| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.0 LAccepted-Finance 43 1 A HEALTH INSTITUTE ROAD P O RABINDRANAGAR DUM DUM CANTONEMENT 24 PARAGANAS NORTH WEST BENGAL 700065 | 24 PARAGANAS NORTH | WEST BENGAL | 700065 | L1 | Accepted-Finance Lowest Rate Quoted | |
| 2 | L2₹19.1 L+₹1.0 L (5.73%)Rejected-Finance | L2 | Rejected-Finance High Rate Quoted | |
| 3 | L3₹83.4 L+₹65.4 L (362.8%)Rejected-Finance | L3 | Rejected-Finance Higher Rate Quoted |
| Sl No | Description | Qty | Unit | SKS PROJECTS L1 | M/S VICKY ELECTRIC CO. L3 | H. ENTERPRISE L2 |
|---|---|---|---|---|---|---|
| 1.00 | SITC OF 100KVA DG:
Supply, Instalation ,Testing and Commisioning at site of 100 KVA, 415V, 50Hz, 3Phase silent new DG Set, comprising of Engine, alternator, integrated AMF panel, Base frame, Fuel tank, Battery, CPCB-IV+ approved Engine & Acoustic Enclosure having following specifications.
ENGINE
Make- Cummins/Greaves Power/Ashok Leyland/Greaves Cotton)
Engine Type : 4 Stroke Diesel Engine, RPM 1500
Rated Output: 122 BHP or Higher, Duty: PRIME
Cooling : Liquid cooled/radiator cooled
Cylinder: 4, In-line
Aspiration : Turbo Charged
Type of Govemer : Electronic
Fuel Tank Capacity Minimum capacity 160 Ltr as per
manufacturer's standard Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan: As per Manufacturer's standard 16.5Ltr/ Hr. or Less, Fuel Consumption at 100% rated Load with Radiator or Fan : As per Manufacturer's standard 22 Lt/ Hr or Less Overload Capacity: 10% overload for one hour for every 12 hours continuous running at full load or better.
Engine instrument Panel : Consisting of starting switch with Key. Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter. Safety Controls Emergency Stop. Low Lube Oil Pressure warning Shutdown, High Engine Water Temp. warning (Shutdown, Sensor failure Indicator, Engine over speed indicator Battery charging and low battery indicator Exhaust Silencer Residential Type
Starting system: 12V starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard
Battery Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning. | 1 | Item. | 15,95,000 ₹15,95,000 | 15,00,500 ₹15,00,500 | 14,28,000 ₹14,28,000 Lowest |
| 1.01ALTERNATOR Make : Stamford/Leroy Somer/Crompton Greavs Rating: 415 V, 3Ph. 50 Hz, 100 KVA,1500 rpm Type Brushless, self excited and self regulated Insulation Class H Protection :screen-protected drip proof ith Min.IP23 degree of protection RPM: 1500 Voltage Regulation (max): +1% Winding connection Star with Neutral Total Distortion factor Less than 3% Total Harmonic distortion in output waveform: 55% AMF PANEL Integrated AMF panel made from 16 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 100 KVA DG set having following specification/features. i)160A MCCB with O/L S/C, E/F protection and microprocessor based protection release , UNreleased etc. -2 sets (L&T/Siemens/ABB) m) in Built By-Pass switch for rated capacity 2On -delay timer for load change over iv) On-delay timer for engine 3)Engine On-Off switch (Push button type) 1 Battery charger complete with voltage regulator, booster selector switch, on-off switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine video Minimum five number indicating lamps to indicate 'mains JON load on mains, Set running, 'load on set' and 'battery charger on' video Audio visual alarm for 'Low lubricating oil pressure, 'High water temperature, Start failure, and DG overload load'. Mode selector for setting the panel on Auto/Man/ Test Mode. Microprocessor based relay with composite meter for digital display of following. Generator voltage/AC Mains voltage. Generator Current in all phases Frequency ,Power Factor Energy Indication for alternator supply Running time indications number of hours of operation and service intervals, service due indications the AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure. | ||||||
| 1.02ACOUSTIC ENCLOSURE The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustict enclosure must be certified as per CPCB-IV norms. BASE FRAME Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting HookType. Rate should be quoted inclusive of all applicable taxes and Duty etc (i) All materials, equipments & accessories must conform to relevant IS /IEC specifications. (ii)The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer (iii) Necessary manufacturer's test certificate for Diesel Engine, alternator etc. Will have to submit in triplicate copy during delivery of the equipment iv) Copy of "Type Approval Certificate" and Certificate of Op must be produced at the time of delivery issued from competent Authority (As per CPCB-IV). (v) Circuit Diagram for AMF Panel must be submitted from thel stars Manufacturer / OEM. (v) The entire set must be warranted at least 15 months from the date of Delivery/24 months/ 5000 Hrs from the date off Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier. | ||||||
| 2.00 | Making Brick foundation and R.C. casting and making neat cement finish after plastering for installation of AMF panel incl. S&F suitable M.S angle/Channel with nuts, bolts & washer etc. as per direction of EIC. | 1 | Job | 5,900 ₹5,900 Lowest | 25,400 ₹25,400 | 25,000 ₹25,000 |
| 3.00 | S & F M.S Exhaust Pipe of 150 mm dia. including connection with existing silencer and S & F Bend, flange, nuts, bolts and washers and necessary fixing materials as required including making necessary welding, as per direction of EIC. | 4 | RM. | 2,832 ₹11,328 Lowest | 23,000 ₹92,000 | 5,500 ₹22,000 |
| 4.00 | S & F MS exhaust pipe of 100 mm dia -Do- - - - -Do- - - - - Do- - - - as per direction of EIC. | 15 | RM. | 2,360 ₹35,400 Lowest | 76,000 ₹11,40,000 | 5,000 ₹75,000 |
| 5.00 | S & F type most heavy support structure made of 75 mm x 50 mm x 6 mm channel on both side at a height of 5 RM bottom of which grouted underground by concreate foundation cross supported with 50 x 50 x 6 mm angle horizontally at 4 points for 100 mm (Horizontal run) exhaust pipe from D.G Set to nearest building outside wall, as per direction of EIC. | 12 | Sets | 4,720 ₹56,640 Lowest | 25,000 ₹3,00,000 | 20,000 ₹2,40,000 |
| 6.00 | S & F rain protection canopy, as per direction of EIC. | 1 | No. | 1,770 ₹1,770 | 1,600 ₹1,600 | 1,500 ₹1,500 Lowest |
| 7.00 | Making insulation by 2” Fire Proof PU Foam as per direction of the EIC.
a)150 mm dia Exhaust pipe | 4 | RM | 1,121 ₹4,484 | 4,500 ₹18,000 | 1,000 ₹4,000 Lowest |
| 7.01 | b) 100 mm dia exhaust pipe | 15 | RM | 1,003 ₹15,045 | 20,000 ₹3,00,000 | 1,000 ₹15,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹36,800
Closing Date
13 Apr 2026, 4:00 pmClosed
SE,SEC,PWD
Office of the Senior Superintending Engineer SOUTHERN ELECTRICAL CIRCLE, 2nd FLOOR, MECHANICAL COMPLEX, BAGUIATI, KOLKATA 700 059.
Construction of college building (second Campus) (G Plus 5) upto third floor at Mrinalini Datta Mahavidyalaya, Ninmta, Kolkata-700049-- SITC of DG Set.
2026_WBPWD_1003201_1
WBPWD/SESEC/eNIT-10/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
120 days
Nimta, Kolkata
As in NIT
4 documents required · 4 mandatory
₹36,800
Superintending Engineer SEC PWD
28 Jul 2026
10 Feb 2026
17 Apr 2026
10 Feb 2026
13 Apr 2026
11 Feb 2026
11 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC OF 100KVA DG:
Supply, Instalation ,Testing and Commisioning at site of 100 KVA, 415V, 50Hz, 3Phase silent new DG Set, comprising of Engine, alternator, integrated AMF panel, Base frame, Fuel tank, Battery, CPCB-IV+ approved Engine & Acoustic Enclosure having following specifications.
ENGINE
Make- Cummins/Greaves Power/Ashok Leyland/Greaves Cotton)
Engine Type : 4 Stroke Diesel Engine, RPM 1500
Rated Output: 122 BHP or Higher, Duty: PRIME
Cooling : Liquid cooled/radiator cooled
Cylinder: 4, In-line
Aspiration : Turbo Charged
Type of Govemer : Electronic
Fuel Tank Capacity Minimum capacity 160 Ltr as per
manufacturer's standard Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan: As per Manufacturer's standard 16.5Ltr/ Hr. or Less, Fuel Consumption at 100% rated Load with Radiator or Fan : As per Manufacturer's standard 22 Lt/ Hr or Less Overload Capacity: 10% overload for one hour for every 12 hours continuous running at full load or better.
Engine instrument Panel : Consisting of starting switch with Key. Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter. Safety Controls Emergency Stop. Low Lube Oil Pressure warning Shutdown, High Engine Water Temp. warning (Shutdown, Sensor failure Indicator, Engine over speed indicator Battery charging and low battery indicator Exhaust Silencer Residential Type
Starting system: 12V starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard
Battery Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning. | 1 | Item. | - | - |
| 1.01 | ALTERNATOR
Make : Stamford/Leroy Somer/Crompton Greavs Rating: 415 V, 3Ph. 50 Hz, 100 KVA,1500 rpm Type Brushless, self excited and self regulated Insulation Class H Protection :screen-protected drip proof ith Min.IP23 degree of protection RPM: 1500 Voltage Regulation (max): +1% Winding connection Star with Neutral Total Distortion factor Less than 3% Total Harmonic distortion in output waveform: 55%
AMF PANEL Integrated AMF panel made from 16 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 100 KVA DG set having following specification/features. i)160A MCCB with O/L S/C, E/F protection and microprocessor based protection release , UNreleased etc. -2 sets (L&T/Siemens/ABB) m) in Built By-Pass switch for rated capacity 2On -delay timer for load change over iv) On-delay timer for engine 3)Engine On-Off switch (Push button type)
1 Battery charger complete with voltage regulator, booster selector switch, on-off switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine video Minimum five number indicating lamps to indicate 'mains JON load on mains, Set running, 'load on set' and 'battery charger on' video Audio visual alarm for 'Low lubricating oil pressure, 'High water temperature, Start failure, and DG overload load'.
Mode selector for setting the panel on Auto/Man/ Test Mode. Microprocessor based relay with composite meter for digital display of following. Generator voltage/AC Mains voltage. Generator Current in all phases Frequency ,Power Factor Energy Indication for alternator supply Running time indications number of hours of operation and service intervals, service due indications the AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure. | - | - | - | - |
| 1.02 | ACOUSTIC ENCLOSURE The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustict enclosure must be certified as per CPCB-IV norms.
BASE FRAME
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting HookType. Rate should be quoted inclusive of all applicable taxes and Duty etc
(i) All materials, equipments & accessories must conform to relevant IS /IEC specifications. (ii)The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer (iii) Necessary manufacturer's test certificate for Diesel Engine, alternator etc. Will have to submit in triplicate copy during delivery of the equipment iv) Copy of "Type Approval Certificate" and Certificate of Op must be produced at the time of delivery issued from competent Authority (As per CPCB-IV). (v) Circuit Diagram for AMF Panel must be submitted from thel stars Manufacturer / OEM. (v) The entire set must be warranted at least 15 months from the date of Delivery/24 months/ 5000 Hrs from the date off Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier. | - | - | - | - |
| 2 | Making Brick foundation and R.C. casting and making neat cement finish after plastering for installation of AMF panel incl. S&F suitable M.S angle/Channel with nuts, bolts & washer etc. as per direction of EIC. | 1 | Job | 3 | ₹3 |
| 3 | S & F M.S Exhaust Pipe of 150 mm dia. including connection with existing silencer and S & F Bend, flange, nuts, bolts and washers and necessary fixing materials as required including making necessary welding, as per direction of EIC. | 4 | RM. | 4 | ₹16 |
| 4 | S & F MS exhaust pipe of 100 mm dia -Do- - - - -Do- - - - - Do- - - - as per direction of EIC. | 15 | RM. | 5 | ₹75 |
| 5 | S & F type most heavy support structure made of 75 mm x 50 mm x 6 mm channel on both side at a height of 5 RM bottom of which grouted underground by concreate foundation cross supported with 50 x 50 x 6 mm angle horizontally at 4 points for 100 mm (Horizontal run) exhaust pipe from D.G Set to nearest building outside wall, as per direction of EIC. | 12 | Sets | 6 | ₹72 |
| 6 | S & F rain protection canopy, as per direction of EIC. | 1 | No. | 7 | ₹7 |
| 7 | Making insulation by 2” Fire Proof PU Foam as per direction of the EIC.
a)150 mm dia Exhaust pipe | 4 | RM | 8 | ₹32 |
| 7.01 | b) 100 mm dia exhaust pipe | 15 | RM | 9 | ₹135 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
Tendernotice_2.pdf
PDF • 2.01 MB
BOQ_2459020.xls
BOQ • 0.34 MB
Corri3.pdf
PDF • 0.17 MB
Corri2.pdf
PDF • 0.18 MB
Corri.pdf
PDF • 0.18 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .