Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹10.6 Cr
EMD Value
₹10.6 L
Closing Date
6 Mar 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Municipal Commissioner, Ahmedabad
AUGMENTATION OF UNDER GROUND TANK NO 5 IN DUDHESHWER WATER COMPOUND UNDER WATER PROJECT DIVISION.
280010
2025-26
Open
Miscellaneous Works
Works
Ahmedabad
3 documents required · 3 mandatory
₹18,000
municipal commissioner, ahmedabad
₹10.6 L
24 Feb 2026
24 Feb 2026
24 Feb 2026
6 Mar 2026
24 Feb 2026
(4) Date of e-Tender (Technical Bid)
Municipal Commissioner Green Design & Engineering services Pvt.Ltd.
Ahmedabad Municipal Corporation 520-521, Shivalik Square,
Sardar Patel Bhavan Nr. Adani CNG Pump,
Ahmedabad – 380 001 Ramapir No Tekro, Old Vadaj,
Gujarat (INDIA) Ahmedabad-380027.
Phone : (091) – 79 – 25391811 Email- [email protected]
Website : www.egovamc.com
SUMMARY OF COST FOR DETAIL PROJECT REPORT
1 Augmentation of Under Ground Sump No 5
2 Mechanical Work
3 Eletrical Work
4 Instrumentation Work
5 Tools & Test Equipment & Office Furniture
6 5 Years O & M Works
TOTAL ESTIMATED AMOUNT RS
ADD (+/-) ABOVE OR BELOW Percentage %
7 TOTAL AMOUNT OF AFTER (ABOVE OR BELOW) RS (A)
7 TOTAL AMOUNT OF AFTER (ABOVE OR BELOW) RS (A)
8 Total Buyback Amount (B) To be Quoted Online
TOTAL AMOUNT OF TENDER RS (A-B) RS
TOTAL AMOUNT OF TENDER RS (A-B) RS
1. Bidder has to quote % Above (Premium) or % Below (Discount) or As per of total Job, Rs.
10,57,49,754.00/- (i.e. Total Estimated Amount Cost w/o buyback value) .
2. Bidder must quote Minimum Rs. 18,40,000/- OR more for buyback items as per Annexure-1 in Scope of
Work, Section- A.3.8 separately online at Sr. 8 as indicated above. Bidder to note that net amount quoted by
the bidder shall be determined by deducting the total amount of buyback quoted by bidder from the amount
the bidder shall be determined by deducting the total amount of buyback quoted by bidder from the amount
quoted for works as above at Sr. No. 7 and the net amount so derived shall be considered for Price
Evaluation purpose to determine lowest bid.
3. Bidder shall quote for buyback items as per Annexure-1 in Scope of Work, Section A-3 online. Bidder to
note that net amount quoted by the bidder shall be determined by deducting the total amount of buyback
note that net amount quoted by the bidder shall be determined by deducting the total amount of buyback
quoted by bidder from the amount quoted for works as above and the net amount so derived shall be
considered for price evaluation purpose to determine lowest bid.
Bidder’s Stamp and Initials
AHMEDABAD MUNICIPAL CORPORATION
AUGMENTATION OF UNDER GROUND TANK NO 5 IN DUDHESHWER WATER
COMPOUND UNDER WATER PROJECT DIVISION
Description Rate
Item Unit Without
Quantity Amount
1 Demolition of Brick work & stone 75.00 Cmt 544.95
masonry including stacking of serviceable
materials and disposal of unserviceable
materials with all lead and lift. (i) In
2 Demolition and disposal of unserviceable 160.00 Cmt 603.23
materials with all lead and lift.(i)
Unreinforced cement concrete
3 Demolition and disposal of stacking of 290.00 Cmt 1,047.38
serviceable materials and disposal of
unserviceable materials with all lead and
4 Supplying Electric breakar machine for 10.00 Shift 1,071.43
RCC slab or Asphalt demolishing work on
site by using operator, fuel, power supply
etc. complete as directed.(no payment
should be allowed for non working
condition of machinary and for pipeline
excavation and M.H. work.allowed only
for break down work)
5 Excavation for foundation for loose and -
soft soil including sorting out and stacking
of useful materials and disposing of the
excavated stuff up to 50 meter lead.
c) From 3 to 5.0 m. 65.00 cmt 141.11
6 Extra over item no. 2 above for lead from 1,760.00 cmt 408.41
50 m to 5 Kms. as directed.
7 Extra over item no. 2 above for lead from 440.00 cmt 454.71
5 Kms. to 10 Kms. as directed.
8 Filling with available excavated earth 660.00 cmt 129.10
(excluding rock) in trenches, plinth, sides
of foundation in layers not exceeding
cm in depth consolidating each deposited
layer by ramming and watering.
9 Extra rate over item of excavation of earth 500.00 cmt 17.86
if excavation is to be done in wet.
condition without resorting to pumping but
incl. of bailing out of water. (Based on
Previously approved rate by C E sir )
10 Providing and casting in situ C.C. in grade 195.00 cmt 4,732.00
M-15 (approx. corresp. to prop. 1:2:4)
(proportions as per mix design or as per
Table 9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap
metal of size 6 mm to 20 mm for RCC
work, including scaffolding centering,
form work, needle vibrated
consolidation, curing comp. (excluding
cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering
etc. comp. for structure for other than
water retaining. Footing (without form
11 Providing and casting in situ C.C. in grade 20.00 cmt 4,906.00
M-15 (approx. corresp. to prop. 1:2:4)
(proportions as per mix design or as per
Table 9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap
metal of size 6 mm to 20 mm for RCC
work, including scaffolding centering,
form work, needle vibrated
consolidation, curing comp. (excluding
cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering
etc. comp. for structure for other than
water retaining. Footing (with form work)
12 Providing and cast in situ C.C. in grade M- -
30 proportions of ingredients as per mix
design by weigh batching using granite,
quartzite trap metal of size 12 mm to
mm and or 6 mm to 12 mm including
scaffolding centering formwork, needle
vibrated consolidation, curing and
hydraulic testing etc. complete (excluding
cost of reinforcement) with centering and
shuttering/deshuttering etc. camp. up to
meter height /depth Av. G.L.for all water
retaining structures
a) R.C.C. Raft and footings with shuttering 495.00 cmt 8,213.00
b) R.C.C. walls 355.00 cmt 8,083.00
c) R.C.C. Beams & staircase 120.00 cmt 8,486.00
d) Columns 70.00 cmt 9,317.00
e) Top Slab of Sump 195.00 cmt 8,213.00
13 Providing and cast in situ C.C. in grade M- -
25 proportions of ingredients as per mix
design by weigh batching using granite,
quartzite trap metal of size 12 mm to
mm and or 6 mm to 12 mm including
scaffolding centering formwork, needle
vibrated consolidation, curing and hydrulic
testing etc. complete (excluding cost of
reinforcement) with centering &
shuttering/ deshuttering etc. for all water
retaining structures.
a) R.C.C. footings & Raft with shuttering 35.00 cmt 8,077.00
b) R.C.C. Verticle Wall 5.00 cmt 7,936.00
c) R.C.C. Columns 55.00 cmt 9,195.00
d) R.C.C. beams, lintels and bracket for 135.00 cmt 8,347.00
gantry or chain pully blocks, plinth beams,
tie beams, weather shed, staircase etc.
e) R.C.C. slabs and platform 145.00 cmt 8,077.00
14 Providing and cast in situ C.C. in grade M- -
20 ( proportions as per mix design or as
per table of IS456 2000 in masses by
weigh batching) using granite, quartzite
trap metal of size 6 mm to 20 mm for RCC
Work including scaffolding centering
formwork, needle vibrated consolidation,
curing complete up to 6 meter depth or
height (excluding cost of reinforcement
and neat finishing) with centering and
shuttering/ deshuttering etc. complete for
structure other than water
retaining.(Without W.P. Chemical)
a) R.C.C. footings & Raft 110.00 cmt 5,520.00
b) R.C.C. Verticle Wall 10.00 cmt 6,779.00
c) R.C.C. Columns 14.40 cmt 7,363.00
d) R.C.C. beams, lintels and bracket for 9.00 cmt 6,722.00
gantry or chain pully blocks, plinth beams,
tie beams, weather shed etc.
e) R.C.C. slabs and platform 10.00 cmt 6,504.00
15 Supply cutting, Bending, Binding and 176.50 MT 77,504.00
placing in position steel as per plan and
design and as per ISS 2502 including cost
of steel and binding wire for reservoirs/
structures only including lift up to 6 meter
height or depth below G.L. for all
Deformed(TMT)bars confirming to
relevant IS Fe-500 grade for all diameters.
16 Extra Over Rate Item No 11 for TMT 35.00 MT 1,073.00
FE500 replaced over CRS TMT FE 500 in
UG Sump Slab and Beam
17 Brick work using common burnt clay 25.00 cmt 4,011.66
building bricks having crushing strength
not less than 35kg / Sq. C. M. in ramp,
steps and Foundation & Plinth in cement
morter1:5 (1 cement : 5 coarse sand)
including racking out joints, curing,
scaffolding required if any etc. complete,
as directed. (B) Conventional
18 Brick masonry in cement mortar (1:5) 290.00 cmt 4,091.84
using common burnt clay building bricks
having crushing strength not less than
35kg/csmt including scaffolding,curing,
etc. complete for walls, parapets, etc. at all
19 Providing Half brick masonry in common 50.00 cmt 593.90
burnt clay building bricks having crushing
strength not less than 35 Kg/csmt in C. M.
1:4 for partition work including raking out
joints, curing, scaffolding etc. complete as
directed for any height.
20 Interior plain faced 15 mm thick cement 1,580.00 smt 295.90
plaster (1:3) with floating coat of neat
cement slurry on Underneath Ceiling of
top of UG tank where specified on
drawings at all levels including
scaffolding, curing, etc. complete. This
rate shall include moulding where
specified. The rate shall include 2%
approved quality water proofing
compound (by weight) of cement.
21 Providing and applying 20 mm thick 1,915.00 smt 202.00
inside cement plaster with water proofing
agent on inside of sump consisting of
mm thick backing coat of CM 1:2 (1
cement : 2 sand) and 8 mm thick finishing
coat of CM 1:1 (1 cement : 1 sand) etc.
complete including necessary curing,
scaffolding required if any etc. complete.
22 Providing and applying 15 mm thick 2,600.00 Smt 222.56
cement plaster in single coat on brick work
with floating coat of net cement slurry for
interior plastering of pumphouse and
outside plastering of sump upto finished
even and smooth in Cement motar 1 : 3 (1
cement : 3 sand) including racking out
joint curing, scaffolding required if any,
with necessary cement finishing etc.
complete as directed.
23 20 mm thick sand faced cement plaster on 1,690.00 Smt 297.68
walls upto height 10 metres above ground
level consisting of 12mm thick backing
coat of C.M. 1:3 (1-cement : 3-sand) and
mm thick finishing coat of C.M. 1:1 (1-
cement : 1 sand) etc. complete. (including
around Pump house)
24 White washing with lime on wall surfaces 100.00 Smt 12.29
(two coats) to give an even shade
including thoroughly booming the surface
to remove all dirt, dust, mortar drops and
other foreign matter etc. complete.
25 Extra over above item for every subseqent 50.00 Smt 5.67
coat of white washing with lime on wall
26 Finishing wall with weather proof exterior 1,690.00 Smt 113.40
emulsion paint on wall surface (two coats)
to give an required shape even shade after
thoroughly brushing the surface to removal
dirt, and remains of loose powdered
materials.etc complete
27 Distempering (two coats) with oil bound 1,775.00 Smt 76.08
distemper of approved brand and
manufacture and of required shade on
undecorated wall surface to give an even
shade, over and including a priming coat
with distemper primer of approved brand
and manufacturer after thoroughly
brushing the surface free from mortar
dropping and other foreign matter also
including preparing the surface even and
sand papered smooth.
28 Applying two coats of Birla(white cement 1,775.00 Smt 40.19
based) or Asian (acryliclapy putty) or
equivalent & two coats of primer of
approved brand and manufacture on new
wall surface to give an even shade
including thoroughly brushing the surface
free from mortar dropping and other
foreign matte rand sand papered smooth.
29 Paint on soffit of tank roof slab with 2 1,740.00 smt 143.00
coats of bituminous paint including
cleaning the surface by scrapping and air
blowers as directed by engineer in-charge.
30 Providing and laying one layer of bitumen 1,025.00 smt 17.00
kraft paper conforming to IS : 1398 of
approved make and quality.
31 Providing 100 mm x 100 mm size vata in 380.00 Rmt 23.45
cement mortar (1:1) including smooth
finish, curing, etc. complete.
32 Providing 100 mm x 100 mm size vata in 230.00 Rmt 44.00
cement concrete (1:2:4) including water
proofing compounds, smooth finish,
curing, etc. complete for the internal side
of the sump, pump house
33 Providing and laying cement concrete -
flooring 1:2:4 (1 cement : 2 coarse sand :
graded stone aggregate 20 mm nominal
size) including water proofing compound
finishing with a floating of neat cement
slurry etc. complete laid in one layer
finished including necessary curing at
bottom of sump.
Average 50 mm thick 1,675.00 smt 348.08
34 Providing and laying Trimix with 1,130.00 smt 48.21
dewatering machine and floater machine
on constructed RCC work including cost
of machine and labour etc. compact
35 Providing and laying polished Kota stone 590.00 smt 1,085.48
slab flooring over 20 mm (average) thick
base of cement mortar 1:6 (1 cement :
coarse sand) laid over and jointed with
grey cement slurry including rubbing and
polishing etc. complete at LT & HT,
office room & Chlorine room. 30 mm
36 Providing and laying polished Kota stone 25.00 smt 1,176.03
slab 25 mm thick in riser of steps, skirting
Dedo & pillars laid on 10 mm thick
cement mortar 1:3 (1 cement : 3 coarse
sand) and jointed with grey cement slurry
including rubbing and polishing etc.
37 Kota stone in Jams and Sills of the 60.00 smt 1,107.00
window and ventilation and Door with one
molding as directed by Engineer-in-
38 Providing and fixing window having 55.00 smt 1,568.27
extruded aluminum Colour anodized
section frame main outer size 95mm x
24mm x 1.17 mm (of Jindal Section no :
2459 @ wt. of 0.738 Kg/mt), horizontal
Three track member size 92mm x
mm x 1.30 mm (of Jindal Section no.
8688, @ Wt. 1.07 Kg/mt), vertical member
of size 92mm x 31.75mm x 1.50 mm (of
Jindal Section no. 8933, @ Wt.
Kg/mt.) with sliding shutters of horizontal
member size 40mm x 18mm x .29 mm (of
Jindal section no. 8947 @ wt.
Kg/mt.) vertical member of size 40mm x
18mm x 1.29mm (of Jindal Section no.
8949 @ wt. of 0.456 Kg/mt with 5 mm
thick transparent bronze colour tinted float
glass with powder coated aluminum
fittings and fixtures and transparent silicon
sealant glass fixing to frame as per details
39 Providing and fixing standared extruded of 23.00 smt 1,163.92
alluminimum section of size 63mm x
38.10mm x 1.2mm (Jindal Section :
@ Wt. 0.643 Kg/mt.) with colour powder
coated alluminium frame for ventilation
with 5 mm thick frosted glass as details etc
complete for Ventilation
40 Providing & fixing in position aluminium 55.00 smt 1,750.00
grill with 15 micron natural matt brush
finish anodised as per over all size shown
on the drawings and aluminium sections of
approved make conforming to IS:733 and
IS : 1285, made out of DG - 104 design (
Jindal or equivivelent ) fixed with required
size F channel, rawl plugs and screws or
with fixing clips, or with expansion hold
esters including necessary filling up of
gaps at junctions, at top, bottom and sides
with required PVC/neoprene felt etc. and
aluminium snap beading for glazing /
panelling, C. P.brass/stainless steel screws,
including standard anodised aluminium
fittings and fixtures of approved make and
of adequate size and in adequate numbers,
including cost and fixing of fixtures etc.
complete as per detailed drawings with all
lead and lifts.
41 Providing precast cement concrete jali or 15.00 smt 640.20
louvers 40 mm thick 1:2:4 mix (1 cement :
2 coarse sand : 4 graded stone aggregate
mm nominal size) reinforced with 1.6 mm
dia. Mild steel wire including roughening,
cleaning, fixing and finishing in CM 1:3
and curing, painting complete
42 Supplying, fixing Push and Pull, 20 gauge 20.00 smt 4,277.00
rolling shutter of approved make for the
sizes indicated on drawings including hood
cover, channel sliding assembly, helical
coil springs, brackets, interlocking latches,
locking arrangements, painting with
coats of enamel paint over one coat of
approved primer paint etc. complete.
Shutters having width below 3.5M (gear
43 Grouting with 1:3 cement, sand mortar for 60.00 cmt 4,536.00
anchor bolt pockets, machine bases, pipe
sleeves, pockets holes, etc. including
roughening and cleaning of concrete
surfaces, curing, etc. complete.
44 Drilling holes for grouting -
Drilling 40 mm Dia. Holes in 30.00 Rmt 458.04
masonry/concrete structures with
providing and fixing 500 mm long GI
Pipeline for pressure grouting including
supply of material, machineries and labour
cost etc. complete.
45 Supplying, cleaning, cutting, bending, 7,200.00 kg 82.50
welding, fabricating, erecting, structural
steel in position irrespictive of location
and levels as per drawings including
handling and transport, etc. complete
including applying two (2) coats of primer
red oxide and two (2) coats of approved
46 Providing and fixing precast reinforced 5.00 cmt 6,504.00
cement concrete trench covers, hatch
covers, etc. of Class M-20 with 20 mm
downgraded coarse aggregate excluding
reinforcement but including shuttering,
vibrating, curing, all handling, transporting
47 Providing and fixing in position 150 mm 20.00 No. 2,576.00
diameter and 610 mm heigh CI air
ventilators including fixing of jali grating
and cover and painting the same. (wt.
48 Providing & Fixing F.R.C. MH seat cover 20.00 No. 1,633.93
incl. carting to the work site etc. comp.
Directed. (Based on rate of central store)
FRC medium duty Chamber seat cover
(FRC) cover 706 x 556 x 50 mm
rectangular cover frame size 600 x
mm clear opening outer size 816 x 666 x
100 mm (MD-10) cover for dewatering
49 Providing and fixing in position 6.0 m 1.00 No. 10,627.00
high aluminium water level indicator
made of 230 mm width and 4 mm thick
aluminium sheet fixed on angle 50 X 50 X
6 mm frame and bracing and fixing in
concrete base as per specification or as
directed by Engineer-in-Charge
50 Providing and fixing 50 mm dia and 300 115.00 No. 40.00
mm long PVC pipe/spout in RCC beams
of U.G. Tank roof slab and RCC
peripheral wall on slab top. Rate shall
include carting/cutting in required size and
shape etc. complete as directed.
51 Providing and fixing 40mm dia. GI pipe 50.00 Rmt 1,397.00
medium weight quality as openable type
with angle iron support at 1.5 m c/c using
75 x 75 x 10 mm angles, 1 m long with
three rows of pipes as railing including
necessary painting with two coats of
approved quality oil paint over one coat of
approved primer including necessary
welding, bolting required, if any.
52 Painting two coats including priming coat 100.00 Sq.M. 121.28
on new steel & other metal surfaces with
enamel paint, brushing, interior to give an
even shade including cleaning the surface
of all dirt, dust, other foreign matter.
53 Providing,Supplying and fixing ISI mark -
G.I pipes with coupling of following class
and diameter including all taxes,
insurance, transportation, freight charges,
octroi, inspection charges,
loading,unloading, conveyance to
departmental stores, stacking etc. complete
(IS:1239) Medium Duty.
a) 25 mm dia GI pipe sleeves 5.00 Rmt 193.00
b) 32 mm dia GI pipe sleeves 5.00 Rmt 249.00
c) 50 mm dia GI pipe sleeves 5.00 Rmt 387.00
d) 80 mm dia GI pipe sleeves 5.00 Rmt 625.00
e) 100 mm dia GI pipe sleeves 5.00 Rmt 898.00
54 Providing and fixing PVC pipe of 25.00 Rmt 349.00
6Kg./csmt of 140 mm dia for rain water
55 Providing, Fabricating & fixing WDS 1.00 No. 15,640.00
name board of Size 3.00mX0.60 made
from ISA 50X50X5 mm M.S angle with
Nos supports at back side vertical member
of angle size 1.1m ht incl 0.3 m hold fast
inserted in compound wall with necessary
dismantling and fixing with cement
concrete. The rate shall also incl 16 g M.S
sheet of size 3.00X0.60 mt incl ACP Sheet
with Printing letter with AMC logo as
directed by EIC. rate shall incl painting
board with 2 coat of enamal paint over one
coat of anti-corrosive primer.
56 Providing, Fabricating & fixing caution 1.00 No. 7,900.00
board of size 1.50m x 0.60m made from
ISA 40 x 40 x 5 mm MS angle with 2 nos.
supports at back side vertical member of of
angle size 1.10m height (inclu. 0.30m hold
fast inserted in compound wall with
necessary dis-mantling and fixing with
cement concrete. The rate shall also
include 14g MS sheet of size 1.50mt x
0.60mt incl ACP Sheet with Printing letter
with logo as directed by EIC. rate shall
incl painting board with 2 coat of enamal
paint over one coat of anti-corrosive
57 Providing and fixing Radium sign board of 1.00 Nos. 7,400.00
size 3.00mt x 0.60 mt made from ACP
sheet with writing coloured reflected letter
of WDS name board with necessary clamp
for hanging board at pump house etc.
comp as directed by EIC
58 Providing throating or plaster drip and 320.00 Rmt 41.25
moulding as instructed by Engineer in
59 Providing and laying chequered precast 20.00 smt 522.78
concrete tiles 22 mm thick with
aggregates of size up to 6 mm in treads of
steps and landing of sump of 20 mm thick
bed of cement mortar 1:6 with neat
cement slurry with pigment to match the
shade of tiles.
Providing and fixing of self supported 540.00 Smt 2,150.00
roofing system with proper overlapping
and seaming b/w different sheets without
making holes preventing the overturning
the roof by wind addition made of from
superior quality, structural grade steel
base metal width 912 mm steel grade:
Grade D and thickness 1.30 mm BMT,
1.35 mm TCT with tolerance of +/-
0.04mm , colour coated Galvalume steel
only. Design, supply & fabrication of self
supported single span arch roof fabricated
from mechanically seamed manufactured
by imported machines to profiles of colour
coated Galvalume Cold Rolled Structural
Steel coils as per standard ASTM A792 M,
XMA3402, Coating-AZM-150 Tata
Bluescope Steel Limited India with
Reverse Branding every 1 meter along the
length with SDP coating. The rate of item
is including fitting as per standard
specification and details drawing &
directed by Engineer in Charge.
61 Providing & fixing in position 40 mm dia. 2.00 Nos. 6,364.00
UGWTS valve controlling MS rod (5.5
mtr) of for operation of valve including T-
shape rod at Top 0.60 mt. length fix at rod
centre and extra top at bottom including
coats of bituminous paint and making
holes etc. completed with 1 mt. Above
finish slab level of tank.
62 Providing and laying broken China Mosaic 100.00 Smt 739.89
flooring for terrace using 12 mm to 20 mm
broken pieces of glazed tiles to be laid
over Cement mortar 1:3 to plain or slope
and to be tempered to bring mortar crème
out upto surface using white cement
including rounding of junctions and
extending them upto 15 cm. along the
wall, clearing with water and oxalic acid
etc. as directed.
63 Manufacture,Supply & Delivery of Ductile -
Iron Flange socket spigot
bends,tees,reducers,or any other specials
ass per BS-EN-545/1995 Class-Aseries
K12 Suitable for use with DI pipes
manufactured as per IS:8392/1994
delivery of specials is to be made to Store
or site of works anywhere in gujarat
including all taxes, loading,unloading
,carting,stacking, insurance , inspection
charges,octroi etc. complete.Bends (Both
side Flange ended)
(b) 350 mm. dia.& Above Pipe 1,000.00 kg 158.00
64 (1) Puddle pipe with flanges at both -
(2) Puddle pipe with one End flanges -
65 (I) Ring flanges -
(b) Above 300 mm dia. 500.00 Kg 158.00
(II) Blank Flanges -
(b) Above 300 mm dia. 500.00 Kg 158.00
66 providing and Fixing PVC coated Step in 10.00 Nos 66.96
Chamber as directed by Engineer in
67 Providing & Supplying JCB Machine on 10.00 Hr 535.71
rental basis in case of emergency situation
and break down type work & also during
unavoidable condition as per instruction of
engg.incharge , rate includes all nece.
shifting, fuel and operating charges and
stacking of useful & non-useful materials
separately up to store. (No payment should
be allowed for non working condition of
machinery and for pipe line excavation
and laying work) ( Based on Previously
approved rate by C E sir )
68 Providing the site grading to the site by 98.00 smt 2.50
excavation / earth fill as per lines and
levels and grading the finished ground
level with surplus imported earthfill in dry
condition, as directed by the engineer-
incharge etc complete.
69 Providing & laying rubble below raft 240.00 cmt 1,250.00
foundation including carting to the work
site , rimming consolidating & dressing
etc, Complate as per Engineer in-charge
70 Making hole of following dia pipe in RCC. -
Rate includes electrical hand operated
braker set, Gas cutting set with all
required equipment & removing debris etc.
71 Making 15 mm groove in RCC work on 500.00 Rmt 26.79
road and finished it good incl. all labour
charges etc comp as directed.
72 Constructing Bombay Pattern Type Catch 10.00 Nos 3,125.00
Pit of size 0.60 x 0.60 depth up to 1 mt
including excavation, B.B.C.C. (1:5:10),
23 cms thick brick maso. wall in the prop.
of CM (1:6) with 40 mm thick IPS
flooring in the prop M15 at bottom and
mm thick cement plaster inside the catch
pit in the proportion of CM (1:3) with out
jali etc. comp. as directed. (As per R.A.
Based on Building SOR 2015-16)
73 CatchPit Jali Fixing P/F FRC catch pit jali 10.00 Nos 1,383.93
with frame 600mm x 600mm clear
opening etc. comp.. As directed by
engineer in charge. (Based on Central
74 Constructing Slab type M.H. Chamber of 5.00 Nos 10,177.68
the following size including excavation,
refilling, brick bats cement concrete
(1:5:10) of thickness 15 C.M., CC Channel
(1:2:4) of thickness 10 C.M., finished
mm thick cement plaster 12 14 inside &
outside (Only for shaft) in CM 1:3,
finishing with cement slurry, P/F 4 mm dia
M.S.Steel HDPE coated steps 35 cm c/c at
35 cm staggered in masonary CM 1:5,
RCC Slab in CC 1:1.5:3 of thickness
C.M., including Cantering &
reinforcement (double jalli at 15 C.M. c/c
bothway 12 mm dia.) but excluding the
cost of Manhole seat cover etc..completed.
of Size 1.00 X 1.40 meter (Inside
Clear,M.H. length should be parallel to the
flow, for pipe dia <= 800 mm) (Based on
Drainage SOR 2009-10)1.00 to 2.00 meter
depth, (Slab at Ground level) for
Rainwater Collection Chamber
75 Constructing Chamber of following size 5.00 Nos 2,261.61
including excavation, refilling, BBCC
(1:5:10) for foundation, C.C.Channel
(1:2:4), finished 15 mm thick cement
plaster inside in CM 1:3, finishing with
cement slurry, Brick masonary in CM 1:5
& excluding the cost of chamber seat
cover etc..completed. (Based on Drainage
SOR 2009-10) 0.60 X 0.45 mt. size Inside
Clear, Depth from 0.0 to 0.90meter for
pipe dia <=150 mm. chamber for
76 Providing & Fixing F.R.C. MH seat cover 5.00 Nos 1,633.93
incl. carting to the work site etc. comp.
Directed. (Based on rate of central store)
FRC medium duty Chamber seat cover
(FRC) cover 706 x 556 x 50 mm
rectangular cover frame size 600 x
mm clear opening outer size 816 x 666 x
100 mm (MD-10) cover for dewatering
77 Providing F.R.C. MH seat cover incl. 5.00 Nos 2,125.00
carting to the work site etc. comp.
Directed. (Based on rate of central store)
F.R.C. Extra Heavy Duty (EHD-35)
Manhole Covers & Frames Cover :
728mm ø & 100 mm thick circular cover,
35.00 MT load design, 100x2mm MS flat
allround, 16mm ø plain round bar for
lifting the cover & should be fitted with
plastic cups. Frame : 560 mm ø clear
opening, outer size- 888x888x175 mm. On
the upper periphery of frame 25 x 3 mm
wide MS flat should be well embed in
concrete to protect the edges of frame.
FRC E.H.D.-35 manhole cover & frame
described as above
78 Making connection to the ex.M.H.in 3.00 Nos 1,339.29
running sewer incl. Dewatering and other
required machinery etc. of following dia
pipes at any convenient time. All damaged
work shall be well repaired as per
instructions. etc..complete. (Based on
Drainage SOR 2009-10)
a) 150 mm to 300 mm dia.
connection for dewatering
79 Manufacturing, supplying, loading, -
unloading to work site, lowering trenches,
laying and jointing RCC pipes following
class with Socket and spigot joints as per
IS 458-2003 including EPDM Rubber ring
as per IS 5382-1985 etc. Comp.As
Directed by Engineer in charge RCC NP3
Supplying and fixing of 300 mm-L x 150 130.00 Rmt 350.89
80 mm-B x 380 mm-Kerb block for Footpath
in M-20 grade using 20 mm nominal size
black trap aggregate of Sevaliya/Timba or
equivalent quality for pre-cast blocks,
reasonably exposed finish/ formwork
mould with well equipped with vibratory
system for kerb stones of approved design
including curing, etc. complete, including
the cost of formwork etc. complete. The
rate shall also include necessary cutting of
asphalt, fixing the Kerb stones in line and
level on 5 cm thick sand bedding with
necessary equipments and materials. The
rate shall also include the flush pointing in
CM (1:3) for all joints of the kerbstones.
Filling of zari alone the sides of the kerb
stone fixed with Bituminous concrete
Bituminous concrete / C.C. mixed in
proper position to flush with the road
surface as directed by Engineer in change
to form a portable mixture.
81 Filling in plinth with sand under floors 50.00 Cmt 455.63
incuding watering, ramming, consolidation
and dressing complete
82 Providing and Laying of Rubber Moulded 350.00 smt 383.04
Paver Block Grey/Coloured 60 mm thick,
M-35 Grade of any size ; shape (Usually
Uni-Paver Blocks) using black trap good
quality aggregate of 20 mm nominal size
for footpath, parking areas, service lanes
and other areas as mentioned in the
drawing / instruction of engineer in charge.
Cost includes formworks using rubber
mould, Rate providing and laying paver
blocks as per required grading and
specification. The paver block shall be
mechanically compacted. The work of
paving blocks shall be executed in line and
level by skill mason of flooring work only.
It should be laid in such a way that the no
cutting of the paver block to be necessary.
If cutting of paver block necessary then it
should be cut by machine only and carting.
The finished surface of the paver block
shall have reasonably good, plain finished.
Paver blocks shall be compacted and shall
be relaid if necessary. Gravel or such type
of materials shall not be allowed for
production. Laying on 5 cms thick sand
bedding. and Laying of Rubber Moulded
Paver Block Grey/Coloured 60 mm thick,
M-35 Grade of any size ; shape (Usually
Uni-Paver Blocks) using black trap good
quality aggregate of 20 mm nominal size
for footpath, parking areas, service lanes
and other areas as mentioned in the
drawing / instruction of engineer in charge.
Cost includes formworks using rubber
mould, Rate providing and laying paver
blocks as per required grading and
specification. The paver block shall be
mechanically compacted. The work of
paving blocks shall be executed in line and
level by skill mason of flooring work only.
It should be laid in such a way that the no
cutting of the paver block to be necessary.
If cutting of paver block necessary then it
should be cut by machine only and carting.
The finished surface of the paver block
shall have reasonably good, plain finished.
Paver blocks shall be compacted and shall
be relaid if necessary. Gravel or such type
of materials shall not be allowed for
production. Laying on 5 cms thick sand
83 Writing letter or figures on any surface 10.00 Per 3.15
with black japan paint (stops, comas, Letter
hyphens and the like not to be measured Per
and paid for separately) (i) Block Cm/Ht
(Letters/Figures) (Per 10 Letter pet
84 Providing in line level plumb, fabricating 35.00 Rmt. 449.00
and fixing three row horizontal barbed
wire fencing and punched tape concertina
coil of 9 turns per meter of 610 mm
diameter fixied with clips on top of the
angle iron posts. The punched tape
concertina coil having sharp barbs at every
25 mm spacing shall be 0.5 mm thick and
19 mm width and weighting 13 Kg./100
mtr. (Average) as per manufacture's
specification. The rate shall also include
providing and fixed 1.20 mt. total long MS
angle 40 x 40 x 6 mm @ 3.00 mt. c/c
spacing embedded in RCC column, angle
posts shall be painted with one coats of red
oxide and two coats of enamel paint of
approved quality at top of compound wall.
85 Labour charges for writing of Capital letter 1.00 No 381.00
"AMC" in green plaster of 30 cm height,
5 mm thick and 12 mm embossed as per
given detail in outside of compound wall
as instructed by engineer in charge.
86 Transporting from AMC store and laying -
spigot and socket New DI pipe line DI-K-9
pipe of various classes with CI/DI/MS
specials of following diameters. Rate
includes excavation up to minimum
mt. depth from top of pipe/as per
requirement in any soil, refilling after
laying pipe, covering and temptation of
carting surplus earth up to 30 mt. lead and
watering and compaction. Clearing the
site. All Joint shall be made tight & leak
a) 150 mm dia 5.00 Rmt. 77.68
b) 200 mm dia 5.00 Rmt. 93.75
c) 250 mm dia 5.00 Rmt. 113.39
d) 300 mm dia 5.00 Rmt. 136.61
e) 350 mm dia 5.00 Rmt. 185.71
f) 400 mm dia 5.00 Rmt. 207.14
h) 600 mm Dia 5.00 Rmt. 384.82
i) 900 mm Dia 5.00 Rmt. 675.00
87 Only removing & recover of existing -
CI/DI pipe lines & specials , removing any
type of joint, carting it to the Muni. Store
as & where directed as per instruction of
Engg. In charefge with excavation &
a) 100 mm Dia 5.00 Rmt. 64.29
b) 150 mm Dia 5.00 Rmt. 77.68
c) 200 mm Dia. 5.00 Rmt. 93.75
88 Removing & relaying of existing CI/DI -
pipe line & Specials, Cleaning of Pipe &
Specials from inside , inclding excavation
refilig etc. Comp. in the line & level with
any type of joint as per instruction of engg.
a) 100 mm Dia 5.00 Rmt. 64.29
b) 150 mm Dia 5.00 Rmt. 77.68
c) 200 mm Dia. 5.00 Rmt. 93.75
89 Labour charges for installing and jointing -
Sluice valve/Scour Valve including
loading, transporting from AMC's
store,lowering in location to the required
with excavation refilling alignment by
crane/tripod and chain block including cost
of total nos. of nuts, bolts, Necessary
gaskets and excluding fixing of tail pieces
with lead & jute etc complete as directed
by Engg. In charge.
90 Providing & supplying ISI mark DI D/F -
Sluice valves as per IS:14846 (Latest
edition) of following class and dia
including all taxes, insurance,
transportation, freight charges, octroi,
inspection charges, loading, unloading,
conveyance to departmental stores,
stacking etc. complete.
(A) PN 1.0 hand wheel operated -
91 Lowering, Laying, Jointing in position -
following C.I /DI- D/F Reflux valve,
Butterfly valves, Sluice Valve and air
valves including cost of all labour, jointing
material, including nut bolts and giving
satisfactory hydraulic testing, etc.
92 Labour charges for removing and recover -
of ex. C.I. Sluice valve with tail pieces and
carting it up to muni. Store or site as per
instruction of Engg. In charge item include
necessary Excavation , removing or
making joints, refilling etc. comp. as
directed by Engg. in charge.
93 Providing and supplying CI/DI Tamper -
proof /Bi Stream Air valves with SS
Float gun metal nozzle of approved make
& quality of following class and diameter
including all taxes, transportation, freight
charges, octroi, inspection charges,
loading, unloading, conveyance to the
departmental stores, stacking etc.
complete. With Isolating Sluice Valve PN
94 Lowering, laying & jointing in position -
following air Valves including cost of all
labour, jointing material, including nut
bolts & giving satisfactory hydraulic
testing, etc. complete. With Isolating
Sluice Valve PN
95 Labour charges for collecting specials 500.00 Kg 21.43
from Municipals store loading,
transportation, unloading to the sie, laying
and fixing CI specials inclusive of all
jointing materials like lead, spun etc. and
labour, excavation re-filling and nece.
Dewatering as per instruction of engg.
96 Manufacture, Supply,Delivery & Fixing of -
Ductile Iron Socket Spigot Bends, tees,
reducers or any other specials as per BS-
EN-545/1995 Class-A series K12 suitable
for use with D.I Pipes manufactured as per
IS:8329/1994 delivery of specials is to be
made to GWSSB store or site of works any
where in Gujarat including fixing, all
taxes, loading, unloading, carting,
stacking,insurance, inspection charges,
octroi etc. complete.
a) For 100 to 300 mm dia 100.00 Kg 148.00
b) Above 300 mm dia 500.00 Kg 151.00
97 Construction of chambers in brick -
masonary, locally available in C.M. 1 :
foundation concrete 150 mm thick in C.C.
1:4:8 of trap metal size 25 mm to 40 mm
thick, inside cement plaster in C.M. 1:3
and cement pointing outside in C. M. 1 :3
& top cover of precast RCC slab 150 mm
thick upto 1 mt. depth from G.L. but excl.
cost of excavation and refilling. With cast
in situ RCC slab in two piece with fixing
FRC frame and cover etc.
complete(excluding cost of frame & cover
) with 23 mm thick brick masonary wall in
C.M.1:6 For Sluice Valve, Air Valve
0.9 x 0.9 x and 1.0 mt. deep chamber 2.00 No. 7,738.00
For Extra depth 0.50 Rmt. 4,479.00
1.3 m x 0.9 m x 1 m deep chamber 2.00 No. 9,389.00
For Extra depth 1.00 Rmt. 5,282.00
1.3 x 1.3 x and 1.0 mt. deep chamber 2.00 No. 11,351.00
For Extra depth 2.00 Rmt. 6,084.00
98 FRC Manhole Cover Providing F.R.C. 5.00 No 2,125.00
MH seat cover incl. carting to the work
site and fixing etc. comp. as Directed.
F.R.C. Extra Heavy Duty (EHD-35)
Manhole Covers & Frames Cover: 728mm
ø & 100 mm thick circular cover,
35.00MT load design,100 x 2mm MS flat
all round,16mm ø plain round bar for
lifting the cover & should be fitted with
plastic cups. Frame:560mm ø clear
opening, -888 x 888 x 175mm. On the
upper periphery off rame 25x3 mm wide
MS flat should be well embed in concrete
to protect the edges off rame. FRC E.H.D.-
35 manhole cover & frame described as
99 FRC heavy duty cover size 730 mm. & 90 5.00 No 1,080.36
mm thick circular cover 20 M.T. design
load and frame size 560 mm clear opening
size 890 x 890 x 120 mm.
100 Carting and Fixing M.H., Chamber or 5.00 No 750.00
Catchpite Seat and Cover in line and level
to match exisisting road level in C.C. 1:2:4
and finishing smooth, watering and
protecting for 7 days etc. complete as
directed. M.H. seat cover will be supplied
byA.M.C.(from any store)
101 Extra rate over item of excavation of earth -
for excavation of asphalt pavement/RCC
of following thickness including
demolishing the asphalt carpet, metal,
soiling/cutting Reinforcement etc. comp.
with stacking the material as directed.
a) up to 0.20 meter thickness (By Manual) 100.00 Smt 71.43
b) up to 0.30 mt (by any type of Breaker 50.00 Smt 178.57
Machine or R.C.C Cutter machine
including cost of operator, fuel &
transportation etc complete.
c) 0.30 mt & above (by any type of Breaker 50.00 Smt 312.50
Machine or R.C.C Cutter machine
including cost of operater, fuel &
transportation etc complete.)
102 Reinstatement of asphalt road/pavement 200.00 Smt 231.47
using same material for soling and new
metalling grouting with tack coat etc
complete as directed.
103 Cutting of existing pipelines of following -
diameters including carting of nece.
specials from AMC store to site and from
site to AMC store (recovered materials)
nace. labours for excavation, jodan &
backfilling fitter, supervisor, etc. complete.
Rate also includes electric cutter,
dewatering pump fuel and transportation
of machineries, chain pulley block if
requires working at an instructed specific
time of day or night etc. complete.
a) 100 (CI/DI) mm dia. 2.00 No 1,446.43
b) 150 (CI/DI) mm dia. 2.00 No 1,464.29
c) 200 (CI/DI) mm dia. 2.00 No 2,455.36
d) 250 (CI/DI) mm dia. 2.00 No 3,169.64
e) 300 (CI/DI) mm dia. 2.00 No 5,142.86
f) 350 (CI/DI) mm dia. 2.00 No 5,544.64
g) 400 (CI/DI) mm dia. 1.00 No 6,598.21
h) 450 (CI/DI) mm dia. 1.00 No 10,187.50
i) 500 (CI/DI) mm dia. 1.00 No 11,580.36
j) 600 (CI/DI) mm dia. 1.00 No 14,285.71
k) 700 (CI/DI) mm dia. 1.00 No 19,214.29
104 Manufacture, Supply & Delivery, Laying -
of Electric Resistance Welded (Up to
400mm)/ Submerged Arc Welded(Above
400mm) M.S.Pipe having beveled ends
plate or coil conforming to IS-3589-2001
or its latest revision/ ammendment for
following thickness outside diameter at
GWSSB store or site anywhere in Gujarat
State including all taxes, insurance,
transportation, freight charges, octroi,
inspection charges, loading, unloading
conveyance to Departmental stores,
stacking etc. all complete.
a) upto 914mm OD & 10mm Thickness of 1,200.00 Kg 70.67
b) Above 914mm OD & Above 10mm 3,585.00 Kg 71.17
Thickness of Plate/Pipe
105 Manufacture, Supply & Delivery of 80.00 Rmt 23,028.00
Electric Resistance Welded (Up to
400mm)/Submerged Arc Welded(Above
400mm) M.S.Pipe having beveled ends
plate or coil conforming to IS-3589-2001
or its latest revision/ ammendment for
following thickness outside diameter at
GWSSB store or site anywhere in Gujarat
State including all taxes, insurance,
transportation, freight charges, octroi,
inspection charges, loading, unloading
conveyance to Departmental stores,
stacking etc. all complete.
I/S epoxy Painting (100 Micron) & O/S
Gunniting (25 mm Thick)
1219 MM Dia OD & Thikness 10 mm
106 Lowering, Laying & Welding in position 80.00 Rmt 1,088.00
to correct line & Level M.S. Pipe with
outer gunniting & inside lining/Epoxy
painting on padestal or chairs upon
prepared formation or prepared bedding in
trenches the rates include conveyance from
store to site of work
loading,unloading,joint
plastrering,hydrotesting etc compelte
above 7 mm thick
107 Providing 406 Micron epoxy coating to 325.00 Smt 332.00
inside pipe line Providing epoxy coating
to inside pipe line with two parts of
Solvent free high build liquid epoxy lining
as per AWWA C210-07 Suitable for
potable water application & shall be
approved by CFTRI- lndia/BS 6920-
UK/international standard /NSF/ANSI/-61
2004 to be fit for contact with potable
water for human consumption with
micron thickness. inclusive of necessary
materials , labour ,Equipment
,Contractor's overhead charges and
profit and including all taxes
108 Providing and applying 3 LPE coating 85.00 Smt 808.00
outsie 3 layers polyethelene (LPE) coating
with required thickness as per DIN_30670
or its latest revision or amendment and
detail specification with necessary material
& Labour and Equipments etc.
109 Gas cutting ( Either square cut or V cut) -
pipes, plates etc. complete for following
thickness plate
a) Above 10 mm thickness plate 200.00 Rmt. 72.00
b) 5 to 10 mm thickness 200.00 Rmt. 56.00
110 Welding in all positions with required -
number of runs, for M.S. pipes internally
and / or externally including gauzing
wherever necessary, fixing appurtenances
and other accessories in connection with
pipe laying work as per specification. Butt
joints with convex fillet welds Lag
a) Above 7 mm thickness plate 200.00 Rmt. 729.00
b) 4 to 7 mm thickness 200.00 Rmt. 681.00
111 Providing and fixing M.S.Flanges to M.S. -
Pipe as per IS specification and as directed
by Engineer in charge.
a) Ring flange - M.S.Special Flanged -
Upto 300mm dia. 500.00 kg 98.00
300 mm dia and above 250.00 kg 98.00
b) Blank flange - M.S.Special Flanged -
Upto 300mm dia. 500.00 kg 98.00
300 mm dia and above 250.00 kg 98.00
112 Dewatering by pumping set of required 100.00 HP/hr 18.32
capacity including temporary platform
carting pumping at site and fixing the same
in position including all accessories, and
fuel and labour etc. complete.
113 Supply , installation , testing & 1.00 No 1,412.00
commissioning of Bourdan pressure gauge
having 150 mm dia with necessary syphon
& S.S. cock and shall be provided at each
pump outlet & pump header as per
specification and data sheet. Range 0-
114 Providing and fixing to wall, ceiling and -
floor galvanised Mild steel tubes (Medium
grade) of the following nominal bore, tube
fitting and clamps including making good
the wall ceiling and floor.(At any floor
a) 15 mm dia GI Pipe 5.00 Rmt. 244.13
b) 20 mm dia GI Pipe 5.00 Rmt. 297.25
c) 25 mm dia GI Pipe 5.00 Rmt. 393.93
d) 40 mm dia GI Pipe 5.00 Rmt. 596.73
e) 50 mm dia GI Pipe 5.00 Rmt. 779.60
115 Providing and laying in trenches -
galvanised mild steel tubes (Medium
grade)of the following nominal bore, tube
fittings (Earthwork in trenches to be
measured and separately)
a) 15 mm dia GI Pipe 5.00 Rmt. 150.91
b) 20 mm dia GI Pipe 5.00 Rmt. 190.97
c) 25 mm dia GI Pipe 5.00 Rmt. 279.39
d) 40 mm dia GI Pipe 5.00 Rmt. 421.12
116 Providing And Jointing Stoneware Pipes -
Incl. Excavation Up to 2 Mt. Refilling,
Transporting Pipes To Work Site,
Unloading, Lowering In Trench, jointing
material Such As Cement, sand, Hemp
Bitumen As Directed, Incl. Watering The
Trenches Spreading And Carting away Of
Surplus material as directed by engineer
a) 100 mm dia 2.00 Rmt. 119.64
b) 150 mm dia 2.00 Rmt. 163.39
c) 230 mm dia 2.00 Rmt. 344.64
117 Repairing of damaged MH including -
removing damaged brick & repairing by
masonry in C.M. 1:5 & plaster in C.M.1:3
& fixing C.I. Steps & excluding seat &
Cover in C.C.1:2:4 rate also includes
removing debris from MH & carting the
same as directed.
a) Up to 0.15 M ( @ two coarse) 5.00 No 732.14
b) Up to 0.35 M ( @ two coarse) 5.00 No 1,160.71
c) Up to 0.65 M ( @ two coarse) 5.00 No 1,794.64
118 Providing, laying, spreading and -
compacting graded stone aggregate to wet
mix macadam specification including
premixing the Material with water at OMC
in mechanical mix plant carriage of mixed
Material by tipper to site, laying in
uniform layers in subbase / base course on
well prepared surface and compacting with
vibratory roller to achieve the desired
density as per MoRTH clause
a) Production & Supply of WMM 50.00 Cmt 1,495.54
b) Laying of WMM 50.00 Cmt 31.25
119 Labour charges for doing washout of water 5.00 No 669.64
pipe line at end including necessary
excavation refilling the pit. Allowing the
water to flow for 15 minutes twice or
thrice as per site condition during supply
hour, dewatering the pit and plugging with
existing wooden butch. etc. comp. as per
Engineer In Charge
120 Barricading the entire break down or 100.00 Rmt 80.36
excavated area on rental basis using
wooden ballies / M.S.angles at max.
meter centre to centre, C.G.I. Sheet,
reflective paint / Board out side to avoid
accident & for smooth traffic diversion &
movement including cautionary board etc.
Item also includes for making temporary
sufficient nos of lighting arrangement
through out the work with necessary
required arrangement. ..The same shall be
removed after completion of work. (Only
for break down work from start to
121 Labour Charges for repairing the joint -
leakage in the existing C.I./DI Pipe line
with specials incl. required materials such
as jute and lead etc , nece. excavation in
any type of soil, refilling, nacessary trust
block etc.comp. as per instruction of
engg.in charge.(Joint reparied under this
item should not be paid in next four
months under normal condition)
a) 80 Mm dia. to 100 MM dia 10.00 joint 379.46
b) 150 Mm dia. to 250 MM dia. 10.00 joint 446.43
122 Labour work for fixing above interlocking 50.00 Smt 69.64
blocks on up to 50mm the sand
bedding,levelling,watering anf fixing. Rate
incl. average 30cm depth for excavation
and or filling,carting away
debries/excavated material up to 5 km and
cleaning the site etc.comp. as directed.
123 Supplying wooden taper plug from jungly -
wood (like limda, ambo ) etc. comp.
a) (A) 15 mm dia to 20mm dia 5.00 No 13.39
b) (B) 25 mm dia to 37mm dia 3.15 No 17.86
c) (C) 50 mm dia 2.00 No 89.29
d) (A) 80 mm dia to 100 mm dia line 1.00 No 312.50
124 Making connection of Any dia 1.00 No 90,000.00
DI/MS/HDPE Pipe with Existing Pipeline
including cutting the pipe to required
annular shape of Required dia. By Electro
Welding and jointing Any dia DI/MS pipe,
including dewatering, excavation, refilling
etc. with all required materials such as
welding rods and other necessary required
materials including giving a satisfactory
leakage proof test.
Removing any kind of pavement incl 500.00 Smt 12.50
125 stacking of serviceble material disposal of
unserviceble material with 50 meter lead
126 Providing and fixing in position 60 cm 10.00 Rmt 5,619.00
wide MS ladder with angle of 75 x 75 x
mm as support and 50 x 50 x 5 mm angle
as step at 200 mm c/c including (both side)
GI side railing with ISA 75 support
including fixing in cement concrete for
any height including making holes in RCC
walls if any and making good the RCC
wall / masonry wall after fixing work of
staircase etc. complete as directed
including two coats of approved quality oil
paint directed including two coats of
approved quality oil paint over one coat of
approved quality primer.
127 Providing and laying white glazed tiles 6 25.00 Smt 908.17
mm thick in flooring, treads of steps
skirting ,dado and landing laid on a bed of
12 mm thick cement mortar 1:3 (1 cement
: 3 coarse sand) finishing with flush
pointing in white cement (Upto 10 ton)
128 Providing and fixing wsh down 1.00 No 1,875.68
watercloset (Europeantype,W.C.Pan) with
integral Por S trap including jointing the
trap with soil pipei n Cement Mortar1:1(1-
Cement:1-fine sand) (Seal and cover to
beme asured and paid for separately)
(A)vitreous China Pattern :(i) in white
colour 32 dia. C. P. brass half turn flush
cock complete including earthwork, bed
concrete of 1:4:8.
129 Providing and fixing flat back white colour 1.00 No. 2,084.70
vitreous china wash basin 550 mm x
mm size with CI brackets painted white.
Wash basin shall have 15 mm dia GI
supply pipe, overflow chase, 15 mm dia
pillar cock and stop cock with PVC bottle
trap and PVC pipe piece upto wall plus
mm dia PVC waste pipe upto floor level
connected to 32 mm dia CI pipe below
floor and connected to nearby floor trap
complete with unions and plumber's white
soldered joints with necessary cleaning
eye, complete. All chases cut in wall for
fixing pipes shall be made good in CM
130 Providing and fixing Flat Back Urinal ( 1.00 No. 1,535.63
Hindware- 44cmx31.5cmx26.5cm) or
equivalent approved and of approved
shade including fixing the same in
concealed CI brackets, CP spreader, CP
dome shaped waste coupling, CP bottle
trap with flanges, CP angle cock flush
pipe making inlet and out let connections
all complete as per the instruction of
Engineer - In - Charge
131 Providing, laying and jointing in true line -
and level U.P.V.C. Pipe (SCH-40) for
including fittings make PRINCE /
SUPREME / ASTRAL / FINOLEX or
equivalent as approved by Engineer In
Charge. Pipe shall be fixed on the wall
with the help of clamp at every two metre
C/C or shall be concelled as directed
including necessary fittings etc. including
testing of pipe and joints and fixing the
same with adhesive solvent, including cost
of all materials.
a) 15mm dia. 29.50 Rmt. 71.93
b) 25mm dia. 25.00 Rmt. 90.93
c) 40mm Dia 15.00 Rmt 146.65
d) 50mm dia 15.00 Rmt 193.73
132 Providing & fixing gun metal check or non -
return full way wheel valve
133 Providing and fixing C.P brass screws 2.00 No 203.79
down Bip tap 15 mm dia polished bright
of approved make and design ,with all
necessary fittings.
134 Providing and fixing screw down bib taps 3.00 No 157.29
of following size.(C)Gun metal screw
down bib tap. i) 15mm dia.
135 Providing and fixing 150 mm x 100 mm 2.00 No 976.00
intercepting sewer trap embedded in
concrete complete including excavation
and backfilling.
136 Constructing Manhole with R.C.C. top 1.00 No 11,314.02
slab in 1:2:4 mix (1-cement: 2-coarses and
:4- graded stone aggregate 20 mm nominal
size) foundation concrete 1:3:6 mix (1-
cement : 3-coarse sand : 6-Brick bats
40+50 mm size) inside plastering 15 mm
thick with Cement Mortar 1:5 (1-Cement :
5-coarse sand)finished with a floating coat
of neat cement and making channels in
cement concrete 1:2:4 mix (1-Cement: 2-
Coarses and : 4-stone aggregate 20 mm
nominal size) finished smooth complete
including curing and festing (i) Inside size
900mm x 1200 mm and 2.0 M. deep
including C.I. cover with frame size
560mm diameter total weight of cover and
frame to be not less than 128kgs. (Wt. of
cover 64Kg. and Wt. of frame 64Kg.) (A)
With 230 mm thick walls of brick msonry
using brick having crushing strength not
less than 35Kg./Sq.cm. in Cement Mortar
1:5 (1-Cement : 5-Coarse sand) (1) A type
depth 0.90 Metre for 150 mm diameter
137 Providing and supplying in standered 15.00 Rmt 322.00
length ISI mark rigid unplasticised PVC
pipes suitable for potable water with
ringfit joint including cost of rings, as per
IS specification no. 4985/1988 including
all local and central taxes, transportation,
freight charges,octroi,inspection charges,
loading, unloading conveyance to the
departmental stores and including cost of
jointing material etc. complete Test
pressure of 4 Kg./csmt of 160 mm dia for
138 Providing and fixing cast iron (Spun) 2.00 No 600.08
Nahni trap of the following nominal
diameter of self cleaning design with C.I.
screaed down or hinged grating including
cost of cutting and making good the walls
and floor 100mm inlet and 50mm outlet.
139 Providing and fixing S.W. gully trap with 2.00 No 1,234.57
C.I. grating brick masonry chamber and
water tight C. I. cover with frame of
mm x 300 mm size (inside) with standard
weight. (i) Square mouth traps.(B) 150mm
x 100mm size P or R type
140 Providing and fixing 100 mm size P or S 1.00 No 311.85
trap for water closet squatting pan
including jointing the trap with the pan and
soil pipe in cement Mortar1:1 (1-Cement :
1-Fine sand) (A) Vitreous China.
141 Providing and laying (to level or slopes) 75.00 Rmt. 288.23
and jointing with stiff mixture of Cement
Mortar in proportion 1:1 Selt glazed stone
ware pipes including testing of pipes and
joints complete.(B)150mm dia. (upto
142 Constructing brick masonry chamber for 2.00 No 3,624.51
under ground C.I. Inspection chamber and
bends with bricks having crushing strength
not less than 35Kg.Cm 2in C.M. 1:5 C.I.
cover with frame (Light duty) 455mm x
610mm internal dimensions total weight of
cover with frame to be not less than 38Kg.
(Wt. of cover 23Kg.) and Wt. of frame
15Kg.) (R.C.C. top slab e with 1:2:4 mix
(1-cement :2- coarse sand :4-graded stone
aggregate 20mm size) foundation concrete
1:5:10 inside plaster 15mm thick with
cement mortar 1:3 finished smooth with a
floating coat of neat cement on walls and
bed concrete etc. complete. (ii) Inside
dimensions 500mmx700mm and 450mm
deep for pipe line with one or two inlets.
143 Providing and fixing over roof black 1,000.00 liter 3.91
colour PVC overhead water tank of
approved manufacture with all necessary
fittings and connection etc,complete on
144 Making holes on existing C.I./ D.I./MS -
water pipe line including necessary GI
fittings item also includes necessary
excavation, dewatering and refilling as per
instruction engg. In charge etc. comp.
a) (a) 15 mm dia 2.00 Nos 312.50
b) (b) 20 mm dia 2.00 Nos 401.79
145 Providing and fixing to wall ,ceiling and -
floor galvanised G.I pipe (medium duty )
of the following nominal diameter with
pipe fitting and clamps including making
good the wall,ceiling and floor pipes to be
tested for a pressure as specified.
a) (a) 15 mm dia 30.00 Rmt 100.00
b) (b) 20 mm dia 15.00 Rmt 127.00
c) (c) 25 mm dia 15.00 Rmt 182.00
d) (d) 40 mm Dia 50.00 Rmt 273.00
Empty boring through all sorts of strata for 50.00 Rmt 1,005.24
providing 450 mm Diameter R.C.C. bored
piles to required depth required depth
including providing necessary casing pipe
with all plants and equipments as required
Providing & laying controlled cement 10.00 Cmt 4,734.35
concrete M 300 for R.C.C. bored piles of
0.450m dia. including ramming, vibrating,
curing and finishing complete.
Fixing of Rebar on concrete structure for -
148 connection with new structure using
Hilti/Fischer or equivalent technology
including all labour, tools & tackels
temporary arrangement, safety measures
10 mm dia. Bar 100.00 Nos 351.00
12 mm dia. Bar 100.00 Nos 420.00
16 mm dia. Bar 150.00 Nos 490.00
20 mm dia. Bar 165.00 Nos 560.00
Name SITC of New Pumping Machinery with related Mechanical, Electrical and
of Instrumentation works with Five Years Operation and Comprehensive Repairing &
Work Maintenance Work For Augmentation of Underground Tank No.-5 at Dudheswar Water
MECHANICAL WORK
Item Qty Unit Amount
VT PUMP-MOTOR SET:
Supply, Installation, Testing and
Commissioning (SITC) of self lubricated type
Vertical Turbine Pump of following duty
parameters & guaranteed efficiency of
following MOC, having 1500 RPM max.
speed, suitable to couple with motor with
column and bowl assembly, discharge head,
base channel / Rolled Steel Joist etc.
MOC: Impeller & sealing rings- CF8M, Bowl
& suction bell of CI FG 260 as per IS
with 2 % Ni, Shaft with coupling - SS
Column Pipe of M.S. ERW of min. 450 mm
dia. & min. 8 mm thk. and each piece of
/ 2.5 m long pipes and total length as per
actual site req. and to achive min.
submergence requirement, Gland packed, MS
Base plate, Thordon bearings, and Suction
Strainer of SS-304 (opening shall be min.
times the area of opening of bell mouth /
suction or as per pump mfg. rec.), Sole plate,
Flex. pin-bush coupling, foundation bolts,
complete hardware's, Hot dip galvanised
(HDG) bolts, nuts & washers, gaskets etc.
complete as per IS and Specs and also
including in scope any other parts /
accessories / fittings required to complete the
work in all respects & satisfactory operation
of VT pump set.
Capacity: 1500 m³/hr,
Head: 40 Meter.
Induction Motor rating Mini. 250 kW or
higher as per manufacturer
INDUCTION MOTOR FOR VT PUMP
Supply Installation Testing and
Commissioning (SITC) of approved make,
energy efficient, Efficiency Class-IE3,
Vertical flange mounting, solid shaft, squirrel
case, Induction Motor rating mini. 250 kW or
higher as per IS 12615: 2018 and as per pump
mfg. recommendation, 3Phase, 415V, 50Hz.,
AC supply, 1500 RPM max.synchronous
speed and having TEFC enclosure with Class
F insulation (temp. rise limited to Class B)
with RTD sensors for winding & bearing
temperature protection.
2.1.1 VALVES 1 Nos. 7,791.00
Supply, installation, testing and
commissioning of Manually gear operated
CI /DI Double Flanged, Non Rising Spindle
type, Sluice Valve conforming to IS
PN 1.0 with SS 304 seat rings and SS spindle
with all hot dipped galvanised hardware's,
bolts, nuts & washers, gaskets, etc. as per data
Size : 150 mm NB (Manually Operated - On
2.2.1 Supply, installation, testing and 7 Nos. 236,468.00
commissioning of Electrically gear operated
CI / DI Double Flanged, Non Rising Spindle
type, Sluice Valve with actuator , integral
starter,etc. conforming to IS 14846 PN
with SS 304 seat rings and SS spindle with all
hot dipped galvanised hardware's, bolts, nuts
& washers, gaskets, etc. as per data sheet.
Size : 500 mm NB (Electric Gear Operated -
Delivery of Pump)
2.3.1 Supply, installation, testing and 7 Nos. 143,423.00
commissioning of double flanged CI / DI
Dual Plate Check Valve conforming to API
594 Class 300 / PN-1.6 with CS dual door,
hinge pin & stop pin of SS 410 , springs of
AISI 304 and seat rings of SS 304 ( renewable
), along with all required accessories, gaskets
and hardwares,etc. and as per
specification.Size : 500 mm NB (On Delivery
2.3.2 Size : 1200 mm NB (On Header Pipe) 1 Nos. 256,800.00
2.4.1 Supply, installation, testing and 1 Nos. 553,140.00
commissioning of Electrically & gear
operated CI / DI DF Butterfly Valve,
conforming to IS 13095 / BS EN 593, PN
with SS 304 renewable seat rings , indicator,
gear box with bolts, nuts & washers, gaskets,
etc. as per specifications.Size: 1200 mm NB
(Elec. Operated on Header Pipe)
2.5.1 SITC of CI / DI Tempor proof Flanged Air 1 Nos. 25,759.00
Valve with Isolation Sluice Valve as per IS
respectively with SS304 float, gun metal
nozzle, complete hardware's, bolts, nuts &
washers, gaskets etc. including all taxes,
Insurance, Transportation, freight charges,
Inspection charges, loading, unloading,
conveyance to departmental stores, stacking,
security etc. as per IS and Specification.
Size: 150 mm NB - Pn 1.0 (On Heder line)
3.1.1 Supply, installation, testing and 7 Nos. 22,200.00
commissioning of double flanged Expansion
Bellows confirming to EJMA/IS standard
with PN 1.0 rating & all necessary St.St.
Size : 500 mm x 300 mm ( L )(Delivery of
3.1.2 Size : 1200 mm x 350 mm ( L ) (On header 1 Nos. 111,512.00
4.1.1 MS FITTINGS & SPECIALS: 60 RMT 22,307.87
Supply, Fabrication, Gas cutting of pipe,
welding, Installation, testing and
commissioning of MS flanged / plain ended
specials and fittings like MS reducer,
expander, Metering bends, Tees, etc.
conforming to IS 3589, flanges confirming to
IS 6392-PN- 1.0, fabricated from MS. plate
with necessary supports & anchoring. Pipe
fabricated from MS plate. (Excluding supply
The scope also includes civil work, casting
PCC thrust block, chipping, grouting,
supporting,etc. require for laying &
connecting the MS pipes & fittings as require
outside the pump house
Size: 1200 mm NB mm x 10 mm Thk (
4.1.2 Size: 500 mm NB X 10 mm ThK 35 RMT 9,106.28
4.2.1 Providing epoxy coating to inside pipe line 227 Sq.m 332.00
with two parts of Solvent free high build
liquid epoxy lining as per AWWA C210-07
Suitable for potable water application & shall
be approved by CFTRI- India/BS 6920-
UK/international standard /NSF/ANSI/-61
2004 to be fit for contact with potable water
for human consumption with 406 micron
thickness. inclusive of necessary materials
labour ,Equipment ,Contractor's overhead
charges and profit and including all taxes.
Size : 1200 mm NB X 10 mm Thk ( For
4.2.2 Size : 500 mm NB X 10 mm Thk ( Delivery 55 Sq.m 332.00
4.3.1 Supply, welding , Installation, testing & 8 Nos. 1,883.56
commissioning of MS flat machined faced
flanges confirming to IS 6392 & drilled as
per IS-1538 with drilling off centre bolt holes
and flange thickness as per PN 1.0 including
cutting & welding.
Size : 150 mm NB Drilled ( For Header Drain
Pipe and Air Valve Pipe)
4.3.2 Size : 500 mm NB Drilled ( Delivery Pipe Of 28 Nos. 10,290.00
4.3.3 Size: 1200 mm NB Drilled (For Header Pipe) 40 Nos. 40,746.44
4.3.4 Size: 1200 mm NB (Blind) 1 Nos. 42,933.90
5.1.1 G.I. PIPES & FITTINGS: 20 RMT 1,404.00
Supply, installation, connection with
equipments as required, testing and
commissioning of GI pipe conforming to IS-
1239 , Medium Duty with coupling, tee,
bend, union, elbow, flanges , etc as all
required fittings for connection complete with
gaskets, hardware, and required accessories as
per IS & SpecificationsSize: 150mm NB (on
Header for Air Valve Piping and header drain
6.1.1 Flanged Joints of Pipes, Fittings and 10 Nos. 611.00
Supply, Installation, Making of IS
Flanged joint of Pipe flanges, Fittings and
Specials Joints with all jointing materials,
rubber packing, GI nut bolts, labour etc.for
complete connection.
Size: 150 mm dia (on Header for Air Valve
Piping and header drain Pipe).
6.1.2 Size: 500 mm dia (Each Pump Del. Flange) 42 Nos. 312.00
6.1.3 Size: 1200 mm dia (For Header Flanges) 24 Nos. 1,295.00
7.1.1 Providing, Supply of Structure Steel at site of 1500 Kg. 64.83
work with freight, loading, unloading carting,
etc. including all taxes and duties complete
such as joints, channels, angles, Iron Rails,
ISA/ISMC/ISMB/MS flat, Plates, Chequered
plates (below 10mm thickness) for cable
trench etc. required for support structure of
Elecrtrical equipments etc. for support on
floor / wall / beam / brackets etc. as per tender
7.1.2 Labour Charges for lowering, laying, Fixing 1500 Kg. 11.36
with fabrication various size section of MS
such as joints, channels, angles, Iron Rails,
ISA/ISMC/ISMB/MS flat, Plates, Chequered
plates, for cable trench etc Complete with two
coats of red oxide and two coats of approved
colour shade of epoxy paint as per relevant IS
and as per specification.
8.1.1 E.O.T. CRANE WITH HOIST 1 Nos. 626,250.00
Providing & erecting Single girder type fully
electrically operated E.O.T. crane with
electrically operated hoist, class II duty,
geared travelling trolley with seven meter lift
complete with long travel rail track (40 mm
sq. bar), moving or cross girder, all three
motions electrically operated by suitable
rating motor IP 54, control panel & down
pendant control block, brake, safety device,
cables form motor to starter panel & other
required accessories & tested as per IS
Specifications.
EOT Crane with single/Box type girder
having motorised motion in all three
directions, manufactured as per IS - 807, IS
3938 & IS - 3177 , class-II, complete with
electrically operated hoist, geared trolley,
cross girder, rail track, brake, wire rope drum,
motors, safety device, pendant push button,
starter panel, cables from motor to starter
panel and all other required accessories like
limit switches, panel, power supply system
(Fastoon cable type), fasteners, epoxy
painting, etc. and tested to 25 % over load
complete as per specifications.
Note: Minimum as specified capacity or
higher as per requirement such that EOT
crane capacity is min.1.25 times of the pump,
motor OR single heaviest component to be
lifted within pump house.
Capacity : 5 Ton. (for Pump Room)
Lift : 10.00 m (max)
Span: 9 m-12 m (or as per actual site
Bay length: 30.0 m (max.)
9.1.1 CHLORINATION SYSTEM 2 Plant 210,642.00
SITC of wall mounted, FRP cabinet type,
Vacuum operated Chlorination plants with
required piping, fitting, valves, safety and
testing kit, etc. Complete arrangement shall
be as per attached standard drawing for one
complete system combaining the Two plants
complete in all respect as per IS and as per
specsification.
Capacity: 05 kg/hr. for each plant making one
complete plant as per attached standard
drawing and shall include the followings:
(1) 1 No. Submersible Pump motor set with
continuous Cable from pump to starter panel
without any Joint with proper conduit piping
and clamping. (2) 1 No. Diffusers, (3) 1 No.
Ejector, (4) 1 No Chlorinator , (5) 1 No.
Vacuum Regulators, (6) 1 No. Strainer , (7)
Nos. Isolation Ball Valves , (8) 1 Non Return
Valve, (9) 1 Nos. Yoke clamp (for cylinder),
(10) 1 No. Pressure Gauge with require piping
and isolation valve, (11) 1 No. Chlorine
Gauge at Cl2 manifold (12) 1 Lot of piping,
fittings, valves & instruments, (13) Vaccum
Gauge , 14) MS support of 50 mm x 50 mm x
4 mm thk, (15) 3C copper armour power
cable from PMCC panel to Chlorine room of
required size with proper piping & Clamping
as equired (16) 1- lot inter connecting piping
of identical pipe size of Cl2 booster pumps
delivery line with isolation valve. (17) 1 No.
common Starter panel with TPNB MCB with
necessary cabling & electrical connections
etc. and other necessary items as per IS &
Tender Specification and Data sheet for Cl2
booster pumps,(18) 1 no common 3/4" Cl2
gas manifold of Carbon steel suitable for two
9.1.2 AUTO SHUT OFF CHLORINE 1 Set 1,195,000.00
CYLINDER VALVE SYSTEMSITC of
Automatic Chlorine cylinder shut off valve
for single chlorine cylinder (100 kg) for
chlorination system comprising of :01) 2 No.
Pneumatic Auto shut off chlorine cylinder
route valve with actuator system with Air line
filter, Solenoid Valve, Air motor, Yoke
clamp, etc. of required capacity , size,
rating02) 1 Lot, Control panel cum PLC with
interconnecting cables/wiring for Auto Shutt
Off chlorine Valve of Cylinder,03) 1 No, Air
Compressor04) 1 Lot, uPVC-SCH 40, Air
piping for Auto Shut off valve as
required,05)1 No Chlorine leak detector of 0-
10 ppm capacity ,06) 1 Lot, Interconnecting
instrument & Power cable,07) 1 No.
Industrial Hooter,
9.1.3 AUTOMATIC LEAK CHLORINE 1 Set 540,000.00
DISSOLVING SYSTEM
SITC of automatic leak chlorine dissolving
system in caustic neutralisation tank for (100
kg) cylinder for chlorination system
comprising of :
01) 2 Nos. FRP Hood for 100 kg Cl2 Cylinder
02) 1 no CF Air Blower
03) 1 Lot Flex. PVC ducting Pipe,
04) 1 No. uPVC SCH 40- Diffuser,
05) 1 No. Relay based Control Panel
06) 1 Lot Cable and Cable Tray for Blower
07) 1 No. PP + FRP Tank for Caustic storage
08) 1 Lot PP Isolation Ball Valve for Tank
09) 1 Lot Hadware, jointing & misc. items as
required to complete the work in all respects
& Civil Foundation.
9.1.4 Supply of safety kit & testing as specified in 1 Set 83,241.00
the specifications.
(1) 1 Set Chloroscope
(2) 1 set. Air breathing apparatus for 45 min
as per IS with O2 bottle,
(3) 1 set. Emergency tool kit
(4) 1 No. Amonia Torch
9.1.5 TRAY FOR CHLORINE SOLUTION 100 RMT 158.00
Providing & Fixing approved make
Perforated C type tray made from CR sheet
along with required accessories to sustain the
weight of uPVC pipe with bends, tees and
clamps for fixing of uPVC pipe and all the
fittings as required as per site condition. The
Perorated type tray shall be single or double
needed as per required and as per IS
2062/1079 and shall be coated with hot deep
galvanised as per IS 2629/4759 with coupler
plate/Fish plate and GI hardware like nut-bolt
and washers, etc. erected providing support
as per specification and as per instruction of
engineer in charge.
Size: 100 x 50 x 1.6 mm thk
10.1.1 DISMANTLING, CARTING AND 1 JOB 75,000.00
STACKING (Mechanical Items)
Dismantling of all Existing SCF Pump-Motor
set, existing Valves, Drain Pumps, Pipes and
Specials (Tees, Band etc), EOT Crane etc. of
Existing SCF Pump House covering with
Plastic and packing in wooden box with all
required accessories and transportation &
stacking at AMC store / site or as per
instruction given by the engineer In-Charge.
10.1.2 DISMANTLING, CARTING AND 1 JOB 85,000.00
STACKING (Electrical Items)Dismantling
of all existing LT Panel, APFC Panel, All
Cubicle panels, Cables, Cable Trays, lighting
fixtures, existing lighting wiring including
loading, shifting & unloading at AMC store /
site or as per instruction given by the engineer
TOTAL ESTIMATE OF MECHANICAL WORK (Without GST)
SITC of New Pumping Machinery with related Mechanical, Electrical and
Name Instrumentation works with Five Years Operation and Comprehensive Repairing &
of Maintenance Work For Augmentation of Underground Tank No.-5 at Dudheswar Water
work Work of AMC.
ELECTRICAL WORK
Sr Unit Rate Total Amount
Sr Unit Rate Total Amount
1.1.1 H.V. CABLES 100 Mtr 1,261.00
Supply, laying, testing & commissioning
of 11 kV, 3C x 240 sq.mm.XLPE (UE)
armoured H.V Cable stranded Aluminium
conductor, galvanised steel flat strip/ round
wire armoured, extruded PVC type ST2
sheathed, heavy duty cable conforming to
IS:7098 (Part-2) & IEC:60502(Part-2).
1.2.1 Supply, Installation, Testing and 4 Nos. 6,985.00
Commissioning of the Heat shrinkable
type Indoor H.T.cable end terminations
suitable for 11 kV, 3C x 240 sq.mm.
XLPE (UE) armoured cable including
necessary earth connectivity connection,
material & consummables making the
termination/ joint complete ensuring the
joint resistance is within the permissble
limit as per IS.
1.2.2 Supply, Installation, Testing and 2 Nos. 11,487.00
Commissioning of the Heat shrinkable
type outdoor H.T.cable end terminations
suitable for 11 kV, 3C x 240 sq.mm.
XLPE (UE) armoured cable including
necessary earth connectivity connection,
material & consummables making the
termination/ joint complete ensuring the
joint resistance is within the permissble
limit as per IS.
Modification of Existing 2500 KVA
Transformer LT side Cable Terminal
Box for required Current rating of Busbar,
Required Insulator, Required space for
Cable Termination.
Design & Supply of 433 V L.V. Cable Box
chamber comprising of followings:
→Complete L.V. cable box with fixing of
suitable disconnecting type flexible copper
strip with solid copper flat bus bar
1.2.1 alongwith fittings of epoxy insulator, 2 JOB ₹ 180,000.00
hardware, GASKETS, earthing
arrangement, Including Cable Box Support
- suitable for 8 runs of 4 Core cable X
→ M.S. Gland plate in undrilled condition
→ Cable box duly painted with EPOXY
Painted gray as per 632 of IS– 5 (as per
your existing transformer paint shade)
NOTE: Work to be execute on OEM
authorised only.
1.2.2 LOW VOLTAGE (LT) PANEL BOARD 1 Nos. 7,478,925.00
SITC of PMCC Panel (50kA) complete in
all respects as per SLD / Specification / IS
and including following as minimum:
(1) Two nos. FP 2500A Microprocessor
EDO ACB for I/C with Digital Voltmeter
with Voltmeter Selector Switch, Digital
Power Factor Meter, Digital Ammeter with
Ammeter selector switch, MFM with RS-
485, R, Y, B, on, off, trip Indicating lamps
& TNC Switch, ON, E-STOP, Reset
Pushbutton, etc.
(2) One no. FP 2500 A EDO ACB for
Bus-Coupler. (Same as per Incomer)
(3) 2500 A TPN Main busbars. (Main &
Auxilary bus-bars size with current density
(4) Six Nos. (3W + 2S + 1 Spare) Soft
starter for min. 250 kW Motor or higher
as per pump Manufacturer reco. with
suitable derating and with 630A TPN
Motor Duty MCCB, 550A AC3 duty line
& Inbuilt / External bypass contactor,
Ten channel temperature scanner with
potential free contacts, fast acting fuse,
MFM with RS-485, door display key pad
& digital MPR+SPP with CBCT, on, off,
trip Indicating lamps & ON, E-STOP,
Local/Remote, Auto/ Manual selector
switch & LCS for Pump- MOV Actuator
with Indication & push button etc.
(5) Two Nos. (2W) VFD starter for min.
250 kW Motor or higher as per pump
Manufacturer reco. with suitable derating
and with 630A TPN Motor Duty MCCB,
550A AC3 duty line contactor, VFD with
inbuilt RS 485 for 250 kW Motor or
higher as per pump manufacturer reco.
with VFD rating minimum (Amp of
motor/pump@ 50°C) with suitable
derating with detachable type door
mounted display key pad, Semi conductor
fuse, Input Choke shall be provided, rating
as recommended by VFD manufacturer &
Output choke as recommended by VFD
OEM for harmonic mitigation,VFD with
3C3 Confromal coating, Ten channel
temperature scanner with potential free
contacts, fast acting fuse, MFM with RS-
485, SPP, On, Off, Trip, Indicating lamps,
Start, Stop, Speed Up & down Push
buttons, Local/Remote, Auto/ Manual
selector switch. & LCS for Pump- MOV
Actuator with Indication & push button etc.
(6) Two nos. 630 A FP Microprocessor
MCCB feeder for APFC Panel.
(7) 3nos. 250A TPN microprocessor
MCCB feeder for Borewell Feeder &
(8) Tr. losses comp. fixed capacitor bank
with Four no. 20 kVAR, Three no.
kVAR & Three nos. 5 kVAR capacitors
bank , 2 nos. 2 kVAR capacitors bank &
One no. 1 kVAR capacitors bankeach with
capacitor duty contactor, timer & 'D' curve
MCB, etc. for each transformer.
(9) Two nos. 63ATPN MCCB feeders (for
PDB - Auxiliary accessories load)
(10) Two no. 32A TPN MCCB spare
(11) One no. Outdoor lighting LDB feeder
with 32ATPN 'C' curve MCB with 32A
contactor & Time switch.
(12) 6 nos. 32A 'C' curve MCB feeders (for
Indoor LDB, 2nos. Chlorination System,
3nos. spare feeders)
(13) 7 nos. 16A DP MCB feeders (for
single phase supply for 2nos. X'mer
marshaling box, HT Panel & 3 Nos.Spare.)
(14) 6nos. 2500A/1A, Cl.-0.5 metering CT
(15) 3nos. 2500A/1A, Cl.-1.0. Summation
(16) 2nos.2500A/1A, Cl.-1.0. CT For
(17) 2nos. Multiplication relay for dry run
protection of pumps
1.2.3 SITC of 430 kVAR APFC Panel with 7% 2 Set 1,016,451.00
AL detuned reactor, complete in all
respects as per SLD / Specification / IS and
including following as minimum:(1) 630 A
FP Microprocessor MCCB I/C.(2) 18 Steps
Microprocessor APFC Relay with
sensitivity 10mA.(3) 4 no. 50 kVAR
capacitor bank with 125A TP Thermal
Magnetic MCCB & 50 kVAR Capacitor
duty contactor with timer(4) 3 no.
kVAR capacitor bank with 100A TP
Thermal Magnetic MCCB & 40 kVAR
Capacitor duty contactor with timer.(5)
1nos. 30 kVAR capacitor bank with 63A
'D' curve MCB & 30 kVAR Capacitor duty
contactor with timer.(6) 2 nos. 20 kVAR
capacitor bank with 40A 'D' curve MCB &
20 kVAR Capacitor duty contactor with
timer.(7) 2 nos. 10 kVAR capacitor bank
with 20A 'D' curve MCB & 10 kVAR
Capacitor duty contactor with timer.(8)
nos. 5 kVAR capacitor bank with 16A 'D'
curve MCB & 5 kVAR Capacitor duty
contactor with timer.(9) 2no. 2 kVAR
capacitor bank with 16A 'D' curve MCB &
2 kVAR Capacitor duty contactor with
timer.(10) 1 no. 1 kVAR capacitor bank
with 16A 'D' curve MCB & 1 kVAR
Capacitor duty contactor with timer.(11)
All capacitors shall be Gas Filled type with
dielectric losses ≤ 0.2w/kVAR. (Suitable
for 0.95 or better Correction).
1.3.1 SITC of Lighting Distribution Board 2 Nos. 7,494.00
(LDB) as under:
3 Phase 4 Wire TPN, 6 way Prewired LDB
(One each for Indoor & Outdoor Lighting)
Suitable to house :
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB 'C' curve (9 nos.)
& 16A SP MCB 'C' curve (9 nos.)
(At Panel Room)
1.3.2 SITC of Power Distribution Board 1 Nos. 10,009.00
(PDB) as under:
3 Phase 4 Wire TPN, 8 way Pre-wired-
MOG / MOV PDB for Auxiliary
accessories Load power supply (For MOV
Pump delivery valves, valve at Header &
for auxiliary load & spare):
Incoming: 63A 4P, MCB 'C' Curve
Outgoing: 10 Nos. 32A 4P MCB 'C' Curve
1.3.3 Local Control Station 7 Nos. 4,840.00
SITC of Pendant type ON_OFF (E-Stop)
LCS pushbutton set complete with
Enclosure, necessary mounting/ fixing
arrangement on wall / pipe support etc. to
be installed near motors for remote
operation, etc. as per IS and specifications.
(Including structural steel)
(For 7 Nos. for Pumps)
1.3.4 SITC of Pendant type ON_OFF LCS 2 Nos. 2,800.00
pushbutton set complete with Enclouser,
necessary mounting/ fixing arrangement on
wall / pipe support etc. to be installed near
motors for remote operation, etc. as per IS
and specifications (including structural
steel) (For 2 no. Chlorine Booster pump)
1.3.5 SITC of Local Control Station with 8 Nos. 4,500.00
pendant type Open_Stop_Close pushbutton
set and with Open, Close, Trip & Local /
Remote Indicating Lamps complete with
Enclouser, necessary mounting/ fixing
arrangement on wall / pipe support etc. to
be installed near motors for remote
operation, etc. as per IS and specifications
(including structural steel)
(For 7 Nos. Actuator Pumps delivery
Valves,1 no. Header Valve)
2.1.1 LOW VOLTAGE (LT) CABLES 1355 Mtr 1,211.00
Supply and unloading & delivery at site,
storage & security at site of 1.1 kV,
A2XFY/2XWY XLPE insulated (IS 7098)
/ PVC insulated (IS 1554) AL conductor
cables as per specification & IS. The cable
when laid outside the building shall be laid
underground in excavated trench, as per
specified method and shall be laid in
prepared trench on cable tray when laid
inside the building.3.5C x 400 sq.
mm.A2XFY Cable (8 Runs for Tr. 1 & 2 to
2.1.2 3.5C x 300 sq. mm. A2XFY Cable (2 Runs 120 Mtr 954.00
for each APFC Panel)
2.1.3 3C x 300 sq. mm. A2XFY Cable (2 Runs 420 Mtr 815.00
for PMCC Panel to each Main Pump )
2.1.4 4C x 6 sq. mm. A2XFY Cable (For WR- 400 Mtr 78.00
DB with TPN MCB at Sump & Pump
House, Outdoor LDB, Indoor LDB,.Each
2.1.5 4C x 10 sq. mm. A2XFY Cable (For TPN 100 Mtr 97.00
MCB for Outdoor light)
2.1.6 4C x 2.5 sq. mm. 2XWY/2XFY Cable (For 300 Mtr 81.00
TPN MCB for EOT at Pump House &
Chlorination Room, TPN MCB at PMCC
room & Pump house maintenance floor,
Chlorination system, Each MOV at Main
Pump and MOV at Header and Outdoor
2.1.7 2C x 2.5 sq. mm. 2XWY/2XFY Cable (For 400 Mtr 175.00
Each Motor space heater(as required), HT
Panel, for 2nos. APFC CT & X'mer
marshaling box Single Phase Supply, for
2.1.8 5C x 1.5 sq.mm. 2XWY/2XFY Cable (For 200 Mtr 130.00
2 no. Chlorine Booster Pump LCS)
2.1.9 7C x 1.5 sq.mm. 2XWY/2XFY Cable (For 400 Mtr 113.00
Each Pump Motor LCS with Ameter, 2 no.
Chlorine Booster Pump LCS)
2.1.10 10C x 1.5 sq.mm. 2XWY/2XFY Cable 400 Mtr 230.00
(2Run Tr. to HT Panel control cable)
2.1.11 12C x 2.5 sq.mm. 2XWY/2XFY Cable 250 Mtr 390.00
(For Actuator LCS of Each Pump, 1Run
Tr. to HT Panel control cable)
2.1.12 10Tride x 1.0 sq.mm. individual triad and 300 Mtr 460.00
overall shielded with aluminum mylar tape
Signal Cable for RTD & BTD of
motor(For Each Main Motor)
2.2.1 CABLE END TERMINATION AND 32 Nos. 1,441.00
SITC of Double compression Weather
proof type Ni-Plated brass cable glands and
crimping type Bimetalic lugs / sockets with
necessary tools and equipments as
specified in specifications and IS.
The glands and lugs / sockets shall be
suitable for cable size and type mentioned
below & as per specificaitons.
1) Earthing the glands and armouring with
earthing clamp and jumper and also
connecting to common earth bar.
2) The job also includes, if necessary,
supply & fixing of extension busbar of
same material on MCCB or panel board
terminal / connector to connect more than
one no. of parallel cables or to connect
higher size cable to lower size unit. The job
also includes earthing the glands and
armour of the cable with common earth bar
or flexible copper mesh.(Cable termination
qty. shall be as per site requirement)
3.5C x 400 sq. mm.A2XFY Cable (8 Runs
for Tr. 1 & 2 to PMCC Panel)
2.2.2 3.5C x 300 sq. mm. A2XFY Cable (2 Runs 8 Nos. 1,009.00
for each APFC Panel)
2.2.3 3C x 300 sq. mm. A2XFY Cable (2 Runs 28 Nos. 960.00
for PMCC Panel to each VT Pump )
2.2.4 4C x 6 sq. mm. A2XFY Cable (For WR- 30 Nos. 111.00
DB with TPN MCB at Sump & Pump
House, Outdoor LDB, Indoor LDB, Each
2.2.5 4C x 10 sq. mm. A2XFY Cable (For TPN 12 Nos. 128.00
MCB for Outdoor light )
2.2.6 4C x 2.5 sq. mm. 2XWY/2XFY Cable (For 70 Nos. 77.00
TPN MCB for EOT at Pump House &
Chlorination Room, TPN MCB at PMCC
room & Pump house maintenance floor,
Chlorination system, Each MOV at Main
Pump and MOV at Header and Outdoor
2.2.7 2C x 2.5 sq. mm. 2XWY/2XFY Cable (For 24 Nos. 75.00
Each Main Motor space heater(as
required), HT Panel, for 2nos. APFC CT &
X'mer marshaling box Single Phase
2.2.8 5C x 1.5 sq.mm. 2XWY/2XFY Cable (For 4 Nos. 150.00
2 no. Chlorine Booster Pump LCS)
2.2.9 7C x 1.5 sq.mm. 2XWY/2XFY Cable (Fo. 10 Nos. 89.00
Each Motor LCS with Ameter, 1no.
Chlorine Booster Pump LCS)
2.2.10 10C x 1.5 sq.mm. 2XWY/2XFY Cable 8 Nos. 185.00
(2Run Tr. to HT Panel control cable)
2.2.11 12C x 2.5 sq.mm. 2XWY/2XFY Cable 13 Nos. 129.00
(For Actuator LCS of 9 nos. Pump and
Header, 1Run Tr. to HT Panel control
2.2.12 10Tride x 1.0 sq.mm. individual triad and 18 Nos. 230.00
overall shielded with aluminum mylar tape
Signal Cable for RTD & BTD of motor
(For Each Main Motor)
3.1.1 CABLE TRAY 200 Mtr. 615.00
SITC of GI ladder type cable trays with
side channels of size - 75 x 15 x 15 mm/
100 x 15 x 15 mm & rungs of size - 35 x15
x 15 mm spaced at 250 mm apart,
fabricated from 2 mm thick sheet steel in
standard length of 2.5 meter, duly hot
dipped galvanized after fabrication as per
IS 2629- 1989/ IS 4759-1984 including
accessories such as coupler plates/ fish
plates, bends, tees, reducers, elbows,
covers and electro- galvanized hardware
etc, erected on existing support as per
specification and instruction of engineer in
750 x 100 mm - Ladder type
3.1.2 450 x 100 mm - Ladder type 200 Mtr 506.00
3.1.3 150 x 100 mm - Ladder type 360 Mtr 402.00
3.1.4 SITC of GI perforated type cable trays 100 Mtr 541.00
with returned edge/ flange, fabricated from
2.0 mm thk sheet steel in the standard
length of 2.5 mtrs, duly hot dipped
galvanized after fabrication as per IS 2629-
1989 / IS 4759-1984 including accessories
such as coupler plates/ fish plates, bends,
tees, reducers, elbows, covers and electro-
galvanized hardware etc, erected on
existing support as per specification and
instruction of engineer in charge.
300 x 50 mm - Perforated type
3.1.5 150x 50 mm - Perforated type 100 Mtr 336.00
3.2.1 Cable Trench, Laying & Installation of 100 Mtr 46.00
Cable: Making cable trench in soft soil of
suitable width of 90cms deep for laying
cable all over the run and back filling the
same and making the surface as normal
ground as per IS & Specification. (For
laying HT & LT cable in ground)
3.2.2 Cable Covering in Trench: Cable 100 Mtr. 133.00
Covering with second class bricks or
cement tiles laid cover the cable crosswise
& also on both side with covering of
7.5cms. Layer of sand above & below
cable (16 bricks per meter.) as per IS &
Specification. (For HT & LT cable trench)
3.2.3 Supply, laying and erection of 120 mm 100 Mtr 136.00
approved make Double Walled Corrugated
pipes (DWC) of polyethelene (confirming
to IS 14930 II) with necessary connecting
accessoies of same material at required
depth for laying of cable below ground /
road surface for enclosing cable and back
filling the same to make ground as per
original. (For HT & LT cable).
DWC Length is Approx. Provide as per
Actual Site Requirements.
3.2.4 Supply, laying and erection of 90 mm 100 Mtr 95.00
approved make Double Walled Corrugated
pipes (DWC) of polyethelene (confirming
to IS 14930 II) with necessary connecting
accessoies of same material at required
depth for laying of cable below ground /
road surface for enclosing cable and back
filling the same to make ground as per
original. (For Pump cable) DWC Length
is Approx. Provide as per Actual Site
3.2.5 Supply, laying and erection of 50 mm 100 Mtr 62.00
approved make Double Walled Corrugated
pipes (DWC) of polyethelene (confirming
to IS 14930 II) with necessary connecting
accessoies of same material at required
depth for laying of cable below ground /
road surface for enclosing cable and back
filling the same to make ground as per
original. (For LT & Street light cables).
DWC Length is Approx. Provide as per
Actual Site Requirements.
4.1.1 CHEMICAL EARTHING SYSTEM 5 Nos 10,489.00
SITC of Maintenance free chemical
earthing (copper) with earthpit of minimum
bore size dia. 225mm Safe Earthing
Electrode consisting Pipe-in-Pipe
Technology as per IS-3043:1987 /Tech
spec. made of corrosion free Pipes having
Outer pipe dia of 48 mm having (plating
thickness as per IS) copper plating, Inner
corrosion free Hot dip galvanised (plating
thickness as per IS) pipe dia of 26 mm with
copper flat strip type connection terminal
14mm dia with constant ohmic value
surrounded by highly conductive corrosion
resistant chemical compound with high
charge dissipation suitable for electrical
installation & of 3Mtr. length of Pipe with
two nos. 25Kg. bag of Back filling
NOTE: Earthing Resistance value & date
shall be painted on the chamber cove
(2nos. Each for neutral of Tr.-1 & 2, HT
4.1.2 SITC of chemical earthing with earthpit of 14 Nos 7,025.00
minimum bore size dia. 225mm Safe
Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS-3043:1987 made of
corrosion free G.I. Pipes having Outer pipe
dia of 80 mm having 80-200 Micron
galvanising, Inner pipe dia of 40 mm
having 200-250 Micron galvanising or
copper coated solid steel road / flat strip
type connection terminal 14mm dia with
constant ohmic value surrounded by highly
conductive corrosion resistant chemical
compound with high charge dissipation
suitable for electrical installation of 11 kV
& 440V of 2Mtr. length of Pipe with one
no. 25Kg. bag of Back filling compound.
(2nos. Each for body of Tr.1 & Tr.
4.2.1 SITC of pipe type earthing having 150 cms 17 Nos 365.00
long and 2.5cms dia. Galvanised iron pipe
with coupling and buch buried in specially
prepared earth pit complete with necessary
8 SWG earth wire
(For Each St. light Pole Earthing &
2nos.Gate light earthing)
4.2.2 SITC of 50mm(w) x 6mm(T) etc. sizes as 575 Kg 77.00
required, HOT deep GI Strip including
supply & fixing using GI spacers, saddles
when laid inside the building and inclusive
of excavation & refilling of earth when laid
outside the building & interconnection with
earth pit & all electro-mechanical
(50X6 G.I Strip wt.2.3 kg/m,
(HT Panel, Transformer, Motors etc.)
4.2.3 Supply, laying and erection of 25mm(w) x 120 Kg 77.00
6mm(T) etc. sizes as required, HOT deep
GI Strip including supply & fixing using
GI spacers, saddles when laid inside the
building and inclusive of excavation &
refilling of earth when laid outside the
building & interconnection with earth pit &
all electro-mechanical equipments.
(25X3 G.I Strip, 0.6 Kg/m, 0.6x
(LT & APFC Panel etc.)
4.2.4 Supply, laying and erection of 40mm(w) x 188 Kg 787.00
6mm(T) etc. sizes Copper Strip including
supply & fixing of bolts, saddles when laid
inside the building and inclusive of
excavation & refilling of earth when laid
outside the building & interconnection with
earth pit & Tr. nutral.
(40X6 Cu. Strip, 1.88 Kg/m, 1.88 x
4.2.5 Supply, laying and erection of 40 mm(w) x 188 Kg 77.00
6 mm(T) etc. sizes as required, HOT dip
galvanized GI Strip including supply &
fixing using GI spacers, saddles when laid
inside the building and inclusive of
excavation & refilling of earth when laid
outside the building & interconnection with
earth pit & all electro-mechanical
(40X6 G.I Strip wt1.88 Kg/m, 1.88 x
4.2.6 SITC of HOT Dip Galvanized iron strip 52 Kg 77.00
wire 8 SWG (For LDB, PDB, LCS,
St.Light Pole, etc.)(8 SWG G.I Strip,
5.1.1 INTERNAL WIRING 410 Mtr 110.00
SITC of Mains & outlet points wiring with
1.1 kV grade FRLS PVC insulated ISI
marked flexible stranded copper conductor
wires with medium class min. 25mm.
dia. Rigid PVC pipe and accessories to
be erected concealed in / to be run on
surface / wall / ceiling with following sizes
as mentioned below. The unit rate wirings
shall be with connector, PVC junction box,
wires, holder, ceiling rose, angle holder,
switch, sockets, switch board, brass
chromium / cadmium plated machine
screws, phase and neutral wires, green
Earth continuity wires etc. as required to
complete wiring from LDB panel to the
final outlet termination points. The wiring
shall be as per IS:732, IS:4648 and
as per tender specification / IS.
(a) SITC of Mains wiring with 3 wire
5.1.2 As per Above (b) SITC of Mains wiring 200 Mtr 128.00
with 3 wire 2.5 sq.mm as per tender
specification & IS.
5.1.3 As per Above.-7.1.1 (c) SITC of Mains 200 Mtr 118.00
wiring with 4 wire 1.5 sq.mm as per tender
specification & IS.
5.1.4 As per Above-7.1.1 (d) SITC of Mains 200 Mtr 151.00
wiring with 4 wire 2.5 sq.mm as per tender
specification & IS.
5.2.1 SITC of Point wiring for Light / Bell/ 85 Nos 415.00
Primary Point with 2nos. 1.5 sq.mm &
earth wire of 1.5 sq.mm (Green) both are
of ISI marked 1.1 KV grade FRLS PVC
insulated multi strand copper wires, length
, pipe to be erected with 6A Modular type
switch / bell push & accessories and earth
continuity of following type, erected on
PVC / Metallic/Wooden box, single
mounting base frame covered with
textured/metallic/white front plate modules
erected on / in wall / ceiling as per pipe
erected, with necessary Lamp
holder/ceiling rose / H.D.Connector as
directed with medium class Rigid PVC
pipe & accessories..
5.2.2 SITC of 6A independent Plug with 2 nos. 14 Nos 593.00
1.5 sq.mm Cu. Mains size wiring &
earthwire of 1.5 sq.mm (green) both are of
.ISI marked 1.1 KV Grade FRLS PVC
insulated multi strand copper wiress with
medium class rigid pvc pipe erected with
ISI marked 3 / 5 Pin socket and 6A
Modular type switch and accessories with
earth continuity of following type erected
on PVC / Metallic/Wooden box, single
mounting base frame covered with
textured/metallic/white front plate
modules erected on / in wall / ceiling as per
pipe erected. with necessary ceiling rose /
H.D.Connector as directed.
(1 No. Torrent HT Room, 1 No. for AMC
HT Room, 8 nos. at Pump House cum LT
Room & 4 No. Chlorination Room)
5.2.3 SITC of One 300/380 mm dia. Ex fan 16A 2 Nos 782.00
independent Plug point near Ex. Fan with
2nos. 4 sq.mm Cu. Mains size wiring
& earthwire of 1.5 sq.mm (green) both are
of ISI marked 1.1 KV grade FRLS PVC
insulated multistrand copper wires with
medium class Rigid PVC pipe and
accessories to be erected complete with
Modular type switch & 5 pin Plug erected
on PVC / Metallic/Wooden box covered
with appropriate front plate modules
erected on / in wall / ceiling as per pipe
erected with following type of accessories.
Plug point shall be near Ex.Fan. (For
Nos. Chlorination Room)
5.2.4 SITC of 5/15A independent Plug with 12 Nos 782.00
2nos. 4 sq.mm Cu. Mains size wiring &
earthwire of 1.5 sq.mm (green) both are
of ISI marked 1.1 KV grade FRLS PVC
insulated multistrand copper wires with
medium class Rigid PVC pipe and
accessories to be erected on wall / ceiling,
complete withModular type switch & 5 pin
Plug erected on PVC / Metallic/Wooden
box covered with appropriate front plate
modules erected on / in wall / ceiling as per
pipe erected with following type of
(For 1 no. Torrent HT Room, 1 no. AMC
HT Room, 1 no. Chlorination Room, 9 nos.
Pump House cum LT Room)
5.2.5 SITC of Single Phase 20A 3 Pin Metal clad 5 Nos. 845.00
Industrial Type Socket with plug top and
20A SPMCB, suitable for flush mounting,
in 16 SWG MS box of suitable size and
covered with 3 mm thick electrical grade
hylam sheet or eqivalent ISI marked
Electrical grade bakelite sheet and
earthing with 2.5 sq.mm insulated copper
wire run inside the conduit including
interconnections etc. complete as required.
(4 Nos. Pump House cum LT Room &
1no. HT Panel Room)
5.2.6 SITC of 3 watts LED Lamps integral 3 Nos. 69.00
type,cool white with PC diffuser suitable
for B22 LAMP holder.(For Panel room,
HT Room & chlorine room door)
5.2.7 1200 mm sweep ceiling fan, capacitor 12 Set 1,581.00
type, having double ball bearing 450mm
down rod, canopies, shackle, rubber bush,
blades, electronic speed regulator, suitable
to operate on 230V,50Hz AC supply
conforming to IS: 374/1979.Fan shall be
painted with white colour.
(1 Nos office room, 9 Nos LT Panel Room
Cum Pump House, and 1 No. HT Room
and 1 No.Torrent Room )
5.2.8 380 mm sweep 1400 R.P.M exhaust fan, 2 Nos. 3,052.00
capacitor type, having double ball
bearing, M.S.blades, mounting frame,
forearms, suitable to operate on 230V,50
HZ AC supply conforming to IS: 2312.Fan
shall be painted with epoxy grey colour
controlled by one 6 A flush type switch on
board and 6A plug point near Ex. fan.
(For 2 Nos. Chlorination Room)
6.1.1 LED LIGHT FIXTURES: 16 Nos 530.00
SITC of Indoor wall mounting LED indoor
fittings with LEDs of wattage 0.2 Watt to
0.5 Watt assembled on single MCPCB,
with housing used as a heat sink shall be
made of thick sheet Steel conforming to IS:
513/CRCA polyester powder coated and
high U.V. & corrosion resistance with
diffuser and/or Polycarbonate optics with
company mark/name 120 to 300 V,Power
Factor more than 0.9, THD < 10 %, CCT
4000 K to 6500K, Uniformity ratio >0.7,
Luminaire efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80
36 Watt or up to 25% higher wattage
Tube Light with integral / non-integral
driver, Surge-2KV, IP-20, 4 feet, Cat-III
(For 2nos. Torrent HT Room, 2nos. AMC
HT Room, 10 nos. pump House cum LT
Room, 2no. Chlorination Room)
6.2.1 SITC of Surface/Wall mounted LED 17 Nos. 6,028.00
Indoor Flood light fittings with High power
White LEDs wattage of 1Watt and above
assembled on single MCPCB, efficiency
more than 130 lm/w and corrosion free
High pressure die cast aluminum housing
with smooth finish powder coated and heat
sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company
mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95,
THD < 10 %, CCT
Uniformity ratio >0.45, Luminaire
efficacy> 85 lumens/watt . LED
driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80
90 Watt Indoor Flood Light (IP-65),
Surge -4KV Cat-III
(15Nos for pump house cum LT Panel
room, 2 Nos Chlorination room)
6.2.2 SITC of 'B' class galvanised iron pipe 32 17 Nos. 340.00
mm outside dia 45 cmslong duly welded on
20 cms x 20 cms x 3 mm thick M.S. base
plate, erected on wall or corner for
mounting luminaire with necessary
hardware materials duly painted for wall
mounting indoor flood light fixtures on
Wall of Buildings.
7.1.1 EXTERNAL LED LIGHT FIXTURES 20 Nos. 6,028.00
SITC of Wall mounted 80W LED
Outdoor Flood Light fittings with High
power White LEDs wattage of 1Watt and
above assembled on single MCPCB,
efficiency more than 130 lm/w and
corrosion free High pressure die cast
aluminum housing with smooth finish
powder coated and heat sink extruded
aluminium with diffuser and Polycarbonate
optics/ lenses with company mark/name
engraved or embossed 120 to 300 V,Power
Factor more than 0.95, THD < 10 %, CCT
5000 K to 5700K, Uniformity ratio >0.45,
Luminaire efficacy> 85 lumens/watt . LED
driver efficiency > 85 %. ( Each fittings
required LM-79 & LM-80 certificates)
Flood Light (IP-65), Surge -4KV,
(20 Nos for Area Lighting)
7.1.2 SITC of 'B' class galvanised iron pipe 20 Nos 340.00
32 mm outside dia 45 cms long duly
welded on 20 cms x 20 cms x 3 mm thick
M.S. base plate, erected on wall or corner
for mounting luminaire with necessary
hardware materials duly painted for
wall mounting indoor & outdoor flood
light fixtures on Wall of Buildings.
8.1.1 SAFETY ACCESSORIES 6 Nos 8,586.00
SITC of following safety accessories
complete with necessary fixing brackets,
other accessories and tools etc. as
required to complete the job.
Supply & Erecting carbon dioxide (CO2)
fire extinguisher of 6.5 kg capacity with
necessary clamps made from 50 x 6 mm
M.S. Flat with nut & bolts grouted in wall
8.1.2 Supplying stand first AID box with 4 Nos. 297.00
anticeptic cream, medicine for use on
wounds due burn, crepe bandage, guage
bandage, medicated ready to use bandage
(Band-aid) adhesive tape for medicinal
user, scissors, anticeptic solution (Savlon
or similar) etc.
(All above contents shall be of standard
(For Pump house Cum LT Room)
8.1.3 Providing printed instruction (First Aid) 3 Nos. 129.00
Chart both in English and Gujarati and
duly framed with front glasses, for
treatment of person suffering from electric
(1no. for HT Room & 1no. For LT Room
Cum Pump house))
8.1.4 Supplying & fixing of FIRE bucket 4 Set 212.00
round bottom of 9 litres capacity made out
of 24 guage G.I. sheet with extra handle at
bottom duly painted white inside and Red
outside with FIRE mark, filled with dry
sand and kept on stand provided or hung
8.1.5 Supplying and erecting floor mounting 1 Nos. 933.00
stand for keeping four nos. of FIRE
buckets comprising 1500 mm in length,
900 mm height frame made out of 30mm X
30 mm X 4 mm angle iron with cross
supports for legs, welded with 4 hooks and
duly painted with one coat of red lead and
two coats of approved enamelled silver
8.1.6 Supply and fixing of 30 W fluorescent 1 No. 6,319.00
lamp operated emergency light with
maintenance free battery for 3 hours
operation during mains power failure.LED
Portable/Rechargeable flood light having
die - cast aluminium enclosure designed
for maximum thermal efficiency of 130lm
luminous efficiency at voltage supply
between 140-270V AV/12V DC at
operating temperature of -20 degree to
60degree celcius with battery back up 3-
8.1.7 Supply and laying of Synthetic Insulating 6 Sq. 1,017.00
Mat of Class - B of min. thickness 2.5 mm Mtr
as per IS:15652 and with good electrical
insulation property for 11kV/22KV as per
site requirement.
8.1.8 Supply and laying of Synthetic Insulating 16 Sq. 763.00
Mat of Class - A of min. thickness 2 mm as Mtr
per IS:15652 and with good electrical
insulation property for 1.1KV/3.3KV as
per site requirement.
(for PMCC & APFC etc. Panels)
8.1.9 Providing pair of rubber hand gloves ISI 2 Nos. 212.00
make suitable for working on 22 KV
9.1.1 DISMANTLING, SHIFTING AND RE- 2 JOB 40,000.00
INSTALLTION (Existing Transformer)
Dismantling, Shifting and Re-installtion of
Transformers including loading, shifting
& unloading, Cable Connection and
Termination, all other required work for
complete job at site or as per instruction
given by the engineer In-Charge.
9.1.2 DISMANTLING, SHIFTING AND RE- 1 JOB 40,000.00
INSTALLTION (Existing HT VCB
Dismantling, Shifting and Re-installtion of
HT VCB Panel including loading, shifting
& unloading, Cable Connection and
Termination, all other required work for
complete job at site or as per instruction
given by the engineer In-Charge.
10.1.2 MISCELLANEOUS: 500 kg 64.83
Providing, Supply of Structure Steel at site
of work with freight, loading, unloading
carting, etc. including all taxes and duties
complete such as joints, channels, angles,
Iron Rails, ISA/ISMC/ISMB/MS flat,
Plates, Chequered plates (below 10mm
thickness) etc. required for support
structure of Elecrto-Mechanical
equipments etc. for support on floor / wall /
beam / brackets etc. as per tender and IS.
10.1.2 Labour Charges for lowering, laying, 500 kg 11.36
Fixing with fabrication various size section
of MS such as joints, channels, angles, Iron
Rails, ISA/ISMC/ISMB/MS flat, Plates,
Chequered plates etc Complete with two
coats of red oxide and two coats of
approved colour shade of epoxy paint as
per relevant IS and as per specification.
11.1.1 LIASONING CHARGES FOR 1 Ls 25,000.00
OBTAINING POWER / NOC:
Liasoning Charges for obtaining N.O.C
from Electrical Inspector / Statutory
authority for Power / Ele. Installation.
(Fees shall be paid by tenderer for
obtaining N.O.C. from Electrical Inspector
/ Statutory authority on behalf of client and
shall be reimbursed on submission of
orignial receipt to Client). Liasoning
Charges shall include preparing required
attasted documents & drawing for
obtaining NOC on behalf of client
(Applicable Fees / deposits shall be
reimburse by Client).
TOTAL ESTIMATE OF ELECTRICAL WORK (Without GST)
Name SITC of New Pumping Machinery with related Mechanical, Electrical and Instrumentation
of works with Five Years Operation and Comprehensive Repairing & Maintenance Work For
Work Augmentation of Underground Tank No.-5 at Dudheswar Water Work of AMC.
INSTRUMENTATION WORK
Item Qty Unit Amount
1.1.1 PRESSURE MEASURING SYSTEM 8 Nos. 1,412.00
Supply, installation, testing & commissioning of
Bourden type Pressure Guage glycerene filled
having 150 mm dial with necessary
fittings/accessories (Manifold valve, nipples, etc.
shall be in SS 316 only) as per specifications &
complete in all respects.
Range : 0 - 6 kg / sq.cm.
(On Each Delivery Side of VT Pump & 01 Nos
for Header Pipe).
1.1.2 Supply, installation, testing and commissioning of 7 Nos. 29,147.00
Blind Pressure Transmitter along with,
manifold valve, required fittings, tubing (all
valves, fittings, tubings, etc. shall be in SS
only) all accessories, hardware, etc. complete in
all respects as per specifications and having
following measurement ranges:
Range : 0 - 6 Kg/cm² (On Delivery of Side of
1.1.3 Supply, installation, testing and commissioning 1 Nos. 29,147.00
of Digital Pressure Transmitter with Display
along with, manifold valve, required fittings,
tubing (all valves, fittings, tubings, etc. shall be in
SS 316 only) all accessories, hardware, etc.
complete in all respects as per specifications and
having following measurement ranges:
Range : 0 - 6 Kg/cm² (On Main Header)
2.1.1 LEVEL MEASURING SYSTEM 1 Nos. 59,436.00
Supply, installation, testing and commissioning of
Ultrasonic type Level Transmitter along with all
required accessories with Large Display,
hardware, hardware, etc. complete in all respects
with local and remote display, as per specification.
The scope also includes providing 4" flanged
puddle pipe approximate 300 mm long including
fixing of the same in civil structure slabe of pump
house for mounting of level Transmitter.The work
also include all necessary work like make
hole,repair / modificationin existing slab,
etc.Level Transmitter having following
measurement ranges for liquid (Water)
Meas. Range: upto 9 m (at any one compartment
of sump) For Sump.
2.1.2 Supply, installation, testing and commissioning of 1 Nos. 12,802.00
Float type Level Switch along with 10 mtr. Cable
and WP Junction Box (at wet well for dry run
protection of pumps) complete in all respects and
as per specification.The scope also includes
providing 4" flanged , puddle pipe approximate
300 mm long including fixing of the same in civil
structure slabe of pump house for mounting of
level switch.The work also include all necessary
work like make hole,repair / modificationin
existing slab, etc.Meas. Range: upto 6 m (at any
one compartment of sump for dry run protection
2.1.3 Supply, installation, testing & commissioning of 1 Nos. 17,718.00
Float & Board type level indicator along with
all accessories, hardware, etc.
complete in all respects as per specifications and
having following measurement ranges:
Meas. Range: upto 6 m (at any one compartment
2.2.1 PLC BASED CONTROL PANEL FOR WDS: 1 Nos. 855,600.00
Supply, Installation, Testing & Commissioning of
PLC Based Instrument control Panel with 10"
Color Touch Screen HMI, 4G or Latest GPRS
modem for remote data transmission in future to
Central SCADA of AMC, Communication with
MFM at PMCC Panel, Ethernet Switch etc.,
Multiplication relay for Dry run protection of
pump, etc. Instrument Control Panel '(PLC
Enclosure / Panel ) with necessary PLC based
logic and wiring , Min 1 nos. flow
indicator/totalizer, Min. 1 no. process Indicator,
Min 2 no. analog signal multiplier, Min. 1 kVA
UPS (with 30 min backup alongwith filter for
harmonic, suitable rating SMF batteries alongwith
battery charger, cabling between UPS and battery
and all other accessories as per standard), etc.
complete in all respects and as per specs PLC
having minimum I/O count of 76DI / 34DO /
All work shall be carried out complete in all
respects and as per tender specification.
Nots: PLC Scada Panel should be hook-up to
Existing Central Scada Panel and all work shall be
carried out complete in all respects and as per
tender specification.
3.1.1 ELECTRO MAGNETIC FLOW METER 1 Nos. 1,110,650.00
Supply, installation, testing and commissioning of
remote type Full Bore type Electromagnetic flow
meter comprising of IP-68 Sensor, IP-65/66
remote transmitter with 10m cable between sensor
and transmitter,Panel mounted flow indicator cum
Totalizer along with all mounting accessories,
hardware, etc. complete in all respect and as per
specs and shall have following size and
measurement range. The scope also includes
necessary connection with header pipe.
Type of Sensor- Zero DN Full Bore type
Meter Size : 1200 mm Pipe
Material : C.I. / M.S.
4.1.1 INSTRUMENT CABLE & ACCESSORIES 400 MTR 141.00
'Supply, Laying, Installation, Connection,
Termination, Testing & Commissioning of
Instrument Cables, along with cable glands, lugs,
cable trays, required junction boxes, fittings and
accessores as per specs.
The unit rate shall include
a. Supply, loading & unloading of the cable at site
B. Shifitng of cable from site store to place of
c. Fixing of cable clamps, brackets, supports, route
markers etc. where ever required to fix the cables
d. Excavation, back filling and levelling of ground
alongwith laying of fine sand, protection bricks
and other necessary civil material for laying cables
outside the building.
e Testing and submission of sketches & reports of
all the cables laid.
4.1.2 CONTROL CABLE 500 MTR 123.00
4.1.3 CONTROL CABLE 500 MTR 260.00
4.1.4 SIGNAL CABLE 300 MTR 150.00
4.2.1 INSTRUMENT CABLE TRAYGI Perorated 150 MTR 302.00
type cable tray shall be made out of galvanized
MS sheets of 1.6 mm thickness with required
asccessories . All material shall be Hot dip
galvanised (816 g/m2) as per IS 2629 as
mentioned in specification and tray hardware shall
be in GI.50 x 50 mm - Perforated type
4.2.2 150 x 50 mm - Perforated type 50 MTR 420.00
4.3.1 CABLE END TERMINATION AND 60 Nos. 57.00
CONNECTION 'Supply, fixing, connection,
testing and commissioning of double compression
brass cable glands and crimping type Bimetalic
lugs / sockets with necessary tools and equipments
as specified in specifications and IS complete in
all respects. The glands and lugs / sockets shall be
suitable for cable size and type mentioned above.
The job also includes earthing the glands and
armour of the cable with common earth bar or
flexible copper mesh as applicable.POWER
CABLEa. 3C x 1.5sq.mm
4.3.2 CONTROL CABLE 60 Nos. 49.00
4.3.3 CONTROL CABLE 35 Nos. 113.00
4.3.4 SIGNAL CABLE 60 Nos. 41.00
5.1.1 EARTHING 4 Nos. 7,797.00
SITC of standard plate type earthing system
conforming to IS:3043 with latest amendment for
various electrical equipments and systems as per
'SITC of 600 x 600 x 3.15mm Copper. Plate type
Earth Pit etc. complete in all respects.Earthing
system shall be complete with following job as a
1)Excavation in hard murram.
2) Supply of copper plateelectode.
3) Supply & fixing of watering pipe, funnel,
4)Supply of civil material and preperation of brick
masonry earth pit chamber with C.I. frame and
covers of suitable size etc.
5)Supply and providing of charcoal and salt for
filling in earth pit. 6) Supply of tools and tackles
necessary for excavation to a desired depth and
doing necessary civil work etc. 7) Testing earth
resistivity before earthing and earth electrode
resistance after completion of work. 8) Supply and
fixing of Equipotential bar with housing alongwith
necessary mounting accessories. 9) Supply and
labour charges for interconnecting the earthing
stations to respective equipments, in built up
trenches, cable tray, walls / ceiling, buried in
ground etc. complete with required size of
earthing strip/wire. 10) Supply of earthing clamp,
5.1.2 SITC and labour charges for interconnecting the 30 Kg 787.00
earthing stations to respective equipments with
fixing accessories like earthing clamp, saddle etc.
in built up trenches, cable tray, walls / ceiling,
buried in ground etc complete with: 25 x 3 Copper
TOTAL ESTIMATE OF INSTRUMENTATION WORK (Without GST)
Name SITC of New Pumping Machinery with related Mechanical, Electrical and Instrumentation works
of with Five Years Operation and Comprehensive Repairing & Maintenance Work For Augmentation
Work: of Underground Tank No.-5 at Dudheswar Water Work of AMC.
Item Description Qty. Unit Rate Amount
1 OFFICE FURNITURE 1 Nos. 3,800.00
Office Table of size 1200 mm length X 600 mm width
2 Steel Office Chair 4 Nos. 1,500.00
3 Padestal fan: Min. 400 mm sweep, 230 v AC with 1 Nos. 2,000.00
speed regulator
4 Ladder: Ladder shall be made out of light aluminium 1 Nos. 6,200.00
allow of good strength. They shall be of step ladder,
foldable, self supportig type with sperader of metalic
angles or high strength.
Ladder: 3 Meter long
5 As per Item No.4 1 Nos. 10,000.00
Ladder: 6 Meter long
6 Steel Cupboard (min.W X H X D: 900 mm X 2 Nos. 20,000.00
GRAND TOTAL OF TOOLS, TEST EQUIPMENTS & SPARE PARTS
GRAND TOTAL OF TOOLS, TEST EQUIPMENTS & SPARE PARTS
Note: Above items shall be handed over to AMC before the commencement of O&M period for new
proposed Water Distribution Station at Dudheswar water Work in Central Zone of AMC.
Ahmedabad Municipal Corporation
Estimate: OPERATION & MAINTENANCE
Name SITC of New Pumping Machinery with related Mechanical, Electrical and Instrumentation
of works with Five Years Operation and Comprehensive Repairing & Maintenance Work For
Work Augmentation of Underground Tank No.-5 at Dudheswar Water Work of AMC.
Name of Ward CENTRAL ZONE
Name of WDS TANK NO.-5, DUDHESWAR WATER
With PF, ESI, WC Policy etc.
Item Per Rate per
Item of Work Qty. Amount in
1 ITI Operator (1 Person per shift) Shift 3 20,785.00
Comprehensive repairing, spares and maintenance Job 1 2,000.00
of entire works (Routine, Preventive, breakdown
Maintenance of all LT Ele. -Mech. Equipment
incl. pumping machineries HSCF, VT, SCF,
2 Polder, Mono block & leakage pumps etc.) along
with labour, administration & management
charges including running office, cost of
lubricants, consumables, spares, tools, statutory
periodical approvals & testing of equipment’s etc.
Routine, Preventive, breakdown Maintenance of Job 1 2,000.00
3 HT Panel and Transformer.
(02 Times per Year)
Chlorination system maintenance (2 plant + Job 1 7,000.00
chlorine cylinder transportation + Connection &
Disconnection of cylinder) and Auto Shut off
Valve safety system Maintenance & Leak
Detection and chlorine scrubber System
maintenance including caustic solution top up.
Cleaning works of Building & Campus of WDS Shift 2 10,000.00
(Cleaning Helper- 1 Person per shift)
11 Final Amount per Month/WDS
12 Total Amount For 5 year/WDS
12 Total Amount For 5 year/WDS
Total Amount For 5 year/WDS Say Rs.
Total Amount For 5 year/WDS Say Rs.
Name SITC of New Pumping Machinery with related Mechanical, Electrical and
of Instrumentation works with Five Years Operation and Comprehensive Repairing
Work & Maintenance Work for Augmentation of Underground Tank No.-5 at
Dudheswar Water Work of AMC.
Item Qty Unit Rate Amount
Existing 2700 m3/hr. SCF Pump-Motor set with 5 Nos.
1 All Pumping Machinery Like Valves, Pipes,
Expansion Bellow etc.
Existing 1500 m3/hr. SCF Pump-Motor set with 2 Nos.
2 All Pumping Machinery Like Valves, Pipes,
Expansion Bellow etc.
3 Existing LT PMCC Panel 1 Nos.
4 Existing APFC Panel. 2 Nos.
5 Existing Soft Starter Cubicle Panel 7 Nos.
6 Removed L.T Cables as per Site Availability 1 Lot.
TOTAL OF BUYBACK AMOUNT (In Rs.)
The rate of the items shall be deducted from the capital cost of the tender and
contractor shall carryout all items.
AMC will take final decision whether to sell item or not. If AMC does not sell
particular item, the bidder will not get rebate amount of that item.
Signature of Contractor Additional City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01. Technical Bid.pdf
02A. Technical Specification Civil.pdf
02B. Technical Specification EandM.pdf
03. Financial Bid.pdf
04. Tender Drawings.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .