GE North Akhnoor
GE North Akhnoor
REPAIR MAINT OF OVERHEAD ACSR CONDUCTOR LT XLPE UG CABLE LED CFL STREET SECURITY LIGHT AND REPAIR TO TRANSFORMERS AND DG SETS AT SUNDERBANI UNDER GE NORTH AKHNOOR
2020_MES_338526_1
GE(N)/AKH-03/2020-21
Open Tender
Civil Works
Item Rate
180 days
Sunderbani
E Class Cat b i
8 documents required · 8 mandatory
₹500
GE North Akhnoor
₹40,000
Yes
19 Oct 2020
11 Apr 2020
12 May 2020
11 Apr 2020
9 May 2020
27 Apr 2020
Amount
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in any type of soil for taking up or laying of cable, complete all as specified & directed. Note : Due care shall be taken while deciding cable route for excavation. However any damage to Signal, BSNL, MES cable water/sewage pipe or any other service while excavation will be made good by the contractor and cost of the same for jointing material & labour is deemed to be included in the cost of excavation.
Excavation in trenches n.exc 1.5 mtr wide exc 1.5 mtr in deep but not exceeding 3.0 mtr deep and getting out for foundation of poles etc. in any type of soil, complete all as specified & directed.
Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25cm, complete all as specifed & directed.
Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point, complete all as specified & directed.
Sand cushioning to under ground cable, laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete punned to 18cm, complete all as specified and directed. Note:- Punned thickness of sand will be measured and paid.
Brick well burnt locally available sub class 'B' laid over sand cushioning for mechanical cable protection in trenches with width of brick perpendicular to the length of cable, complete all as specified & directed.
PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate as in foundation of poles etc including necessary form work, finished exposed surface even and fair without using extra cement, complete all as specified & directed.
PCC 1:2:4 type B-1 using 20mm graded crushed stone aggregate as in coping of pole etc including weathering, slightly rounded or chamfered angles and throating including necessary form work, complete all as specified and directed.
PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in stay, foundations, filling and mass concrete including necessary form work, complete all as specified & directed.
Steel tubular swaged poles in vertical position/as strut poles swaged type 410-SP-31, 9 Mtr long, ISI marked complete with cast iron base plate, finial taper plug, bolts, nuts washers and screws as required duly painted with two coats of aluminium paint over a coat of red oxide primer above ground level including painting below GL (externally) with two coats of bituminous paint, numbering of poles with cut stencil lettering in size 6mm thick and 50mm high and white and black strips of size 30cm width each with synthetic elamel paint upto 1.5m above coping etc, complete all as specified and directed. Note:- 1. Earth work and PCC will be measured and paid seperately under appropriate items.
Steel tubular swaged poles in vertical position/as strut poles swaged type 410-SP-55, 11 Mtr long, ISI marked complete with cast iron, finial taper plug, bolts, nuts washers and screws as required duly painted with two coats of aluminium paint over a coat of red oxide primer above ground level including painting below GL (externally) with two coats of bituminous paint, numbering of poles with cut stencil lettering in size 6mm thick and 50mm high and white and black strips of size 30cm width each with synthetic elamel paint upto 1.5m above coping etc, complete all as specified and directed. Note:- 1. Earth work and PCC will be measured and paid seperately under appropriate item.
Steel tubular swaged poles in vertical position/as strut poles swaged type 410-SP-64, 12 Mtr long, ISI marked complete with cast iron, finial taper plug, bolts, nuts washers and screws as required duly painted with two coats of aluminium paint over a coat of red oxide primer above ground level including painting below GL (externally) with two coats of bituminous paint, numbering of poles with cut stencil lettering in size 6mm thick and 50mm high and white and black strips of size 30cm width each with synthetic elamel paint upto 1.5m above coping etc, complete all as specified and directed. Note:- 1. Earth work and PCC will be measured and paid seperately under appropriate item.
Stay Assembly using stay rod of 20mm dia with complete accessories as shown in Electrical Plate No 1 of SSR 2009 Part-I such as loop type insulator, porcelain, vitreous white/ brown or green, large size with overall dimensions 90x140mm clearance of hole 25.5mm, stay wire of size 7/2.24mm, stay plate 300x300x6mm thick, 14mm dia 400mm long GI stay bow, 20mm dia 1.9m long GI stay rod etc., complete all as specified & directed. Note :- Earth work and PCC shall be measured and paid for separately)
Unbinding of loose ACSR conductor of any size and any type on LT/HT poles including earth wire and re-stretching the same to required sag and binding the conductors with new binding wire, jumpering of conductors, re-connecting of service connection, street light connection etc.
Taking down existing worn out/rusted GI earth wire, cradles, guards of any size and shape at any position from steel/pre-stressed concrete LT/HT poles and stretching new GI earth wire of 8 SWG (4 mm dia) on LT/HT poles for continuous earth wire/guards and cradles (hexagonal/rectangular) including binding with 1.6 mm dia GI wire etc, complete all as specified & directed.
ACSR conductor of any size drawn straight horizontal on over head lines on existing poles including binding with insulators, weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag, jointing jumpers etc, complete all as specified & directed.
Structural steel work as in cross arms, bracings, supports, clamp and back plate fabricated from steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed by Engineer-in-Charge and applying two coats of aluminium paint over one coat of red oxide zinc chrome primer after preparation of surfaces including dismantling of existing cross arms, complete all as specified & directed.
Shackle type insulator porcelain vitreous white, brown or green 100mm high and 115mm dia for conductor of working pressure 1100 volts including galvanised mild steel straps of 31x5mm size, 14mm dia insulator bolts, washers and nuts including dismantling of existing old unserviceable insulators, complete all as specified & directed.
Pin type insulator porcelain, vitreous, white/brown or green including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm dia and 150mm height for working pressure 11000 volts grade including dismantling of existing old unserviceable insulators, complete all as specified & directed.
Pin type insulator porcelain, vitreous, white/brown or green including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm dia and 150mm height for working pressure 33000 volts grade including dismantling of existing old unserviceable insulators, complete all as specified & directed.
Disc type insulator porcelain vitreous white, brown or green 145mm high and 255mm dia ball and socket type, single disc assembly for tension with tension clamp for conductor of working pressure 11000 volts including dismantling of existing old unserviceable insulators, complete all as specified & directed.
Disc type insulator porcelain vitreous white, brown or green 145mm high and 255mm dia ball and socket type, single disc assembly for tension with tension clamp for conductor of working pressure 33000 volts including dismantling of existing old unserviceable insulators, complete all as specified & directed.
Switch air break, gang operated, disconnecting switch, triple pole, each pole consists of galvanized steel base, HT insulators non-ferrous knife, spring loaded contacts, arcing horns of adequate section to break magnetizing current of the transformers, mechanically operated suitable for horizontal or vertical mounting, fixed type, mounted on insulator and steel frame with operating mechanism worked from ground level, provided with locking arrangement for operating handle, consisting of MS channel, HT post type insulator, contacts of copper alloy, high pressure, heavy duty contact assembly, operating rod of 25mm dia GI pipe medium grade of adequate length, drop out expulsion assembly of phases fuses etc conforming to IS:1018 of 1972 with continuous current rating with 15 insulators of current rating upto 200 amps 11000 volts grade including taking down old unserviceable GOD, complete all as specified & directed.
Lightening arrestor, expulsion type consisting of multiple spark gaps in series with one or more non linear resister to limit voltage surge on AC power circuit to interrupt power flow current suitable for outdoor installation and exposed direct to sun with ambient temperature below - 10 degree C to 50 degree C suitable for surge discharge capacity 65 KA, 11000 volts grade conformign to IS-4350 including all fittings & dismantling of existing lightening arrestor, complete all as specified & directed.
Cable jointing kit for HT 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95-120 sqmm including testing and commissioning, complete all as specified & directed.
Cable jointing kit for HT 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95-120 sqmm including testing and commissioning, complete all as specified & directed.
XLPE insulated, screened PVC bedded galvanized steel strip or wire armoured electric power cables (heavy duty) of size 70 Sqmm, 3 core with aluminium conductor (multistranded) 11000 volts grade (earthed) connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion and removal of old unserviceable cable, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
Taking out carefully LT under ground cable of any sizes and descriptiion from trenches, complete all as specified & directed.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 95 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm 2.0 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sqmm 2 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
Earthing of galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr depth below normal ground level) with top edge of earth not less than 1.5 mtr below normal ground level, surrounded on all sides by 150mm thick charcoal & common salt starting from ground below earth plate upto 150mm above GI plate in alternate layers connected to and including galvanised iron earth strip of 32x6mm by means of steel bolts, nuts, check nuts and washers, test point made of GI strip 40x8mm 10cm long, PCC 1:2:4, type B-1 in pit with precast RCC 1:2:4 type B-1 in cover reinforced with XPM not less than 4 Kg per Sqm with 40mm bore GI light grade protection pipe, 20mm bore GI medium grade watering pipe with funnel including charcoal, dust, salt, all as shown in electrical plate No 3 of SSR Part-I (2009) complete with necessary earth work in any type of soil, removal including testing on completion, complete all as specified & directed. Note : (a) The cost of earth work, PCC pit of required size, funnel, watering pipe, wire mesh, charcoal, dust, common salt, 20mm bore medium grade watering pipe & 40mm bore light grade GI pipe as protection to earth lead wire etc shall be deemed included in the unit rate for earthing. (b) After completion, during testing, if desired earth resistance is not obtained, earthing will be regenerated at no extra cost.
Earthing of galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr depth below normal ground level) with top edge of earth not less than 1.5 mtr below normal ground level, surrounded on all sides by 150mm thick charcoal & common salt starting from ground below earth plate upto 150mm above GI plate in alternate layers connected to and including earth lead wire 4.0mm (8SWG) by means of steel bolts, nuts, check nuts and washers, test point made of GI strip 40x8mm, 10cm long PCC 1:2:4, type B-1 in pit with precast RCC 1:2:4 type B-1 in cover reinforced with XPM not less than 4 Kg per Sqm with 15mm bore GI light grade protection pipe, 20mm bore GI medium grade watering pipe with funnel including charcoal, dust, salt, all as shown in electrical plate No 3 of SSR Part-I (2009) complete with necessary earth work in any type of soil, removal to a distance not exceeding 50 mtr, including testing on completion, complete all as specified & directed. Note : (a) The cost of earth work, PCC pit of required size, funnel, watering pipe, wire mesh, charcoal, dust, common salt, 20mm bore medium grade watering pipe & 15mm bore light grade GI pipe as protection to earth lead wire etc shall be deemed included in the unit rate for earthing. (b) After completion, during testing, if the earth resistance equal or less 2 ohms is not obtained, earthing will be regenerated at no extra cost till the desired earth resistance is obtained.
Repairing of the 11 KV gang operating switches by replacement of the following spares ;- (a) Replacement of post insulator 11 KV
(b) Replacement of male contact/moving contact 11KV
(c) Replacement of female contact/fixed contact 11KV
(d) Replacement of copper flexible braider along with MS cross link
1100 volts grade heavy duty cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including 4mm dia suspension GI wire with stranded conductor 10 Sqmm twin core cable flat or circular including taking down old unserviceable service connections, complete all as specified & directed.
LT indoor/outdoor cable end termal joint (epoxy joint) any type suitable for aluminium conductor cable of size 70 Sqmm to 120 Sqmm 3.5 core.
LT indoor/outdoor cable end termal joint (epoxy joint) any type suitable for aluminium conductor cable of size 150 Sqmm to 185 Sqmm 3.5 core.
Disconnecting all electrical connections of existing LT panel, taking out LT panel from its existing location safely (without making any damage) and reinstalling the same at another suitable location after applying one coat of synthetic enamel paint to entire panel board after preparation of surfaces including testing, complete all as specified & directed.
Construction of platform suitable for transformer/voltage stablizer of size 3.00m x 3.00m x 1.20m clear height from ground level, 1.00m deep foundation, 150mm thick PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in foundation below ground level, 23 cm wide brick masonry in cement mortar 1:6 below & above ground level, hollow space to be filled hard core of size n.exc 63 mm, deposited spread and levelled in layers not exceeding 15cm thickness, watered and well rammed with 100 mm thick cement concreate 1:2:4 type B-2 as in floor/top of platform, brick surfaces plastered in cement mortar 1:4 including protection with XPM, gate and chain link fencing rail around the platform with angle iron of 50x50x6mm frame upto 1.20m clear height supports grouted in PCC 1:2:4 type B-1 using 20mm graded crushed stone aggregate as in foundation of angle iron including excavation in any type of soil, returning filling in & removal of surplus soil to a distance 50m, complete all as specified & directed.
Taking down carefully unserviceable street light from poles/building of any type and size after disconnecting the electrical connections for carrying out necessary repairs if found repairable or depositing to MES store if accessories or component found unserviceable, complete all as specified & directed.
Repairing the street light fittings of any type and capacity by replacing defective connecting accessories such as tube light rod/HPSV Lamp/ HPMV Lamp/ Ballast HPSV/ Ballast HPMV/ Capacitor/ Ignitor etc and also replace the burnt wiring with required rating of wiring, complete all as specified & directed.
Street light bracket made out of 40mm bore medium grade pipe of 1.50m length, bent to required shape for fixing on PCC/Steel pole with 02 Nos. clamps of flat iron (40 x 6mm), nuts, bolts and washers including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer including dismantling o existing bracket, complete all as specified and directed.
Street light bracket made out of 32mm bore medium grade pipe of 1.50m length, bent to required shape for fixing on PCC/Steel pole with 02 Nos. clamps of flat iron (32 x 6mm), nuts, bolts and washers including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer including dismantling o existing bracket, complete all as specified and directed.
S&F in replacement Copper ballast 240 v suitable for 70 Watt HPSV fitting incld taking down complete. Make : Havells/Cromton Greaves/Phillips/Surya
S&F in replacement Copper ballast 240 v suitable for 150 Watt HPSV fitting incld taking down complete. Make : Havells/Cromton Greaves/Phillips/Surya
S&F in replacement Copper ballast 240 v suitable for 250 Watt HPSV fitting incld taking down complete. Make : Havells/Cromton Greaves/Phillips/Surya
S&F in replacement ignitor for sodium vapour lamp (HPSV lamp) for 70/150/250/400 Watt in street light fitting incld taking down complete. Make : Litons/Bajaj/Myna/Philips/Surya.
S&F in replacement flexible twin core 4.0 Sqmm aluminium cable in street light fitting all as specified.
Electronic drivers suitable for LED street light fittings of 25/30/45/48/60 watt capacity including taking down old unserviceable drivers, complete all as specified & directed.
LED street light luminaries 45W LED 6000K, 230 volts, new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover with IP66 protection and impact resistance of IK07 with toughened glass cover and all accessories, mounted on GI bracket including taking down old unservicabele street light fittings, complete all as specified & directed. Make : Havells, Cat Part No.ENDURAPEARLNEOSL45WLED757SASYTOPC or equivalent in Philips/ Crompton/ Bajaj/ Wipro/ Syska/ GE Lighting/ Surya
S&F in repair capacitor of rating 2.5 to 10 Micro fard suitable size for street/security light of 70/150/250//400 watt all as specified.
Main switch, iron clad, triple pole & neutral of capacity 63 Amp with fuses including dismantling of existing switch, complete all as specified & directed.
Main switch, iron clad, triple pole & neutral of capacity 32 Amp with fuses including dismantling of existing switch, complete all as specified & directed.
LT busbar chamber (factory made), cubical type, weather, dust and vermin proof of size 600x400x100mm, outdoor type of suitable size made out of 2.00mm thick MS sheet fixed on floors having two doors on both sides with locking arrangement and painting all steel surface internally and externally with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer with aluminium bus bar of 200 amp capacity 4 strips for three phase & one neutal & making all electric connection with existing system including dismantling of existing busbar chamber, complete all as specified & directed.
MCCB of capacity 250 Amps, 4 pole, 415 volts, 50Hz, rupturing capacity 36 KA (minimum) or higher, AC, 50 C/S, fixed in panel boards, complete all as specified & directed.
MCCB of capacity 200 Amps, 4 pole, 415 volts, 50Hz, rupturing capacity 36 KA (minimum) or higher, AC, 50 C/S, fixed in panel boards, complete all as specified & directed.
MCCB of capacity 160 Amps, 4 pole, 415 volts, 50Hz, rupturing capacity 36 KA (minimum) or higher, AC, 50 C/S, fixed in panel boards, complete all as specified & directed.
MCCB of capacity 160 Amps, 4 pole, 415 volts, 50Hz, rupturing capacity 25 KA (minimum) or higher, AC, 50 C/S, fixed in panel boards, complete all as specified & directed.
MCCB of capacity 100 Amps, 4 pole, 415 volts, 50Hz, rupturing capacity 18 KA (minimum) or higher, AC, 50 C/S, fixed in panel boards, complete all as specified & directed.
MCCB of capacity 63 Amps, 4 pole, 415 volts, 50Hz, rupturing capacity 18 KA (minimum) or higher, AC, 50 C/S, fixed in panel boards, complete all as specified & directed.
Digital voltmeter, 0 to 500 volts, fixed in panel boards on incoming supply, complete all as specified & directed.
Digital ammeter, 0 to 300 , fixed in panel boards on main load, complete all as specified & directed.
Indication pilot light to operate on direct supply, 230v, AC with 2.4 Watt bulb (R, Y, G) with smooth lens, complete all as specified & directed.
Complete panel wiring with PVC insulated multistranded FRLS copper conductor of suitable current carrying capacity, end terminated with GI lugs, bolts, nuts and washers, complete all as specified & directed.
TRANSFORMERS Taking down carefully transformer of 50 KVA to 75 KVA capacity from four pole and two pole structures, platform, transporting of transfromer to workshop and draining out the transformer oil in clean barrels, opening the top cover of the transformer oil, disconnecting the electrical connection, taking out the core/winding coils out of the tank, taking the defective/burnt out HT/LT coils, cleaning the tank and cleaning out the dust particles, refitting the core in the tank after necessary repairs (repair shall be measured and paid separately) and heat treatment, connecting all the electrical connections, refitting the top cover and other accessories and making the transformer absolutely leak proof, pouring in the insulating oil in the transformer, before installation all test should be carried out i.e. load test, insulation test, Di- electric strength test satisfactory and transporting the transformer and back to same placing in position and securing properly on 4 pole/2pole structure/platform at site and making all HT/LT connections, installation,testing and commissoning complete all as specified and directed . Note (a) The rates are inclusive of transportation of transformer from site of installation to workshop and back including T&P required. (b) HT/LT winding will be measured and paid separately.) :-
All as per Srl item No. 74 above but of 100 KVA to 200 KVA capacity.
Rewinding of complete/Partly HT coils of transformers of 50 KVA to 75 KVA capacity with super enamalled copper conductor of appropriate gauge alongwith allied materials as already used in the transformer, complete all as specified & directed.
All as per Srl item No.76 above but of 100 KVA to 200 KVA capacity.
Dismantling/Opening carefully LT coil copper wire/strip wound and rewinding the same after providing new necessary packing/insulation with cotton tape/insulation paper material using the same old strip/wire, complete all as specified and directed.
Rewinding of of LT coils with cotton braided copper wire/strip of appropriate gauge along with allied materials, complete all as specified & directed. Note : Extra wire/strip if used shall be measured and paid separately under relevant item.
HT bushing assembly with brass nut, stud, washer and insulator suitable for transformer out door type of capacity 50 KVA to 200 KVA capacity, complete all as specified & directed.
12mm dia LT bushing assembly with brass nut, stud, washer and insulator suitable for transformer out door/indoor type of capacity 50 KVA to 75 KVA capacity, complete all as specified & directed.
12mm dia LT bushing assembly with brass nut, stud, washer and insulator suitable for transformer out door/indoor type of capacity 100 KVA to 200 KVA capacity, complete all as specified & directed.
Temperature gauge dial 0 degree centigrade to 75 degree centigrade suitable for transformer of 50 KVA to 200 KVA capacity, complete all as specified & directed.
Breather assembly of 200 gm capacity suitable for transformer of 50 KVA to 200 KVA capacity, complete all as specified & directed.
Painting to 50 KVA to 200 KVA distribution transformers by preparation of exposed surfaces by scraping, removing of old rusted paint from the body, cleaning surface with high quality thinner and applying two coats of synthetic enameled paint waterproof smoke greay over a coat of red oxide zinc chrome primer by spray painting including marking SM NO, SL NO and CAPACITY on body with white synthetic enamel paint including painting to fencing of transformers, complete all as specified & directed.
Filtration, heating and dehydration of transformer oil (at site) on load system, EHV grade having dielectric strength not less than 40 KV (RMS) with 4mm gap high viscosity in transformer of capacity of 50 KVA to 200 KVA as per IS-335 of 1983 for reducing of moisture, acidity carbon particle in transformer oil, complete all as specified & directed. Note :- The filtration, heating and dehydration of transformer oil shall be carried out at site. The unit rate quoted by the contractor shall deemed to included for arrangement of filtration machine and its transportation to various locations of installation of transformer and toping up of Transformer Oil.
Supply only Transformer Oil of dielectric strength 40 KV (RMS) with 4 mm gap of discharge 2 sec for topping up of transformer, complete all as specified & directed.
Repair/maintenance of brick masonary plateform of size 3 x 3 x 1.2 m by rendering 10mm thick cement mortar in cement mortar 1:3 on old fair faces of brick work or concrete surfaces all around, 10 cm thick PCC B-1(1:2:4) work on top of plateform, new MS iron fencing, painting on cement plastered surfaces all around of plateform and MS iron fencing with two coats of synthetic enamelled plastic paint over a coat of primer, letter writing in 65 mm height as Transformer Srl No, Make, SM No, Date of Installation, Location etc including taking out old cement mortar/lime mortar plaster, demolition of old broken PCC on top of plateform and removing the demolished material (old PCC & plaster) at a distance not less than 50 mtr away from starting point, complete all as specified & directed.
REPAIR TO DG SET Carrying out servicing/maint of 110 KVA DG set, Make : 'Greaves/Kirloskar' including 'B' check as per manufacturers mannual through authorised dealer of DG set manufacturer of existing DG Make and testing of DG set complete all as directed by Engineer-in-Charge. Note :- All material/spares parts required for carrying out above maintenance/servicing shall be measured and paid separetely as 'Supply only' items as mentioned below and shall be of make-Greaves/Kirloskar/Cummins as per make of DG set and labour element required for replacing the spares parts including replacement of minor spare parts which are essential for carrying out servicing/maintenance of DG sets shall deemed to be included in the unit rate quoted by the tenderer against item No. 01 above.
Supply only Lub oil filter cartrige
Supply only Diesel filter insert
Supply only Diesel filter paper
Supply only Fuel pre filter
Supply only Air clean element primary
Supply only Air clean element secondary
Supply only Hose pipe & Flexible pipe complete set.
Supply only Fan belt for water pump (make-Fenner/Poly-F/ Roulunos).
Supply only Fan belt for alternator dynamo (make-Fenner/ Poly-F/Roulunos).
All as per item No. 89 here in before but for DG Set of capacity 25 / 30 KVA.
Supply only Lub oil filter cartrige
Supply only Fuel filter insert
Supply only Fuel pre filter
Supply only Air clean element
Supply only Fan belt for alternator dynamo (make-Fenner/ Poly-F/Roulunos).
All as per item No. 89 here in before but for DG Set of capacity 15 KVA make Kirloskar
Supply only Lub oil filter
Supply only Fuel filter insert
Supply only Fuel pre filter
Supply only Air clean element
Supply only Hose pipe & Flexible pipe complete set.
Supply only Fan belt for alternator dynamo (make-Fenner/ Poly-F/Roulunos).
Repair/servicing of radiator assembly of 110 KVA DG Set (Kirloskar) after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out water from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing complete all as directed by Enginer-in-Charge. (Note- Pre mixed coolent shall be measured and paid separately under relevant item of schedule)
Supply and fixing new Self starter, auto lock, 12/24V of existing make, on the 110 KVA DG Set and taking out u/s self starter from DG set.
All as per item No. 113 but for 15/25/30 KVA DG Set.
Dismantling and repair/calliberation of fuel pump of 110 KVA DG Set including replacement of seal and kit from authorised delears work shop including refixing and testing complete.
All as per item No. 115 but of capacity 15/25/30 KVA DG Set.
Repair/Servicing of water pump and replacement of water kit and water seal of 110 KVA DG Set complete all as directed.
Dismantling and taking down alternator assembly from existing engine and transporting to workshop and carry out servicing / maintenance of alternator unit of capacity 110 KVA DG set as per the phase work :- (a) Opening of Alternator and cleaning / remvoing dust from armature and field coil. (b) Cleaning of used / old lubricated substances drive/non drive end bearings. (c) Cleaning end cheeking of AVR unit (d) Cheking and tighting of coupling bolts and replacement of rubber inserts. (e) M&L for carrying out heat varnishing for field and armature coil and kept in heating chamber for 48 hours for drying properly. (f) Replacement of Bearings as per existing size. (g) Reassembling complete unit and carrying out testing at workshop and transportation to installation and coupling with DG Set including necessary alignment, cable connections all as specified and directed by Engr - in Charge
All as per item No. 118 but of cpacity 15 to 30 KVA DG Set
Supply and replacement of piston with rings, cylinder linner and gaske set complete including caliberation and overhauling of injector assembly complete all as directed suitable for 15 to 110 KVA DG set.
Supply & repalcement of water temp gauge with cable complete as per sample.
Supply & replacement of Lub oil pressure gauge complete with cable as per sample.
Supply & replacement of Amp meter as per sample.
Supply & repalcement of frequency meter as per sample.
Supply and replacement of coolent for radiator Make : Kirloskar/Greaves/castrol/HP.
Supply, replacing and topping up of engine oil 'K-Oil' in Kirloskar/Cummins DG Set after servicing complete including taking out old burnt Engine oil from DG Set. Make : Kirloskar
Supply and topping up of electrolite for 1280 specific gravity for 12 volts batteries.
Supply only Push buttons as per sample or as directed
Supply only toggle switch Make as per sample or as directed
Supply only Jute cotton waste (as per sample) for cleaning & day to day maintainance of silencer & DG set installed at different location at this station.
Supply only cotton cloth waste (as per sample) for cleaning & maintainance of DG set at this station.
M/s Mool Raj Romesh Chander
ARORA ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .