| 1 | L1₹46.0 LAccepted-AOC DOOR NO 38 I H COLONY MALKAPURAM POST VISAKHAPATNAM 530 011 | VISAKHAPATANAM | ANDHRA PRADESH | 530011 | ₹46.0 L Quoted ₹46.3 L | L1 | Accepted-AOC Lowest Bid Accepted |
| 2 | L2₹59.6 L+₹13.3 L (28.7%)Rejected-Finance | ₹59.6 L+₹13.3 L (28.7%) | L2 | Rejected-Finance Not Being Lowest Bidder |
| 3 | Rejected-Technical | - | - | Rejected-Technical Due to No remark in WLR and complaint lodged by one more partner due to dispute in partnership deed |
| 4 | Rejected-Technical DOOR NO 2 31 23 SECTOR 7 SBI COLONY MVP VISAKHAPATNAM 530 017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | - | - | Rejected-Technical being not enlisted with category c vi |
Tender Value
₹42.5 L
EMD Value
₹85,000
Closing Date
23 Mar 2022, 6:00 pmClosed
Shri VK Tiwari, IDSE, Commander Works Engineer
Commander Works Engineers, Station Road, Visakhapatnam - 530 004
SPECIAL REPAIRS FOR REPLACEMENT OF BER FIRE PUMPS AT NAD and MO, VISAKHAPATNAM
2022_MES_499873_2
82218 / E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Visakhapatnam
Class D
Category c vi
9 documents required · 9 mandatory
₹500
Yes
Garrison Engineer Utility - II
₹85,000
Yes
13 Apr 2022
2 Mar 2022
28 Mar 2022
2 Mar 2022
23 Mar 2022
9 Mar 2022
Amount
Dismantling existing BER Electric Driven Pump Set from the foundation, disconnecting all electric connections, demolition of existing PCC Foundation of any description, removing rubbish / debris to outside MD land and transporting the Pump Set to MES Store Yard including necessary T & P complete all as specified and as directed.
Dismantling existing BER Diesel Driven Fire Pump Set from the foundation, disconnecting all electric connections, demolition of existing PCC Foundation of any description, removing rubbish / debris to outside MD land and transporting the Pump Set to MES Store Yard including necessary T & P complete all as specified and as directed.
Dismantling existing BER Vertical Turbine Pump Set from the foundation, disconnecting all electric connections, demolition of existing PCC Foundation of any description, removing rubbish / debris to outside MD land and transporting the Pump Set to MES Store Yard including necessary T & P complete all as specified and as directed.
Supply, install, testing and commissioning of Fire Pump, Electrically Driven, Coupled with TEFC, 75 KW / 100 HP, 2970 RPM Motor, Horizontal Split Casing, Centrifugal type conforming to IS – 12469 with CI Casing, Bronze Impeller and Stainless Steel Shaft mounted on heavy duty bearings Suitable for continuous operation with Range of Operation 0 % to 150 % of rated capacity, suitable for operation 440 Volts, 3 Phase, 50 Hz, AC Supply, 2850 LPM discharge at 85 metres Head, with pressure of 3.5 KG / Sq.cm including PCC 1:2:4, Type B1, using 20mm graded aggregate as in Foundation complete all as specified and as directed.
Supply, install, testing and commissioning of Fire Pump, Diesel Engine Driven, of 112 HP Capacity, Horizontal Split Casing, Centrifugal type conforming to IS – 12469 with CI Casing, Bronze Impeller and Stainless Steel Shaft mounted on heavy duty bearings Suitable for continuous operation with Range of Operation 0 % to 150 % of rated capacity, for 440 Volts, 3 Phase, 50 Hz, AC Supply, 2850 LPM discharge at 90 metres Head, with pressure of 3.5 KG / Sq.cm including 2 Nos of 12 Volts, 180 AH Batteries and including PCC 1:2:4, Type B1, using 20mm graded aggregate as in Foundation complete all as specified and as directed.
Supply, install, testing and commissioning of Jockey Pump, Horizontal End Suction, Centrifugal type Conforming to IS – 12469 with CI Casing, Bronze Impeller and Stainless Steel Shaft mounted on heavy duty bearings suitable for automatic operation with non–overloading power characteristics for frequent Start/ Stop operations suitable for operating on 440 Volts, 3 Phase, 50 Hz, AC Supply, 300 LPM Discharge at 85 metres Head complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m deep in Soft / Loose soil for laying Cables / Pipes etc. complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick of excavated soil complete all as specified and as directed. Note: A deduction of 10% shall be made from total computed volume of filling to cater in bulk irrespective of machinery used for ramming.
Removal of excavated material [Soil] to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Supplying and laying MS ERW Pipe, 150 mm bore, Heavy Grade , conforming to IS – 1239 including all fittings as in Riser and Sprinkler or laid in floors or fixed to walls and ceilings with flanged/ welded joints including testing and taking down existing MS Pipe of any description and in any position complete all as specified and as directed. Note: The external surfaces of pipes shall be painted with 2 coats of synthetic enamel paint over a coat of Zinc chrome primer on exposed surfaces and the external surfaces of pipes hidden under ground shall be treated with a coat of corrosion resistant bituminous paint and the rate quoted shall be deemed to include for this provision also.
All as described in item No. 11 herein before but MS ERW Pipe of 100 mm bore
All as described in item No. 11 herein before but MS ERW Pipe of 80 mm bore
S & F in repairs Sluice Valve, Cast Iron body, Stainless Steel Spindle, Gun Metal Rings including Wheel for operation, Flanged and Drilled, 150 mm Dia, confirming to IS – 14846, Class PN –1.6, Long Body type including all Joints with Rubber Gasket and Jointing Materials, Bolts, Nuts, Washer complete all as specified and as directed.
S & F in repairs Sluice Valve, Cast Iron body, Stainless Steel Spindle, Gun Metal Rings including Wheel for operation, Flanged and Drilled, 100 mm Dia, confirming to IS – 14846, Class PN –1.6, Long Body type including all Joints with Rubber Gasket and Jointing Materials, Bolts, Nuts, Washer complete all as specified and as directed.
S & F in repairs Butterfly Valve, Cast Iron body, double Flanged and Drilled, 80 mm Dia, confirming to IS – 13095, Class PN –1.6, including all Joints with Rubber Gasket and Jointing Materials, Bolts, Nuts, Washer complete all as specified and as directed.
Supplying and laying 150mm bore Ductile Iron Pressure Pipes, Centrifugally Cast [Spun], Class “K-9” with Double Flanged ends [Screwed] confirming to IS – 8329 with inside Cement Motor Lining and Black Bitumen External coating in standard lengths suitable for jointing with Flat Rubber Gasket [SBR or EPDM] conforming to IS – 638, Nuts & Bolts including necessary DI specials such as bends [any type, radius and angle], tapers any type [straight, bend, increasing, decreasing or double socket etc], sockets, tail pieces, connecting pipes, tee pieces, single branch, “Y” junction, double branch, cross, collars, caps and plugs, adopters etc as required, including taking down existing unsv pipes complete all as specified and as directed.
Supplying and laying 100mm bore Ductile Iron Pressure Pipes, Centrifugally Cast [Spun], Class “K-9” with Double Flanged ends [Screwed] confirming to IS – 8329 with inside Cement Motor Lining and Black Bitumen External coating in standard lengths suitable for jointing with Flat Rubber Gasket [SBR or EPDM] conforming to IS – 638, Nuts & Bolts including necessary DI specials such as bends [any type, radius and angle], tapers any type [straight, bend, increasing, decreasing or double socket etc], sockets, tail pieces, connecting pipes, tee pieces, single branch, “Y” junction, double branch, cross, collars, caps and plugs, adopters etc as required, including taking down existing unsv pipes complete all as specified and as directed.
S & F in repairs Cast Iron Non Return Valve with bypass arrangement with suitable flanges, suitable for 150 mm bore pipes confirming to IS – 5312, Class PN –1.6, including necessary nuts, bolts, washers, rubber gasket etc for jointing complete all as specified and as directed.
S & F in repairs Cast Iron Non Return Valve with bypass arrangement with suitable flanges, suitable for 100 mm bore pipes confirming to IS – 5312, Class PN –1.6, including necessary nuts, bolts, washers, rubber gasket etc for jointing complete all as specified and as directed.
S & F in repairs Cast Iron Non Return Valve with bypass arrangement with suitable flanges, suitable for 80 mm bore pipes confirming to IS – 5312, Class PN –1.6, including necessary nuts, bolts, washers, rubber gasket etc for jointing complete all as specified and as directed.
S & F in repairs Foot Valve, Cast Iron Body, 150mm bore with Flanged ends, end lift type with brass strainers, any pattern with Bypass Arrangement and Confirming to IS – 4038, ISI Marked including all Joints with Rubber Gasket and Jointing Materials, Bolts, Nuts, Washer complete all as specified and as directed.
S & F in repairs Foot Valve, Cast Iron Body, 100mm bore with Flanged ends, end lift type with brass strainers, any pattern with Bypass Arrangement and Confirming to IS – 4038, ISI Marked including all Joints with Rubber Gasket and Jointing Materials, Bolts, Nuts, Washer complete all as specified and as directed.
S & F in repairs Pressure Gauge of Water Ranging from 0 to 14 Kg suitable for fixing at delivery side of pumpset including provision of suitable stop cock and necessary GI tube and fittings complete all as specified and as directed.
S & F in repairs Electrically operated Automatic Water Pressure Switch, operating pressure 0 to 10 Kg per Sq.cm., Universal type including provision of suitable mounting arrangement for installing of pressure swithc and providing necessary water supply and electro mechanical connections complete all as specified and as directed.
Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to 32 X 6mm GI Strip [Earth Lead] and GI pipe 50 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the Plate by means of GI Bolts & Nuts complete all as per Electrical Plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. including taking down old earthing complete all as specified.
S & F in repairs Earth continuity Conductor or main earthing lead made of GI Strip of size 32 X 6mm, fixed to wall on batten or recess or chases or burried in ground or fixed to poles or any other indicated situation including drawing through GI Pipe for earthing etc. complete all as specified and as directed.
Fabricating, Supplying, Installing on top of suitable flange hydrant line and testing of Air Cushion Vessel, made out of made of 300mm dia 4mm thick 1 mtr long MS sheet including provision of air release safety valve and necessary fittings including taking down of existing vessel complete all as specified and as directed.
Cutting Bituminous Road / Hardstanding etc. as required for Jointing / Laying Cables and Pipeline of width not exceeding 300mm and depth not exceeding 200mm and refilling after laying and making good with PCC 1:2:4, Type B1 using 20mm graded stone aggregate, 150mm thick and removing rubbish to a distance not exceeding 500m complete all as specified and as directed.complete all as specified and as directed.
Demolition of Brick / Stone Masonry built in Cement Mortar including all quoins arches pillars etc and removing rubbish to a distance not exceeding 50m complete all as specified and as directed.
M & L for brick work with Fly Ash bricks, straight or curved on plan exceeding 6 m mean radius built in Cement Mortar 1:4 complete all as specified and as directed.
M & L for Construction of Valve Chamber of size 900 X 900 X 900 mm internal size suitable for Sluice Valve, with PCC 1:4:8, Type D2, using 40mm graded aggregate for foundation, 200 mm thick Brickwork with Fly Ash Bricks in Cement Mortar 1:6, 40 mm thick PCC, 1:2:4, Type B1, using 20mm graded aggregate Coping, rendering in CM 1:4, 15 mm thick including demolition of existing valve chamber, necessary earth work excavation in any type of soil etc., removal of surplus soil off the premises complete all as specified and shown on drawing CEDD / TD / 119, Sheet No. 1 / 1 dated 20 August 1983, revised up to 21 September 1992.
S & F in repairs Factory made FRP Composite Tank / Chamber Cover of size 900 X 900mm made with standard designs conforming to IS: 1726-1991, having load bearing of 2.5 Ton including frame complete all as specified and as directed.
M & L for One coat of synthetic enamel paint on old painted steel surfaces of any description not other wise described over 10 cm width or girth incuding necessary preparation of surfaces complete all as specified and directed.
Continental Engineers and contractors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .