Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.6 LAccepted-AOC | L1 | Accepted-AOC lowest | |
| 2 | L2₹9.5 L+₹1.8 L (23.0%)Rejected-Finance | L2 | Rejected-Finance other than lowest | |
| 3 | L3₹10.6 L+₹2.9 L (38.2%)Rejected-Finance | L3 | Rejected-Finance other than lowest |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
10 Apr 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Garrison Engineer Ludhiana
Garrison Engineer Military Engineer Services Near Jagraon Bridge Ludhiana-141001 (Punjab)
Repair and maint to Capacitor bank and misc work at Dholewal, Doraha and CG Complex under GE Ludhiana
2025_MES_700574_1
GE/LDH-75/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Dholewal, CG Complex and Doraha
As per NIT and Tender documents
9 documents required · 9 mandatory
₹500
GE Ludhiana
₹20,000
Yes
23 Jun 2025
11 Mar 2025
12 Apr 2025
11 Mar 2025
10 Apr 2025
26 Mar 2025
11 Mar 2025 - 25 Mar 2025
Amount
Supply & fixing in replacement current transformer CT 25/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement current transformer CT 50/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement current transformer CT 75/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified and directed .
Supply & fixing in replacement power factor controller relay latest micro controller based tech with true RMS sensing alarm avilable , delay adjustment , LCD display range 08 steps , 7 segment LED display size 144 X 144mm Auxillary supply 90-550 VAC, NTC tempature sensor , power factor measurement range 0.8 lag to 0.8 le suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement power factor controller relay latest micro controller based tech with true RMS sensing alarm available , delay adjustment , LCD display range 12 steps , 7 segment LED display size 144 X 144mm Auxillary supply 90-550 VAC, NTC tempature sensor , power factor measurement range 0.8 lag to 0.8 le suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement heavy duty cylindrical capacitor 1 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement heavy duty cylindrical capacitor 3 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and directed .
Supply & fixing in replacement heavy duty cylindrical capacitor 5 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement heavy duty cylindrical capacitor 10 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement heavy duty cylindrical capacitor 15 KVAr, 3 Phase, 440 V, 50Hz suitable for APFC Panel complete all as specified and directed.
Supply & fixing heavy duty cylindrical capacitor 20 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and directed.
Supply and fix in replacement capacitor duty contactor 3P, AC3 , 12 amp (2NO, 2NC) of suitable up to 5 KVAR APFC panel ratings for APFC Panels complete all as specified and directed
Supply and fix in replacement capacitor duty contactor 3P, AC3 , 20 amp (2NO, 2NC) of suitable up to 10 KVAR APFC panel ratings for APFC Panels complete all as specified and directed
Supply and fix in replacement capacitor duty contactor 3P, AC3 , 32 amp (2NO, 2NC) of suitable up to 15 KVAR APFC panel ratings for APFC Panels complete all as specified and directed
Supply and fix in replacement capacitor duty contactor 3P, AC3 , 40 amp (2NO, 2NC) of suitable up to 20 KVAR APFC panel ratings for APFC Panels complete all as specified and directed
Supply and fixing in replacement 4 Pole MCCB 63 Amp, 50 Hz, 415 V with rupturing capacity 16 KA complete all as specified and directed
Supply and fixing in replacement 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 16 KA complete all as specified and directed.
Supply and fixing in replacement 4 Pole MCCB 125 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and directed.
Supply and fixing in replacement 4 Pole MCCB 160 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and directed.
Supply and fixing in replacement 4 Pole MCCB 250 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and directed.
Supply and Fixing in replacement C Curve 3 Pole MCB 32 TO 63 Amp, 50 Hz, 415 V with rupturing capacity 10 KA complete all as specified and directed.
Supply and fix in replacement wiring complete 6.0 Sqmm single core PVC insulated FR LS cable 1100 volts grade multistranded copper conductor cable with multistranded copper conductor cable as earth continuity conductor complete all as specified and directed
Supply & fixing in replacement panel mounted voltmeter three phase including with CTs/ PT ratio 4 digit display , class 1.0 in 96X96 Sq mm flush mounted case suitable for APFC Panel complete all as specified and directed.
Supply & fixing in replacement panel mounted Ammeter three phase including with CTs/ PT ratio 4 digit display, class 1.0 in 96X96 Sq mm flush mounted case suitable for APFC Panel complete all as specified and directed
Material and labour in replacement of indicator lamp in red, yellow and blue colour with lamp holder multi LED type complete including wiring with copper conductor cable of suitable size complete all as specified and directed
M&L for painting of panel board inner & outer complete with synthetic enamel paint two coats by spraying including filling cavaties with filler one coat after cleaning all dust/rust including writing the Distribution/Panel Number and panel details all as directed . Note: The Quoted rates are inclusive of three coats white wash to fountation of Panel Board/ Painting to Angle Frames with two coats of synthetic enamel paint over a coat of red oxide primer including preparation of surfaces complete all as specified and directed
Material & labour earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed with layers of charcoal dust and common salt, earth electrode GI strip 32 x 6mm connected to GI earth plate electrode by means of bolts, nuts, check nuts and washers of galvanized iron and thimbles and other end of earth strip connected to test point and protected by galvanized iron pipe light grade 50mm bore and GI pipe 20mm bore light grade with funnel and wire mesh for watering including necessary excavation and earth works. PCC chamber in cement concrete (1:3:6) type C-2 using graded stone aggregate and RCC cover in PCC 1:2:4 and all as shown in Electrical Plate No. 3 of MES Schedule (Part-I) of 2009 complete all as specified and directed. Notes : (i) Outer edge of earth pit will be 1.5m away from the outer edge of PCC chamber. (ii) Water pipe shall be provided in slanting position.
M&L demolition of cement concrete of any description and in any position complete all as specified & directed including removal of demolished material from site as directed.
M & L PCC (1:4:8) type D-2 using 40mm graded crushed stone aggregate as in foundation of electric poles, struts, PCC block including necessary form work and fair finish to exposed surfaces without using extra cement etc. complete all as specified and directed
M & L PCC (1:3:6) type C-1 using 20mm graded stone aggregate as in foundation filling upto ground level etc. complete all as specified and directed
M&L PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregate as in coping of poles etc. with slightly rounded or chamfered angles including necessary form work and fair finishing the exposed surface without using extra cement complete all as specified and directed .
M & L for supply, erecting and fixing in position 9 metre long steel tubular swaged pole type 410 SP-22 complete with cast iron base plate, final taper plug, bolts, nuts & screws conforming to IS-2713 (Part- I & III) of 1980 and painting the pole with two coats of aluminum paint over a coat of primer including black and white strips 30cm each upto 1.5 metre from top of PCC foundation block and numbering of poles in 80mm high white letter using synthetic enamel paint over base etc including taking down old existing pole and proper connection with existing condoctor complete all as specified and directed
Supply, laying, jointing, testing and commissioning in replacement of cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, laid in trenches, fixed by means of MS saddles on or fixed on poles including connection with proper lugs for the following size including taking out old one complete all as specified and directed.
6 Sqmm 2 Core
10 Sqmm 2 Core
16 Sqmm 4 Core
25 Sqmm 3.5 Core
35 Sqmm 3.5 Core
50 Sqmm 3.5 Core
Excavation in trenches soft/loose soil not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of pipes/cables etc getting out and bottom surface to required gradient complete all as directed & specified
M&L returning filling in including spreading leveling watering and well ramming in layers each not exceeding 25 cm thickness complete all as specified and directed.
M&L removal of surplus spoil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Supplying, filling in trenches, spreading, leveling sand cushioning 8 cm below cable and 15 cm above the cable for under ground cable complete all as specified & directed .
M & L old size sub class 'B' bricks laid flat in trenches over the cable with length of brick perpendicular to the direction of the cable adjacent/abutting each other complete all as specified and directed
Supply & fix in replacement PVC exhaust fans (4") AC single phase 100 mm sweep or as per existing sample of panels ext fan with louver complete all as specified and directed
Tree pruning near overhead LT/HT lines and poles (tools and allied items required for tree pruning will be provided by the contractor) complete all as specified and directed.
M&L in replacement of power house name board box type with in built LED lights fitted with required height of angle iron frame size of 23 ft x 2.5 ft of arcylic sheet complete all as specified and directed .Note (i) Rough data shall be provided by the Engr-in-charge. (ii) Rates for necessary brick work and angle iron frame, LED lights shall be included in quoted rates.
Supplying and laying in replacement synthetic rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006,(supersending IS 5424) suitable for electrical shock safety of size 2 m x 1 m complete all as specified and directed
Supplying and laying in replacement synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006,(supersending IS 5424) suitable for electrical shock safety of size 2mx1 m complete all as specified and directed
Durga Electricals (BID ID -3275331)
JASSI TRADERS (BID ID -3279921)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .