |
Updated dates
Tender Value
₹39.9 L
EMD Value
₹79,840
Closing Date
23 Feb 2026, 6:00 pmClosed
GE(MAINT)EZHIMALA
GARRISON ENGINEER (MAINT) MILITARY ENGINEER SERVICES INDIAN NAVAL ACADEMY POST KANNUR DIST KERALA 670 310
AS PER BOQ AND TENDER DOCUMENTS
2025_MES_741519_2
GE MAINT EZHIMALA 8806
Open Tender
Civil Works
330 days
Ezhimala
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (Maint) Ezhimala
₹79,840
Yes
19 Mar 2026
20 Jan 2026
2 Mar 2026
20 Jan 2026
23 Feb 2026
4 Feb 2026
20 Jan 2026 - 27 Jan 2026
Material and labour for servicing of 2 Nos 2 HP booster pumps, 230V by checking functionality, abnormality, cleaning, proper alignment of fan covers, tightening nut bolts including scrapping of rust and painting on pumps, 20 ltrs expansion tank complete all as specified and as directed.
Supply & Fix in replacement of single phase computerized alternating twin pump controller suitable to operate 2 Nos 2 HP booster pumps alternatively with following features, a) short circuit protection, b) overload protection, c) low voltage protection, d) dry run protection, e) 1 inch graphic display showing voltage, current, Auto/manual mode, pressure switch high/low f) Both pumps bypass toggle switches, g) Inbuilt timers for ON time/OFF time. complete all as specified and interconnected with fioat switch/pressure switch, making electrical connections and testing at site including taking down unserivecable panel
Supply & Fix in replacement of float switch with counter weight to interconnect with booster pump for safety of dry run complete all as specified and as directed.
Supply & Fix in replacement of pressure switch (regulation range 2-14 bar, diff range 0.7 to 4 bar) including taking down unserivceable complete all as specified and as directed.
Supply & Fix in replacement liquid filled pressure gauge (0-10 bar/0-150 Psi ) including taking down unserviceable complete all as specified and as directed.
Material and labour for 3 phase centrifugal monoblock pumpset foundation alignment upto 10 HP capacity including disconnection of pumpset electrical connections/suction and delivery pipes,removing of pumpset from foundations, removing of rusted/broken foundation bolts by dismantling of PCC/RCC and making good of foundation by observing with water level indicator/ mercury level indicator maintaining asthetic view and re-fixing pumpset with new foundation bolts on re- aligned foundation and testing at site complete all as specified and as directed.
All as per item No. 6 here-in-before but of capacity single phase, 1 HP pumpsets.
Supply & Fix in replacement of powder coated metal safety guards of min size 300mmx200mmx220mm complete all as specified and as directed.
Supply & Fix in replacement of dry run protection relay (current based) with adjustable current setting, single phase, 240V compatible with MU2P single phase DOL starter and testing with pump dry run complete all as specified and as directed by Engr-in-charge. Make : L&T (i-AD) or equivalent in siemens/C&S Note : The relay should trip the supply min 3 times of dry run condition inpresence of JE/AGE, otherwsie contractor has to ensure its functionality without extra cost.
Supply & Fix in replacement of single phase preventer & dry run protection relay (current based) with adjustable current setting, three phase, 4l5V compatible with MK1/MU/MUG three phase starters and testing with pump dry run complete all as specified and as directed. Make : L&T (i-ADS) or equivalent in siemens/C&S Note : The relay should trip the supply min 3 times of dry run condition inpresence of JE/AGE, otherwsie contractor has to ensure its functionality without extra cost.
Supply & Fix in replacement of single phase i-protector wire harness of min 1.5 Mtr length complete all as specified and as directed.
Supply & Fix in replacement of three phase i-protector wire harness of min 1.5 Mtr length complete all as specified and as directed.
Supply & Fix in replacement orange/black coloured iron fan covers suitable to 3 phase pumps of capacity upto 10 HP capacity complete all as specified and as directed.
All as per item No.13 here-in-before but of capacity single phase, 1 HP pumpsets.
Supply & Fix in replacement of external PVC fan frame of 3 phase pumpsets capacity upto 10 HP complete all as specified and as directed.
All as per item No.15 here-in-before but of capacity single phase, 1 HP pumpsets.
Material and labour for scraping the old paint by using wire brush and emery paper and preparation of the surface for painting the following pump set's /control panel /suction and delivery pipe of the pump house with one coat of primer and two coat of synthetic enamel paint all as specified and directed at site of the following items of Water supply installations:-
10 HP Pumpsets
7.5HP Pumpsets
5HP Pumpsets
01 HP pump
Material and labour for cleaning of treated water tanks of 50,000 ltrs capacity by dewatering the sump, removal of sand/muddy water/ sewage sludge by using sludge pumps, removal of left out sludge from the floor, transport & deposit of sludge at designated place/ dump yard including making necessary breakage of slab/roof of sump to movement manpower/tools/ventilation to caryyout job work and making good complete all as specified and as directed by Engr-in-charge. Location : Golf pump house Note : Contractor has to make sure availability necessary ventilation before commencement work, contractor has to carryout work safety procedures. contractor is solely responsible for any damage to government property and working manpower.
Supply & Fix in replacement of 3 phase, 75 kW/l00 HP VFD drive, C Choke, Inbuilt PLC, LCD Display unit,150 Amps including removal of unserviceable soft starter module and re-fixing VFD drive. The VFD drive specifications as, capacity : 75 KW/100 HP suitable for 100 HP pumpset, Application : Variable speed and smooth start. Protection : Overload, Under voltage and all other protections for 100 HP pumpset. Rated Voltage / Frequency : 3-phase AC 380-480 V ( -15% to +10%), 50 / 60 Hz . Make : DELTA (C-2000 series) VFD750C43A-00 or equivalent in ABB/Siemens
Supply & Fix in replacement MCB, 230V, 10kA 'C' curve, DP 6-32A in the panels complete all as specified and directed. Make : L&T/C&S/Havells or equivalent
Supply & Fix in replacement of old u/s DOL starter (Direct on line) 1 phase 230 Volts 50 Hz relay range 06 to 10 Amps including taking down old material complete all as specified and as directed. TYPE: MU2P Make : L&T/C&S/AE
Supply & Fix in replacement of old u/s DOL starter (Direct on line) 3 phase 415 Volts 50 Hz relay range 6-I0A/9-14A including taking down old material complete all as specified and as directed by Engineer-in-Charge. TYPE: MK1 Make : L&T/C&S/AE
Supply & Fix in replacement FASD (Fully Automatic Star Delta starter) 3 phase 415 Volts 50 Hz relay range 13-22A including taking down old material complete all as specified and as directed. TYPE: MKl Make : L&T/C&S/AE
Supply & Fix in replacement of old u/s Rigid non-metallic PVC conduit of dia 25mm exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.complete all as specified and and as directed.
Supply & Fix in replacement of old u/s PVC insulated and FRLS PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, 3 core x 16 sqmm including taking down old unserviceable material complete all as specified and as directed. Make : Finolex/Hazells/Polycab or equivalent
All as per item No.26 here-in-before but of 3 core x 6 sqmm.
All as per item No.26 here-in-before but 3 core x 2.5 sqmm.
Supply & Fix in replacement of 12.5 KVAR box type MPP capacitor, 440V connected to motor starter panels complete all as specified and as directed.
All as per item No.29 here-in-before but of capacity 20 KVAR.
Supply & Fix in repair copper conductor cable of 1100V grade, PVC insulated, round sheathed (flexible) un-armoured industrial cable of size 50 Sqmm x 3 core with proper saddles & lugs complete all as specified and as directed. Make : Polycab/Gloster/KEI or equivalent.
Supply & Fix in replacement of SS cable tray of size 75mm width, 25mm height including necessary bends, covers complete all as specified and as directed.
Supply & Fix as in repairs LT Panel indoor type floor mounted free standing dust and vermin proof panel / DB with IP-42 protection, CPRI approved, frame fabricated out of 40mm x 40mm x 4mm angle iron, 3 mm thick CRCA sheet for entire outer panel with single door and locking arrangements & 1.6 mm for inner compartment with 40mmx4mm flat Iron, including Separate cubicle chamber with cable alley not less than 300mm width for installation/connecting switchgears with the main bus bar using aluminium bus link or copper conductor flexible wires suitable for switch rating and connecting outgoing terminals of the switchgear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles, MS surfaces epoxy based powder coated, shade as approved over a coat of red oxide primer, surfaces pre-treated in seven tank process for de-greasing, de-rusting & Phosphated, panel having front and rear opening and provision for installation of separate cable alleys, all MCCBs must be have thermal magnetic release, busbar chamber and switchgear compartments, Provision in cable alleys for bottom cable entry for incoming & outgoing cables, affixing MV danger plate at suitable intervals / locations including erection, testing and commissioning complete all as specified and as directed including the following fixtures amd fitments mentioned below.
Outgoing:- Separate cubical chamber with a cable alley not less than 300 mm width for installation/ connecting the following switch gear with the main bus bar using aluminium bus link or copper conductor flexible wires suitable to the switch rating and connecting outgoing terminals of the switch gear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles.
(i) MCCB, 4 pole 160 A, 36 KA -01 No (ii) MCCB, 4 pole 100 A, 16 KA -04 Nos (iv) MCB TPN 40 A - 02 Nos (iv) MCB, SPN 40 A -03 Nos Make of MCCB: L&T / Seimens / Schneider / ABB
All as per serial item No. 33 here-in-before but with the following fittings & fixures :-
Outgoing:- (i) MCCB, 4 pole 125 A, 36 KA - 01Nos (i) MCCB, 4 pole 125 A, 16 KA - 02 Nos (ii) MCCB, 4 pole 100 A, 16 KA - 02 Nos (iii) MCB SPN 32 A - 02 Nos Make of MCCB: L&T / Seimens / Schneider / ABB
Material & Labour for painting old surfaces of Feeder Pillar boxes / LT panels of any sizes at site with two coats of synthetic enamel paint DANCOT/Asian make shade / tint as approved including preparation of surfaces, cleaning rusted portion complete all as specified and as directed.
Supply and fix in repair following fixtures / fittings for replacement in LT Panel boards:-
MCCB, 36 KA, 4 pole, 400A
MCCB, 36 KA, 4 pole, 250A
MCCB, 36 KA, 4 pole, 200A
MCCB, 36 KA, 4 pole, 160A
MCCB, 16 KA, 3 pole, 125A
MCCB, 16 KA, 3 pole, 100A
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exeeding 1.5 m deep, getting out the excavated earth bottom surface to required gradient complete all as specified and as directed.
Material & Labour for removal of excavated material such as soils n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point.
Returning filling in, and including spreading and leveling in layers not exceeding 25 cm thick complete all as specified and as directed.
Material & Labour for spreading riddle earth for cushioning and covering of the UG cable in two layers, first laylers of 80 mm thick before laying of cable and second layer of 150 mm thick after laying of cable in trenches/ ducts including consolidation of each layers complete all as specified and as directed.
Material and labour well burnt old size sub Class ‘B’ bricks, laid flat, in trenches for cable protection complete all as specified and as directed.
Material & Labour for cutting the existing road/ hard standing made of concrete or premix carpet, WBM, soling and moorum filling including excavating for laying the cable/ pipe, width 0.5 Mtr and depth 0.7 Mtr all as directed and making good the road/ hard using pre mix bituminous as required at site to match with the existing surface all as specified and as directed. NOTE: Before using the hand drilling/ breaker machine diamond cutter will be used as specified and as directed.
Supply and laying XLPE insulated, armoured, heavy duty, 1100 Volts grade aluminium conductor cable cross sectional area 70 Sqmm, 3.5 core in trenches or fixed to wall/ passing through pipe/ pole and testing compete all as specified and as directed. Note : (i) Excavation & earth work, Brick protection and sand cushioning shall be measured and paid for separately.
All as per description of item No.46.00 here-in-before but Cross sectional area 95 sq mm, 3.5 core
M&L for earthing complete with Galvanised steel earth plate eletrode 600 mm x 600 mm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filled in alternate layers and electrode connections by using Galvanised earth strip 25x4mm connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 40 mm dia GI pipe medium grade for protection of GI earth strip and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) type C1 chamber, MS funnel, wire mesh, 50 mm thick RCC 1:2:4 type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I. Note: (i) Cost of GI earth wire and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item. (ii) The unit rate shall also includes for Wire mesh, funnel, excavation, returning filling , removing , PCC chamber pit, RCC cover, test point etc.
Material & Labour for earthing continuity conductor or main earthing lead fixed to wall on batten on recess or chases or buried in ground or dawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of size 25 x 4 mm Aluminium strip for connection.
Supply, repair and replacement of power contactor ML-4 TP,Fr 3 size Amps rating 100/70, 415V of coil voltage 220 V with aux contact 2 No + 2 NC including taking down the old unserviceabel contractor part No SS 90910 complete all as specified and as directed. Make : L&T or equivalent
Taking down carefully Aluminum/ copper point wiring complete for light, fan, 5 A socket, 15 Amps socket, 2 way points and bell point etc in any type of wiring with boards, holders and any type of electrical fittings etc complete & making good to disturbed area, complete all as specified and as directed.
(b) One fan/Exhaust point point controlled by one switch
Supply & Fix modular switch 6 Amp, 230 volts AC one way, complete all as specified and as directed. Make -Indoasian/Havells/Legrand/Schneider/Gold Medal
Supply & Fix modular fan regulator electronic step type complete all as specified and as directed. Make -Indoasian/Havells/Legrand/Schneider/Gold Medal
Supply & Fix of ceiling rose 3 terminal suitable for 230 volts AC supply, complete all as specified and as directed.
Supply & Fix in repair Modular white cover plate with frame & plastic boxes 8 module 230 Volts AC complete all as specified and as directed.
Supply & Fix in repair Modular white cover plate with frame & plastic boxes 6 module 230 Volts AC complete all as specified and as directed.
Supply & Fix in repair Modular white cover plate with frame & plastic boxes 4 module 230 Volts AC complete all as specified and as directed.
Supply & Fix in repair Modular white cover plate with frame & plastic boxes 3 module 230 Volts AC complete all as specified and as directed.
Taking down old US submain wiring of aluminium conductor cable of 2.5 ,4,6,of any size sq.mm, complete all as specified and as directed.
Material and labour for 2.5 Sq mm Sub main wiring with 2 runs of single core PVC insulated unsheathed multistranded copper conductor cables FRLS of drawn through and including PVC conduit of suitable size with all necessary fittings and provn of one run of 2.5 sqmm single core PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor and connecting to common earth dolly all as specified and as directed.
Material and labour for 4.0 Sq mm Sub main wiring with 2 runs of single core PVC insulated unsheathed multistranded copper conductor cables FRLS of drawn through and including PVC condiut of suitable size with all necessary fittings and provn of one run of 4.0 sqmm single core PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor and connecting to common earth dolly all as specified and directed.
Material and labour for 6.0 Sq mm sub main wiring with 2 runs of single core PVC insulated unsheathed multistranded copper conductor cables FRLS of drawn through and including PVC conduit of suitable size with all necessary fittings and provn of one run of 6.0 sqmm single core PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor and connecting to common earth dolly all as specified and as directed.
Attending day to day complaints which including interruption/failure of power supply/voltage variation/tripping of circuit breaker including MCBs/MCCBs/ACBs, etc. including replacement of unserviceable switch, sockets , fan regulator, fan condenser, light fittings etc. Removing burned cable from DBs and repair the same with new MCBs. NOTE :-- (i) New parts shall be measured and paid separately under relevant item(s) of this schedule as 'Supply Only'. (ii) Necessary T&P i.e. ladder, tools etc required for checking and making the fittings and fixtures in serviceable conditions and its fixing in position and testing shall be arranged by the contractor at his own cost. (iii) If contractor fail to attend the complaint within 2 hrs, a penality of Rs.200.00 per hr will be imposed on him upto 12 hrs then after a penality of Rs.500.00 per hr will be imposed. In this matter GE's decision is final.
Supply only modular switch 6 Amp, 230 volts AC one way, complete all as specified and as directed.
Supply only modular bell push AC, 230 Volts 6 Amp complete all as specified and as directed.
Supply only modular Modular switch 2 way 6A 1 module, 230 Volts 6 Amp complete all as specified and as directed.
Supply only modular fan regulator electronic step type complete as specified and as directed.
Supply only of ceiling rose 3 terminal suitable for 230 volts AC supply, complete all as specified and as directed.
Supply only of call bell, ding dong, 230 volts AC supply all as specified and as directed.
Supply only Switch piano type single pole, one way 15 Amps 230 Volts AC circuit complete all as specified and as directed.
Supply only stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. all as specified and as directed.
Material and labour for disconnecting, taking down & removing carefully the existing ceiling fan, exhaust fans, wall bracket fans, air circulating fans etc. of any description, any sweep and from any position / locations for repairs / servicing dismantling & opening of the fans, checking serviceability of parts, overhauling by necessary cleaning, oiling & greasing, painting of fan with leaf, fixing the serviceable parts in position, removing & replacement of defective/ unserviceable parts, if any, with new parts, reassembling the fans, making necessary adjustment and proper alignment of blades, painting ,hanging / fixing the repaired fans in position, connecting to existing electric sources and testing at site to the entire satisfaction of Engineer-in-Charge complete all as specified and as directed. Note: - (i) The replacement of defective / nonfunctional parts shall be measured & paid separately as “Supply only" under appropriate item of Sch ‘A’. Fixing charges for new items are deemed to be excluded under this item. (ii) Supply only the following new parts suitable for the ceiling/ exhaust fans, wall bracket fans & pedestal fans, air circulating fans etc. of any description, any sweep. (iii) Fixing & testing charges of these items are deemed to be included in the rates quoted by the tenderer for Sch ‘A’ above item.
Supply only ball bearing No 6200 to 6203, all as specified and as directed.
Supply only capacitor of capacity 2.5 mfd (PVC body), all as specified and as directed.
Supply only capacitor of capacity 3.15 mfd (PVC body), all as specified and as directed.
Supply and fix in repairs twin core flexible cords with multistranded copper conductor of size 1.50 sqmm,1100 volts grade from ceiling rose to connector block of ceiling fans/ exhaust fans all as specified and as directed.
Supply and fixing of 300mm long down rod 15 mm dia, MS tube light grade, duly finished with powder coating of white colour, including necessary holes and threading etc. complete all as specified and as directed.
Supply and fixing of 900mm long down rod 15 mm dia, MS tube light grade, duly finished with powder coating of white colour, including necessary holes and threading etc. complete all as specified and as directed.
Supply and fixing of 1200mm long down rod 15 mm dia, MS tube light grade, duly finished with powder coating of white colour, including necessary holes and threading etc. complete all as specified and as directed.
Taking out & removing old burnt-out windings of electric fans of any description and rewinding of fan motor with appropriate size super enameled copper wire (Make : Atlas/Finolex/Devi Dayal) as approved by the Engineer-in-charge including insulating material such as illuminous paper, Letherized paper, cotton tape, glass sleeving, insulating varnish etc testing at workshop and transportation to site, connecting and testing on full load to the entire satisfaction of Engineer-in-charge for the following fans:-
Rewinding of motor of ceiling fans 1200/1400 mm sweep.
Rewinding of motor of exhaust fans 225/250 mm sweep.
Rewinding of motor of exhaust fans 300/400 mm sweep.
Rewinding of motor of exhaust fans 450 mm sweep.
Supply and fix MCB SP 240 Volt of capacity 16 to 32 Amps ‘C’ series, complete all as specified and as directed.
Supply and fix in replacement of old unservisable mild steel frame with four legs suitable for 300 mm to 450 mm exhaust fan smoke grey colour painted including nuts and bolts suitable for Khaitan /Polar/Bajaj/Orient/CG/Havells complete all as specified and as directed.
Supply and fix in replacement fan blade of mild steel duly painted split pin suitable for 300 mm to 450 mm exhaust fan of smoke grey colour including nut and bolt suitable for Havells,CG complete all as specified and as directed.
Supply and fix in replacement fan blade of mild steel duly painted split pin suitable for 1200 mm celing fan of existing colour including nut and bolt suitable for Havells,CG complete all as specified and as directed.
Supply and fix in replacement of fan motor suitable for exhaust fan of Size 450 mm sweep,100-120 Watt,230 V,50 Hz,minimum 2100 RPM to ISI marked complete all as specified and as directed.
Supply and fix in replacement of fan motor suitable for exhaust fan of Size 300 mm sweep,50-60 Watt,230 V,50 Hz,minimum 1360 RPM to ISI marked complete all as specified and as directed.
Supply and fix in replacement of fan motor suitable for ceiling fan of Size 1200 mm sweep,100 Watt,230 V,50 Hz,minimum 1360 RPM, ISI marked complete all as specified and as directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 4.09 MB
BOQ_839120.xls
BOQ • 0.52 MB
TenderDocument8806.pdf
Tender Documents • 1.15 MB
Download all tender documents and submit your bid