Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹11.7 LAccepted-AOC | L-1 | Accepted-AOC L1 | |
| 2 | L-2₹13.1 L+₹1.5 L (12.5%)Rejected-AOC 146 CP COLONY 7 NO CHOURAHA KALPANA NAGAR MORAR GWALIOR 474006 | GWALIOR | MADHYA PRADESH | 474006 | L-2 | Rejected-AOC L2 | |
| 3 | L-3₹13.2 L+₹1.5 L (13.1%)Rejected-AOC 2 65 GORWA UDAYPARK SOCIETY REFINERY ROAD VILLAGE TOWN VADODARA CITY VADODARA VADODARA GUJARAT 390016 INDIA | VADODARA | GUJARAT | 390016 | L-3 | Rejected-AOC L3 | |
| 4 | L-4₹13.9 L+₹2.3 L (19.4%)Rejected-AOC 63 SECTOR 4 R FARIDABAD HARYANA 121004 | FARIDABAD | FARIDABAD | HARYANA | 121004 | L-4 | Rejected-AOC L4 | |
| 5 | L-5₹16.1 L+₹4.4 L (38.1%)Rejected-AOC | L-5 | Rejected-AOC L5 |
Tender Value
₹15.8 L
EMD Value
₹31,559
Closing Date
1 Aug 2022, 6:00 pmClosed
Asstt.General Managar (Engg-Elect)
Engg.Offices, C.A.Porbandar. 360577
SITC of Flag High Mast System including Pole Lighting System at Civil Enclave, Jamnagar
2022_AAI_121966_1
AAI/JAM/AGM(E-E)/e-NIT-1/22-23
Open Tender
Electrical Works
Item Rate
60 days
Jamnagar Airport
Please refer Tender documents.
18 documents required · 18 mandatory
₹1,180
GM AAI
₹31,559
29 Nov 2023
14 Jul 2022
3 Aug 2022
15 Jul 2022
1 Aug 2022
15 Jul 2022
15 Jul 2022 - 20 Jul 2022
Amount
Design, supply, Installation, Erection, Testing and commissioning of 25.765 Mtrs High Flag Mast Shaft in three telescopic sections (with base plate welded to the bottom sections) made of hot dip galvanized steel totally on externally and internally & suitable for wind velocity as per IS:875 (latest revision) along with special type dome including erection of flag mast, include supply and installation of twin dome LED aviation system with 3C x 4 sqmm copper conductor armoured cable & other assemblies as required with following accessories etc as per the tender specifications. a) Raising and lowering mechanism consisting of flag with double drum winch assembly, head frame assembly on top with self lubricating bearing, stainless steel wire ropes of minimum 6 mm. dia (Grade 316) etc. designed to operate with integral electric driven power tool motor of 2 hp capacity and also for manual operation. b) Providing and fixing of foundation bolts of M30 X 850 size manufactured from special steel along with nuts, washers, suitable size anchor plate and template, etc,as required. c) Design & construction of shallow foundation of suitable size with M20 grade concrete for high mast tower suitable for safe soil bearing capacity as per IS specifications and site conditions at required depth with all materials & labor and soil investigation. d) Painting of Flag mast PU painting of High Mast shaft with a coating of etch primer and PU paint(Factory Painted) e) providing and fixing of DWC HDPE pipe of size 40 mm dia (2 pieces of min. 0.75 m length) in the foundation.
Design & supply of 5 mtrs. Hight Hot Dip GI OCTAGONAL continuously tapered galvanised pole with suitable to mount maximum 2 nos. LED 320W flood light fittings at top, suitable for wind velocity as per IS 875 (but not less than 50 m/sec.), fabricated out of 3 mm thick high tensile sheet steel in single piece construction having 130mm bottom, 70 mm top, suitable for installation on a precast foundation with supply of 4 nos. of foundation bolts & anchor plate, rigid flange plate (200x200x12mm min.) welded with the base of pole for fixing on foundation bolts complete as required for structural stability as specified, weather proof and vandal resistant door flush with the exterior surface containing a terminal plate of 5 mm thick bakelite sheet with 63 Amp heavy duty connector for loop in loop out cable terminations suitable for upto two numbers 4 core 25 Sq.mm cables, including supply of 2A, 10kA, DP, C series, MCB for each fixture connections, earthing bolts for continuous earth connection complete, as required as per technical specifications. other assemblies as required with following accessories etc as per the tender specifications. a) Design & construction of shallow foundation of suitable size with M20 grade concrete foundation including excavation and refilling including positioning of template & foundation bolts (supplied with pole to match with pole base plate) & providing and fixing of DWC HDPE pipe of size 40 mm dia (2 pieces of min. 0.75 m length) in the foundation. b) Erection of pole with the help of suitable equipments and T&P.
Design, Supply, Installation, Erection, Testing & Commissioning of Indian National Flag of Size 30 ft x 20 ft in 100% knitted polyester with reinforced super strong nylon webbing on all three sides & rope / toggle sleeve complete as per relevant IS code.
Supply of 320 W ±5% energy efficient Flood Light LED luminaire with minimum system lumen output of 35000 lm, luman efficacy 110 lm/watt, PF>0.95, CRI>70, CCT - 5700K, IP 65 protected, die-cast aluminium housing with heat resistant diffuser and MS powder coated bracket suitable to operate on 240 V, 50 Hz AC complete as required suitable for focus to Flag Mast.
Supply, installation, testing and commissioning for 2 KVA (1 Ph- 1Ph) online UPS with minimum 30 mins of battery Back up suitable for operation on 230 V 50 Hz AC supply with output voltage 230 V 50 Hz etc complete as required.
Supply of following sizes of XLPE insulated PVC sheathed, Aluminium conductor armoured electric cable of 1.1 KV grade confirming to IS 7098 PART-I with upto date amended.
3.5C X 25 sq.mm
4 C X 16 sq.mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3.5C X 25 sq.mm
4 C X 16 sq.mm
SITC of 63A, 36kA, FP MCCB with adjustable thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
Erection, testing and comissioning of 5 Mtr.high G.I. OCTAGONAL flood light pole & bracket / channel with all accessories by providing and making reinforced M 20 cement concrete foundation including excavation and refilling including positioning of template & foundation bolts (supplied with pole to match with pole base plate) & providing and fixing of DWC HDPE pipe of size 40 mm dia (2 pieces of min. 0.75 m length) in the foundation for loop-in-loop-out of the cable along with earthing to the pole complete, as required as per technical specifications.
Installation, testing and commissioning of LED Flood light fitting with all accessories on existing pole of 5 mtr height with bracket / channel, including supplying and drawing of 3core 4 sq.mm. FRLSZH PVC insulated PVC sheathed flexible copper conductor cable from loop-in-loop-out box upto the individual streetlight fitting(s), connection etc. complete as required & as specified.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required.
Upto 35 sq. mm
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required
80 mm dia
Providing and fixing of advance technology earth electrode earthing system fabricated from High Tensile steel rods(Cu bonded Earth electrode Rod technology) with SS Double Sided Clamp (175mm X 50mm x 3mm) & cavity between rods pressure filled with highly conductive non-corrosive crystalline material complete with chemically modified homogeneous earth enhancing compound (Loresco powerfil carbon based back fill compound 25 Kg) to treat the soil for lowering the effective ground impedance for each earth pit to make it maintenance free and to minimize the ground voltage potential rise i/c excavation of Eco friendly rust proof heavy duty weather proof polyethylene earth pit chamber with suitable to accommodate earth electrode(254 mm Top, 330mm dia bottom & 260 mm height), prefabricated MS enclosure with cover plate all as reqd. & conforming to (IS:3043 : 1987) duly CPRI/ERDA approved all as required & as specified for Size : - Electrode rod dia = 17.2 mm Length of electrode rod = 3 Mtr
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing alongwith existing surface / recessed conduit / submail wiring / cable as required.
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required. 90 mm dia (OD-90 mm & ID-76 mm nominal)
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Manish Electricals
Techno Electricals
BR Power Control and Automation Services
om shri ganpati electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .