Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.5 LAccepted-AOC | L1 | Accepted-AOC Being lowest tenderer | |
| 2 | L2₹18.1 L+₹13,365 (0.74%)Rejected-Finance 22 JANKALYAN SOCIETY NAVJIVAN AJWA ROAD BARODA 390 019 | BARODA | VADODARA | GUJARAT | 390019 | L2 | Rejected-Finance Not being lowest tenderer | |
| 3 | L3₹21.2 L+₹3.2 L (18.1%)Rejected-Finance PREM SAROVAR HOTEL NAINITAL 263 001 UTTARAKHAND | NAINITAL | UTTARAKHAND | 263001 | L3 | Rejected-Finance Not being lowest tenderer |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
7 Oct 2023, 6:00 pmClosed
GE RANIKHET
GE (MES) RANIKHET
REPAIR MAINT OF INTERNAL EXTERNAL ELECTRIFICATION INCLUDING EXTERNAL WATER SUPPLY SYSTEM AT NAINITAL UNDER GE RANIKHET
2023_MES_617957_1
GE/RKT/48 OF 2023-24
Open Tender
Civil Works
Item Rate
270 days
Nainital under GE Ranikhet
As per NIT
6 documents required · 6 mandatory
₹500
GE RANIKHET
₹50,000
Yes
29 Dec 2023
9 Sept 2023
14 Oct 2023
9 Sept 2023
7 Oct 2023
23 Sept 2023
Amount
BOQ ( Sch A ) EM Works M & L for supply, transporting, erecting truly in vertical position and fixing of steel tubular pole swaged, over all length 9 metres, type 410 – SP – 31 complete with mild steel base plate, pole cap, finial taper plug, MS bolts, nuts & washers, necessary excavation & earthwork in hard / dense soil, PCC sub base block as mass concrete of size 600 X 600 X 150 mm in cement concrete 1:4:8 Type D-2 in base of foundation, PCC foundation block of size 600 X 600 X 1500 mm in cement concrete 1:3:6 Type C-2, pole plinth of size 600 X 600 X 300 mm in cement concrete 1:2:4 Type B-1 including necessary form work as required at site and painting of pole with two coats of anti corrosive black bituminous paint through out internally and externally upto planting depth (embedded in concrete) and remaining portion of the pole painted two coats of aluminium paint over a coat of red oxide primer on complete exposed surface including painting of 05 Nos. bands / strips of 30 cm wide each with two coats of synthetic enamel paint (black & yellow) at a distance of 30 cm from plinth block upto 1500 mm height and marking / sign writing of pole number and feeders locations of pole with thick synthetic enamel paint (white) including dismantling of existing damaged steel pole/strut etc complete all as specified and directed.
M&L for mild steel work Fe-410-S grade in cross arms, bracing, supports,clamps and back plate, fabricated from structural steel section including nuts bolts and washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and including two coats of aluminium paint over a coat of red oxide primer including dismantling cross arms of mild steel channel or angle section etc complete all as specified and directed.
Supply and fixing pin type, porelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65mm dia for 1100 volts grade complete all as specified and directed.
Supply and fixing shakle type, porelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts in repair insulators suitable for working pressure in 1100 volts of height 75 mm and max dia 90mm alongwith galvanised steel fittings section of straps in 31X3 mm and dis of bolts 12mm complete all as specified and directed.
M&L for MCCB 4 pole 415V adjustable type 160 Amps with breaking capacity 36 KA complete all as specified and directed.
M&L for MCCB 4 pole 415V adjustable type 200 Amps with breaking capacity 36 KA complete all as specified and directed.
M&L stay assembly complete comprising of 7/3.15 galvanised stranded stay wire of required length fixed to pole with and including FI clamp 50x6mm size, bolts, nuts washers, galvanized steel stay rod 16mm dia and 1800 mm long , stay bow 400 x 14 mm galvanised steel plate 230 x 230 x 6 mm two numbers , thimbles loop insulator size 90 x 140 mm clearance hole 16 mm including earth work/excavation in any type of soil, PCC 1:3:6 type C-2 in foundation of stay assembly, disposal of surplus soil to a distance of 50m including two coats of aluminium paint over a coat of red oxide primer on exposed mild steel work including dismantling existing stay assembly etc complete all as specified and shown in electric plate No 1 and directed.
M&L for stringing stretching and stengthening of over head conductor (ACSR) on existing LT steel tubular pole or RS joist LT electric pole including binding and jointing the conductor with and including 14 SWG winding wire etc complete all as specified and directed. Note:-Any breakage or damage shall occured insulator shall be replaced by the contractor at his own cost and unit rate quoted by contractor shall deemed to include the same. (a) Weasel (6/1x2.59 aluminium and 1x2.59 steel)
M&L for stringing, drawing of GI wire 4 mm dia on LT electric lines including binding, jointing and for guarding cradle made to shape hexagonal/rectangular or any shape fabricted etc complete all as specified and directed.
M&L in replacement of anti climbing device spikes type fabricated out of MS bar (round, square and flat) including nuts bolts, washers and welding in two halves made to shape to suit the cross section of the pole etc complete all as specified and directed.
M&L in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letter figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for LT 20x15 cm size etc complete all as specified and directed.
Supply and fixing or passing through pipe, stranded conductor 6 Sqmm, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4 mm suspension wire, one twin core cable flat or circular etc all as specified and directed.
All as per item No 12 above but 10 Sqmm Cable
All as per item No 12 above but 16 Sqmm Cable
Supply , laying , connecting, testing and commissioning of 120 Sqmm 3.5 core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable with stranded aluminium conductor 1100 Volts laid in trenches, fixed to walls/ drawn through pipe and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed. Note;-(Excavation and earthwork, sand cushioning and cable protection shall be measured and paid for separately.)
All as per item No 15 above but 50 Sqmm 3.5 core
All as per item No 15 above but 35 Sqmm 3.5 core
All as per item No 15 above but 16 Sqmm 2 core
M&L for Earthing complete with galvanized sheet earth plate electrodes 60x60x6.3 mm thick buried directly in ground (earth pit not less than 2. 25mtr deep below ground level) with top edge of plat not less than 1.5 mtr below normal ground level connected to galvanized iron strip 25 x 4 mm as earthing lead by means of bolts, nuts , check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 and including excavation and earth work, GI pipe light grade 15 mm bore for protection of GI wire from earth electrode to and incl the earth test point of galvanized Iron/steel of size 75x75x 25mm, supplying and laying charcoal dust, common salt, PCC 1:2:4 type B1 chamber and MS angle iron frame 40x40x3mm and RCC cover 40mm thick (1:2:4) type B1 using 20mm graded stone aggregate reinforced with 6 mm dia TMT bars @ 75mm C/C both ways with MS handle 12mm dia, PGI funnel and wire mesh,20 mm dia GI pipe light grade for watering and connected to earth test point including brazing at all joints except at test point and testing complete all as specified and directed NOTE:- i) Earth lead beyond 7.5 m from electrode to earth terminal point/main switch board & GI pipe light grade 15 mm dia for protection against mechanical damage to lead shall be measured separately. ii) On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost by the contractor.
Excavation in trenches not exceeding 1.50m wide and not exceeding 1.5M depth in hard/dense soil and getting out for laying pipes, cables etc and fitting incl forming bottom surface to required level and slope complete all as specified and dircted.
Returning, filling in, trenches including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in hard/dense soil complete all as specified and dircted.
Removing surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above starting point complete all as specified and dircted.
M&L for dry clean sand filling in trenches below and around under ground cable cushioning complete all as specified and directed.. Note :- Thickness of sand cushioning shall be measured after punning.
M&L for brick sub class 'B' old size brick for protection of cable complete all as specified and directed.
M&L for GI tubing light grade 80 mm bore for cable protection laid in trenches/fixed to wall, poles including MS flat iron, clamps,nuts, bolts, etc complete all as specified and dircted.
M&L for GI tubing light grade 40 mm bore for cable protection laid in trenches/fixed to wall, poles including MS flat iron, clamps,nuts, bolts, etc complete all as specified and dircted.
S&F cable jointing kit for 1.1 KV grade cable for stairght through joint complete with jointing material (Epoxy based) and accessories suitable for 3.5 core XLPE armoured Al conductor cable of size 120 Sqmm to 150 Sqmm complete all as specified and dircted.
All as per item No 27 above but cable size 35 Sqmm to 70 Sqmm.
M&L for prepartion of old painted steel and iron surfaces and painting to steel tubular LT poles with two coats of synthetic enamelled paint upto 1.5 m height above from ground level/plinth block (in yellow, Red and black strips of 30 cm wide each) and applying two coats of aluminium paint above 1.5 m height of poles including painting on cross arms, bracing, clamps etc and writing pole Nos with thick black synthetic enamel paint complete all as specified and dircted.
M&L for stringing stretching and stengthening of over head conductor (ACSR) on existing LT steel tubular pole or RS joist LT electric pole including binding and jointing the conductor with and including 14 SWG winding wire etc complete all as specified and directed. Note ;- (i) Cutting/trimming of tree branches all around the LT over head conductor of any span upto 1.5m away including removing the same shall deemed to be included in unit rate quoted by contractor (ii) Any breakage or damage shall occure in insulator shall be replaced by the contractor at his own cost which shall also deemed to be included in rate quoted by contractor (a) Weasel (6/1x2.59 aluminium and 1x2.59 steel)
Supply and Fixing pole mounting box / junction box made out of 1.66mm thick MS CRCA sheet / fibar sheet of size 230 x170 x 105 mm complete suitable for three phase connection with clamps of flat iron/GI off size 25 x 4 mm including suitable size nut, bolts, washer etc to fix on pole and provide with hinged door and locking system all painted with two coats of synthetic enamel paints over one coat of red oxide primer and comprising of the following :- (i) Aluminium bus bar 150mm long size 20 x 50 mm fixed on four Nos porcelain insulator each bus bar provided with four Nos of Nuts, bolts, washer for incoming and out going cable. (ii) MCB SP 230V 5 to 32A, 10 KA – 1 Nos.
Trimming of trees all as along the LT line in such away that there is clear distance of 3.00 mtr between tree and electric line. The work will be executed to the entire satisfaction of Engineer-in-charge irrespective of the size of the tree branches etc complete all as specified and directed. Note :- (1). Tree branches will be left as it is the wood belong to Cantt Board/DO. They will be responsible for the wood. (2) Contractor shall employ sufficient labour to complete the full one job within 15 days. (3). Contractor will be responsible for any type of accident while trimming the trees. (4) Contractor superviser will take proper shut down for MES installation before starting the work and clear it before resuming power supply, however full assistant will be provided by MES staff.
M & L for servicing, overhauling, checking and testing complete of DG set 100 KVA at Nainital as under:- (a) Supply and replacement of Lub oil filter Primary and Secondary, hose bend & hose pipe, air filter. (b) Drain out old lubricant oil from oil sump and supply and filling of fresh lubricant oil 20 W 40 grade. (c) Drain out water from radiator of engine and cleaning the same with anti rusting solution and supply and filling of coolant. (d) Checking and making necessary adjustment to drive belts, speed governor and fuel injectors for smooth function of the engine complete all as specified and directed.
M & L for servicing, overhauling, checking and testing complete of DG set 40 KVA at Nainital as under:- (a) Supply and replacement of Lub oil filter Primary and Secondary, hose bend & hose pipe, air filter. (b) Drain out old lubricant oil from oil sump and supply and filling of fresh lubricant oil 20 W 40 grade. (c) Drain out water from radiator of engine and cleaning the same with anti rusting solution and supply and filling of coolant. (d) Checking and making necessary adjustment to drive belts, speed governor and fuel injectors for smooth function of the engine complete all as specified and directed.
Surface dressing n.exc 15 cm deep incl in any type soil including taking out all sapling shrubs, brushwood, undergrowth, roots, and trees n. exc 30 cm girth all removing to a distance n.exc 100 m from starting point complete all as specified and directed (The area is to be carried out in and around, structure viz transformes, HT and electric poles over head reservoirs, around power house and pump house and other E/M installation at Haldwani & Ranibagh).
Taking up or down steel tubing of any grade including all GI fitting laid in trenches or on open surface and connections for relaying or removal complete all as specified and directed for the following sizes :- (a) 50 mm dia
All as per item No 36 above but 40 mm dia
All as per item No 36 above but 32 mm dia
All as per item No 36 above but 25 mm dia
All as per item No 36 above but 20 mm dia
All as per item No 36 above but 15 mm dia
Re-fixing of following bore old steel water tubing and connection in new or old position as in trenches including cleaning of old pipes and provision of new GI fittings as required complete all as specified and directed:- (a) 50 mm dia Note :- Serviceable GI tubing retreived from item 36 to 41 will be reused.
All as per item No 42 above but 40 mm dia
All as per item No 42 above but 32 mm dia
All as per item No 42 above but 25 mm dia
All as per item No 42 above but 20 mm dia
All as per item No 42 above but 15 mm dia
Supply and laying in trenches GI tubing medium grade with all GI fittings (such as bend, elbow, tees, connectons, short pieces, bak nuts, union, valve, caps and plugs etc) for pipe complete all as specified and directed for the following sizes :- (a) 50 mm dia
All as per item No 48 above but 40 mm dia
All as per item No 48 above but 32 mm dia
All as per item No 48 above but 25 mm dia
All as per item No 48 above but 20 mm dia
All as per item No 48 above but 15 mm dia
M & L for Welding of GI leakage pipe 15 mm to 50 mm size by electric resistance uniform thick welding by providing electric supply upto location using suitable size of electrode and other pipe lifting and safety equipments including necessary excavation and earth work in any type of soil as required etc (quoted rates shall be deemed to be included the cost of such provision) complete all as specified and directed.
M & L for Cleaning of valve pit chambers, removing algae, silt, sludge accumulated at bottom of valve pit chambers up to the entire satisfaction of Engineer in Charge complete all as specified and directed.
Taking down unserviceable gate valves of bore 50 mm for replacement including S & F Gun-metal, gate valves ISI Marked with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed.
All as per iter No 56 above but 40 mm bore
All as per iter No 56 above but 25 mm bore
All as per iter No 56 above but 20 mm bore
All as per iter No 56 above but 15 mm bore
S & F 40 mm dia Ball valves high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed complete all as specified and directed (Minimum weight 40mm-690gms)
All as per iter No 61 above but 25 mm bore (Minimum weight 25mm-455gms)
Taking down carefully aluminium/copper wiring of any size (for light, fan, socket or power etc complete) including fixture and fittings such as switches, sockets, ceiling roses, pendent holders regulators, tube lights, bells etc and making good disturbed surfaces of wall, roof etc to match with existing surface complete all as specified and directed
Supply & Fixing point wiring for one light point/ fan point controlled by one, one way switch with 1.5Sqmm size, PVC insulated and unsheathed 1100volts grade, single core stranded (multistrand) copper conductor (FRLS) PVC cable drawn into & including PVC casing/capping and accessories including sunk cast iron or pressed steel terminal boxes for mounting fittings like switches, sockets & fan regulators etc with 3 mm thick plastic laminated sheet covers fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.5 Sqmm multistranded copper conductor cable earth wire and connected to earth, etc and making good disturbed surfaces of wall, roof etc to match with existing surface complete all as specified and directed (Note:- wiring shall be done in colour coding as directed by Engineer in charge)
All as per item No 64 above but one bell point controlled by one switch
All as per item No 64 above but one light point controlled by one two way switch
All as per item No 64 above but one socket outlet 5 Amps on the same board.
All as per item No 64 above but one socket outlet 5 Amps on independent board
All as per item No 64 above but wiring with 2.5sqmm copper wire (FRLS) PVC and 2.5 sqmm earth wire for socket outlet 5 pin 15 amps on independent board.
Supply & Fixing point wiring for one light point/ fan point controlled by one, one way switch with 1.5Sqmm size, PVC insulated and unsheathed 1100volts grade, single core stranded (multistrand) copper conductor (FRLS) PVC cable drawn into & including medium grade PVC conduit (not less than 20mm outer dia) with all fittings and accessories fixed concealed (including chase cutting in brick/ stone masonry walls for fixing conduit and plastering and whitewash/colouring the external surface and matching the same with existing surface) and sunk cast iron or pressed steel terminal boxes for mounting fittings like switches, sockets & fan regulators etc with 3 mm thick plastic laminated sheet covers fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.5 Sqmm multistranded copper conductor cable earth wire and connected to earth etc and making good disturbed surfaces of wall, roof etc to match with existing surface complete all as specified and directed (Note:- wiring shall be done in colour coding as directed by Engineer in charge.)
All as per item No 70 above but one bell point controlled by one switch.
All as per item No 70 above but one light point controlled by one two way switch.
All as per item No 70 above but one socket outlet 5 Amps on the same board.
All as per item No 70 above but one socket outlet 5 Amps on independent board
All as per item No 70 above but wiring with 2.5 sqmm copper wire (FRLS) PVC and 1.5 sqmm earth wire for socket outlet 5 pin 15 amps on independent board.
Supply & Fixing lamp holder (dome type) PVC insulated body with cord grip cap for angle/battern fitting complete all as specified and directed.
Suppy & Fixing switch piano flush type single pole, one way 6 Amp complete all as specified and directed.
Supply & Fixing switch piano, flush type single pole 15 Amp complete all as specified and directed.
Suppy & Fixing switch piano flush type single pole, two way 6 Amp complete all as specified and directed.
Supply & Fixing socket outlet 2 in 1, 3 pin, 6 and 16 Amp flush type complete all as specified and directed.
Supply & Fixing socket outlet 2 in 1, 3 pin, 6 Amp flush type complete all as specified and directed.
Supply & Fixing Bell push, flush type, 5 Amp complete all as specified and directed.
Supply & Fixing steped type electronic fan regulator flush type on the existing phenolic laminatedsheet etc complete all as specified and directed.
Supply & fixing Bell AC 230 volts, 50 Hz single pole complete all as specified and directed.
Supply & Fixing ceiling rose, PVC/ Poly carbonate, isolated body three terminal complete all as specified and directed.
Supply and fixing of following rating of modular type ,white polycarbonate,switches, sockets, fan regulator suitable for 250V, AC, 50Hz.Electrical supply and as directed:- (a) 6 Amp one way switch, 1 module
All as per item No 86 above but 6 Amp two way switch, 1 module
All as per item No 86 above but 6 Amp 2/3 Pin combined socket shuttered, 2 module
All as per item No 86 above but Modular Switch 1 way 16 Amp, 1 Module
All as per item No 86 above but Modular socket 6A/16Amp, 2/3 pin combined, 2 Module
All as per item No 86 above but 6 Amp bell push switch modular type
All as per item No 86 above but Steped type electronic fan regulator modular, 120W-2 module
Supply and fixing of following sizes of modular front plates, white with frame on existing boxes complete as required:- (a) 2 Module
All as per item No 93 above but 3 Module
All as per item No 93 above but 4 Module
All as per item No 93 above but 6 Module
All as per item No 93 above but 8 Module
Supply and fixing anodised rust proof 18 SWG MS box, flush type of following sizes (to be of same make as modular switches and sockets) to be recessed in wall /gypsum partition complete as required as under :- (a) (1-2 Module)
All as per item No 98 above but (3 Module)
All as per item No 98 above but (4 Module)
All as per item No 98 above but (6-8 Module)
Supply & Fixing sheet metal enclosure for DBs(double door type) single pole and neutral 4 way including blanking plate as required with 200 Amps rated bus bar, 240 volts fixed including taking down unserviceable main switches MCB DB’s of any make and type including teakwood board etc complete and making good the disturbed surfaces including colour wash complete all as specified and directed.
All as per item No. 102 above but 8 way
All as per item No 102 above but 12 way
Supply & Fixing sheet metal enclosure for DBs(double door type) Triple pole and neutral 4 way including blanking plate as required with 200 Amps rated bus bar, 415 volts fixed and concealed in wall including taking down unserviceable main switches MCB DB’s of any make and type including teakwood board etc complete and making good the disturbed surfaces including colour wash complete all as specified and directed.
M&L for PVC/Polycarbonate rectangular block for mounting, switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet cover of size 100mm x 100 mm and 50 mm deep incl fixed with screws and cup washers and taking down unserviceable switch board of any make and type including teakwood board etc complete and making good the disturbed surfaces including colour wash complete all as specified and directed.
All as per item No 106 above but 175 x 100 x 50 mm deep
All as per item No 106 above but 200 x 150 x 50 mm deep
All as per item No 106 above but 250 x 200 x 50 mm deep
Supplied & Fixing Rigid non matallic PVC conduits external dia 20 mm ISI marked exclusive of boxes (Junction/terminal) but inclusive of all tee, bends, elbows, reducers, bell mounth tube ends and fixing accessories such as couplers, lock, nuts, saddles, pipe hooks etc for exiting point/main/sub-main wiring complete all as specified and directed.
Supply & Fixing 240V, 10KA 'B' curve miniature circuit breaker (MCB) of single pole and current carrying capacity 5 to 32 Amp, in the MCB DB complete with connection testing and commissioning complete all as specified and directed .
Supply & Fixing 240V, 10KA 'C' curve miniature circuit breaker (MCB) of single pole neutral (SPN) and current carrying capacity 32 Amp, in the MCB DB complete with connection testing and commissioning complete all as specified and directed .
Supply & Fixing 240V, 10KA 'C' curve miniature circuit breaker (MCB) of single pole neutral (SPN) and current carrying capacity 40 to 63 Amp, in the MCB DB complete with connection testing and commissioning complete all as specified and directed .
Supply & Fixing 415V, 10KA 'B' curve miniature circuit breaker (MCB) of triple pole neutral/four pole (TPN/FP) and current carrying capacity 40 to 100 Amp, in the MCB DB complete with connection testing and commissioning complete all as specified and directed .
Material and labour for Sub main wiring with 2 run of 2.5 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable ISI marked, drawn in to and including Rigid non metallic PVC conduit ( ISI marked) Heavy grade, 20 mm dia (external) inclusive of junction/terminal boxes, all fittings and accessories fixed concealed with and including 1.5 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable ISI marked as earth wire, connected with thimble from main DB to sub main DB including cutting and chasing and making good surface as original by plastering and whitewash/ colour/ distemper etc including taking down existing old sub main wiring complete all as specified. Note :1 The cost of earth wire is included in the quoted rates. 2. Two run of 2.5/4/6 Sqmm and one run of 1.5 Sqmm incl PVC conduit will be measured as one unit ie one running metre”
All as per item No.115 above but 2 X 4 Sqmm inclusive 4 Sqmm earth wire.
All as per item No 115 above but 2 X 6 Sqmm inclusive 6 Sqmm earth wire.
Material and labour for Sub main wiring with 2 run of 2.5 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable ISI marked, drawn in PVC casping caping ( ISI marked) Heavy grade inclusive of junction/terminal boxes, all fittings and accessories fixed and including 1.5 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable ISI marked as earth wire, connected with thimble from main DB to sub main DB including cutting and chasing and making good surface as original by plastering and whitewash/ colour/ distemper etc including taking down existing old sub main wiring complete all as specified. Note :1 The cost of earth wire is included in the quoted rates. 2. Three run of 2.5/4/6 Sqmm and one run of PVC conduit will be measured as one unit ie one running metre”
All as per item No. 118 above but 2 X 4 Sqmm inclusive 4 Sqmm earth wire.
All as per item No. 118 above but 2 X 6 Sqmm inclusive 6 Sqmm earth wire.
Supply and fixing LED luminaire 600 mm x 600 mm, 36 watt, 220 V AC recessed type (warm/milky white as required on site) with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling, life of tube light not less than 50,000 hours including connecting up with driver three core flexible copper conductor cases of suitable size complete. Make C&S, Havells, Bajaj, Philips, Wipro Note:- Contractor shall submit 2 year warrenty of material from manufracturer alongwith purchase voucher.
S & F LED light fitting 1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size. Make : Havells cat pat HEXAFT10WLED857SSYMBOPC or equivalent cat part in Make :- C&S, Havells, Bajaj, Philips, Wipro Note:- Contractor shall submit 2 year warrenty of material from manufracturer alongwith purchase voucher.
Supply and fixing post top lantern LED type 20Watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed .
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper cable of suitable size complete all as specified and directed .
Supply and fixing LED lights T-5 fitting 1x 20W (warm/milky white as required on site), 220V, AC with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose 1.5 RM and life of tube light not less than 50,000 hours complete all as specified and directed.. Make C&S, Havells, Bajaj, Philips, Wipro Note:- Contractor shall submit 2 year warrenty of material from manufracturer alongwith purchase voucher.
M&L for servicing of water heater (Geyser) upto 50 Ltr capacity of any make by cleaning sludge and slurry, calcium inside inner water storage tank and make the geyser in operational condition all as specified and directed. Comprising of the following works :- (i) Rectifying water leakage in inner copper/iron storage tank by using welding (ii) Replacement of heating element upto 2000 Watt. (iii) Replacement of Thermostat of suitable size as required on site. (iv) Checking & tightening the electrical connection (v) Replacement of safety valve. (vi) Replacement of NRV (Non returning valve) of suitable size as required at site .
Supplied & Fixing PVC casing/capping inclusive of boxes (Junction/terminal) and fixing accessories such as couplers, lock, nuts, saddles, pipe hooks, fixing pin etc for exiting point/main/sub-main wiring complete all as specified and directed.
Supply and fixing in repair heating element upto 2000 watt tringular type/cap type (as required on site) for water heater/gyser all as specified and directed
S & F LED Bulb 9 watt all as specified and directed
Supply and fix changeover switch AC 23 side handle 4 pole , 415 Volt 100 Amp, on load side handle operated complete all as specifide and directed .
Supply and fix changeover switch AC 23 side handle 4 pole , 415 Volt 200 Amp, on load side handle operated complete all as specifide and directed .
S & F exhaust fan mettalic body ISI Mark, 300 mm size with blades, frames and louvers including cutting opening through brick/stone /PCC block wall, making of holes and grouting of suitable size of nuts and bolts for 300 mm exhaust fan and making good dismantled portion and making connection with wire of suitable size and connecting accessories complete all as specified and directed.
S & F exhaust fan made of sturdy Engineering plastic type ISI Mark, copper winding of sweep 300 mm size complete with louvers including cutting opening through brick/stone /PCC block wall, making of holes and grouting of suitable size of nuts and bolts for 300 mm exhaust fan and making good dismantled portion and making connection with wire of suitable size and connecting accessories complete all as specified and directed.
M&L for earthing complete with galvanized sheet earth plate electrodes 60x60x6.3 mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of plat not less than 1.5 mtr below normal ground level connected to galvanized earth lead wire 4 mm dia as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 and including excavation and earth work, GI pipe light grade 15 mm bore for protection of GI wire from earth electrode to and including the earth test point of galvanized Iron/ steel of size 75x75x25mm, supplying and laying charcoal dust, common salt, PCC 1:2:4 type B1 chamber and MS angle iron frame 40x40x3mm and RCC cover 40mm thick (1:2:4) type B1 using 20mm graded stone aggregate reinforced with 6 mm dia TMT bars @ 75mm C/C both ways with MS handle 12mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade for watering and connected to earth test point including brazing at all joints except at test point and testing complete all as specified and directed. NOTE:- i) Earth lead beyond 7.5 m from electrode to earth terminal point/main switch board & GI pipe light grade 15 mm dia for protection against mechanical damage to lead shall be measured separately. ii) On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost by the contractor.
Supply and fixing LED Security/Street light fittings 35 watt 230V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant inclding thermal management in multiple optics complete with IP 65/66 Protection with GI Pipe light grade bracket 1.2 mtr long 40 mm dia fixed to wall with suitable size 2 Nos MS Clamps including nuts, bolts and washers and making connection with using 1.5 sqmm pvc insulated multi standard copper conductor three single core complete all as specified and directed
Supply and fixing LED flood light 70 watt, 230 V AC out door type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp and average life of flood light not less than 50000 hours, including clamps, nut, bolts, fixing in wall including 2 sqmm PVC twin core aluminium cable from conductor to street light not less 2.0 metre , testing complete all as specified and directed.
Supply and fix electronic meters temper proof LCD display with polycarbonate cover 230v, 10-60amp, accuracy class-I 50Hz, confirming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH including suitable copper wire as requirement at site complete all as specified and directed. Existing old meter will be deposited at MES store.
Supply and fix electronic meters temper proof LCD display with polycarbonate cover 3 phase, 415 Volst, 10-60amp, accuracy class-I 50Hz, confirming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH including suitable copper wire as requirement at site complete all as specified and directed. Existing old meter will be deposited at MES store.
aditya construction
Ramsons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .