Executive Engineer
Electrical Division HPPWD Palampur
Construction of Centre of Excellence in Mental Health for Dr.RPGMC Kangra at Tanda (SH- Revised estimate for providing Fire Alarm and PA system therein)
2021_PWD_51429_1
Elect. Division HPPWD Palampur
Open Tender
Electrical Works
Item Rate
90 days
Kangra at Tanda in Distt. Kangra
Please refer Tender documents.
12 documents required · 12 mandatory
₹1,500
Executive Engineer Elect. Division HPPWD Palampur
₹49,200
2 Oct 2021
19 Aug 2021
28 Aug 2021
19 Aug 2021
27 Aug 2021
19 Aug 2021
Amount
Supply, Installation, Testing and Commissioning of Microprocessor based Intelligent Addressable Main Fire Alarm Control Panel with Suitable Loops modules and each loop capable of supporting not less than 125 detector and 125 devices; Loop length up to 1.5 km, 600 Character/7" Color LCD touch screen display with bright colors to indicate alarms and events, Integrated Ethernet Ports & 2 Nos of RS 485 for networking, evacuation speaker zones, AHU Modules, Damper switch, Smoke extraction Fans, Lifts.. etc. The Panel shall support 8000 history logs in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 24 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger.The panel should also have IP30 or better protection. The panel shall have seamless integration with EVAC certified Public Address System and shall be complete with all accessories. Fire Alarm Panel and Public Address System should be of same make. Shall be EN54 -Vds/UL-FM Certification as required complete in all respect and to the best satisfaction of Engineer-in-charge. Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing and Commissioning of Active and networkable repeater panel with 4x20 character LCD display complete system function keys for programming and control like system reset, alarm acknowledgement, alarm silence, trouble acknowledgement etc. Shall be UL/EN/VDS Listed. Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing and Commissioning of addessable Double ACTION manual call point & necessary fixing arrangements with key complete as required. MCP should have IP40 or better protection rating Shall be EN54 -Vds/UL-FM Certification Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing and Commissioning of addressable multisensor detector including mounting base with LED… etc. complete as required with inbuilt Isolators as per NFPA 72 style 7 wiring requirements or with isolator base/module for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be EN54 -Vds/UL-FM Certification. Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing and Commissioning of addressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required with inbuilt Isolators as per NFPA 72 style 7 wiring requirements or with isolator base/module for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be EN54 -Vds/UL-FM Certification. Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing & Commissioning of addressable Response Indicator with in built isolator & matching screws complete with GI Junction box, Cable lugs at cable end and ferruling. Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing and Commissioning of Addressable Monitor Module with 2 inputs, which shall monitor normally open or normally closed contacts.The module shall have an LED to indicate module status.It Shall be UL/EN/VDS Certified. Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing and Commissioning of Addressable Control Relay Module having two ptential free contacts with a maximun switching current of 2A @ 30V DC. Shall be UL/EN/VDS Certified Make Bosch/ Siemens Fire Finder / Honeywell Notifier
SITC of minimum 1000 Mtr. Range Siren generatorprovided at the roof of the building with separate power suppl, relay etc. with all accessories required to complete the job in all respect up to the entire satisfaction of engineer incharge. Make: National/Kheraj
Supply, Installation, Testing and Commissioning of 15 W Horn type loud speakers with following features:- Built-in 100 / 70 V LMT compliance with IEC60268 - Part 5, Power tapping 15 / 7.5 / 3.75 W, Sound pressure level at 15 W / 1 W (1 kHz, 1 m) 115 / 103 dB (SPL)complete with necessary mounting hardware & accesories. Certified to UL/ EN standards. Make Bosch/ Siemens Fire Finder / Honeywell Notifier
Supply, Installation, Testing & commissioning of Wall Mount Speaker with operation 12 Watts Bosch/ Siemens Fire Finder / Honeywell Notifier
SITC of Booster amplifier 480 watts Frequency response: 60 Hz to 15 khz (+1/3db), Inputs :XLR & phone jack , Input 1, Input 2-4, Impendence :20kΩ, Sensitivity : 1 V balanced , S/N >: >85 dB complete in all respect Bosch/ Siemens Fire Finder / Honeywell Notifier
SITC of PVC unsheathed s/c stranded ( ISI marked ) copper contuvtor cable 1100v grade in existing pipe excluding cost and erection of pipe but including connection etc. with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer – in charge of work MAKE FINOLEX/POLYCAB/HAVELLS
PVC unsheathed copper size 1.5 sq mm single core
SITC of 2 core multistrand 1.5 sq mm annealed copper conductor speaker cable in existing pipe/ channel I/C connection etc.Make Finolex/Polycab/havel's
Supply, Installation, Testing and comissioning of 2KVA UPS Cum inverter, including batteries and 2 hour Backup. MAKE LIBERT EINOVA/APC /Luminous
Supply, Installation, Testing and comissioning of 17U Equipment Rack with provision for housing all control equipment with front & rear door, Blower for cooling and proper locking arrangements and as per the specifications, complete in all respect upto the entire satisfaction of Engineer - in - Charge of the work. Makes: Valrack /Netrack/ Comrack
Insat Techno Services
Vowels Technology and Services
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .