Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.9 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹20.1 L+₹65,370 (3.35%)Rejected-AOC | L2 | Rejected-AOC REJECTED | |
| 3 | L3₹21.2 L+₹1.7 L (8.77%)Rejected-AOC PLOT NO 626 627 GIDC BEHIND GANGOTRI DIARY PORBANDAR 360 577 | PORBANDAR | GUJARAT | 360577 | L3 | Rejected-AOC REJECTED | |
| 4 | L4₹22.0 L+₹2.5 L (12.9%)Rejected-AOC 13 THAKKAR PLOT DEEPAK KUNJ PORBANDAR 360575 | PORBANDAR | GUJARAT | 360575 | L4 | Rejected-AOC REJECTED |
Tender Value
₹19.5 L
EMD Value
₹39,000
Closing Date
7 Nov 2020, 6:00 pmClosed
GE I CG PORBANDAR
Military Engineer Services, GE I CG Porbandar, DHQ No. 1, Opp. Birla Cement Factory, Porbandar-360575
REPAIR/ MAINTENANCE OF INTERNAL ELECTRIFICATION, MAINTENANCE OF ACs, GEYSERS AND WATER COOLER ETC AT CG DHQ-01, CG JETTY AND CGAE PORBANDAR
2020_MES_384805_2
8555
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DHQ-01, CG JETTY, ICGAE PBR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I CG PORBANDAR
₹39,000
Yes
21 Dec 2020
22 Oct 2020
9 Nov 2020
22 Oct 2020
7 Nov 2020
26 Oct 2020
Amount
SCHEDULE 'A'
Taking down carefully burnt out aluminium/copper wires from concealed point wiring without removing/ taking down conceled conduit and terminal boxes (light, fan, socket or power) complete (fittings such as switches, ceiling roses, pendent, regulators, sockets, flourescent tube light fittings etc to be measured and paid for seprately) and stacking materials properly for removing under schedule of credit and making good the disturbed surfaces of walls/ceilings and floors etc complete all as spd and directed. Note: (i) Existing MS sunken terminal and conduit boxes need not be removed. (ii) Cover plate of terminal box shall be removed.
Disconnecting of unserviceable sub main wiring of any size and removing wires from existing concealed conduit & removing from site and making good the disturbed surfaces. Note: (i) Existing concealed conduit boxes need be removed.
Disconnecting electric connections and taking down old unserviceable MCB SPN/SP/TP and DB's of any capacity.
M&L point wiring complete with copper conductor 1.5 sqmm single core PVC insulated but unsheathed multistranded conductors FRLS, 1100 Volts grade, drawn through existing conduit including 1.5 sqmm PVC insulated but unsheathed multi stranded copper conductor FRLS cable as earth continuity wire with cover plate fixed on existing terminal boxes,complete all as specified and directed. Make of wire: Finolex/RR Cables/Havells/Anchor (a)One light point controlled by one, one way switch
(b) One fan/Exhaust point controlled by one, one way switch.
(c) One 3 pin 6 Amps socket outlet on same board.
(d) One 3 pin 6 Amps socket outlet on independent board .
(e) One light point controlled by two 2 – way switches ,
(f) One bell/buzzer point controlled by one switch
M&L point wiring complete with copper conductor 2.5 sqmm single core PVC insulated but unsheathed multistranded conductors FRLS, 1100 Volts grade, drawn through existing conduit including 2.5 sqmm PVC insulated but unsheathed multi stranded copper conductor FRLS cable as earth continuity wire with cover plate fixed on existing terminal boxes,complete all as spd and directed. Make for cable Polycab/RR/ANCHOR/Havells Note: (i) Existing MS sunken terminal and conduit boxes need not be removed. (ii) Cover plate of terminal box shall be removed.
S&F bell ding dong type, AC, 230 volt, single pole Make : Anchor/Cona/SSK/MDS
S&F bell push piano flush button type 5 Amp. Make : Anchor/Cona/SSK/MDS
S&F ceiling fan regulator electronic type rotary four step . Make : Anchor/Cona/SSK/MDS
S&F switch piano flush type 5 amps, single pole one way 240 volts. Make : Anchor/Cona/SSK/MDS
S&F Socket outlet 3 Pin 5/6 Amp flush type. Make : Anchor/Cona/SSK/MDS
Switch socket combination 2 in 1, 3 pin, 5 and 15 Amp flush type universal Make : Anchor/Cona/SSK/MDS
S&F of ceiling rose, surface type bakelite 65x17.5mm, three terminals, complete all as specified and directed. Make : Anchor/Cona/SSK/MDS
M&L Point wiring complete with 1.5 Sqmm single core PVC Insulated but unsheathed multistranded copper conductor FRLS cable 650/1100 Volt grade down through and including non metallic rigid PVC heavy duty concealed conduit, min 20mm external dia,, but shall be increased to suitable size, as per requirement in accordance with clause 19.125 of SSR Part I, ISI marked, including conduit accessories like bends,tees,junction box etc fixed concealed/recessed in wall or ceiling etc including 1.5 Sqmm earth wire, single core PVC insulated but unsheathed multistranded copper conductor FRLS cable as earth continuity wire including Modular metal flush box of suitable size for the following:- Note: Cost of cutting / chasing on wall and making good after repair shall be deemed to be included in quoted rate . Make for cable : Havells/RR CABLES/Polycab/Anchor (a) One light controlled by one, one way switch
(b) One fan point/Exhasut fan controlled by one, one way switch
(c) One 3 pin 6 Amps socket outlet on same board
(d) One 3 pin 6 Amps socket outlet on independent board .
(e) One bell/buzzer point controlled by one switch
(f) One light point controlled by two 2 – way switches ,
M&L Point wiring complete with 2.5 Sqmm single core PVC Insulated but unsheathed multistranded copper conductor FRLS cable 650/1100 Volt grade down through and including non metallic rigid PVC heavy duty concealed conduit, min 20mm external dia,, but shall be increased to suitable size, as per requirement in accordance with clause 19.125 of SSR Part I, ISI marked, including conduit accessories like bends,tees,junction box etc fixed concealed/recessed in wall or ceiling etc including 2.5 Sqmm earth wire, single core PVC insulated but unsheathed multistranded copper conductor FRLS cable as earth continuity wire including Modular metal flush box of suitable size for the following:- (a) one 3 pin 15 or 16 Amps socket on the independent board with the required modules. Note: Cost of cutting / chasing on wall and making good after repair shall be deemed to be included in quoted rate . Make for cable : Havells/RR CABLES/Polycab/Anchor
S&F Modular switch 1 way, 6 Amps, 1 modular (ISI marked).complete all as specified and as directed. Make Anchor ABB/Cona/Legrend
S&F Modular switch 1 way, 16 Amps, 1 modular (ISI marked).complete all as specified and as directed. Make Anchor ABB/Cona/Legrend
S&F Modular socket, 6 Amps, 2/3 pin combind 2 module (ISI marked).complete all as specified and as directed. Make Anchor ABB/Cona/Legrend
S&F Modular socket, 6/16 Amps, 2/3 pin combind 2 module (ISI marked).complete all as specified and as directed. Make Anchor ABB/Cona/Legrend
S&Fmodular fan regulator, 120 watt, 2 moduler (ISI marked).complete all as specified and as directed. Make Anchor/ ABB/Cona/Legrend
M&L Point wiring complete with 4.0 Sqmm single core PVC Insulated but unsheathed multistranded copper conductor FRLS cable 650/1100 Volt grade down through and including non metallic rigid PVC heavy duty concealed conduit, min 20mm external dia,, but shall be increased to suitable size, as per requirement in accordance with clause 19.125 of SSR Part I, ISI marked, including conduit accessories like bends,tees,junction box etc fixed concealed/recessed in wall or ceiling etc including 4.0 Sqmm earth wire, single core PVC insulated but unsheathed multistranded copper conductor FRLS cable as earth continuity wire including Modular metal flush box of suitable size for the following:- (a) one 3 pin 15 or 16 Amps socket on the independent board with the required modules. Note: Cost of cutting / chasing on wall and making good after repair shall be deemed to be included in quoted rate . Make for cable : Havells/RR CABLES/Polycab/Anchor
M&L Sub main wiring with two runs of 2.5 sqmm single core PVC insulated but unsheathed multistranded copper conductor FRLS 1100 Volts grade cable fire retardant low smoke drawn through and including PVC concealed conduit heavy duty grade ISI marked 25mm dia (external) including conduit accessories like bends, tees, junction boxes etc including 2.5 sqmm PVC insulated but unsheathed multistranded copper conductor FRLS cable as earth continuity wire fixed complete all as specified and directed. Note: Cost of cutting / chasing on wall and making good after repair shall be deemed to be included in quoted rate . Make of cable: Havells/ Finolex/ RR Kable/ KEI
M&L Sub main wiring with two runs of 4.0 sqmm single core PVC insulated but unsheathed multistranded copper conductor FRLS 1100 Volts grade cable fire retardant low smoke drawn through and including PVC concealed conduit heavy duty grade ISI marked 25mm dia (external) including conduit accessories like bends, tees, junction boxes etc including 4.0 sqmm PVC insulated but unsheathed multistranded copper conductor FRLS cable as earth continuity wire fixed complete all as specified and directed. Note: Cost of cutting / chasing on wall and making good after repair shall be deemed to be included in quoted rate . Make of cable: Havells/ Finolex/ RR Kable/ KEI
S&F 20W surface/Wall mounted LED Luminaire , with high efficiency long life LED chips, CRI=80(Minimum) PF>.95, System luminous efficacy >100, Operating voltage 140V-270V including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to LED fitting Complete all as spd and as directed by engineer-in-charge. Make: Philips Cat No BN 308C-LED-2220S-6500/ Osram cat No Luxpower Batten 19WL840/Wipro
S&F in replacement MCB Distribution box,12way for MCB SPN, 415 Volts, double door powder coated sheet metal enclosure confirming to IP 65 including standard bus bar fixed on existing bricks/stone wall in semi-concealed type including (i) MCB SPN 40 Amps 'C' series 10 KA - 01 No (ii) MCB SP 6 to 32 Amps 'C' series 10 KA - 10 Nos all as spd in repair. Make:- Legrand / Schneider/ Hager /L&T /Hensel /
S&F MCB DB SPN, 8 Way, Double door, IP 43 Protection with acrylic door and connected accessories like insulated busbars, neutral bars & earth bar, blanking plates complete all as spd and directed and comprising of following. Make Legrand/Siemens/Schneider a) Incoming MCB 40-63 Amp TP 415 Volt , C series 16 KA ---01 Nos (b) Outgoing MCB 6 to 32 Amp, SP 10 KA C series ---02 Nos (c) Outgoing MCB 20 Amp, SP10 KA C series ------03 Nos (d) Outgoing MCB 10 Amp, SP 10 KA C series ------01 Nos Make Legrand/Siemens/Schneider/Hager
MCB SP 230 Volts, 6-32 Amps, Cseries 10 KA complete all as specified and as directed. Make Legrnad/ Siemens/Schneider/Hager
MCB DP 230 Volts up to 40 Amps C series10 KA complete all as specified and as directed Make Legrnad/ Siemens/Schneider/Hager
S & F 25 Watt LED high performaance street light luminaire, spun housing, aluminium/ die cast grey finish power coated body, high purity PC fresnel diffuser with silicon jackets,with inbuilt integrated electronic driver, rated Voltage 240 Volt ,50 HZ, operating voltage Range 120-270 Volt ,2500 lumen, 0.11A, IP-66 Protection with mounting clamps, bolts and nuts, fixed to vintage type bracket suitable for external pole of dia upto 35mm complete all as specified and as directed Make: Wipro(Skyline LR-02) /Philips/Osram
Comprehensive maintenance, including servicing and testing of Split type air conditioners of following capacity of any make complete for minimum service two times during the contract period of each unit by cleaning cooling coil, condenser fins, blowing off dust from machines & air filters, checking and de-carbonizing,compressor, greasing of blower motor, checking and removing any vibration testing after fixing at site all as directed. Note: (a) Cost of any minor nature repair / items such as nuts ,bolts,washers,screws,rubber mounting pads of compressor etc and labour required for removing / refixing including transportation of equipment to work shop and return (b) replacement of defective cooling coil, condenser fins, blower and blower motor, fan and fan motor, compressor, air filters, starting capacitors,PCB/ refrigerent charging etc as per requirment and cost of replacment of all these items is deemed to be included in unit rate quoted. (c) Replacment of outdoor/indoor unit if required shall be measeured and paid sepreatly.The decsion of requirment of replacement of inddor/outdoor unit shall be final and binding. (A) Split type AC more than 5 Yrs i)1.5 Ton
(ii) 2.0 Ton
(B)Split type AC with in 5 Yrs i)1.5 Ton
Taking down for replacment of outdoor unit of split type AC and installing a new unit inclduing replacment of MS wall bracket,and replacment of refrigerent tubing inclduing charging with refrigerent, as per site requirment up to 6 mtrs with insulation connecting with indoor unit complete all as specified and as directed. (i) 1.5 Ton
(ii) 2.0 Ton
Taking down replacment of indoor unit of split type AC and installing a new unit at site and including refixing of indoor unit on wall and outdoor unit an wall mounted and replacement of refrigerant tubing as per site std requirement upto 6 RM,with insulation material complete all as specified and as directed. Note- Gas charging if required deemed to be included in unit rate. (i) 1.5 Ton
(ii) 2.0 Ton
Taking down of split type AC from site for repair/replacement of indoor unit and re installing split type AC( 1.5/2 Ton capacity) at site and including refixing of indoor unit on wall and outdoor unit an wall mounted and replacement of refrigerant tubing as per site std requirement upto 6 RM,with insulation material complete all as specified and as directed.
M & L charging of refrigerant gas (as per exsisting refrigerent) with appropriate quantity including testing for smooth functioning complete all as specified and as directed. for following (fpr units other than under comprensive maintainence a)1.5 Ton Inverter AC / water coolers 40/ 80 ltr capacity / refrigerator (300 to 315 Ltr)
Repairs to Water Coolers Servicing of water cooler by cleaning the inner tank including disconnecting and reconnecting with plumbing line complete all as specified and as directed a) Water cooler 40/80 ltr capacity
S&F in repair thermetically sealed compressor for water cooler of capacity 40 ltr/hr including charging with R134a gas, single phase alongwith capacitor and relay, and testing of water cooler complete all as specified and as directed. by Engr-In Charge. Make : Copeland/Tecumseh. Note : Cost of cutting of existing worn out compressor will be deemed to be included in unit rate.
Taking out burnt unserviceable condenser fan motor,and replacement with new electric motor,single phase 230V suitable for water cooler 40ltrs/hrs with condenser fan blade complete all as spd and as directed
M& L Repairs to body of water cooler in patches as per requirment by cutting and removing rusted sheet and providing new stainless steel sheet of grade 304 and as per the exsisting thickness, duly welded brazed including provision of hardware and remouting of compressor as per requirement complete all as directed
Supply and fix inreplacment of following items of water cooler (i) Thermostat for water cooler of capacity 40/80 ltr/hrs.
(ii) Bib tap Cast copper alloy 15 mm bore, Push type, chromium plated.
(iii) PVC Connection with brass unions at both ends
(iv) PVC Float valve with epoxy coated aluminium arm , with PVC polythene
(v) PVC drain out pipe 25 mm dia bore as per existing by providing necessary GI Clamps nuts bolts etc.
Repairs to Refrigerators M & L Charging of refrigerant gas with appropriate quantity including testing for smooth functioning for following capacity of refrrigerator complete all as specified and as directed for following (i) Refrigerator capacity 315 Ltr
(ii) Refrigerator capacity 180 Ltr
S& F in replacement compressor start relay suitable for following capacity refrigerator complete all as specified and as directed and as directed Make -As per existing (i) Refrigerator capacity 315 Ltr
(ii) Refrigerator capacity 180 Ltr
S& F in replacement of overload relay suitable for following capacity refrigerator including necessary capillary complete all as specified and as directed Make -As per existing (i)Refrigerator capacity 315 Ltr
(ii)Refrigerator capacity 180 Ltr
S& F in replacement of condensor fan motor suitable for following capacity refrigerator including necessary capillary complete all as specified and as directed Make -As per existing (i) Refrigerator capacity 315 Ltr
(ii)Refrigerator capacity 180 Ltr
S& F in replacement of condensor fan suitable for following capacity refrigerator including necessary capillary complete all as specified and as directed. Make -As per existing (i) Refrigerator capacity 315 Ltr
(ii) Refrigerator capacity 180 Ltr
S& F in replacement of condensor suitable for following capacity refrigerator including necessary capillary complete all as specified and as directed. Make -As per existing (i) Refrigerator capacity 315 Ltr
(ii) Refrigerator capacity 180 Ltr
S& F in replacement of compressor Run Capacitor suitable for following capacity refrigerator including necessary capillary complete all as specified and as directed. Make -As per existing (i)Refrigerator capacity 315 Ltr
(ii) Refrigerator capacity 180 Ltr
S& F in replacement of Temp control thermostate suitable for following capacity refrigerator including necessary capillary complete all as spd and as directed Make -As per existing (i) Refrigerator capacity 180 Ltr
Taking down Ceiling / Exhaust / wall mounted fan,dismantling blades and refixing after repairing at site complete all as specified and as directed for the following. Notes: (a) Spare parts will be measured and paid separetely. (b)
(b) Exhaust Fan of size 240 mm
(c) Exhaust Fan of size 450 mm
(d) Wall mounted fan of size 300 mm
Dismantling of motor of following items, cutting of burnt winding of rotor and rewinding with same gauge copper wire winding with insulated material and reassembling all as spd and directed by Engineer-in-Charge. (i) Ceiling Fan 1200 mm sweep
(ii) Exhaust Fan 240 mm
(ii) Exhaust Fan 450 mm
(iv) Wall mounted fan 300 mm
Supply only spare parts of ceiling Fan of following rating all as spd and directed (i) Capacitor 2.5 MFD
(ii) Capacitor 3.15 Mfd
(iii) Ball Bearing No 6201
(iv )Ball Bearing No 6202
Supply and fix in replacement of unserviceable ‘U’ clamp with nut bolts, washers, fastener split pins , rubbers bush of suitable length for hanging of ceiling fans complete all as required and specified and as directed.
Storage type water heater Dismantling electric/water connection and taking down of storage type water heater,servicing,cleaning of inner tank etc.at site.and replacement of burnout parts etc. and refixing in situ all as spd and directed. Note- wornout parts shall be measured and paid seperatly.
Supply & fixin repair of following spare parts for storage type Gyser (a) Heating element 1.5 KW with rubber gasket .
(b) Thermostat as per sample/suitable to 25 Ltrs capacity ISI marked.
(c) Hot/Cold water connection pipe 450 mm length.
(d) Safety valve.
(e) 3 core 1.5 sqmm PVC insulated cable 1.5 m long with 3 pin 15 Amp plug.
S&F 33W Verge LED recess mounted luminaire,240V, 50Hz, 6500CCT, Nominal Lumen output 3065lm, Square/rectangular in shape complete all as specified and as directed by Engr-in-Charge, fixed in repair. Make: LM29-451-XXX-2765 of Wipro/ Philips/GE Lighting Note- cost of replacing light fitting in existing cut out of false ceiling and making necessary alterations to ceiling board and making good disturbed surfaces as per existing deemed to be included in unit rate
S&F Recessed mounted LED downlighter with high efficiency, housing made of extruded alluminium ,240V, 50Hz, 24 watt, CCT 5700 K, round in shape, complete all as specified and as directed by Engr-in-Charge, fixed in repair. Make:cat no: Wipro LDR06X-301-XX-40-XX*/ or Equivalent from Philips / GE Lighting. Note- cost of replacing light fitting in existing cut out of false ceiling and making necessary alterations to ceiling board and making good disturbed surfaces as per existing deemed to be included in unit rate
S&F White powder coated pressure cast aluminium housing and bottom frame complete with LESs, driver and accessories pre wired upto terminal block lumen output 2048lm, 18W, 240V complete all as specified and directed. Note- cost of replacing light fitting in existing cut out of false ceiling and making necessary alterations to ceiling board and making good disturbed surfaces as per existing deemed to be included in unit rate Make: Wipro-LD81-171-XXX-60-XX / Crompton LSDEP-18-WW /Equivalent.
S&F LED security light/Flood light luminaire 1x70watt W having IP-66 protection, with minimum system efficiency as> 85%,made of pressure die cast housing toughned glass with excellent thermal management. The fitting should have rate CCT 5000K complete with all accessories and complete all as specified and as directed, fixed in repair Make : Pillips (BVP120)/ Wipro (LK 20)/ GE (Tassel)/ CG Jupitor) Note- cost of replacing light fitting in existing cut out of false ceiling and making necessary alterations to ceiling board and making good disturbed surfaces as per existing deemed to be included in unit rate
S&F LED recess mounted luminaire,240V, 50Hz, Nominal Lumen output 18W,5700CCT, Square/round in shapecomplete all as specified and as directed by Engr-in-Charge, fixed in repair. Make: Philips/ Wipro/GE Note- cost of replacing light fitting in existing cut out of false ceiling and making necessary alterations to ceiling board and making good disturbed surfaces as per existing deemed to be included in unit rate Note: Make: LD-06-22188-57-RF-18 of Wipro / or Equivalent in OSRAM /Philips
S&F LED recess mounted luminaire,240V, 50Hz, Nominal Lumen output 440 lm, CCT 6500K, Square/round in shape complete all as specified and as directed by Engr-in-Charge, in replacement. Make: Philips (Green - LED Ultima)/ Osram (ACE Down Light) Note- cost of replacing light fitting in existing cut out of false ceiling and making necessary alterations to ceiling board and making good disturbed surfaces as per existing deemed to be included in unit rate
Supply and fix in replacment of avation light Input Voltage : 172v-275vAC LED : 302+302 Current : 200MA Power Factor : 0.9 Body : Pressure Die Cast Aluminum complete all as specfied and as directed .Make Bajaj 110731 BGAV 302 LED
M & L servicing and cleaning of solar water heater of 200Ltrs capacity including descalling and cleaning of cold/ Hot water tanks, complete all as directed.
M & L replacement of worn out insulation for hot water GI pipe of dia 15 mm from solar water heater system complete all as specified and as directed.
Supply & Fixing air release valve 20 mm dia of copper with operating handle complete all as specified and as directed.
S&F 25 mm dia Rigid non-metallic PVC casing capping inclusive of junction boxes (1 to 4 way), medium duty, including all Tees, bends, elbows, reducers, bell mouth tube ends, and fixing couplers, lock nuts, saddles, pipe hooks etc, fixed in repairs Make Press fit/Finolex/Anchor
S&F 20 mm dia Rigid non-metallic PVC casing capping inclusive of junction boxes (1 to 4 way), medium duty, including all Tees, bends, elbows, reducers, bell mouth tube ends, and fixing couplers, lock nuts, saddles, pipe hooks etc, fixed in repairs Make Press fit/Finolex/Anchor
M&L Earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using GI Wire 4mm dia as earthing lead (upto the test point ) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected upto test point and GI pipe light grade 20mm bore for watering and including funnel , wire mesh , PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, RCC pit cover type B-1 including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 1991(Part-I) complete all as specified and as directed by Engineer-in-charge. NOTE : Earth wire upto 7.5mtr length is deemed to be included in quoted rate.
Parth Infrastructure Pvt. Ltd.
K K Construction Co
OM ENGINEERING
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .