Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.3 LAccepted-AOC G 16 JAY COMPLEX BELOW UMA CO OP BANK NIZAMPURA VADODARA GUJARAT 390002 | VADODARA | VADODARA | GUJARAT | 390002 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹22.9 L+₹8,050 (0.35%)Rejected-Finance | L2 | Rejected-Finance Other then lowest bidder | |
| 3 | L3₹25.1 L+₹2.3 L (10.1%)Rejected-Finance 274 210 DAFNALA ROAD SHAHIBAUG AHMEDABAD GUJARAT 380009 | AHMADABAD | GUJARAT | 380009 | L3 | Rejected-Finance Other then lowest bidder | |
| 4 | L4₹26.0 L+₹3.2 L (14.0%)Rejected-Finance NEAR DOON INSTITUTE BHALLA FARM SHYAMPUR RISHIKESH DEHRADUN UK 249 204 | DEHRADUN | DEHRADUN | UTTARAKHAND | 249204 | L4 | Rejected-Finance Other then lowest bidder |
Tender Value
₹24.3 L
EMD Value
₹48,500
Closing Date
17 Apr 2023, 6:00 pmClosed
CWE (AF) CHILODA
HQ CWE (AF) Chiloda Military Engineer Services P.O CRPF Campus Vayu Shakti Nagar Gandhinagar 382042
SPECIAL REPAIR TO HT UG DISTRIBUTION SYSTEMS AND INDOOR OUTDOOR BREAKERS AT AF STN BARODA
2023_MES_584961_1
82143/BRD/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BARODA
As per tender document
7 documents required · 7 mandatory
₹500
Yes
GE (AF) BARODA
₹48,500
Yes
15 May 2023
9 Mar 2023
24 Apr 2023
9 Mar 2023
17 Apr 2023
6 Apr 2023
10 Mar 2023 - 22 Mar 2023
Amount
Surface excavation not exceeding 30cm deep and averaging 15 cm deep and getting out in soft/loose soil complete all as specified and directed
Excavation in trenches not exceeding 1.5m width and not exceeding 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed
Returning, filling in trenches, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil complete all as directed.
M&L Dry sand cushioning to underground cable with screened, washed river sand, including punning gently all as specified and directed. Note: - Thickness after punning will be measured for payment.
Removal of excavated material at a distance not exc 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point in soft / loose soil complete all as directed.
Supply and spreading of aggregate of size 63 to 40 mm graded stone aggregate on surface with 10 cm depth inside pole mounted Sub Station yard complete all as specified and directed by Engr in Charge.
M & L PCC (1:4:8) type D-2 (using 40 mm graded stone aggregate) for foundation of the pole complete all as specified and directed.
M & L PCC (1:3:6) type C-2 (using 40 mm graded stone aggregate) for filling mass concrete arround the pole complete all as specified and directed.
M & L PCC (1:3:6) type C-1 (using 20 mm graded stone aggregate) for coping of the pole including necessary form work complete all as specified and directed.
S&F Cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts & bolts , washers , welding bending cold or hot , drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide primer complete as in repairs all as specified and directed by Engineer-in-Charge.
M&L Stay assembly for HT poles comprising of 20mm dia, 2.15 mtr long galvanized stay rod , having 7 / 3.15mm GI stay wire stranded and 300mm X 500mm X 6mm thick MS stay plate, complete all as shown on electrical plate No 1 of SSR, Part-I with and including all necessary fittings/accessories like loop type insulator, shackle & stay clamps, necessary excavation and earth work in any type of soil and PCC works in (1:3:6) type C-2 (using 40mm graded stone aggregate) complete all as specified and directed by Engineer-in-Charge including taking out and dismantling old unserviceable stay assembly.
S&F Danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figures and conventional skull and bones in signal RED colur and fixed with MS clamps bolts and nuts of approved size for HT 25x20 cm size complete as in repairs all as specified
Supply , jointing and testing cable jointing kit for 11 KV(Earthed) grade cable for indoor termination heat shrink type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured at cable of size 50 sqmm to 95sqmm as in repairs all as specified
Supply , jointing and testing cable jointing kit of 11 KV grade cable for outdoor termination, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 Sq mm, as in repairs all as specified.
Supplying & Laying un-reinforced pre cast flat concrete cable protection cover of class HV, type I, size 300mm x 180mm x 40mm, factory made, complete as in repairs all as specified
Supply ,laying, jointing and testing 11 KV (Earthed), aluminum conductor, screened, XLPE insulated, armoured shielded and PVC sheathed cables conforming to IS 7098 (Part-II) amended upto date having cross sectional area 95 Sqmm 3 core as in repairs all as specified
Maintenance/ complete testing, overhauling and calibrating of unserviceable HT VCB 11 KV 630 Amps, 50Hz of Make Areva, disconnecting and opening the complete Busbar assembly and replacement of all unserviceable busbar insulators and providing anti track spray on the inner surface of busbar chamber busbar ends and on busbar insulators maintenance of HT VCB trolley includes operating mechanism tripping system, vacuum interrupter cleaning all part thoroughly and lubrication all moving part, checking of the insulation resistance value of all 11 KV CT and PT and replacement of the unserviceable CT & PT checking of CT for proper functioning checking of protection device calibrating the same as per requirement and re setting if required reassemble complete VCB after obtaining and colour with synthetic enamel paint over a red oxide primer after preparation of old painted surface complete all as directed. Scope for Maintenance of VCB (i) Checking the closing & operation of VCB and functional checks and repair replacement of the defective components (ii) Overhauling and calibration of relays (secondary injection/Primary injection on each multiple setting of relays) (iii) Setting and coordination of relays (iv) Checking and recording of IR value of VCB trolley and panel (v) Checking/ repairing / rectification of the control wiring (vi) Replacement of panel heater 80 watt (vii) Replacement of worn out bushing PT/ Busbar support insulators (viii) Replacement of unserviceable and open circuit CT’s (ix) Checking fiber plates, gaskets applying multi grease to the mechanical parts& dry graphite conductive sealant to contracts of PT etc & re assembling the same and commissioning complete to entire satisfaction of Engr in Charge
Note : (i) All spares such as busbar insulator, CT, PT, Tripping coil/ closing coil space heater, power pack, protection relay etc required for replacement shall be measured and paid separately under respective item of schedule here in after as supply only. (ii) Machine grease oil liquid sealant and any minor item costing upto Rs 750 will be included in the unit rate of above item and for satisfactory function of the breakers and no extra cost will be allowed. Decision of accepting officer in this regard will remain final & binding. (iii) The overhauling of HT breakers to be carried out either through OEMs service Engineer/ authorized dealer/ San & Engg consultant/ Triotech consultant / those who possess HT handling licensee (iv) Anti track high gloss spray shall be measured and paid separately
Maintenance, complete testing , overhauling and calibrating of unserviceable HT VCB 11 KV 630 Amps, 50 Hz, Make -CG , disconnecting and opening the complete Bus bar assembly, and replacement of all unserviceable busbar insulators and providing anti track spray on the inner surface of busbar chamber bus bar ends and on busbar insulators, maintenance of HT VCB trolley includes operating mechanism, tripping system, vacuum interrupter cleaning all part thoroughly and lubrication all moving part, checking of the insulation resistance value of all 11 KV CT and PT and replacement of the unserviceable CT & PT, checking of CT for proper functioning checking of protection device calibrating the same as per requirement and re-setting if required, reassemble complete VCB after obtaining and replacement of the U/S part including painting with two coat spray paint of approved paint colour with synthetic enamel paint over a red oxide primer after preparation of old painted surface complete all as directed. Scope for Maintenance of VCB: (i) Checking the closing & opening operation of VCB and functional checks and Repair/ Replacement of the defective components. (ii) Overhauling and Calibration of relays (secondary injection/Primary injection on each multiple setting of relays). (iii) Setting and coordination of relays. (iv) Checking and recording of IR value of VCB trolley and panel. (v) Checking/repairing/rectification of the control wiring. (vi) Replacement of panel heater 80 watt. (vii) Replacement of worn out bushing PT/ Busbar support insulators (viii) Replacement of unserviceable and Open circuit CT's. (ix) Checking fiber plates, gaskets applying multi grease to the mechanical parts & dry graphite conductive sealant to contacts of PT etc. & re-assembling the same and commissioning complete to entire satisfaction of Engr-in-Charge.
Note:- (i) All spares such as busbar insulator, CT, PT, Tripping coil/closing coil, space heater, Power pack, protection relay etch required for replacement shall be measured and paid separately under respective item of schedule here in after as supply only. (ii) Machine grease, oil, liquid sealant and any minor item costing upto Rs 750 will be included in the unit rate of above item and for satisfactory function of the breakers and no extra cost will be allowed. Decision of accepting officer in this regard will remain final & binding. (iii) The overhauling of HT breakers to be carried out either through OEM's service Engineer/authorised dealer/San & Engg consultant /Triotech consultant/ those who possess HT handling licensee. (iv) Anti track High gloss spray shall be measured and paid separately
Suppy only Spare parts of 11 KV VCB,630 Amps capacity of Make: Areva , conforming to the respective cat part given as under :- (Note :(i) Fixing & testing element of following item is deemed to be included under Sch `A’ item No 18 & 19 above. (ii) Quantity of under mentioned items is tentative and contractor shall have no claim on account of variation of quantity or non execution of any of the item.
(a) Spout insulator (Epoxy)
(b) Current Trasformer 11 KV Single Phase indoor resin cast CT ratio 60/30/5-5 Amps Class 1.0 insulation level 28 KV/75 KV as per IS 2075
(c) Busbar Spout
(d) Strip type Heater 80 Watt
(e) Closing coil 30 V
(f) Tripping coil 30 V
(g) Spring charging motor 1Ph 110V/ 230V AC complete
(h) Angle Boots for XLPE cable of size 95 Sqmm 11KV
(j) Straight Boots for XLPE cable of size 95 Sqmm 11KV
HT bushing with spindle
Termostat 0-100 Degree Celcius
Moving Contact rod
Upper fix contact
Lower fix contact
Top and bottom male contact
Female contact
11 KV Busbar support insulator for VCB
Partition fibre plate
Copperstrip 800Amps
Gear wheel mechanism
Supply only of MC61 Anx Nemerical Microprocessor based over current and earth fault relay including 2Nos+2NC contractor including taking out existing relay complete all as specified and directed Make : L&T- MC61AN200
Retrofitting & Testing charges for MC61 Anx Relay with fixing plate and hardware
Potential Transformer 11 KV/110V Three phase rasin cast PT complete
M &L Anti track spray for VCB, minimum 4 coat at the interval of 15 min, High gloss, high dielectric strength , Electric Strength upto 50kV/1mm layer of paint, Thermal Stability upto 200 Deg. Celsius, Tracking Index < 400, Permittivity at 50 Hz - 56.5., flexible tough epoxy anti- track coating with excellent resistance to abrasion, wear, oil, water acids & alkalis, Restores “IR” values & prevents breakdowns, di-electric coating designed to prevent tracking, arcing and flash overs caused by dust and moisture specifically on bus bar end-bushings, inside busbar chamber surface and insulators. Weather proof & non-ageing Applications: Ultra high hydrophobicity & UV, weathering durability complete all as specified
S&F Testing power pack, rating 110 V/230 V, AC input, 30 volts DC output for auxiliary supply including necessary control wiring in existing panel complete all as specified by Engr- in- Charge. Make: CG/ALAN/EQUIVALENT
M&L Horizondal boring under road/ drain by manual method for and inserting the light grade pipe 100mm dia for cable protection
M&L 100mm GI tubing light grade with all fitting laid carefully under road or drain/ trenches complete all as specified
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP – 55), 11 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole with and including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole finished with two caots of aluminium paint over one coat of red oxide primer complete including dismantling of unserviceable RCC/ steel poles /struts, any size all as specified Note :- Earth work, PCC in foundation and coping, cross arms, danger notice board and anti climbing device shall be measured and paid separately
M & L Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of the plate not less than 1.5 Mtrs below normal ground level, connecting to the Galvanised iron earth lead 32 x 6 mm size by means of bolts, nuts check nuts and washers of galvanised iron and 32 x 6 mm dearth lead protection by provision of GI medium grade pipe 40 mm bore including provision of concrete pit in PCC (1:2:4) type B1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4gs/Sqm) and frame of angle iron 25mm x 25mm x 6mm with lugs 02 Nos and with 6 mm dia MS bar handle made to shape, GI medium grade 20mm bore pipe for watering perforated at the bottom 1.75 meter long placed on top edge of earth plate common salt and charcoal filling test point made out of 40mm x 8 mm FI with fixing arrangements, funnel, wire mesh and earth work in hard dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 Mtrs all as per electrical Plate No.3 of SSR Part I and connecting to earth test point all as specified or indicated including testing on completion Note: (i) Item includes the cost of 7.5 metre length GI pipe for protection of earth lead and earth lead . Any variation in length shall be adjusted through deviation order (ii) Earth resistance of earth pit should be less than 0.5 Ohms. On testing after completion if the desired earth resistance in not obtained the earthing will be redone at no extra cost
Dismantling and taking down existing unserviceable GOD switch and Supply, fixing, commissioning and testing of outdoor, gang operated switch, single throw single break off load type, of current rating upto 200 Amps, nine pole, each pole consisting of galvanized steel base, HT insulators as per IS, nonferrous knife and spring, loaded contacts, arcing horns of adequate section to break magnetizing current of the transformers, horizontal GI pipe of adequate length for phase separation, adequate length of GI pipes for operation from ground level and operating handle with locking arrangement complete in both OFF & ON positions. All ferrous parts hot dipped galvanized and nonferrous heavily tinned to withstand weather and suitable for vertical mounting with fuse unit carrier of 200 Amps rating and fuse element upto 50 Amps along with rod for expulsion fuses and 3 Nos post insulators for fuses complete all as specified and as directed by Engr-in-Charge. Make :- Jaipuria Brothers/ HEI/ ECE
Shiv Kripa Tradimg
ALBA AC AND REF SERVICES
BK CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .