| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying and erection of 7 Mtrs long continously tapered octagonal pole (bolt fixing type) in single section with single longitudinal weld & galvanized having top dia 70MM as per following specification:- Make Bajaj/Nezone/Crompton/Jintal/Tata/Utkarsh a) Top dia - 70mm b) Bottom dia - 130 mm c) Thickness of sheet - 3mm d) Base plate size - 220mm X 220 mm X 12mm e) The pole shall be complete with following :- Set of foundation bolts -4 nos, 20mm dia, 600 mm in length complete with anchor plate. The foundation bolt shall be hot dipped galvanised. f) Integral junction box duly hot dipped galvanised complete with door and locking arrangement as required. | 25 | each | - | - |
| 2 | Supplying and fixing of 4 Pole,3 phase 63 Amp heavy duty connector bolt type with bakelite sheet MCB din rail in the existing junction box of the octagonal pole (as per item No 1) etc as required | 25 | each | - | - |
| 3 | Providing and erection of channeled shaped Flood Lighting Bracket of required size (To be appoved by Engg-in-charge) suitable for mounting of flood lighting luminaire on polygone (8 sides) cross section, octagonal type, 7 Meter height pole with 04 Nos 18 mm dia symmetrically located holes / slots including providing and fixing matching G.I nuts-bolts and washers required for fixing the bracket on the pole as per specifications. | 25 | each | - | - |
| 4 | Supplying,Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 Hz,Operating temp range -5 °C to 50 °C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI ≥70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (A) 100 WATT | 50 | Job | - | - |
| 5 | S/L of 3 Core cable 1.5 sqmm size of PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010 from looping box to light fitting including interconnection with connector,testing complete etc as required | 175 | Each | - | - |
| 6 | S.I.T.C of feeder pillar , outdoor type, dust and vermin proof made out of 2 mm thick CRCA sheet of nominal size 0.9 mt. x 0.75 mt X450 deep, front and back openable- hinged type door, duly eposy based pwder coated (from inside and outside), and fixed on M S angle iron frame work of size 40 mmx 40 mmx 6 mm length with 4 nos. 750 mm long legs duly welded to the frame structure and out of which 300 mm will be grouted in 1:2: 4 cement concrete foundation i/c supply and fixing of following accessores, connection and interconnection, inter locking wiring, thimbling, numbering-ferrules up & lowering system, earthing stud etc. complete as reqd.(Panel should be as per design & drawing approved by Engg in charge) (I)Main incomer 415 V, 100 Amp 4 Pole, 36 KA MCCB,Ics=100%Icu,Adjustable termal & adjustable magnetic : 1 No. (ii) Indicating lights - 03 Nos (3 Nos for Incoming power supply) (iii)Out going 415 V,40 Amp 4 Pole, 25 KA MCCB,Ics=100%Icu,Adjustable termal & adjustable magnetic : 2 No | 1 | each | - | - |
| 7 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required a) Double pole | 25 | each | - | - |
| 8 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. | 3 | Each | - | - |
| 9 | Providing and laying earth connection from earth electrode with 6 SWG gia G.I. wire in 15 mm dia G I Pipe from earth eletrode including connection with G.I. thimble excavation and filling as required | 27 | Meter | - | - |
| 10 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. | 111 | MTR | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.77 MB
BOQ_975991.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .