Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹3.7 L
Closing Date
2 Dec 2026, 3:00 pm6d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Vadodara Division: Electrical works in connection with extension of platforms, provision of Foot Over Bridges, raising of rail level platform at Nadiad, Kosamba, Panoli, Hathuran, Kosad and Chavaj stations.
BRC-EL-P-28-26-27~WR
BRC-EL-P-28-26-27
Open
Works - General
12 Months
Vadodara, Gujarat
₹0
₹3.7 L
4 Nov 2026
4 Nov 2026
18 Nov 2026
60 days
110 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 1,55,95,645 | ||
| — | 100.00 | — | — | ||
| Wiring of light/fan/exhaust fan points in PVC casing-capping/conduit - The price shall cover for wiring of light/fan/exhaust fan point with 1.5 sq. mm, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS and 1.0 sq. mm, single-core, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing-capping double lock type, ISI marked or medium grade PVC conduit of not less than 19 mm diameter, ISI marked as per site conditions with surface mounted molded polypropylene switch board with modular cover plate of suitable size including switches/angular holders/ceiling rose. Space shall be kept on board to accommodate modular electronic fan regulator. Molded polypropylene switch board shall be as per IS: 14772. The accessories shall be of modular type. | — | — | — | 36,500 | |
| — | 600.00 | — | — | ||
| Providing board with two switches and two sockets, 6 Amp - The price shall cover for wiring of multi-plug point (switch, 6 Amp - 2 Nos and socket, 6 Amp - 2 Nos) on separate surface mounted polypropylene switch board with modular cover plate of suitable module with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire in medium grade PVC casing capping, double lock type, ISI marked or medium grade PVC conduit of not less than 19 mm diameter, ISI marked as per site conditions at an approximate distance up to 3.0 meter or as per site requirement. PVC box shall be as per IS: 14772. | — | — | — | 1,45,200 | |
| — | 1040.00 | — | — | ||
| Wiring of sub-main with copper wire, single-core, 2.5 sq. mm in casing-capping/conduit - The price shall cover for wiring of two wire sub- main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked or medium grade PVC conduit of not less than 19 mm diameter, ISI marked as per site conditions. | — | — | — | 1,15,440 | |
| — | 1300.00 | — | — | ||
| Wiring of sub-main with copper wire, single-core, 4.0 sq. mm in casing-capping/conduit - The price shall cover for wiring of two wire sub- main with 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked or medium grade PVC conduit of not less than 19 mm diameter, ISI marked as per site conditions. | — | — | — | 1,52,100 | |
| — | 950.00 | — | — | ||
| Wiring of sub-main with copper wire, single-core, 4.0 sq. mm - 5 Nos and 2.5 sq. mm - 1 No in PVC conduit with junction box - The price shall cover for wiring of five wire sub-main with 4.0 sq mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with five wires of 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in green colour as earthing wire in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked or medium grade PVC conduit of not less than 19 mm diameter, ISI marked with heavy duty PVC junction box as per site conditions. | — | — | — | 1,79,550 | |
| — | 50.00 | — | — | ||
| Providing PVC junction box with eight-way connector - The price shall cover for supply and fixing of PVC junction box with eight way connector of reputed make and quality, ISI marked in existing sub-main and its connection from existing sub-main with 1.5 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor and 1.0 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor in green colour as earthing wire of 1100 Volt grade, ISI marked, conforming to relevant and latest IS. | — | — | — | 26,300 | |
| — | 510.00 | — | — | ||
| Providing PVC Junction box - The price shall cover for supply, fixing, testing and commissioning of pole mounted junction of SMC model No. GS-JB 3020 (1) of SINTEX or similar make for connecting the incoming and outgoing cables and connecting wire of street lights. Junction box shall be complete with suitable connectors and fuse unit for streetlight. Complete unit shall be mounted on the pole/wall/pillar by means of suitable hardware, terminal strips, cable glands, clamps etc. | — | — | — | 4,75,320 | |
| — | 85.00 | — | — | ||
| Fixing, testing and commissioning of ceiling fan - The price shall cover for fixing, testing and commissioning of ceiling fan on existing hook and its connection by FRPVC insulated, flexible copper cord, 1100Volt grade, 24/0.20mm from existing ceiling rose with earth connection. A suitable suspension clamp made from G.I. flat of 40 x 6 mm with MS 'S' shaped hook of diameter not less than 10 mm shall be provided as per site requirement if fan hook is not available and is included in the scope of work. The ceiling fans shall be supplied by railways at site in-charge's office/store. | — | — | — | 14,705 | |
| — | 10.00 | — | — | ||
| Providing Exhaust fan 300 mm sweep/heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 300 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade | — | — | — | 14,610 | |
| — | 6.00 | — | — | ||
| Providing Exhaust Fan, 380/400 mm sweep, industrial, heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 380/400 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade. | — | — | — | 12,300 | |
| — | 3.00 | — | — | ||
| Supply, installation, testing and commissioning of MCCB, four-pole, 100 Amp in outdoor type MS enclosure - The price shall cover for supply, fixing, testing and commissioning of MCCB, four-pole, 100 Amp, with thermal-magnetic release range 80 - 100 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle in sheet steel modular enclosure or pre-fabricated double-door enclosure of same make as the MCCB as far as possible. The enclosure should be suitable for outdoor installation conforming to IP: 65 protection. | — | — | — | 33,972 | |
| — | 10.00 | — | — | ||
| Providing lighting control board with MCB DP, 32 Amp - 1 No, Time Switch, 16 Amp - 1 No and Single-Phase Contactor, 32 Amp - 1 No - The price shall cover for supply, fixing, testing and commissioning of lighting control board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The board shall be equipped with MCB DP, 10 KA breaking capacity, 32 Amp rating - 1 No, Time switch, 16 Amp - 1 No and Single phase contactor of rating 32 Amp - 1 No. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 42,110 | |
| — | 12.00 | — | — | ||
| Providing Distribution Board with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two pole, 25 Amp - 1 No and outgoing MCB DP 6/10 Amp - 5 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer MCB DP 16/32 Amp - 1 No, RCBO, two-pole, 30 mA sensitivity, 25 Amp - 1 No and outgoing MCB SP, 6/10 Amp - 5 Nos. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 1,06,920 | |
| — | 4.00 | — | — | ||
| Providing Distribution Board with incomer MCB TPN, 63 Amp - 1 No, outgoing MCB DP, 16/20/32 Amp - 6 Nos with Time Switch, 16 Amp - 1 No and Single-Phase Contactor, 32 Amp - 1 No - The price shall cover for supply, fixing, testing and commissioning of lighting control board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The board shall be equipped with incomer MCB TPN, 63 Amp - 1 No, outgoing MCB DP, 16/20/32 Amp - 6 Nos, Time switch, 16 Amp - 1 No and Single phase contactor of 32 Amp rating - 1 No. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 52,568 | |
| — | 3.00 | — | — | ||
| Providing Distribution Board with incomer SFU, four-pole, 125 Amp - 1 No and outgoing Changeover Switch, four-pole, 63 Amp - 1 No, SFU, four-pole, 63 Amp - 4 Nos and MCB DP, 32 Amp - 4 Nos with bus-bar arrangement, indication lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 79,371 | |
| — | 3.00 | — | — | ||
| Providing outdoor type, wall/floor mounted, double-door, Distribution Board with incomer MCCB, four-pole, 63 Amp - 1 No and outgoing MCB,TPN, 40 Amp - 4 Nos, MCB DP, 20 Amp - 2 Nos, Time Switch, 16 Amp - 2 Nos and Single-Phase contactor, 32 Amp - 2 Nos with multifunction meter, indication lamps, bus-bar, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 81,129 | |
| — | 4.00 | — | — | ||
| Providing lighting control board with incomer MCCB, four-pole, 63 Amp - 2 Nos, outgoing MCB DP, 32 Amp - 8, Time Switch, 16 Amp - 6 Nos and Single-Phase Contactor, 32 Amp - 6 Nos - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 1,14,444 | |
| — | 4.00 | — | — | ||
| Providing Distribution Board with incomer MCCB, four-pole, 63 Amp - 1 No, RCBO, four-pole, 40 Amp - 1 No and outgoing MCB TPN, 32 Amp - 2 Nos and MCB DP, 16 to 32 Amp - 8 Nos - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 1,37,988 | |
| — | 2.00 | — | — | ||
| Providing outdoor type, double-door, wall/floor mounted, Distribution Board with incomer MCCB, four-pole, 100 Amp - 1 No and outgoing MCCB, four-pole, 63 Amp - 3 Nos with indication lamps, bus-bar, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three- phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 79,368 | |
| — | 3.00 | — | — | ||
| Providing outdoor type, double-door, wall/floor mounted, Distribution Board with incomer MCCB, four-pole, 100 Amp - 2 Nos and outgoing MCCB, four-pole, 63 Amp - 2 Nos with multi-functional meter, indication lamps, bus-bar, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 1,38,567 | |
| — | 9.00 | — | — | ||
| Providing Distribution Board with incomer MCCB, four-pole, 125 Amp - 1 No and outgoing MCCB, four-pole, 63 Amp - 4 Nos with multifunctional meter, indication lamps, bus-bar, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 4,22,928 | |
| — | 4.00 | — | — | ||
| Providing Distribution Board, outdoor type, double-door, wall/floor mounted with incomer MCCB, four-pole, 100 Amp - 2 Nos, outgoing MCB, TPN, 32/40 Amp - 2 Nos, MCB DP, 25/32 Amp - 8 Nos, Time Switch, 16 Amp - 2 Nos and Single-Phase Contactor, 32 Amp - 2 Nos with multifunctional meter, indication lamps, bus-bar, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 2,17,812 | |
| — | 4.00 | — | — | ||
| Providing Distribution Board, outdoor type, double-door, wall/floor mounted, with incomer MCCB, four-pole, 125 Amp - 2 Nos and outgoing MCCB, four-pole, 100 Amp - 2 Nos, MCCB, four-pole, 63 Amp - 2 Nos and MCB TPN, 32 Amp - 2 Nos with multifunctional meter, indication lamps, bus-bar, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 3,25,060 | |
| — | 1.00 | — | — | ||
| Providing Distribution Board outdoor-type, double-door, wall/floor mounted with incomer MCCB, four-pole, 200 Amp - 2 Nos and outgoing MCCB, four-pole, 125 Amp - 4 Nos and MCCB, four-pole, 63 Amp - 4 Nos with multi-functional meter, indication lamps, bus-bar arrangement, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 2,48,101 | |
| — | 3.00 | — | — | ||
| Providing Distribution Board, outdoor type, double-door, wall/floor mounted, with incomer MCCB, four-pole, 250 Amp - 2 Nos and outgoing MCCB, four-pole, 125 Amp - 4 Nos and MCCB, four-pole, 63 Amp - 4 Nos with multifunctional meter, indication lamps, bus-bar, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design.The LT panel shall be indoor/outdoor type, double-door, rectangular cubicle type, dust and vermin proof suitable for floor mounting for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 8,61,213 | |
| — | 1798.00 | — | — | ||
| Digging of cable trench 450/600 mm wide and 900 mm deep in all types of soil including hard, rocky etc. - The price shall cover for digging of 450/600 mm wide and 900 mm deep trench in all types of soil including soft, rocky as per cable route plan and filling back the trench after laying of cables. This also includes clearing of roots of trees and bushes and other temporary obstructions on the selected route. | — | — | — | 2,31,942 | |
| — | 3900.00 | — | — | ||
| Digging of cable trench 100 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of cable in HDPE pipe, 50 mm diameter - The price shall cover for digging of cable trench of size 100 x 200 mm deep in concrete/tar road/platform surface and its refilling/ plastering after laying of cable in 50 mm diameter HDPE pipe in existing trench. Supply and laying of HDPE pipe, 50 mm diameter is included in the scope of work. | — | — | — | 15,83,400 | |
| — | 850.00 | — | — | ||
| Supply and laying of RCC half round pipe, 150 mm diameter - The price shall cover for supply of half round RCC pipes of 150 mm inner diameter and 1.0 meter in length as per given description in Annexure-XXI of tender document. The internal surface shall have a smooth finish without any bulge or projections to avoid damage to the cable. The price shall also cover for laying of half round RCC pipes above the cables for mechanical protection on laid cables in the existing trench. After laying of RCC half round pipe, the trench shall be filled up with soil available thereby. | — | — | — | 64,600 | |
| — | 2280.00 | — | — | ||
| Supply and laying of DWC pipe, 63 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 63 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively.The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 1,91,520 | |
| — | 500.00 | — | — | ||
| Supply and laying of DWC pipe, 75 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 75 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively.The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 68,000 | |
| — | 650.00 | — | — | ||
| Supply and laying of DWC pipe, 120 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 120 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively.The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 1,07,900 | |
| — | 550.00 | — | — | ||
| Providing uPVC pipe, 50 mm diameter - The price shall cover for supply of uPVC pipe of 50 mm nominal bore diameter and working pressure of 14 kg/sq. cm along with coupling, elbow, tee etc. for protection of cable. The upright cable shall be encased in uPVC pipes for mechanical protection. The pipe shall be clamped with flat MS clamp at each location on upright cable length. uPVC Pipe shall be as per ASTM-D: 1785, Sch-80.The price shall also cover for laying the uPVC pipes in ground/road and under the track by digging open trench method. Each length of the pipes shall be joined together using proper size of uPVC coupler and properly aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 97,350 | |
| — | 600.00 | — | — | ||
| Supply and fixing of PVC maxi trunking of size 100 x 50 mm - The price shall cover for supply, fixing, testing and commissioning of ISI marked PVC Maxi Trunking of size 100 x 50 mm with all accessories. The PVC Maxi trunking shall be fixed at site by fabricated clamp of 18 SWG GI sheet at a distance not more than 1.5 meters by machine screw/GI nut bolts, washers etc. The existing power cables shall be laid in the PVC Maxi trunking properly dressed and secured by means of suitable clamps/fasteners etc. | — | — | — | 3,00,000 | |
| — | 730.00 | — | — | ||
| Supply and laying of HDPE pipe, 110 mm diameter by pushing method under track/road - The price shall cover for supply of HDPE (High Density Polyethylene) pipe of 110 mm nominal diameter as per IS 4984-1995 with accessories required for laying such as coupler, bend etc. as per description given in Annexure-XXI of tender document. The price shall also cover for laying the HDPE pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 11,03,760 | |
| — | 320.00 | — | — | ||
| Supply and erection of G.I. perforated cable tray of size 150 x 100 x 100 mm on MS frame with cover - The price shall cover for fabrication, supply and fixing of M.S. perforated cable tray, hot dip galvanized as per latest ISS/BSS of size 150 x 100 x 100 mm and 2.0 mm approximate thickness with appropriate cover of thickness 1.6 mm. The cable tray shall be fixed horizontally or vertically at site and the existing LT cables shall be laid/shifted in the cable tray by disconnecting from the panel/switch end and reconnecting as per site requirement duly tied with suitable clamps with GI nuts, bolts and washers in a safe and secure manner. The fixing clamps shall be fabricated from 50 x 50 x 6 mm MS angle or 50 x 6 mm MS flat duly painted and fixed at approximate distance of 1.5 to 2.0 meter apart with 2" long dowel/fisher rack bolts. The tray shall be fabricated in lengths of 2.0 m and couplers shall be provided at joints. The cable tray cover shall be fixed with GI screws. | — | — | — | 2,91,200 | |
| — | 550.00 | — | — | ||
| Supply and erection of G.I. perforated cable tray of size 200 x 100 x 100 mm on MS frame with cover - The price shall cover for fabrication, supply and fixing of M.S. perforated cable tray, hot dip galvanized as per latest ISS/BSS of size 200 x 100 x 100 mm and 2.0 mm approximate thickness with appropriate cover of thickness 1.6 mm. The cable tray shall be fixed horizontally or vertically at site and the existing LT cables shall be laid/shifted in the cable tray by disconnecting from the panel/switch end and reconnecting as per site requirement duly tied with suitable clamps with GI nuts, bolts and washers in a safe and secure manner. The fixing clamps shall be fabricated from 50 x 50 x 6 mm MS angle or 50 x 6 mm MS flat duly painted and fixed at approximate distance of 1.5 to 2.0 meter apart with 2" long dowel/fisher rack bolts. The tray shall be fabricated in lengths of 2.0 m and couplers shall be provided at joints. The cable tray cover shall be fixed with GI screws. | — | — | — | 4,97,750 | |
| — | 6700.00 | — | — | ||
| Laying of cable in trench - The price shall cover for laying, testing and commissioning of LTUG armoured cable in existing trench/pipe and its connection at both ends. The cable shall be tested with 500 Volt Megger earth tester before laying it in the trench. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to this office as well as site in-charge after laying of cable. Cables shall be supplied by railways at site engineer's stores. | — | — | — | 1,40,700 | |
| — | 3020.00 | — | — | ||
| Laying of cable on wall/cover shed/existing tray with MS clamp - The price shall cover for laying, testing and commissioning of LTUG armoured cable on wall/cover shed/in existing tray and its connection at both ends. The cable shall be tested with 500 Volt Megger before laying it in the tray. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to site engineer and Divisional Office after laying of cable. | — | — | — | 99,660 | |
| — | 35.00 | — | — | ||
| Supply, fixing, testing and commissioning of 5.0 meter height G.I. street light octagonal pole, double arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0 meter height double arm, G.I. street light octagonal pole as per the specifications mentioned in Annexure-XXI of tender document. | — | — | — | 5,41,275 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of 5.0 meter height G.I. multipurpose octagonal pole, double arm, for mounting of Street Light fitting, Coach Guidance Board, Public Address System and CCTV camera complete with all accessories, junction boxes and foundation etc. - The price shall cover for supply, fixing, testing and commissioning of 5.0 meter height double arm, G.I. multipurpose, octagonal pole for mounting of platform light fitting, Coach Guidance Board, Public Address System and CCTV camera as per the below mentioned specifications. There shall be a common template minimum for 15 poles. Detailed specifications are given in Annexure-XXI of tender document. | — | — | — | 22,50,000 | |
| — | 1390.00 | — | — | ||
| Design, manufacture, display, installation of wall/hanging/floor mounting type signage/ directional boards in flat/half elliptical/Parabolic/Triangular shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2.0 mm thickness. The text/graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed/ router cut on monomeric calendared vinyl of 70 um thickness and shall be firmly pasted on display sheets/Retro Reflective Boards. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement to be provided by the contractor with their own materials, labour, all Tools & Plants, lead, lift, transportation etc including all applicable taxes. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The scope of work covers various stations of Vadodara division. The work shall be carried out as per the "Guidelines on Standard Signages at Stations on Indian Railways, 2023" issued by the Ministry of Railways, Government of India. The work shall be executed strictly as per the specifications given in the document which is attached as Annexure. Colour scheme, font sizes, directional arrows, materials, fabrication, text, pictogram shall be as given in the document. | — | — | — | 30,42,710 | |
| — | 2300.00 | — | — | ||
| — | 1550.00 | — | — | ||
| — | 275.00 | — | — | ||
| — | 58.00 | — | — | ||
| — | 60.00 | — | — | ||
| Removal of unused existing rail poles complete with over head line spans and other accessories and shifting of the released materials - The price shall cover for removal of existing rail/tubular poles complete with structure, overhead line spans and other accessories by digging pole from base with required tools, tackles and manpower in a safe and secure manner. The dismantled rail/round poles, cross-arms, insulators, M.S. clamps, G.I. pipes and released fittings if any shall be segregated, transported and handed over to the site engineer at his office/stores with challan. | — | — | — | 1,38,300 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TechSpecsofEnergyEfficientLEDBasedLuminaire.pdf
ATTACHMENT
RailwayBoardsletterNo.2018_CE-I_CT_9dated04.06.18.pdf
ATTACHMENT
WesternRailwaysSpecificationsforACBLTPanelsMCCBandMCB.pdf
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf
ATTACHMENT
BankGuaranteeverification.pdf
ATTACHMENT
TenderDocument-BRC-EL-P-28-26-27NEWGCC.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .