Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹60.4 LAccepted-AOC NEAR RELIANCE PETROL PUMP RAMGARH CANTT 829122 DIST RAMGARH JHARKHAND | RAMGARH CANTT | RAMGARH | JHARKHAND | 829122 | L1 | Accepted-AOC The Awarded Value is Inclusive of GST | |
| 2 | L2₹52.7 L+₹1.5 L (2.84%)Rejected-Finance 521 UBI ROAD SINGRAULI SINGRAULI SINGRAULI MADHYA PRADESH 486889 | SINGRAULI | MADHYA PRADESH | 486889 | L2 | Rejected-Finance Rejected Since L2 Bidder |
Tender Value
₹57.5 L
EMD Value
₹72,000
Closing Date
11 Oct 2022, 10:00 amClosed
SO EnM Argada Area
GM OFFICE Argada Area
Installation of 06 Nos. VCB with reorganization of Bus Pipe system of 11 KV/3.3 KV at Main Sub Station Gidi-C under Argada Area.
2022_CCL_256889_1
SO(EnM)/AA/e-NIT/22-23/26
Open Tender
Electrical and Maintenance Works
Item Rate
45 days
Gidi C
Please refer Tender documents.
2 documents required · 2 mandatory
₹72,000
1 Jun 2023
21 Sept 2022
12 Oct 2022
22 Sept 2022
11 Oct 2022
22 Sept 2022
22 Sept 2022 - 29 Sept 2022
Amount
A:- Foundation for Installation of VCB Brick work with common burnt clay modular bricks of class designation7.5 in foundation and plinth in:Cement mortar 1:4 (1 cement : 4 coarse sand) 1.5 Mtr X 0.24 Mtr X 3 Mtr X 2 Side X 6 Nos=12.96 CUM 1.5 Mtr X 0.24 Mtr X 1.52 Mtr X 2 Side X 6 Nos=6.56 CUM
Providing and laying in position cement concrete of specified grade excludingthe cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 20 mm nominal size) 0.24Mtr X 2 Mtr X 3 Mtr X 6 Nos=8.64 CUM Structure 0.5 Mtr X 0.75 Mtr X 0.75 Mtr X 16 Nos=4.50 CUM
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1cement : 3 coarse sand), finished with a floating coat of neat cement.18 mm thick.
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m inwidth as well as 10 sqm on plan) including disposal of excavatedearth, lead upto 1.5 m, disposed earth to be levelledand neatly dressed. 2.8.1 Ordinary rock . 3 Mtr X 2 Mtr X 0.5 Mtr X 6 Nos=18 CUM 0.75 Mtr X 1 Mtr X 1 Mtr X 16 Nos=12 CUM
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. 2.52 Mtr X 1.25 Mtr X 2 Mtr X 6 Nos=37.80 CUM
Febrication and errection work of iron and steel for 2 nos gates, column, bracing housting. Placing etc.
Cost of GOAB 630Amp, 11 KV grade
Cost of Alloy aluminum pipe 48.3 mm dia inner dia 40.8mm wall thk 3.6mm
Cost of Post Insulator
Cost of Support Connector
Cost of Bi-metalic
Cost of Tee-Connector
Cost of Pipe to Pipe Conector
Cost of Palm/Pad Connector
Cost of Alumuniam Paint
Cost of Red Oxide paint
Erection and commissioning of VCB
Cost of Cable 2.5 Sq mm 3 core
Cost of Cable 2.5 Sq mm 16 core
Eretction cost sl no-7 to 19
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre belowground as strip earth electrode, including connection/ terminatingwith G.I. nut, bolt, spring, washer etc. as required. (Jointing shallbe done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.
(B) O/H Line re-organization 3.3 KV Erection of pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required.Above 10.00 metre and upto 12.00 metre
Supplying and erection of 11 KV pin insulator complete with largesteel head G.I. pin, nuts, washers etc. as required.
Supplying and erection of 11 KV disc insulator for 11 KV overhead lines with galvanised insulator fittings, ball and socket typeand complete with galvanised strain clamps, bolts, nuts, washers etc. as required.
Supply of G.I. wire
Erection of G.I. Wire No. 8 SWG including binding etc. as required
Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter andabove including binding etc. as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg permetre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg permetre) cross arm for two 11 KV over head line conductorscomplete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flatiron clamps, bolts and nuts including drilling holes for insulatorpins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required.
Supplying and erection of a set of cross bracing FRLSame workfor 11 KV over head line double pole structure having four membersfabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height ,complete with 50 mm X 6mm M.S. flat iron clamps, bolts andnuts including drilling holes for insulator pins, bolts and nuts etc(as per drawing) and painting with primer and finish paint as required.
Dismantling of pole/ street light standard/ strut embedded incement concrete foundation etc. as required.
Dismantling of over head lines comprising of copper/ aluminiumover head conductor, G.I. wire, cross arms, insulators etc. as required.
Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm(7.14 kg per metre) double pole cross arm for three wire 11KVover head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded onone side to the channel iron and with bolts and nuts on the otherside for tying the cross arms together, including drilling holes forinsulator pins/ fittings, bolts, nuts and washers etc (as per drawing)and painting with primer and finish paint as required.
Supplying and erection of bow stay set complete (galvanised)with 19/20 mm dia X 1.8 metres long stay rod, anchor plate ofsize 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle( 20 mm X 60 cm ), 7/ 4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand: 6 graded stone aggregate 40 mm nominal size ) foundationincluding excavation and refilling and also with 0.6 m long braceof size 50 mm X 50 mm X 6 mm angle iron with 50 mm dia pulleyfixed at one end of the brace as required.
Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 3.3 KV overhead lines with rated voltage 5 KV (rms) with a nominal discharge current rating of 2.8 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required
(C) Remote Control System Cost of Volt Meter
Cost of Fuse Base & Carrier
Cost of Push Button
Cost of Indicating Lamp
Cost of Amp meter
Cost of Auxiliary Contact, 4 pole, 4NO+4NC
Cost of Limit Switch
Cost of Rectifier Unit,40Amps, DC Voltage Grade-110V
Cost of Local Remote Switch
Cost of Electronic Industrial Hooter
Cost of cable 12 core X 2.5 sq mm
Painting, nut & Bolts as required.
Wiring with ferruls & Lugs
Labour Cost on item sl no-38 to 49
(D) Interlocking arragements Cost of Limit Switch
Cost of Cable 2.5sq mm x 2 core copper
Cost of Auxiliary Contact, 4 pole, 4NO+4NC
Labour Cost on item sl no-53 to 55
(E) Sky Netting Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm
Erection of pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required.Above 10.00 metre and upto 12.00 metre
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Cost of D’ iron clamp
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.
Cost of Cost of lightning conductor
Labour Cost on item sl no-63
Total impact of GST for the purpose of CTC
Sandeep and Co.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .