Tender Value
₹87.4 L
EMD Value
₹1.6 L
Closing Date
2 May 2024, 6:00 pmClosed
CWE (AF) Jamnagar
CWE (AF) Jamnagar AT AF STN No1 Jamnaagr
SPECIAL REPAIRS TO INFRASTRUCTURE OF ARTICLE A TP AF STN JAMNAGAR
2024_MES_649207_1
81191/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Jamnagar
as per NIT
7 documents required · 7 mandatory
₹1,000
GE (AF) No-1 Jamnagar
₹1.6 L
Yes
25 Jun 2024
4 Apr 2024
4 May 2024
4 Apr 2024
2 May 2024
18 Apr 2024
6 Apr 2024 - 12 Apr 2024
Amount
Supply and fix in repair IP based fence energizer comprises with following features Fence Voltage Alarm (Inbuilt in Energizer): The unit is designed to sense any type of tampering / intrusion over the fence or system and activate the audio alarm within 1.2 seconds. The unit is also having a 12V output terminal for triggering additional gadgets like CCTV, Floodlights, Computer peripherals etc complies with BIS 302-1-76 & IEC 60335-2-76 standards for safety and complete all as specifed and as directed. a. Input voltage : 12 V DC b. Power consumption : <17 VA c. Output voltage : > 7 KV d. Pulse interval : 1.2 second e. Output energy : 2.5 Joules f. Front Panel display : Fence ON and Pulse indication CE marking in compliance with International safety standards vide No. IEC 60335-2-76, IS 8437 (Part - I - Human safety) and EMC directives. G. Can trigger an external device upon tampering. H. Fence Energizer can be used as a standalone system or can be interfaced to a Central Monitoring station through TCP / IP using additional controllers. I. Suitable for High security applications. J. Front Panel display consists of LEDs and LCD Make -: crown solar power fence energizer model- CS-250 or techno commercial equivalent model of make Omega solar FieldGard .
Supply, Installation, testing and commissioning of Hard Disc - 6 TB HDD, for Surveillance complete all as specifed and as directed. Make: WD Purple/Seagate Surveillance/ Sony
Supply and fixing connecting and testing of CAT6 6 pair LAN cable with solid annealed bare electrolytic grade copper conductor and overall FR PVC jacketing shielded twisted pair (STP) in existing channel / conduit, etc. as required, complete all as specifed and as directed. Make: D-link / Digisol/ Havells
Supply and fixing connecting and testing optical fibre cable 12 core cat 6, Cable Type Armoured Loose Tube Jelly Filled (Multi-Tube), rodent resistant. Fiber Type Single Mode, 9 / 125, 250 micron primary coated buffers, Fiber Core As per Telecordia GR20, ITU-T G652D, IEC- 60793-2-50, TIA/EIA, 492-CAAB, No of Cores 12, Armouring Corrugated Steel Tape Armor, Cable Construction Type, BELLCORE GR 20 / IEC 794-1 - Loose tube Corrugated steel tape, (0.155mm Min)CSTA provided with FRP Rod as strength members, Outer Jacket Construction High density polyethylene, anti - termite, anti - rodent suitable, for direct burial application, @1310nm < = 0.35 dB/Km, @1500nm < = 0.20 dB/Km, Maximum Tensile Load >= 2670 N complete all as specifed and as directed. Make: D-link /Finolex/Legrand
Supply, fixing, testing and commissioning One loop panel with loop cards, 640 character with in / out media converter microprocessor based analogue addressable type (UL/EN approved) net workable fire control panel with zonal indications,zener barriers, signal booster for network connectivity modules with optic fibre cable, patch cords and fibre optic media converters for both sides of the panels along with automatic speech dialer facility and where ever is required and with battery power pack as per specifications and complete all as specifed and as directed. Make -SIEMENS Model -:FCM2019-U3 or techno commercial equivalent model of make RAVEL/HONEY WELL
Supply, installation, testing and commissioning of intelligent addressable network control active repeater panel with network card communication module on FACP network configuration to monitor and control all local fire alarm control panels located in individual buildings built in buzzer and RS485 port on CPU board with optional network software connectivity, Media converters with patch cords, fire/fault indicators, audio visual signals, battery, battery charger, central processing unit 80 character display unit complete in all respects
Supply installation Testing and Commissioning of Video Management Software VMS should have smart motion Search for server side motion detection and quick retrieval of events:- *Edge Storage Auto Gap Fill functionality detects when a gap in local camera recording occurs, and automatically downloads video and audio (if present) to fill the gap *web based client allows viewing and exporting video without installing any software *Imports users and roles from existing LDAP servers to reduce administrative overhead, and enables single sign-on (SSO) *Capable of listening for ASCII commands on a serial and Ethernet port simultaneously *Supports shared displays so operators can send video to surveillance personnel who need it most *Check on VMS and camera health using SNMP *Supports IPv4 and IPv6 cameras *Enables and supports Risk Management Framework (RMF) *TLS-based encryption over HTTPS *Extensible through mapping and plugins, including video information overlays and license plate recognition *should include feature, which is capable of polling for alarms from devices and performing specified actions when an alarm state change occurs *Incorporates FIPS 140-2 validated cryptographic modules. To ensure seamless deep integration VMS should be of same camera OEM.
Supply installation Testing and Commissioning of Graphic software to monitor & control the status of the FACP from the windows based system-with visual & sound alert for the fire and fault conditions-with three level multi users access complete all as specifed and as directed.
Supply installation Testing and Commissioning of configuration software -GUI based-Location programming for each device- Monitor & control the status of the FACP's from the PC complete all as specifed and as directed.
Supply installation Testing and Commissioning of Building application to the Software (including points connected various communication protocols) including controller setup, configure software-HMI computers and application functions Command, Control Display, operation and reporting rate also includes communications hardware and software to connect a multimeter PM1200 alarms including communication protocol, driver and suitable communication adapter to operate the system. Desigo CC software upgradation (TREND) for data retriever.
Note for item No 13.01 to 13.02 and 14 :Items listed below include delivery and installation testing of controllers DDC Web Server Made, Smartstruxure up to 32 expansion cards with a capacity of 464 inputs / outputs Rhvambna panels are suitable include transformers, fuses, clips and aiding materials needed include protections against over-voltages, the installation includes connection, wiring , testing, writing software in the controls as indicated in the specification. supply and installation of control which will be the same in size with the option to exchange when the distribution points including the I / O controller of different types within the designer will be approved as specified in the specification. Total amount of material required will also deemed to include rates of Supply and installation of all communication adapters required for proper operation of the control center even if not specified in the technical specifications.
Supply installation Testing and Commissioing of Controller (Automation Server: AS-L) Smartstruxure Bacnet / IP DDC up to 464 inputs \ outputs with capacity for expansion cards up to 32 expansion cards - the controller is Web Server total 4GB memory HMI software includes built-in software on the same controller viewing position, the controller includes an internal hot backup and will owner Address IPv6, the controller will include applications in sending emails to alert defined in the controller and viewing position and has the ability to hot swap HOTSWAP without disconnecting the input voltage of the controller will know convert graphs and data to Excel without having to independently position View to independently position View including communications hardware and software to connect the control system of HVAC includes a LON communication protocol TCP \ IP or BACNET driver and appropriate communications adapter to operate the system as indicated in the specification
Supply installation Testing and Commissioing of communications coordinator for the DDC controller for 250 units MODBUS media as indicated in the technical specifications Bill of Quantities This includes all connections required hardware and software you have connected to the system will work perfectly and applicative
Supply installation Testing and Commissioing of configuration software -GUI based-Location programming for each device- Monitor & control the status of the Power fencing from the PC
Dismantling of existing compete set of electric motor with blower unit of AHU/CSU with connected accessories and Supply installation Testing and Commissioing new electrical motor with blower all as specified and directed by Engg -in-charge AHU/CSU comprising following job included in rate quoted for respective item. (i) Blower and Motor both have V pully and V belt as per site requirement (ii) Blower motor should be fitted on adjustable frame as per site requirement. (iii) Contractor must be visit the AHU/CSU before placing the order and replacement motor shall be exact matching. (iv) Old Blower with motor deposited to AGE E/M Storeyard
Electric motor with blower unit of AHU unit of capacity 25 TR, 8000 CFM, Make:- Zeco Aircon Ltd, Manufacturer Sr No- 1724602-1,2,3,4 or equivalent make as per manufacturer recommendation.
Electric motor with blower unit of AHU unit of capacity 15 TR, 5000 CFM, Make:- Zeco Aircon Ltd, Manufacturer Sr No- 1724601-1,2 or equivalent make as per manufacturer recommendation.
Electric motor with blower unit of CSU unit of capacity 3 TR, 1200 CFM, Make:- Zeco Aircon Ltd, Manufacturer Sr No- 1724604-1-72 or equivalent make as per manufacturer recommendation.
Supply, installation, testing and commissioning of end suction & top discharge type centrifugal pumps back pull out type for following capacity pump, complete with cast iron body, bronze impeller complete with mechanical seals, TEFC squirrel cage high efficiency induction motor, base plate, mounting channel frame, accessories and fittings i.e. flexible connectors (bellows) at inlet & outlet connections, mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/rubber type mounting of resistoflex make as specified and matching manufacturers specification of old unit as of the following capacities. The Pumps shall be insulated with Nitrile Rubber with suitable thickness, including taking down old Pump & motor and deposited in Store yard of AGE E&M.
Filter feed Pump of 2 HP capacity, 3 Cum/Hr @ 26 M head Make : Kirloskar Brother or equivalent make recommend by OEM & approved by the GE. Make: Kirloskar Type:KDS235 S.No: A18AGF000182 Size(mm): 50 x 40 Head(m): 26 KW/HP: 1.5/2.0 Ph: 3
Hot Water Generator Pump of 2 HP capacity, 38 USGPM @ 25 M head. Make : GRUNDFOS or equivalent make recommend by OEM & approved by the GE PUMP Make: Grundfos Type: CM10-2ARAVAVBVFAAN T Liq max: 90/40 'C / 194/104 'F Model: A96943350-P1-1722/1723 P max: 6/10 bar / 87/145 PSI / 0.6/1.0 MPa T amb: 55'C/131'F MOTOR Type: MG80CFD1CML1A Model: 97903649-P1-1718 P: 1.2 KW / 1.61 HP I: 2.8-3 A
Supply, installation, testing and commissioning of Fan assembly unit suitable for 180 TR chiller of size 800 mm dia, fixed in repairs all as specified and directed by Engr-in-charge. Make :- Voltas, ZAHIL ABEGG Model No. FN080-SDQ.6N.V7P5 185477
Supply, installation, testing and commissioning of temp sensor & Humidistats to operate Scada system of Air conditioning Plant installed at CSU , fixed in repairs all as specified and directed by Engr-in-charge. Model: QFM2160, 0-10 Volt DC for 2o Miliamp Analog output Make: Siemens or equivalent to Johnson Control, Scheinder
Supply, installation, testing and commissioning of hot water generator heating coil of capacity 90 KW complete all as specifed and directed by Engineer in charge. Note:- Contractor must visit the site before placing the same order
Supply, installation, testing and commissioning of hot water generator heating coil of capacity 45 KW complete all as specifed and directed by Engineer in charge. Note:- Contractor must visit the site before placing the same order
Supply, installation, testing and commissioning of hot water generator heating coil of capacity 30 KW complete all as specifed and directed by Engineer in charge. Note:- Contractor must visit the site before placing the same order
Supply, installation, testing and Commissioing in repair of mild steel chilled water piping of class 'C' heavy duty conforming to IS : 1239 (part I) 1991 and IS : 3589 to 1991 grade 330 of size 200 mm dia thickness 8.00 mm, cut to reqd length, and installed with welded joints, including all necessary fittings such as elbows, tees, bends, reducers, flanged, supports, Air purge, valves, drain valve etc. duly insulated and as per specification 50mm thick TF quality EPS pipe section insulation of 18 Kg/ cum density and covered with 28 gauge aluminium sheet caleding and as per specification. Make : TATA/Jindal/Zenith / Surya Prakash
Supply, installation, testing and Commissioing in repair of mild steel chilled water piping of class 'C' heavy duty conforming to IS : 1239 (part I) 1991 and IS : 3589 to 1991 grade 330 of size 150 mm dia thickness 5.40mm, cut to reqd length, and installed with welded joints, including all necessary fittings such as elbows, tees, bends, reducers, flanged, supports, Air purge, valves, drain valve etc. duly insulated and as per specification 50mm thick TF quality EPS pipe section insulation of 18 Kg/ cum density and covered with 26 gauge aluminium sheet caleding and as per specification. Make : TATA/Jindal/Zenith / Surya Prakash
Supply, installation, testing and Commissioing in repair of mild steel chilled water piping of class 'C' heavy duty conforming to IS : 1239 (part I) 1991 and IS : 3589 to 1991 grade 330 of size 125 mm dia thickness 5.40mm, cut to reqd length, and installed with welded joints, including all necessary fittings such as elbows, tees, bends, reducers, flanged, supports, Air purge, valves, drain valve etc. duly insulated and as per specification 50mm thick TF quality EPS pipe section insulation of 18 Kg/ cum density and covered with 26 gauge aluminium sheet caleding and as per specification. Make : TATA/Jindal/Zenith / Surya Prakash
Supply, installation, testing and Commissioing in repair of mild steel chilled water piping of class 'C' heavy duty conforming to IS : 1239 (part I) 1991 and IS : 3589 to 1991 grade 330 of size 100 mm dia thickness 5.40mm, cut to reqd length, and installed with welded joints, including all necessary fittings such as elbows, tees, bends, reducers, flanged, supports, Air purge, valves, drain valve etc. duly insulated and as per specification 50mm thick TF quality EPS pipe section insulation of 18 Kg/ cum density and covered with 26 gauge aluminium sheet caleding and as per specification. Make : TATA/Jindal/Zenith / Surya Prakash
Supply, installation, testing and Commissioing in repair of mild steel chilled water piping of class 'C' heavy duty conforming to IS : 1239 (part I) 1991 and IS : 3589 to 1991 grade 330 of size 80 mm dia thickness 5.40mm, cut to reqd length, and installed with welded joints, including all necessary fittings such as elbows, tees, bends, reducers, flanged, supports, Air purge, valves, drain valve etc. duly insulated and as per specification 50mm thick TF quality EPS pipe section insulation of 18 Kg/ cum density and covered with 26 gauge aluminium sheet caleding and as per specification. Make : TATA/Jindal/Zenith / Surya Prakash
Supply, installation, testing and commissioning of 50 mm bore galvanised steel water tubing, medium grade including necessary fittings such as GI bends / elbow, tee, union etc complete and connecting to water supply pipe line laid in trenches complete all as specified and as directed by Engineer-in-Charge.
Supply, installation, testing and commissioning of 25 mm bore galvanised steel water tubing, medium grade including necessary fittings such as GI bends / elbow, tee, union etc complete and connecting to water supply pipe line laid in trenches complete all as specified and as directed by Engineer-in-Charge.
Supply, installation, testing and commissioning of cast iron sluice valve 50 mm dia PN 1.6 as per IS-14846,body,dome,wedge-CI IS:210,ring-brone IS:318, spindle-SS Is :6603 , gland packing greasy jute packing, fastener-Cs, Gasket-Natural rubber, nominal size as under, both ends flanged in existing line, after removal of old unserviceable sluice valve without damaging to existing pipe line complete all as specified and directed by Engr-in -Charge.
S&F in gun metal gate valves of size 25 mm bore ISI marked with iron wheel head screwed both ends for iron pipe and fixed, all as specified and directed .
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5mtr in depth for foundation. (Laying of under ground cables) in soft/loose soil and getting out all as directed.
Excavation in trenches n.exc 1.5 mtr wide and not exc 3mtr depth and getting out in soft/loose soil all as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in hard/dense soil all as directed.
Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed by Engineer –in- Charge at a level not exceeding 1.5mtr above the starting point all as directed.
Supply, installation, testing and commissioning UPS of cap 600 VA suitable for backup for SCADA system of Air conditioning Plant installed at BMS including taking down old UPS & deposit old/Unserviceable item to AGE EM Store Yard all as specified and directed by Engr-in-charge. Make : Scheinder Electric or Equivalent
Supply, installation, testing and commissioning UPS of cap 1000 VA suitable for backup for SCADA system of Air conditioning Plant installed at BMS including taking down old UPS & deposit old/Unserviceable item to AGE EM Store Yard all as specified and directed by Engr-in-charge. Make : Scheinder Electric or Equivalent
Supply & fixing in repair UPS of cap 6 KVA suitable for backup for B4A & B4B system of Air conditioning Plant installed at BMS and deposit Existing old/Unserviceable item to AGE EM Store Yard all as specified and directed by Engr-in-charge. Make : Scheinder Electric or Equivalent
Supply and replacement of UPS battery of capacity 42 Ah and deposit Existing old/Unserviceable item to AGE EM Store Yard all as specified and directed by Engr-in-charge. Make:- Amron/Exide or equivalent make of PS Clause.
Supply and replacement of UPS battery of capacity 26 Ah and deposit Existing old/Unserviceable item to AGE EM Store Yard all as specified and directed by Engr-in-charge. Make:- Amron/Exide or equivalent make of PS Clause.
Supply and replacement of UPS battery of capacity 150 Ah and deposit Existing old/Unserviceable item to AGE EM Store Yard all as specified and directed by Engr-in-charge. Make:- Amron/Exide or equivalent make of PS Clause.
M&L in replacement of MCCB, 4 pole, 415 Volts, 800 Amps, 85 KA, 50 Hz, AC fixed in existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete and deposit Existing old/Unserviceable item to AGE EM Store Yard complete all as specified and as directed.
Supply and laying in existing conduit 3C x 2.5 sq.mm, 1.1 kV grade, PVC power copper cable complete and deposit Existing old/Unserviceable item to AGE EM Store Yard all as specifed and as directed.
Supply install printer latest 2024 Model with one full set of consumables i.e. Toner and Paper complete all as specified and as directed. (i) Printing technology-Laser (ii) Type of printing-Black & white (iii) Cartridge technology-Separate Drum and Tonner (iv) Memory-512 MB (v) Paper size-A3 (vi) Network Connectivity-Yes (vii) Duplexing feature-Yes make- Canon/HP/Espon/ Ricoh
M&L testing and commissioning for single electrode chemical earthing. The chemical earthing as shown in sketch No.02 will have specification as follows :- (a) Copper electrode of wall thickness minimum 2 mm not less than 3 mtr length with not less than 75mm outer dia. filled with maintenance free chemical compound & copper strip of size 50x6mm upto 0.15 mtr above ground electrode. (b) Fixing of copper Earth Electrode by drilling / boring 250 mm dia hole,upto 05.00 mtr deep in any type of strata, placing electrode in hole, return filling excavated soil by mixing min 20 kg GEL and 100 kg Soil Resistivity Improvement (SRIP) compound as per manufacturer instruction.( Boring in additional after 05 mtr length as per site requirement shall be measured and paid separately.) (c) FRP earthing result display board 254 x 380mm made out of plastic material showing information related to type of earthing, earthing result, due date of testing along with fixing size 610mm height made of plastic solid pipe of dia 20 mm. (d) PCC earthing pit in PCC 1:2:4 type B-1 of internal size 300 mm x 300 mm x 300 mm with 120 mm thick wall and 700 mm x 700 mm x 150 mm thick bed concrete and 50 mm thick precast chamber cover of RCC 1:2:4, type B1 for, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), complete all as shown in the electrical plate No 3 of SSR part –I complete. (e) Contractor must visit the site before quoting the tender to understand the difficulty and cost for carrying out the job in the station. It is important that contactor ascertain the quantum of work. (f) Contractor must produce the certificate from the manufacturer that chemical earthing has been carried out by manufacturer. The manufacturer must also mention the warranty for chemical earthing. (g) Extension strip from electrode strip up to 0.15 m height from GL to be deemed included in quoted rate including brazing (h) The earthing result will be obtained for each electrode must be less than 1Ω. Otherwise contractor is liable to do chemical earthing to meet the result. Make :- Powertrac / PRAGATI / McML's Earthing Solution (MES) / Ashlock
Prime Decor
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .