Executive Engineer FMD Baramulla
khawja Bagh barmulla
Electrical work to be carried out at Jetty Store yard of Flood Mechanical Division Baramulla
2025_IFC_277093_2
NIT 03 of 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
7 days
Executive Engineer FMD Baramulla
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹1,800
5 Jun 2025
14 May 2025
22 May 2025
14 May 2025
21 May 2025
14 May 2025
Amount
Repairs to 100A LT Distribution panel at jetty store yard by way of removing accumulated carbon from all electrical connections inside panel by way of applying carbon tetra chloride active chemical/CRC2-26 spray to make the surface clean. Adjustment of all protection devices, removing of dirt, dust and other greasy substance with the help of thinner/acetone and blowing of compressed air inside the panel compartment. The job also includes the charge for providing of brass bolts with nuts as per sample for incoming and outgoing connections of Bus bar (2Kg).
Replacement of damaged 4P 100Amp MCCB with new one inside panel having breaking capacity 35KA at 415V at jetty store yard. The MCCB shall have adjustable thermal and magnetic setting and shall be of reputed make. All the tools /tackles, carriage, skilled labours etc. involved in the job are to be provided by the firm.
Replacement of damaged Changeover with providing and retrofitting of new 415V,50Hz,4P manual type on load 125 Amp changeover inside panel. All the tools /tackles, carriage, skilled labours etc involved in the job are to be provided by the firm.
Repairs to 63 KVA substation installed at jetty yard store by way Supply and erecting of three-piece nonlinear resistor type lighting arrestor suitable for three wire, 11kv overhead lines with rated voltage 9V (rms) with a nominal discharge current rating of 5A and complete with galvanized clamping arrangement nuts bolts and washers. The job also includes providing and fitting of channels of ISMC-75 (24 kg) with clamps, nuts, bolts and washers for lighting arrestor. The job also includes earthing to lighting arrestor, G.I strip (15kg), Baby insulator (06no), Baby Clamps(06 no), Earthing rod of G.I (01 no) for the completion of work.
Supply, installation, testing & commissioning of 35 sqmm PVC insulated unarmored insulated 1100V single core copper cable to be laid from LT Distribution to existing voltage stabilizer at jetty store yard of reputed make. The cable shall be thimble at each end with reputed make thimble with the help of skilled labour, hydraulic crippling tool, tape roll and other tools & tackles for the completion
City Engineering Works (BID ID -2373782)
M/s SIMAR ENTERPRISES (BID ID -2372548)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .