Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹83 L
EMD Value
₹1.7 L
Closing Date
26 Dec 2022, 6:55 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Exen Eng PHE Mech Div North Sopore
Exen Eng PHE Mech Div North Sopore
Electro-Mechanical works
2022_PHE_197223_8
PHE/MDNS/NIT/JJM/E-28 of 2022-23
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
Tantraypora Goom Ahmadpora
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Yes
Exen Eng PHE Mech Div North Sopore
₹1.7 L
Yes
Exen Eng PHE Mech Div North Sopore
29 Jul 2023
23 Nov 2022
27 Dec 2022
23 Nov 2022
26 Dec 2022
24 Nov 2022
24 Dec 2022
Amount
Providing, fitting, installation, testing and commissioning of VT pumping unit of following specifications: A. PUMP 1. Discharge = not less than 18000 GPH 2. Type = Self water lubricated, VT pump, open line shaft. 3. Liquid to be handled = Raw Water 4. RPM = 1460 5. Head = not less than 100 Meters, Column length=10m(app) 6. Efficiency = Not less than 75% B. Prime Mover 1. Type = Vertical hollow shaft, AC induction 2. Power Supply = 03 Phase, 41 5V± 10% AC 3. Frequency = 50Hz±3% 4. RPM = 1450 Synchronous 5. Efficiency = Not less than 75% 6. HP = Corresponding to Head and discharge but not less than 55HP. Rest of Specification/Details are as per clause 6 of as per Annexure "C" of SBD
Fabrication of base frame, gantry mechanism/CGI Shed with windows and doors including hinges, towerbolts etc as per site requirment.The drawings and Dimensions for Gantry/CGI shed/pump base frame etc will be provided by Site In Charge at the time of execution of job Rest of Specification/Details are as per clause 17 of as per Annexure "C" of SBD.The quantity of the steel/CGI sheets may vary as per site requirement as it is conditional to civil structures being constructed.
Providing of Structural steel in built up sections , trusses and framed work, including cutting , hoisting , grouting, fixing in position and applying a priming coat of steel primer and 02 coats of paint of approved shade all complete welded.
Providing corrugated G. S. sheet 0.63 mm thick with zinc coating not less than 275 gram/m2 roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved surface)excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
Providing and fitting of, Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units. Size: DN150 PN:1.6/16 Rest of Specification/Details are as per clause 12 of as per Annexure "C" of SBD
Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve( NRV) as per IS 5312. Size: 150mm PN: 1.6/16 Rest of Specification/Details are as per clause 13 of as per Annexure "C" of SBD
Fabrication, providing and fitting of split type MS clamps10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts. Size: 150mm Rest of Specification/Details are as per clause 16 of as per Annexure "C" of SBD
Providing, fitting and successful testing of 03 MT capacity, chain pulley block (01 no) with monorail of spur gear type with a minimum lift of 06 mtrs robust chain as per IS 3832:2005. The equipment shall be heavy duty type. The job includes supply of suitable diameter and length soft flexible steel Sling (Qty = 02 Nos) for hoisting of above chain pulley block. “Test Certificate of manufacturer is Mandatory”Rest of Specification/Details are as per clause 24 of as per Annexure "C" of SBD
Providing, fitting and successful testing of 01 MT capacity, chain pulley block (01 no) of spur gear type with a minimum lift of 06 mtrs robust chain as per 3832:2005. The equipment shall be heavy duty type. The job includes supply of suitable diameter and length soft flexible steel Sling (Qty = 02 Nos) for hoisting of above chain pulley block. “Test Certificate of manufacturer is Mandatory”Rest of Specification/Details are as per clause 24 of as per Annexure "C" of SBD
Providing, supplying and fitting of GI flanged Rising Main at site. The Pipe shall be hot dip Galvanized, Class-B confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) as per clause 8 of as per Annexure "C" of SBD Size : DN 150 Class: B (Medium) The pipe shall be laid underground as per the defined contour/site requirement after carrying out the earth work excavation. The job includes backfilling of the excavated soil after laying, complete in every respect. The road cuts and safe overburden thereof with oversized pipe jacketing, offsets/bends, head load from road side to the site of installation after cleaning of pipes are also included in the job.
Providing, fitting, testing and commissioning of 50mm ARV (Air Release valve) as per IS 14845 to be fitted to G.I rising Main, details as per clause 14 of as per Annexure "C" of SBD
Providing and fitting of delivery manifold system with washout arrangement for VT pumping units fabricated out of 12meter B-Class Heavy duty , 150 mm NB MS pipe conforming IS1239 with fabrication of suitable No. of MS Bends /offsets/Tee joints/ pipe spacer/reducer joints/ISMC 100 supports etc/as per site requirement and as per the directions given by the site Incharge. The job includes providing and fitting of adequate number of 22mm thick MS flanges conforming to IS 6392 Part 1st Table-17/as per site requirment. The flange welding shall be carried out in double layers using reputed make electrodes to form strong and leak proof joint. The job further includes Providing and Fitting of nuts and bolts (conforming to IS:1363 Part 1st) and Rubber Insertion Gaskets (conforming to IS: 638/79) to be used between flanged joints as per site requirement. Painting of complete delivery manifold system with two coats of anticorrosive red oxide primer after surface preparation by grinding, buffing, emery cloth etc and then painting with two coats of approved paint. The job includes cost on account of material, carriage, gas cutting, welding, skilled labour, necessary tools and tackles etc and finally connecting of delivery manifold with rising main and testing of the delivery manifold on full load.
Tool kit comprising of following tools: Pipe wrench 18” -01 No. Adjustable wrench 12” – 01 No. Ring spanner set of 12 pieces. - 01 set. Open ended spanner set of 12 pieces -01 set. Combination Plier - 01 No.,Nose Plier-01No, Line tester-01No. Screw driver (+ -) with removable plastic handle – 10” 01 No. Hammer – 1kg 01 No, Chiesel-01No.
Creation of pole mounted , outdoor type Electric Sub Station by way of S/I/T/C of 11/0.433 KVA , 3 Phase Distribution Transformer with Bimetallic Terminal connectors Energy level -2 Aluminum wound Specifications conforming to IS : 1180 (Part 1) 2014 with latest amendments Type of cooling: ONAN. Rating: 100KVA HT Transformer, 3 phase (Level 2). Manufacturers certificate be apended and rest of specification as per cluase 26 of as per Annexure "C" of SBD
Supply, installation, erection of 9 mtrs long H.T pope of specifications ST410 (SP-33). The job further includes drilling of holes for installation of various accessories .wherever required the job further includes G.I wire earthing of pole as per REC standard as per Clause 32 of as per Annexure "C" of SBD
Cement bottoming 1:2:4 mix as per REC mix as per REC standards 0.5 cum/pole
P/F of Galvanized nuts, bolts of various sizes as per site requirement.as per details in Clause 33 of as per Annexure "C" of SBD
GI Barbed wire for Anti Climbing with fixtures.
P/F Danger Plate with clamps as per details in Clause 34 of as per Annexure "C" of SBD
Wedge connecters/PG Clamps
Providing and fitting G.I Channel /platform for T-bed/Angle/ Flat /Riser of sizes including clamps as per Clause 27 of as per Annexure "C" of SBD
Supply, Installation, Testing and commissioning of Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT post double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings , operating handle and 2 length of 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs as per Clause 28 of as per Annexure "C" of SBD
Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation as per Clause 29 of as per Annexure "C" of SBD
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type as per Clause 30
Supply and fitting of 11 KV polymeric composite disc insulator 12 KV, minimum falling load 45KN, Lighting impulse 75KV Positive, and 80 KV Negative , creepage distance 320 mm.
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative , creepage distance 320 mm as per Clause 31
Painting of poles Red oxide as per Clause 37
Painting of poles Aluminum paint as per Clause 38
Sundry items like aluminium lugs,jumpers,binding tape.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,neutral,G.O Set, lightening arrestor, LT Control Panel and voltage stablizer as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
P/L of ACSR conductor of size 0.05 as per the relevant IS standard as per clause 78
Providing and fitting of 4 pole MCCB on LT side of 100KVA distribution transformer enclosed in SS weather proof enclouser with IP30 protection for outdoor use having below mention specifications Current Rating = 250A. Rated operational voltage = 415 V + 15 % Rated frequency = 50+/-3%Hz Ambient temperature = 40C˚ Ultimate S.C Breaking Capacity (415V AC, 50 Hz) = 50kA Type of release = Thermal-Magnetic Release=Range=200-250A. The job includes providing and fitting of required size thimbles,clamps and fixtures etc required for the job.
Galvanised stay set with 50x8mm stay clamp, guy insulator(02No.),anchor plate(200x200x6mm),nuts and bolts,2No. Turnbuckels,1.8m long,16mm diameter solid GS stay rod and 7/3.15mm dia GI standerd wire complete.
Supply,installation,testing of 50 sq mm XLPE HT cable (ABC type) of 11 KV Grade with following specifications size cross sectional area in squre mm )=3x50 phases Red, Yellow , Blue
P/F of 11 KV cable termination kit for connecting 50 Sq mm XLPE cable (ABC type) with the existing HT line near tapping point and HT transformer.
Supply, Installation, testing and commissioning of 11KV, 3-phase HT Trivectometer. The foundation base is MS base frame and suitable for HV chamber and LV chamber. The Lv chamber is suitable for installation of CT and PTs and termination cable kit as per the latest standard IE rules. The thickness of MS sheet steel should not be less than 2mm,duly coated and painted. The fitted accessories are as under: i.01 set(3 Nos) single phase indoor type resin cost current transformer having ratio of 10/5 for 15 to 100 KVA. ii.01 set 11 KVA/110 volts ,3 phase potential transformer resin cost. iii.01 set copper bus bar duly insulated by monopolist tape. iv.PVC copper wire flexible for multi standard secondary connections for CT wiring v. Copper legs duly crimped in wires and cables. vi. Pedestrial made out of angle iro . vii.35 mm square, 3 core XLPE Armored AL cable including clamps for fixing-40 Mtr viii.11 KV cable termination kit suitable for 35 mm square XLPE cable-2 nos ix. Heat shrink type indoor cable terminal kit-2 Nos The job includes all sorts of transportation charges/head load, skilled labour component etc as per the site requirement
Providing of bamboo ladders 18 feet long along with 15 feet long Link rods and HT Glove pair (01 No each) as per Clause 62
Providing, fitting, testing and commissioning of manually operated copper wound, 3-phase, AC power supply multi step voltage stabilizer. Rating: 100KVA Manufacturers test certificate to be apended and rest of specification as per clause 45 of as per Annexure "C" of SBD.
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electromechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. Rest of Deatils/Technical specification are as per clause 56 of as per Annexure "C" of SBD
Providing and Fitting of 95 sqmm, 3.5 core LT 1.1 KV, XLPE Armoured Aluminium Cable conforming to IS: 7089 part 1st as service line from the HT transformer to control panel as per clause 72 of as per Annexure "C" of SBD.
Providing, installation, testing of power wiring for working voltage up to and including 1100 Volts, 50mm2 PVC insulated multi stranded annealed copper conductor for internal connections as per clause 68 of as per Annexure "C" of SBD
Illumination of pump house by way of providing & fitting of lighting points viz: a) Wiring to lighting points with main wire as 1.5 mm sq. and for branches 1 mm sq. PVC single core multi-stranded copper conductor insulated, unsheathed 1.1 KV grade ISI marked with length as required. b) Recessed pvc conduit/ channel 1.5” and 1” as required. c) 6 Ampere flush type switches ISI marked. d) Switch board frame fabricated out of wooden/ iron including flushing ways for above frames on walls as per site requirement. e) Phenolic / phylum laminated sheet cover for fitting of switches over the above frame. f) Ceiling roses, square blocks, angle holders, PVC corner/ending points accessories, washers, star screws, cement nails, rawl plugs as per site requirement.
Providing and fitting of 10 watt LED lamps for holders of above item.
Providing and fitting indicator points ISI marked.
Providing and fitting Fan regulating points with 01 No 400 mm sweep wall fan and 03 no 150 mm exhaust fans ISI marked
Providing and fitting 03 pin flash type socket 6 Ampere ISI marked
Illumination of Pump House premises: Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) for outdoor application. Having following specifications: Input: 90-240 V 50 Hz Power Factor: >0.9,IP-68, Rest of Deatils/Technical specification are as per clause 52 of as per Annexure "C" of SBD The job includes cost on account of 2.5 Sq. mm copper conductor, MCB Switch, holding arm, clamps etc/as per site requirement.
Fabrication of 6’x3’ (2No’s) angle iron beds having 2' height using 50x50x6mm angle iron by way of providing and fitting of Structural steel in built up sections , trusses and framed work, including cutting , hoisting , fixing in position and applying a priming coat of approved steel primer all complete welded as per clause 59 of as per Annexure "C" of SBD
Providing and fitting of 19mm Ply wood board to be fitted on the angle iron beds.The job includes cutting and fixing of Ply wood on angle iron beds of item no. 47 for resting. Rest of Deatils/Technical specification are as per clause 60 of as per Annexure "C" of SBD
Supplying of 6kgs quilts (2 no’s) with cotton cover, 6kgs Mattress(2nos), sleeping bed sheets (2 no’s), pillows (2 no’s), fur blankets(2 no’s),12mm thick foam sheet and good quality matting of size 12'x10' for the operators . The job also includes providing of Heat blower (1 no.), Rice cooker (01No), 5kg filled Gas cylinder with burner/ stove standard make, Steel patella(utensil) 5ltrs 01 No., Electric heater 01 No., dual type electric and Solar type chargeable LED lantern (01 no), good quality Door Lock (03No). Note: All items should be of good quality and standard
Supply, installation, Testing & commissioning of 1050VA Full Sine wave power inverter with 12V, 180AH Tubular inverter Battery Rest of Deatils/Technical specification are as per clause 55 of as per Annexure "C" of SBD
Supply, installation of 6 kg Co2 type fire extinguisher manufactured as per IS:15683 OF 2006 with IS mark and comply with DGMS(Approval) . Rest of details as per specification in clause 50 of as per Annexure "C" of SBD
Renovation to old Water Supply Scheme Ahmadpora: Part of cleared water shall be stored in the sump of old Ahmadpora water supply scheme and has to be lifted to already constructed OHT (decided during joint site visit). As such, minor renovation involved is as mentioned below, as already mentioned in DPR.
Supply, Installation, Testing & Commissioning of 6000gph, 60m head, 12.5 HP Open Well Pumping Units as per IS 14220 at Filter Water Stage. PUMP: • Type of pump : Open well Submersible Pump (Horizontal) MOTOR: - • Method of starting : Star – Delta. • Frequency : 50Hz + 3% • Voltage : 415 + 6 %, - 15% • Class of insulation : Suitable for above rating. Dual Mechanical Seals (01 No) and Bearings (02 No) for each pumping unit must be provided as spare parts. Note: Providing of test certificate & Characteristic Curve of pumping equipment is compulsory and pumping unit is to be approved from the concerned Sub Divisional office before procuring. The main specicifications of pumping unit are given below: Motor Rating: 12.5HP Detailed specifications as per clause 3 of as per Annexure "C" of SBD
Providing and fitting of Size: 10sq.mm flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipments . The cable connections terminal shall be fitted with copper thimbles of required size. as per clause 48 of as per Annexure "C" of SBD
Providing and fitting of, Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units. Size: DN100 PN:1.6/16 Rest of Specification/Details are as per clause 12 of as per Annexure "C" of SBD
Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve( NRV) as per IS 5312. Size: 100mm PN: 1.6/16 Rest of Specification/Details are as per clause 13 of as per Annexure "C" of SBD
Fabrication, providing and fitting of split type MS clamps10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts. Size: 100mm Rest of Specification/Details are as per clause 16 of as per Annexure "C" of SBD
Fabrication of 6’x3’ (1No’s) angle iron beds having 2' height using 50x50x6mm angle iron by way of providing and fitting of Structural steel in built up sections , trusses and framed work, including cutting , hoisting , fixing in position and applying a priming coat of approved steel primer all complete welded as per clause 59 of as per Annexure "C" of SBD
Providing and fitting of 19mm Ply wood board to be fitted on the angle iron beds.The job includes cutting and fixing of Ply wood on 6'x3' angle iron beds of item no. 56 for resting. Rest of Deatils/Technical specification are as per clause 60 of as per Annexure "C" of SBD
Supply, installation, Testing & commissioning of 1050VA Full Sine wave power inverter with 12V, 180AH Tubular inverter Battery Rest of Deatils/Technical specification are as per clause 55 of as per Annexure "C" of SBD
Supplying of 6kgs quilt (1 no.) with cotton cover, 6kgs Mattress(1no.), sleeping bed sheet (1 no.), pillow (1 no.), fur blanket(1 no.),12mm thick foam sheet and good quality matting of size 12'x10' for the operators . The job also includes providing of Heat blower (1 no.), Rice cooker (01No), 5kg filled Gas cylinder with burner/ stove standard make. patella(utensil) 5ltrs 01 No., Electric heater 01 No. Note: All items should be of good quality and standard
M/S EURO LIGHT ENTERPRISES
BUHROO MECHANICAL PRIVATE LIMITED
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .