Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-AOC 0001D ATM HOUSE AIR FORCE NEENA THAPA GORAKHPUR UTTAR PRADESH 273008 UDYAM UP 32 0054752 | GORAKHPUR | UTTAR PRADESH | 273008 | L1 | Accepted-AOC LOWEST QUOTED BIDDER | |
| 2 | L2₹14.2 L+₹2.8 L (24.5%)Rejected-Finance | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 3 | L3₹15.6 L+₹4.2 L (36.5%)Rejected-Finance | L3 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
13 Oct 2022, 6:00 pmClosed
CWE AF SECUNDERABAD
CWE AF SECUNDERABAD BOWENPALLY POST SECUNDERABAD 500011
MAINT / REPAIRS TO HT VCB / HT ISOLATION TRANSFORMERS AT AIR FORCE STATION BIDAR
2022_MES_550676_1
85575/E8
Open Tender
Civil Works - Others
Item Rate
180 days
GE AF BIDAR
AS PER NIT
9 documents required · 9 mandatory
₹500
GE AF BIDAR
₹30,000
Yes
18 Oct 2022
8 Sept 2022
15 Oct 2022
8 Sept 2022
13 Oct 2022
29 Sept 2022
8 Sept 2022 - 23 Sept 2022
Amount
Disconnection and removing HT cable connections connected to the HT VCB and carried out complete Overhauling servicing of 11 KV, 3 phase 50 Hz VCB upto 630 Amps capacity (drawnout / fixed type) complete including finding out the defective parts such as fixed male & female contacts, under voltage relays, power pack unit, spring charge motor, operating mechanism, gear box, CT & PT units, VCBs Bottles, Triping / closing coil, HT Fuses, 11 KV LBS fix & moving arm and charging unit complete including reconnecting the cables testing and commsissioning of the following Makes as existing at site complete all as specified and as directed. Makes : - MEGHAWIN / AREVA / SIEMENS / ABB / Schenider Note :- (1) Spring charge motor, Triping/ closing coil, HT Fuses & moving arm and cast resin bushes measured spearately under respective item of the schedule. (2) Miscelleneous items required for satisfaction of job deemed to be inclusive in the unit rate.
Supply only single phase over current or earth fault relay 24/110 V suitable for existing breakers complete all as specified and as directed. Make :- L&T or equivalent approved make.
Supply and fixing multi function digital panel meter having the parameters the HT voltage,current, frequency, power factor , KVA, KVAR etc suitable for suitable for operating voltage 24/110/230 volts including taking out old one complete all as specified and as directed. Make :- L&T / CADLE / Socomech
Supply only Tripping coil DC 24/110 volts suitable for existing breakers complete all as specified and as directed.
Supply only Closing coil DC 24/110 volts suitable for existing breakers complete all as specified and as directed.
Supply only Spring charge motor 1.5 KW single phase for functional of HT VCB suitable for existing makes complete all as specified and as directed.
Supply only auxillary relay VAA model Model No.VAA33ZG8344BCH ALSTOM suitable for existing breakers complete all as specified and as directed. Make :- L&T or equivalent approved make.
Supply only single phase under voltage or over voltage relay 20/110 V or 82/264V suitable for existing breakers complete all as specified and as directed. Make :- L&T or equivalent approved make.
Supply only female contact made out of copper with silver coating type suitable for existing make HT 11 KV breakers complete all as specified and as directed.
Supply only cast resin bush unit of suitable for existing HT 11 KV breakers along with copper studd duly coated with sliver plate for fixing of 11 KV bus bars along with suitable nut bolts and watchers.complete all as specified and as directed.
Supply and fixing of Gear box of 11 KV HT VCB panel including taking out old one complete all as specified and as directed. Make :- Magawin or equivalent approved make.
Supply only HT barrel fuse 2 Amps suitable for 11 KV potential transformer of existing makes complete all as specified and as directed.
Supply only HT barrel fuse 32 Amps Din type suitable for existing HT 11 KV breakers complete all as specified and as directed.
Supply only HT barrel fuse 32 Amps BS type suitable for existing HT 11 KV breakers complete all as specified and as directed.
Supply only plastic sleeve suitable for moving arm unit (male & female) type suitable for existing HT 11 KV breakers complete all as specified and as directed.
Supply only trip circuit supervision relay VAX30-34V model No.VAX31ZG8043FCH Make- Alstom including taking out old one complete all as specified and as directed.
M&L for servicing of HT breakers mechanical parts including greasing of moving parts and checking of spring charging motor for its proper functioning and testing and resetting the same complete all as specified and as directed
Supply and fixing power pack unit of capacity 230 / 24 Volts 3 phase and making necessary connection to PTs complete including taking out old one complete all as specified and as directed. Make :- Power pack or equivalent approved make
Disconnecting & Removing the unserviceable GOD horizontal / vertical of capacity 400 A, 11 KV from the Two pole / four pole / six pole structure carefully and supply and fix gang operated air-break switch 400 Amps, 11 KV, triple pole, mounted on post insulator along with 25 mm light grade GI tubing operating from operating mechanism from ground level complete all as specified and as directed. Note :- Cost of Jumper connections along with fixing material deemed to inclusive in the unit quoted rate.
Description all as per Ser Item No.20 above but of capacity 200 Amps complete all as specified and as directed
Disconnection and Removing the unserviceable / burnt out Isolation Transformer Three Phase 440 V / 440 V copper winding and rewinding the same with fine enamelled bare copper conductor of same gauge size,turns, and weight and keeping the core and windings into the hot air oven till the moisture evoporates complete all as specified and as directed for the following capacities :- Note :- Rates Quoted deemed to be inclusive of all Misc items such as Cotton tape, Varnishing,impregnated paper etc..
(a) Isolation Transformer LT of capacity 50 KVA (oil cooled)
(b) Isolation Transformer LT of capacity 125 KVA (oil cooled)
(b) Isolation Transformer LT of capacity 250 KVA (oil cooled)
(c) Isolation Transformer LT of capacity 400 KVA (oil cooled)
Disconnection and Removing the unserviceable / burnt out primary and secondary copper windings and rewinding the same with fine enamelled bare copper conductor of same gauge size,turns, and weight and keeping the same into the hot air oven till the moisture evoporates complete all as specified and as directed for the following capacities :- Note :- Rates Quoted deemed to be inclusive of all Misc items such as Cotton tape, Varnishing,impregnated paper etc..
(a) Transformer 11/0.433 KV , 50/63 KVA
(b) Transformer 11/0.433 KV , 100 KVA
(c) Transformer 11/0.433 KV , 160 KVA,
(d) Transformer 11/0.433 KV , 200 KVA
(e) Transformer 11/0.433 KV , 250 KVA
Disconnection and Removing the unserviceable / burnt out Secondary LT Bushing units complete and replace the same with same size and capacity of bushing with brass Studs along with suitable nut bolt and washers complete all as specified and as directed for the following Transformers :-
(a) Transformer 11/0.433 KV , 50/63 KVA
(b) Transformer 11/0.433 KV , 100 KVA
(c) Transformer 11/0.433 KV , 160 KVA,
(d) Transformer 11/0.433 KV , 200 KVA
(e) Transformer 11/0.433 KV , 250 KVA
(f) Transformer 11/0.433 KV , 315 KVA
(g) Transformer 11/0.433 KV , 1000 KVA
Disconnection and Removing the unserviceable/ burnt out Primary 11 KV HT Bushing units complete and replace the same with same size and capacity of bushing with brass Studs along with suitable nut bolt and washers complete all as specified and as directed for the following Transformers :-
(a) Transformer 11/0.433 KV , 50/63 KVA
(b) Transformer 11/0.433 KV , 100 KVA
(c) Transformer 11/0.433 KV , 160 KVA
(d) Transformer 11/0.433 KV , 200 KVA
(e) Transformer 11/0.433 KV , 250 KVA
(f) Transformer 11/0.433 KV , 315 KVA
(g) Transformer 11/0.433 KV , 1000 KVA
M & L for Silica Gel of Transformer including removing the unserviceable Silica gel complete all as specified and as directed
Cleaning of yards Such as Transformers / Four pole / Three pole / Two pole structure complete and M&L for spreading of Crushed metal stone aggregate 30 mm to 40 mm grade required thickness at site complete all as specified and as directed
M&L for preparation of old painted surface of 11kV / 433 Volts outdoor type transformer,painting with spray gun through out externally with two coats of synthetic enamel paint of approved colour and writing number in white colouron black ground of transformer of capacity 50 to 315 KVA complete all as specified and as directed
Disconnecting and removing the unserviceable 11 KV Disc type insulator from HT poles and S&F Disc type insulator, porcelain, vitreous 145mm hight and 255mm dia ball and socket type, white, brown or green single disc assembly of 11000 Volts ISI Marked along with fixing material such as GI bolt, nut and washers etc. complete all as specified and as directed.
Disconnecting and removing the unserviceable 11 KV Pin type insulator from HT poles and S & F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 11000 Volts ISI Marked along with fixing material such as GI bolt, nut and washers etc. complete all as specified and as directed.
Disconnecting and removing the unserviceable 11 KV Lightening arrester carefully from the 2/4/6 Pole structure and Supply & fix lightining arrester suitable for 11000 Volts of peak discharge capacity 30 Kilo Amp, 3 Phase including connecting of the same to the supply with necessary fixing materials such as nut bolt, washers etc. complete all as specified and as directed
Disconnection and removing the unserviceable 11 KV Expulsion fuse single pole carefully from the 2 / 4 / 6 Pole structure and Supply & fixing Expulsion fuse / drop out fuse single pole along with post insulators suitable for 11000 Volts, 50 A capacity including connecting of the same to the supply with necessary fixing materials such as Aluminium jumpers, Aluminium binding wire etc complete all as specified and as directed
M&L for stringing and fixing in position of ACSR conductor in OH line connections as per site requirement including provision of aluminium binding wire complete all as specified and as directed
Restringing of HT 3 lines of existing over head line of ACSR conductor after disconnecting from the insulators & jumpers to the required tension & sag & binding up & connecting to insulators & jumpers properly test complete, chopping off trees branches (coming in the way/line) complete all as specified and as directed . Note :- (a) Trimming of tree branches up to 1.5 RM from the conductor deemed to be inclusive in the unit rate (b) single conductor shall be considered for measurement
Dismantling ACSR conductor of any size and any position complete all as specified and as directed
Supply and fixing LED indicating lamp red,blue,amber,green,white of operating voltage 24/110/230 volts including taking down old indicators complete all as specified and as directed
Supply and filling for toping up of transformer oil as per IS of approved make complete all as specified and as directed
S&F PVC sleeves of 15 mm dia in RYB colour for protection of Jumper on HT / LT poles /structure complete all as specified and as directed
De-hydration and fillteration of transformer oil, HT OCB and LT OCB of any capcity and type installed at various locations without disturbing from its position to achieve of electric strength not less than 40KV complete all as specified and as directed
S& F Silica gel container (breather unit complete) suitable for existing transformers complete all as specified and as directed
MAYUR ELECTRIC SERVICES
E M CONSTROL SYSTEM
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .