Superintending Engineer
O/o SE, Kozhikode Corporation, [email protected]
Electrical Work
2026_LSGD_892479_1
PP/EG7/2026-27/SE/33/171
Open Tender
Electrical Works
Item Rate
180 days
KOZHIKODE CORPORATION
Please refer Tender documents.
11 documents required · 11 mandatory
₹2,760
Yes
₹50,000
Yes
25 Nov 2026
25 Nov 2026
3 Dec 2026
25 Nov 2026
2 Dec 2026
25 Nov 2026
90 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply and Installation of Flood light | |||||
| 1.001 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. | 35 | cum | - | - |
| 1.002 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). | 13.5 | cum | - | - |
| 1.003 | OD2945/2026-2027:Steel reinforcement for RCC work including straightening, cutting, bending, tying, placing in position and binding all coponents upto plinth level | 0.5 | tonne | - | - |
| 1.004 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels | 6 | sqm | - | - |
| 1.005 | OD2948/2026-2027:Supply installation testing and commissioning of Stadium type Octagonal Pole made of Hot dipped Galvanised GI sheet made of 4 mmthick , continously tapered shaft with 1 segment or 2 segment of overlapping 400 mm with an overall length 12 Metre, Provision for fixing 8-12 Nos flood fitting on each in the existing RCC foundation. The bottom dia of the shaft shall be minimum 250 mm and top 90 mm . The shaft shall be with base plate of 375 x 375 x 25 mm and of 4 Nos M30 x 850 mm size of I bolt and with MonkeyClimbing ladder arrangement and Platform and suitable for wind speed as per IS 875 Part III 2015 - Complete 12 meter | 6 | each | - | - |
| 1.006 | OD4503/2026-2027:Supply Conveyance, installation, testing and commissioning of 400W LED floodlight luminaire output 120 lumen/W with a robust, single-piece pressure die-cast aluminium housing, finished with corrosion-resistant powder coating. The luminaire shall be equipped with toughened glass and designed to meet IP66 ingress protection and IK08 impact resistance standards. The floodlight fitting shall be supplied with a 30° beam angle, ensuring adequate and uniform illumination across the designated ground area..The Luminaire shall UV resistance non yellowing Polycarbonate/PMMA Lens to ensure desired photometry. Lens should be mechanically fixed and fixing by glue is not acceptable. The optics should be having a good Throw & Spread to achieve a better overall Uniformity. The LED used shall be high power with >1W to <5W. The luminaire should have CRI > 70, and CCT of 5700K and shall be compliant with IP66 and IK08 classification. Luminaire shall be designed to emit at least 48000 nominal lumens with system efficacy of at least 120 lumen/watt. Operating Temperature Range is -10degC to 50degC. The luminaire shall be designed to ensure lumen depreciation L70 over 50000 burning hours as per LM 80 report.The luminaire should have fins on the back to ensure good heat dissipation and to prevent dirt from settling on the luminaire along with aiming angle scale. Driver should be fully potted BIS certified and shall have a power factor >0.95 and THD <10% with a minimum inbuilt surge protection of internal 4kV & external 10kV and suitable for an operating voltage range of 140 to 280V AC . (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) | 48 | each | - | - |
| 1.007 | 90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43) | 6 | each | - | - |
| 1.008 | 90.11.1.20:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) | 1 | each | - | - |
| 1.009 | 90.12.5.42:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 25 sq mm | 25 | metre | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.05 MB
PRELIMINARYAGREEMENTCOMMON.pdf
Tender Documents • 0.14 MB
BOQ_1528009.xls
BOQ • 0.35 MB
viewsbd171.pdf
Tender Documents • 1.84 MB
FIP.pdf
Tender Documents • 0.01 MB
Affidavit.pdf
Tender Documents • 0.31 MB
ePay.pdf
Tender Documents • 0.01 MB
FOT.pdf
Tender Documents • 0.01 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .