Loading…
Loading…
Tender Value
₹10.0 Cr
EMD Value
₹10 L
Closing Date
22 Jul 2026, 6:00 pmClosed
executive Engineer,GSPHCL,Ahmedabad
CONSTRUCTION OF TOWN POLICE STATION (G+1) AT NALSAROVAR, Dist.-AHMEDABAD(INCLUDING ELECTRICAL WORK) (First attempt) (SBD)
320030
03(2026-2027)
Open
Civil - All
Works
Ahmedabad
18 documents required · 16 mandatory · 2 optional
₹18,000
GUJARAT STATE POLICE HOU.CORPORATION LTD.Ahmedabad
₹10 L
2 Jul 2026
2 Jul 2026
2 Jul 2026
22 Jul 2026
2 Jul 2026
Rate in Total Amount
Item No. Item Description Total Qty Unit Rate in Words
Providing and erecting Point wiring with 1.1 KV grade ISI marked 2 X 1.5 sq. mm copper PVC insulted FRLS
wire with 1.5 sq. mm (green) copper PVC insulated FRLS wire for earth continuity in FIA approved ISI mark
medium class white colour 20/25 mm dia. embossed rigid PVC pipe with PVC fitting fixed with adhesive solution
erected on/in Brick Wall / slab along with continuous G.I. fish wire to draw wires and laid in approved manner
zari for PVC pipe and boxes shall be filled with cement mortar and finishing the surface to match the wall / ceiling
complete with approved make 5/6 Amp. ISI make modular type switch and accessories mounted in 20 G. G.I. RS: Four Hundred
company fabricated metallic box covered with appropriate front plate modules erected flushed with wall / ceiling Eighty One only
with necessary modular lamp holder / modular ceiling rose / HD Connector (make & model approved by EIC and
matching colur with switches accessories) (Deep Junction box 75mm depth if required) as directed for concealed
wiring. Light point. Cat.-III.
Necessary sheet / tape / polythene / sand must be erected or filled in all box to prevent mortar going into the
box. Length of point wiring must not increase than 10 mtr. For that necessary switch boards and their locations
must be finalised before execution by agency otherwise payment will not be done for extra long point. (For future
extention, if required, agency has to erect one higher size metal box and modular plate as per instruction of EIC.
Cost of blank plate shall be paid as per tender item) [This item include cleaning (inside/outside) of all G.I. switch
boards, electric point box, fan box, MCBDB & box cutting plaster finishing for modular plate without any gap]
[conductor resistance should be as per IS:8130/1984]
For Secondary Light Point, Cat.-III RS: One Hundred
For Bell Point, Cat.-III RS: Four Hundred
Eighty One only
For Fan Point.(with 6A Modular type switch and Two Module hum free 5/6 step EME step type Electronic fan RS: Six Hundred
243D regulator both having ISI Make ) Cat-III 175.00 Point 668.00
Sixty Eight only
For separate Point (with 6 Amp. Switch & 3/5 pin socket both having ISI mark) Cat. III RS: Five Hundred
For Looped on switch board (with 6 Amp. Switch & 3/5 pin socket both having ISI mark) Cat. III
RS: Two Hundred
Fifty Five only
Providing and fixing Plug Point wiring with 1.1 KV grade ISI marked approved make 2 x 2.5 sq.mm copper PVC
insulated FRLS wire with 1.5 sq.mm (green) copper PVC insulated FRLS wire for earth continuity in FIA
approved ISI mark white colour medium class 20/25 mm dia. embossed rigid PVC pipe with PVC fitting fixed
with adhesive solution erected in wall/slab along with continuous G. I. fish wire to draw wires and laid in
approved manner zari for PVC pipe & boxes shall be filled with cement mortar & finishing the surface to match
the wall / ceiling complete with 16 Amp Modular type Swich and accessories mounted in 20 G. GI company RS: Seven Hundred
fabricated metallic box covered with appropriate front plate modules erected flushed with wall. (a) 16 Amp. Thirty Eight only
Indicator switch & 1 No. 6/16 A universal socket white colour suitable for 3/5 pin top duly both having ISI mark.
(Necessary sheet / tape / polythene / sand must be erected or filled in all box To Prevent Mortor Going In To The
Box) Cat.-III. (Conductor resistance should be as per IS:8130/1984)
Providing & Erecting Plug Point wiring with approved ISI marked 1.1 kv 2 x 4.0 sq.mm copper PVC insulated
FRLS wire with 2.5 sq.mm (green) copper PVC insulated FRLS wire for earth continuity in FIA approved ISI
mark white colour medium class 20/ 25 mm dia. embossed rigid PVC pipe with PVC fitting fixed with adhesive
solution erected in wall/slab along with continuous G. I. fish wire to draw wires and laid in approved manner.zari
for PVC pipe & boxes shall be filled with cement mortar & finishing the surface to match the wall / ceiling
complete with 1 No 25 Amp Modular type Single pole MCB Swich and 1 no 25A universal 3 pin socket suitable
RS: Nine Hundred
245 for 3 pin top duty both having ISI mark .mounted in 20 G. GI company fabricated metallic box covered with 17.00 Point 991.00
appropriate front plate modules erected flushed with wall.Above accessories will be erected combined or
separately as per site requirement and instruction of EIC. (conductor resistence should be as per IS:8130/1984
Cat III (Gyser Point) (Necessary sheet / tape / polythene / sand must be erected or filled in all box to Prevent
Mortor Going In to The Box)
Providing & Erecting Plug Point wiring with approved ISI marked 1.1 kv grade 2 x 4.0 sq.mm copper PVC
insulated FRLS wire with 2.5 sq.mm (green) copper PVC insulated FRLS wire for earth continuity in FIA
approved ISI mark white colour medium class 25 mm dia. embossed rigid PVC pipe with PVC fitting fixed with
adhesive solution erected in wall / slab along with continuous G.I. fish wire to draw wires and laid in approved
manner. zari for PVC pipe & boxes shall be filled with cement mortar & finishing the surface to match the wall /
ceiling complete with approved make 20 Amp. Modular type indicator switch and accessories mounted in 20 RS: Eight Hundred
246 SWG GI company fabricated metallic box covered with appropriate front plate modules erected flushed with wall 21.00 Point 863.00
Sixty Three only
/ ceiling. (a) 20 Amp Indicator switch & 1 No. 20 A universal socket white colour suitable for 3 pin top duly both
having ISI mark (A.C POINT ONLY) CAT III (Necessary sheet / tape / polythene / sand must be erected or filled
in all box to Prevent Mortor Going In to The Box)
Providing and erecting Medium Class FIA approved and ISI mark white colour (embossed) RIGID PVC PIPES
of following size complete erected with necessary PVC fittings & Junction boxes fixed with adhesive solution &
clamps on / in wall / ceiling along with continuous fish wire to draw mains with necessary fittings and junction RS: Twenty Four
boxes for following dia. For 20 mm. dia. only
For 25 mm. dia. RS: Thirty Three
Providing & Erecting Mains with FRLS PVC Insulated wire ISI marked 1.1 KV grade with FIA approved ISI mark
medium class 20/25/32 mm dia. embossed rigid PVC pipe with PVC fitting fixed with adhesive solution to be
erected on/in brick wall / slab along with continuous G. I. fish wire to draw mains laid in approved manner with
plastering by cement mortar & finishing the surface to match the wall / ceiling complete with FRLS PVC insulated
wire for earth continuity. (Approved ISI make only) (Conductor resistance should be as per IS:8130/1984 ) [a] 2 x RS: Sixty Two
1.5 sq.mm. FRLS copper multi stranded conductor mains with 1.5 sq.mm. FRLS copper multi stranded only
conductor for earthing as per standard colour code. (with 20 mm dia. PVC pipe) [Wire must be having box
2 x 2.5 sq.mm. FRLS copper multi stranded conductor mains with 1.5 sq.mm. FRLS copper multi stranded
conductor for earthing as per standard colour code. (Conductor resistance should be as per IS:8130/1984) RS: Eighty Two
For 2 x 4.0 sq.mm. FRLS copper multi stranded conductor mains with 2.5 sq.mm. FRLS copper multi stranded
conductor for earthing as per standard colour code. (with 20/25 mm dia. PVC pipe) [Wire must be having box RS: One Hundred
packing] (Conductor resistance should be as per IS:8130/1984 ) Eleven only
For 2 x 6.0 sq.mm. FRLS copper multi stranded conductor mains with 2.5 sq.mm. FRLS copper multi stranded
conductor for earthing as per standard colour code. (with 25 mm dia. PVC pipe) [Wire must be having box RS: One Hundred
248D packing] (Conductor resistance should be as per IS:8130/1984 ) 230.00 Mtr. 146.00
For 4 x 10.0 sq.mm. FRLS copper multi stranded conductor mains with 4.00 sq.mm. FRLS copper multi
stranded conductor for earthing..As per standard colour code. (with 25/32 mm dia. PVC pipe) (Conductor RS: Four Hundred
resistance should be as per IS:8130/1984 ) Twenty One only
Providing & fixing 25 mm. dia Pvc insulated G.I corrugated flexible pipe with necessary socket, PVC bushes
RS: Thirty Seven
249 Saddle. 50.00 Mtr. 37.00
Providing & erecting Modular type accessories mounted on 20G. company Fabricated Galvanised Metal box
covered with appropriate front plate modules erected flushed with wall / ceiling with 1 Nos. TV Socket,1 Nos. of RS: Seven Hundred
16 Amp SP Switch & 3 Nos. of 6 Amp 3/5 pin plug. [For TV Switch board] Cat III Eighty Eight only
TV Co-axial Socket Outlet.Cat-III
RS: One Hundred
Fifty Nine only
For Two pin / RJ-11Telephone Socket (For One Gang) Cat III
RS: One Hundred
Fifty Nine only
For Blank plate single Cat-III
RS: Twenty Five
For Modem Jack for Computer Open RJ-45 Cat III
RS: One Hundred
Fifty Nine only
For Modular indicating call bell Cat.-III
RS: Three Hundred
Twenty Six only
For Modular Buzzer Cat.-III
RS: One Hundred
Forty Eight only
Providing & erecting Switch board for Computer or electric apparatus consisting of following items in single
board erected on Metal board with 3 mm thick PC (Polycarbonet) / Acrylic sheet erected as directed. 2 no. RS: One Thousand
251 6/16 Amp. universal Socket, 2 nos. 16 Amp. indicator switch, 2 nos. 6 Amp. Switch & 2 nos. 6 Amp. 5 pin Plug. 73.00 Each 1122.00 One Hundred Twenty Two
For Computer power Supply board. Cat.-III. only
Providing & erecting following size of TV Co-axial flexible cable comprising inner conductor of solid bare copper
insulated with Foam PE & Secondary conductor made of poly - Aluminium film bonded Al. Braids @ suitable
RS: Thirty Nine
252 coverage overall sheathed with black PVC insulation. for RG-6 [Polycab/ Finolex / RR Kabel Make] 300.00 Mtr. 39.00
Providing & Erecting 2.0 mtr long Earthing system by making minimum bore of 225 mm dia in soft soil. Suitable
for doing pipe-in-pipe technology earthing.Earthing electric rod must be made from Corrosion free Hot dip
galvanizing pipes having following specification.
(A) Earthing Electrode: outerpipe:- 88 mm minimum O.D., ISI 'B ' Class ISI mark of Reputed Brand, Inner pipe:-
42 mm minimum O.D., Pipe B Class ISI mark reputed Brand Terminal Size: 70mm X 100mm length, Terminal
Should be made from inner pipe for that pipe must be pressed and gave rectangular shape so its work as a
terminal.The hot deep galvanising must be done after above process.Galvanised thickness must be minimum
micron any where. SS Nut bolt:- 2 no.with washer suitable for 14mm dia. hole must be provided at terminal. total RS: Seven Thousand
minimum Weight(approx.) of earth electrodewith inside conductive material minimum should be 26 kg. Twenty Five only
(B) Inner chemical (CCM Compound)- Resistivity:- 0.2 ohm/meter testing as per IEC 62561-2017, Voltage drop:-
< 1 volt at no load & dry form, Sulphar content:- <2%
(C) Back fill Compound:- Earthing compound should be capable to retain moisture for long time Back Filling
Compound weight is 25 Kg.
(D) Chamber and cover:- Earthing chamber should be size of 400 mm X 400 mm X 400 mm depth and Cover
should be heavy duty cast iron with required size of 300 mm X 300 mm X 4 mm thick.
Necessary test report must be submitted.
1. Short circuit test by ERDA/ CPRI for 25KA
2. Resistivity test of conducting material from NABL accredited lab.
3. Hot dip galvanised / zinc coating micro test from reputed laboratory.
4. General test report from OEM regarding specification of earthing.
[Make and model approved by EIC Strictly subject to item specification only] [OEM has to submit all detail &
sample for approved before supplying]
[Water must be poured in bore before starting earthing. Earthing value must be measured with earth tester.
Agency has to bring the earth resistance to at least 02 ohms & voltage between neutral & Earthing upto 02 volt.
Agency has to maintain earthing & its value for one year. Earthing must be done in the presence of A.E.
For above earthing additional charges for boring in hard rock soil (by breaker) & filling soft soil in earth pit
(certificate for soil have to given by DEE / AE along with photographs) RS: Two Hundred
Seventy Six only
Providing & Erecting Mains with ISI marked, 1.1 KV grade electrolyte multi stranded, annealed copper conductor
with heat resistant PVC insulated conforms to IS:694, IEC - 227 erected in existing pipe of following size
(Specifically for control panel, relays, power switchgears, motor starters & control wiring) with required size of RS: Twenty Seven
copper lugs, nuts and bolts if required. For One wire 2.50 sq. mm only
For One wire 6.00 sq. mm
254B 130.00 Mtr. 56.00 RS: Fifty Six only
For One wire 10.00 sq. mm
For one wire 16.00 sq. mm (For Solar system earthing & Panel Earthing)
RS: One Hundred
For one wire 35.00 sq. mm
RS: Two Hundred
Ninty Eight only
Providing and erecting required size HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/
Transformer LT panel board, Motors etc. using proper clamp with min 80 micron as per IS.Test certificate must RS: Seventy Seven
255 be submitted by agency. 50.00 KG 77.00
Providing and erecting required size Copper strip for earthing of H.T. OCB / ACB/ Transformer, LT panel board,
Motors etc. using copper clamp. RS: Seven Hundred
Eighty Seven only
Supplying & erecting M.S./ G.I metal Box having 16 Gauge painted with red oxide be concealed in wall with
necessary plastering & finishing covered with 3mm thick Laminated sheet with grooving as directed of following RS: Five and Paise
257 depth. 3" Depth 1000.00 Sq inch 5.94
Ninty Four only
Supplying and erecting 8W led lamps with following wattage capacity of 220 to 240 voltage, minimum
burning hours life, 500 V in built-surge protection,Polycarbonate diffuser, mounting suitable for E14 / E27 / B22 RS: One Hundred
258 lamp holders, pf >= 0.5 LED Lamps integral type, with PC diffuser suitable LAMP holder 18.00 Each 111.00
Supplying and Erecting LED indoor fitting of approximately 4feet long with LED of wattage 0.2W to 0.5W
assemble on single MCPCB with housing use as a heat sink shall be made from Aluminum extrusion having
enough strength (sample must be approved by EIC) with polycarbonate diffuser with following specification: (A)
Company mark/name on the fitting.(B) Rated input voltage and frequency: 220V to 240 VAC ; 50Hz.(C) Rated
input wattage: max. 24w(D) Rated input current : 0.2 Amp
(E) Power Factor : Min. 0.90(F) ATHD : Max. 15%(G) Rated Luminous flux: Min. 2420 lm RS: Three Hundred
259 (H) CCT: 6500K(I) CRI: Min. 80Ra(J) Driver Efficiency: Min. 80%(K) LED life span: Min. 50000 Hrs @ L70(L) 15.00 Each 370.00
Over Voltage protection: Withstand up to 440V/AC for 4 Hrs.(M) Surge protection : Min. 2KV
(N) IP rating: IP 20(O) IK rating : IK 02(P) Short circuit , Open circuit & Reverse Polarity Protection must be
provided(Q) Fixing clamp design & strength should be sufficient to hold the fitting erected on wall or ceiling.(R)
core copper wire of appropriate size with earthing connector
(Note:-The manufacturer/ authorized Channel partner of the manufacturer has to submit 5 yrs free replacement
Guarantee for complete Fixture) [Approval will be given strictly subject to item specification]
SITC of Indoor Commercial recess/surface mounted (IP20) Max. 24 w Cool/warm white Color LED Down lighter
office Lighting Luminaire with external separate driver having BIS certification with fully die cast aluminium alloy
housing without any PVC/Plastic part with corrosion resistant powder coated finish as a heat sink with Poly
Carbonet diffuser LED complete (only from Philips Lumileds, CREE, BridgLux, Seoul, Nichia & Osram CRI >
RS: Seven Hundred
260 CCT 5600K (5400 to 5800K bin). The led's should be mounted onbacklit Metal core based PCB for better heat 405.00 Each 751.00
conduction and long life of LED. (LM 79 for complete fixture, LM80 for individual LED Report mustbe submitted)
The fixture should have extra protection of driver like over/under voltage, THD<15%, P.F.>0.90, for 24 w fixture
wide voltage range from 100 to 270 V, 50/60 HZ, 4 KV surge protection.
Fixure must have Min. 2160 Lumens light output. Fixture Efficacy should be>=90 Lumens/watt. (L70 @
Hrs) The Fixture should be able to easily mount on POP/Grid False cieling. The Luminiare should be tested as
per IP20 standards and following test reports should be submittedat the time of approval. Model Approved By
EIC as per Specification only (Note:- The manufacturer/authorized Channel partner/dealer of the manufacturer
has to give a 5 yrs. free replcement Guarantee for complete Fixture)
SITC of Indoor Commercial recess/surface mounted (IP20) Max. 18 w Cool/warm white Color LED Down lighter
office Lighting Luminaire with external separate driver having BIS certification with fully die cast aluminium alloy
housing without any PVC/Plastic part with corrosion resistant powder coated finish as a heat sink with Poly
Carbonet diffuser LED complete (only from Philips Lumileds, CREE, BridgLux, Seoul, Nichia & Osram CRI >
RS: Five Hundred
261 CCT 5600K (5400 to 5800K bin). The led's should be mounted on Metal core based PCB for better heat 150.00 Each 584.00
Eighty Four only
conduction and long life of LED. (LM 79 for complete fixture, LM80 for individual LED Report mustbe submitted)
The fixture should have extra protection of driver like over/under voltage, THD<15%, P.F.>0.90, for 18 w fixture
wide voltage range from 100 to 270 V, 50/60 HZ, 4 KV surge protection.
Fixure must have Min. 1620 Lumens light output. Fixture Efficacy should be>=90 Lumens/watt. (L70 @
Hrs) The Fixture should be able to easily mount on POP/Grid False cieling. The Luminiare should be tested as
per IP20 standards and following test reports should be submittedat the time of approval. Model Approved By
EIC as per Specification only (Note:- The manufacturer/authorized Channel partner/dealer of the manufacturer
has to give a 5 yrs. free replcement Guarantee for complete Fixture)
Providing and erecting max. 10 W LED battern having main housing aluminium extruded and front cover of
polycarbonate. Electrically and photomatry parameters are as under:240 V, 50 Hz. System wattage.:10W+10%,
PF>=0.95, system lumens min. 1000, CCT- 3000K to 6500K, CRI>=80, THD<=15%, Delivery efficiency>=85%,
LM 80 certified LED, 30000 Hrs@ L70, Electronic CC driver, insulated copper wire, for internal wiring, IP20
Operating voltage:160 to 270 V, Surge-2 KV, length of this fitting should be 2ft. RS: Three Hundred
262 Luminaire efficacy> 85 lumens/watt ,LED 13.00 Each 309.00
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity
of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) Tube Light
with integral driver 8 Watts, Surge-2 KV, IP-20, conventional 1 to 2 feet
Providing and erecting PVC body surface mounting LED Bulk head type 9 watt Lighting Fitting with electronic
driver having THD < 15%, CRI>80, P.F.0.95 And lumen output from luminaire 720 lm, input voltage range 160- RS: Seven Hundred
270 V AC, 50 Hz cool white (3000 to 6500 k), inbuilt driver having efficiency >=80lm/w, -20 deg C to + 60 deg C Eighty only
working temperature, AL frame with Beam Angle 120 deg.
Supply, Installation, Testing and Commissioning of suitable sweep, BEE 5 Star rated, Ceiling fan with Brush
Less Direct Current (BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust free 3 nos.Aluminium
blades, 2 nos. canopies, shackle kit with earthing provision, copper winding, Power factor not < 0.9, Service
Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM,230v (tolerance as per IS : 374- RS: Two Thousand
264 2019), THD < 10%, compitible with electronic regulator unit for Speed Control and all remaining accessories 175.00 Each 2603.00 Six Hundred Three
including safety pin, nut bolts, washers, temperature rise = 75 degree C (Max.), suitable for 140 to 285 Voltage only
and rectifier circuit with surge, over current and overload protection , 50 Hz, Single phase AC Supply, earthing
etc. Complete as required.[ Make shall be approved by Engineer in Charge] (A) 1200 mm Sweep (48")
Supplying & Erecting Fan Hook Of 10 mm M.S Round bar bounded to the RCC bars up to 50 mm Length each
side & piereced through 18 Gauge G.I Box having 125 mm dia depth of 75 mm complete erected concealed in RS: One Hundred
ceiling with necessary modular plate / sheet Twenty Five only
Supplying and erecting approved make oscillating type bracket fan A.C. 23OV. 50cy/s 400/450 mm sweep wall
RS: Two Thousand
mounted with height adjustment and rotary tilting device complete with guard, flexible Core plug top complete
266 7.00 Each 2509.00 Five Hundred Nine
erected with lead wires as directed. ( Make:- Baja,Usha, Crompton, Orient, Havells)
Supplying and erecting 19 / 20 mm. nominal bore "B" Class G.I Pipe /M.S. Pipe down rod erected duly painted
for fan complete with necessary 24/0.2 flat 3 core flexible cable with earthing.The Down rod RS: One Hundred
thickness,hole,locking arrangement,construction,power coating,colour shed should be same as original down rod Seven only
brought with ceiling fan.For that agency has to give original down road sample to fabricator and one sample
Supplying and erecting approved make 200mm sweep low noise decorative exhaust fan having
Aerodynamically designed and Blanced Blade, Blade finish Opaque,body colour White , finish Glossy , Rated
RS: One Thousand
Speed 1350/1800 revolution per minute ,air delivery 500m³ / hr , noise level 50 dB , Power Consumption
268 20.00 Each 1687.00 Six Hundred Eighty Seven
W, ,Rated Voltage 230 V , no. of blades 7 , guard 18 Louvers , square frame ABS body with inbuilt lowers
and square frame.( Havell s Make Ventilair LX or Bajaj, Usha, Crompton and Equivalent Model Approved by
EIC subject to Above Specification )
Providing and erecting Decorative Ding Dong call bell Stereo type 250 Volt complete erected on existing
polished wooden block or in M.S. box with 3 mm thick white ISI mark laminated sheet. (Anchor (chime), Vision, RS: One Hundred
Rider make) Seventy only
SITC of Vertical Air Termination Solid aluminium with Base - 10 mm dia. and 1000 mm long. Air Termination
Base tested for conditioning, Ageing Test & Lightning impulse current withstand test: 100 kA of 10/350 µs RS: Nine Thousand
270 waveform in an accredited. Third party laboratory as per 6.3 & 6.4 of IEC 62561-1 2017 protocol with MAST 34 3.00 Each 9323.00 Three Hundred Twenty
mm dia. 3000 mm long- Cold Galvanized as per EIC (Axis Electrical,OBO, JEF, CAPE, DHEN or equivalent Three only
make approved by EIC)
SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid and tested as per IEC 62561- 2 conducted
in the Govt. accredited thirty party laboratory to meet the requirement of IS/IEC 62305 with Required
Accessories - Aluminium Holding clamp at every 1 mtr distance, Aluminium/SS cross splicer at every crossing of
Alu. conductor, Expansion piece with connectors at every 20 mtr distance, Aluminium straight Splicer to connect RS: Two Hundred
271 conductors. All Accessories should be tested as per IEC 62561-1 2018 Cl. 6.3 for conditioning & Ageing Test & 300.00 Mtr 297.00
Ninty Seven only
6.4 for Lightning impulse current withstand test: 100 kA of 10/350µs waveform(Ageing & Electrical test )
conducted in a sequence manner & tested in the Govt. accredited Third party laboratory to meet the
requirements of IS/IEC 6230 (Axis Electrical,OBO, JEF, CAPE, DHEN or equivalent make approved by EIC)
SITC of Galvanized Steel Flat 25x6 mm thickness from earth electrode directly in ground as required. Zinc
coating: 500 g/m square (Approx:70 micron coating) tested and used exclusively for lightning protection earthing RS: One Hundred
system and ring equipotential bonding. [make and model approved by EIC strictly as per tender specification] Fifty Three only
SITC of 14.2 mm dia 3 mtr long Earth electrode of High tensile steel electrode with 250 micron copper bonding &
1 bag of Carbon fill Based environment friendly backfill tested as per IEC 62561-7 in NABL accredited RS: Five Thousand
273 Laboratory and suitable stainless Steel double sided clamp. Eco Friendly rust proof heavy duty weather proof 4.00 Per set 5933.00 Nine Hundred Thirty Three
Polyethylene Earth Pit Chamber with following dimensions: 254 mm dia (top), 330 mm dia (bottom) & 260 mm only
(height). [make and model approved by EIC strictly as per tender specification]
Providing & erecting weather proof, dust & vermin proof, floor mounted front operated indoor type cubical panel
board having IP-42 & above protection as per approval from engineer incharge and made from 2 mm. thick CRC
M.S. sheet for outer body & doors, 1.6 mm. thick CRC M.S. sheet for internal partitions with necessary
supporting angles, flats including skirting, bending, drilling, welding, riveting with internal partitions & cable alley
as per requirements & instruction of engineer-In-Charge with erection of supplied switchgears, busbars with
suitable size of interconnecting PVC copper wire / Copper-Aluminium strips, rubber gromets, rib, control wires,
backelite control fuses, measuring instruments, earth bus & earth bolts, foundation flange-bolts-base plates, RS: Sixteen Thousand
274 sufficient nos. of hinged doors, handle with locking arrangement, rubber gasket complete with Required Nos. 4.00 Sq. Mtr. 16230.00 Two Hundred Thirty
heavy Duty Connector with Cadmium plated nut and bolt for Anti rusting. The panel shall be supplied with Seven only
Tank chemical process which shall be carried out before applying painting, painted with powder coating. (The
rates excludes the cost of switchgears, busbars, interconnecting mains & Copper / Aluminium strip, fuse, meters
etc. The dimension shall be measured excluding base beams) The standard companies switch gear shall be
used and only manufacturers at CPRI approved factory as per IEC 61439 and shall be certified by that company
whose switch gears are used after fabrication for beneficial use. With 350 mm depth
Panel manufacturer have to give 5 years maintenance and service support if in case of breakdown or fault.
Panel manufacturer have to submit electrical meter calibration report. Agency should design the panel in such a
way that there should not be any excess in panel area (sq.mtr) & length of bus-bar (mtr), if any excess occurs
draw attention to GSPHCL at the time of approval of G.A. drawing.
Loading and unloading of above item shall be done by hydra and skill work force under supervision of electrical
engineer and guidelines given by manufacturer to avoid damage to the item. Picture of it to be submitted in
running bill / final bill.
Size of door and Ele. room / Pump room shall be checked by agency's engineer before giving order. If found any
problem in size discuss with GSPHCL engineer for rectification before giving order. [Including Necessary
numbering / marking on PANEL done with red colour radium sticker as per site requirement and instructions
given by EIC on site. Font / number size given by EIC on site as per requirement] (All Panel as per IEC
as per NBC Guideline) [Manufacturer must be of Gujarat state so three stage inspection can be done]
Supplying and erecting tripple pole & neutral 440V / 500 V Panel mounting Copper Busbars with four equal Nos.
of electrolyte bus having current density not more than 1.6 Amp. / sq.mm (Rated current / cross section area)
RS: One Thousand
duly wraped with colour insulating tape for phase sequence of following current carrying capacity, erected with
275a 1.00 Rmt 1942.00 Nine Hundred Forty Two
necessary bus bar supports / insulators, main cable socket to each bar, erected in existing cubical panel with
necessary connections.For electrolyte copper busbars Suitable for 100 Amp. capacity.
For Suitable for 200 Amp. Capacity
RS: Three Thousand
275b 1.00 Rmt 3171.00 One Hundred Seventy
For Suitable for 300 Amp. Capacity
RS: Four Thousand
275c 1.00 Rmt 4861.00 Eight Hundred Sixty One
Supplying & erecting approved make Four Pole 415 V change over switch interior for panel mounting with
operating mechanism A.C.23 duty confirming to IS [a] For 250Amp FP . Cat III
276a 1.00 Each 13221.00 Thousand Two Hundred
Twenty One only
For (C)100-125A FP C/O Switch . Cat III
RS: Seven Thousand
276b 2.00 Each 7713.00 Seven Hundred Thirteen
For 63A FP C/O Switch
RS: Four Thousand
276c 1.00 Each 4738.00 Seven Hundred Thirty
Supplying and Erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of
35 K.A. at 415 V. having normal current rating 250 A. with Variable or fixed thermal & magnetic release suitable RS: Twenty Thousand
277 to work on A.C.supply 50 c/s. with all internal connections spreader tinned copper & complete erected in existing 2.00 Each 20739.00 Seven Hundred Thirty
16 G.M.S. housing. housing. ICS=100% of ICU only Nine only
Providing and Erecting approved make Four pole moulded case circuit breaker having breaking capacity ICU of
25 KA. at 415 V. having normal current rating 25 A to 100A. with variable or Fixed thermal & magnetic release RS: Six Thousand
278 suitable to work on A.C.supply 50 c/s. with all internal connections,spreader tinned copper & complete erected in 4.00 Each 6112.00 One Hundred Twelve
existing 16 G.M.S. housing. ICS=100% of ICu only. ( only
Providing and Erecting approved make Four pole moulded case circuit breaker having breaking capacity ICU of
35 KA. at 415 V. having normal current rating 125A. with variable or Fixed thermal & magnetic release suitable RS: Seven Thousand
279 to work on A.C.supply 50 c/s. with all internal connections,spreader tinned copper & complete erected in existing 3.00 Each 7976.00 Nine Hundred Seventy Six
16 G.M.S. housing. ICS=100% of ICu only. only
Providing and erecting following additional parts for panel mounting MCCBs (A)Extended operating rotary handle
with pad lock with three position trip,off,on suitable for 25A to 250 A panel mounting. Company must be same as RS: Eight Hundred
280 Switchgear company. 11.00 Each 865.00
Sixty Five only
Approved make Earth fault Relay suitable to mount with inter connection to moulded case circuit breaker having
CT ratio & MCCB rating as following along with shunt trip 220V AC. with all internal connections & complete RS: Five Thousand
281 erected in existing M.S.housing. For 250A- 400A, CT Ration 1/400 (For Sub Panel, Main Panel) 3.00 Each 5362.00 Three Hundred Sixty Two
Supplying and erecting approved make panel mounting type Digital Voltmeter having 3 x 1/2 digits LED display,
0.5 class of accuracy 0 to 750 AC Volts range erected on existing panel board with all connection, wiring etc. RS: One Thousand
282 with manufacturers calibration certificate. 3.00 Each 1263.00 Two Hundred Sixty Three
Supplying & erecting aproved make Panel mounting type Digital Ammeter having Three Digits LED Display,0.5
RS: One Thousand
class of accuracy, External CT operated Calibrated for 0 to 1000 Amps suitable to operate on 500 Volt AC
283 3.00 Each 1543.00 Five Hundred Forty Three
erected on existing panel board with all connection wiring etc.with manufacturers calibration certificate.
Supplying, erecting, testing and commissioning of Ammeter / Voltmeter selector switch for 3 phase AC supply
500 V on existing panel board with necessary connections. RS: Three Hundred
Supplying and erecting approved make set of indicator lamps LED lamp, lense cover, bakelite holder complete
erected with necessary connections. RS: Forty Three
Providing, erecting, testing and commissioning of L.T. Current Transformer with bus bar primary 50/5 to 1000/5
ratio 15 VA burden having 0.5 Class Accuracy Duly secured with insulating materials connected to the meter. RS: Two Hundred
Seventy Two only
Providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system
and having breaking capacity 10 KA to be erected in existing box. confirming to IS 8828/1996 with ISI Mark ( RS: One Hundred
For 3 phase DB 24nos. , 6 nos. Main Panel and sub panel) Eleven only
Providing and erecting 240 volt MCB double pole switch for M&I(C Curve) having 10 KA Breaking capacity and
confirms to IS : 8828 in existing with earthing terminal having following capacity. For 6-32 Amp Capacity. RS: Two Hundred
Ninty Seven only
Providing and erecting 240 volt MCB double pole switch for M&I(C Curve) having 10 KA Breaking capacity and
confirms to IS : 8828 in existing with earthing terminal having following capacity. For 40 Amp Capacity. RS: Three Hundred
Twenty Seven only
Providing and erecting 415 Volt MCB four pole motor & inductive load(c Curve) having 10 KA Breaking capacity
and confirms to IS : 8828 in existing metal box having following capacity. For 40 Amp FP. RS: Six Hundred
Providing and erecting 415 Volt MCB four pole motor & inductive load(c Curve) having 10 KA Breaking capacity
and confirms to IS : 8828 in existing metal box having following capacity. for 63 Amp FP. RS: Seven Hundred
Providing and erecting 240 volt MCB double pole switch for M&I(C Curve) having 10 KA Breaking capacity and
confirms to IS : 8828 with same company Metal box with earthing terminal having following capacity. with RS: Five Hundred
necessary quarter Numbering with oil paint by Painter. for 40 Amp Capacity. Two only
Providing and erecting 240 volt MCB Four pole switch for M&I(C Curve) having 10 KA Breaking capacity and
confirms to IS : 8828 with same company Metal box with earthing terminal having following capacity. with RS: Nine Hundred
necessary quarter Numbering with oil paint by Painter. For 63 Amp Capacity. Five only
Supplying & fixing box for housing RCCB + MCB combination made of 18 SWG sheet steel duly powder coated
with gasket, dust & vermin proof bakelite shield two earthing terminals for following type of RCCB, RCCB + MCB
with necessary numbering / marking with oil Paint by painter. [a] For 2 pole [Box must be of same company as RS: Two Hundred
MCB, ELCB used] Seventy Two only
For 4 pole [Box must be of same company as MCB, ELCB used]
RS: Four Hundred
Providing and Erecting approved make ELCBs / RCCBs conforming to IS: 12640 and having sensitivity of 30 mA
and Short Circuit withstand capacity of 6 KA and suitable for operation on single phase 240 V. having RS: Two Thousand
295 characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component. 2.00 Each 2213.00 Two Hundred Thirteen
for following Max. rating erected as directed for 40 Amps.DP only
Providing and erecting metalic danger notice board as per language suggested by engineer inchrge for MEDIUM
VOLTAGE installation to be erected as per IS-2551 RS: Sixty Nine
Supplying & erecting bank of all polypropylene condenser (APP type) with standard capacity of 2,3,5,7,
& 15 KVAR units of P.F. correction for operation on 3 phase 50 c/s, 400 /440V (+ / - 10%) with externally
discharging resistance, earthing terminal & built on angle iron of channel iron frame work and provided with
terminal cover box. Complete erected on provided iron bracket or on floor duly tested by license. RS: Six Hundred
Providing ad erecting approved make single phase Double Door metal clad D.B. as per relevant indian
standards ammended upto date.
Supplying and fixing following way single phase MCB distrubution board of company fabricated with sheet box
with powder coated inside and outside after apply seven tank chemical process of MS sheet cover complete with
suitable integral single piece construction tinned copper busbar and link with all necessary interconnection and
with necessary size MS frame for mounting MCBDB. Manufacturer must be provided (1) IP 43 and as per
IS:8623-1 & 3, IEC 61439-1 & 3 having D type PU gasket. (2) Seven tank Powder coating Certificate (3) Tinned
Copper/Brass make neutral & Earthing link with isolation & Protecting Cover for 240 Volts on surface / recess
complete with loose wire box, terminal connectors for all incoming and outgoing circuits, with suitable size FRLS RS: Five Thousand
298 PVC insulated copper conductor up to terminal blocks and internal connection, tinned coppper bus bar, 1 no. 14.00 Each 5868.00 Eight Hundred Sixty Eight
tinned copper neutral link, tinned copper earth bar, din bar, detachable gland plate, interconnections, powder only
painted including earthing etc.
Single phase incoming and horizontal single phase outgoing. For 16 Way MCBDB: Including 40 Amp. 30 mA
double pole ELCB (ELCB confirming to IS:12640/1988 having sensitivity of 30 mA and breaking capacity of
KA), MCB 40 Amp. double pole switch (C curve confirms to IS:8828 having breaking capacity of 10 KA) and S.P.
MCB of rating 6 to 32 Amp. with NL suitable to operate on 240 Volt A.C. power. (6 Amp:- 4 Nos., 16 Amp:-
Nos. & 25 Amp: 4 Nos.) Cat.-III
(The DBs should be used of same company of MCB / ELCB to be used) (MCBDB must be erected in line & level
with spirit level and finish the external edge with box cutting plaster) (Same colour MCB(SP/DP) should be used
as same as MCBDB) [Including Necessary numbering / marking on box done with red colour radium sticker as
per site requirement and instructions given by EIC on site. Font / number size given by EIC on site as per
Supply, Installation, Testing & Commissioning of Three Phase, 440 V Surge Suppressor protection Device (SPD)
& 40 Amp TPN MCB (or As per SPD OEM guide line for the protection of SPD which is erected such a way that
it can be operated easily) SPD must be capable to protect all electrical and electronics equipments if SPD blast
RS: Six Thousand
or fuse then the panel builder must have replace it soon during defect liability period.The Detail Specification of
299 3.00 Each 6319.00 Three Hundred Ninteen
SPD are As per Attached sheet with Annexture -A(E). (Hakel,ikra,OBBO make) (With Three year
Gaurantee/warranty)
Supplying and erecting Servo Controlled Voltage Stabilizer (SCVS) as per following requirement: (1) Input
Voltage Range - Three Phase 340 To 480 Volt AC. (2) Out put Volatge - Three Phase 415 Volt AC (Line - Line)
with Voltage Regulation of +/- 1%. (3) Frequency range - 47 Hz To 63 Hz. (4) Efficiency - More or equal to 98%.
(5) Type of Stabilizer - Suitable for Balance & Unbalance Load and Voltage including SPD (6) Controlled Type -
Digital Micro Controller Based Disply. (7) Rate Of Correction - Upto 100 Volt / Sec (Line - Line) (8) Servo Motor
Drive - AC Syncronous Stepper Motor - As per KVA Capacityy, Out put volatge and Voltage regulation
requirement. (9) Nil Wave form Distortion and Effect of Load POwer. (10) Responce Time - 10 milli second. (11)
Protection requirements - Input low Cut off protection / Input High Cut Off Protection / Output Low Cut Off
protection / IOutput High (12) Fault Annuciation Panel LED shows Input present, Input high Input low, Output RS: Two lac Nine
300 Normal, Output High, Outpur low, Overload. (13) Output On time delay - 10 seconds (14) Ambient Tempeature 1.00 Each 209875.00 Thousand Eight Hundred
capacity - 0 - 45 RH upto 90 %. (15) Enclosure Type - IP 20 (16) Type of Cooling - Air ,Output:Bypass switch Seventy Five only
with changeover switch and Provied SPD & 4 year free replacement guarantee on Stamp paper.
Loading and unloading of above item shall be done by hydra and skill work force under supervision of electrical
engineer and guidelines given by manufacturer to avoid damage to the item. Picture of it to be submitted in
running bill / final bill.Size of door and Ele. room / Pump room shall be checked by agency's engineer before
giving order. If found any problem in size discuss with GSPHCL engineer for rectification before giving order. (75
KVA) (Fuji Electric, Servomax Limited, Krykard, protekG Make)
Supplying and erecting Servo Controlled Voltage Stabilizer (SCVS) as per following requirement: (1) Input
Voltage Range - Three Phase 340 To 480 Volt AC. (2) Out put Volatge - Three Phase 415 Volt AC (Line - Line)
with Voltage Regulation of +/- 1%. (3) Frequency range - 47 Hz To 63 Hz. (4) Efficiency - More or equal to 98%.
(5) Type of Stabilizer - Suitable for Balance & Unbalance Load and Voltage including SPD (6) Controlled Type -
Digital Micro Controller Based Disply. (7) Rate Of Correction - Upto 100 Volt / Sec (Line - Line) (8) Servo Motor
Drive - AC Syncronous Stepper Motor - As per KVA Capacityy, Out put volatge and Voltage regulation
requirement. (9) Nil Wave form Distortion and Effect of Load POwer. (10) Responce Time - 10 milli second. (11)
Protection requirements - Input low Cut off protection / Input High Cut Off Protection / Output Low Cut Off
protection / IOutput High (12) Fault Annuciation Panel LED shows Input present, Input high Input low, Output RS: Seventy
301 Normal, Output High, Outpur low, Overload. (13) Output On time delay - 10 seconds (14) Ambient Tempeature 1.00 Each 70438.00 Thousand Four Hundred
capacity - 0 - 45 RH upto 90 %. (15) Enclosure Type - IP 20 (16) Type of Cooling - Air ,Output:Bypass switch Thirty Eight only
with changeover switch and Provied SPD & 4 year free replacement guarantee on Stamp paper.
Loading and unloading of above item shall be done by hydra and skill work force under supervision of electrical
engineer and guidelines given by manufacturer to avoid damage to the item. Picture of it to be submitted in
running bill / final bill.Size of door and Ele. room / Pump room shall be checked by agency's engineer before
giving order. If found any problem in size discuss with GSPHCL engineer for rectification before giving order. (20
KVA) (Fuji Electric, Servomax Limited, Krykard, protekG Make)
Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with
ignition free & flame proof confirming BS with necessary end caps Internal and external bend, flat bends,
RS: Two Hundred
302a coupler, tee etc. All necessary accessories and measuring of following sizes.For 75 mm x 50 mm trunking (MK / 20.00 Mtr. 275.00
Seventy Five only
Legrand/OBO Make Only)
100 mm x 50 mm trunking (MK / Legrand/OBO Make Only) RS: Four Hundred
Twenty Four only
Providing, erecting, fabricating the M.S. structure as per requirement of site as per structure design Including
proper size approved by EIC of M.S. angles, flats, bars, square pipe, channels, sections (Tata,Zindal,Asian,Jsi
Make) complete with cutting, welding, grinding and finishing duly painted with Asian/Nerolac make premium
quality oil paint and true care red oxide metal primer,asian paint make with erection on site as per direction of RS: Seventy Four
engineer in charge with necessary grouting cementing, plastering and finishing complete. All hole opening of and Paise Ninty Two only
square pipe end must be closed with M.S plate welding. Payment will be done on KG as per Actual weight.
Supplying & erecting 12 mm thick backelite sheet of approved make and grade on 25 x 25 x 3 mm red oxide
painted angle iron frame suitable for fixing ICDP SWITCH and energy meter (contractor shall make approved RS: Two Thousand
304 drawing of Bakelite sheet To arrange required No. of Energy meter & ICDP switch -busbar etc. as per Actual 2.00 Sq. Mtr. 2289.00 Two Hundred Eighty Nine
space available in electrical room at site) only
SITC of specified make X color for Cat.-6 Data and Y color for Cat.-6 voice cable to be done in prelaid PVC pipe
/ raceway, but without the cost of raceway or pipe (the wire is to be drawn from MFD/ JB to outlet point) (a) CAT RS: Forty Seven
305 - 6 (For Computer Cabling and For Voice Cabeling) (Molex, Avaya, D-Link, Legrand make Only) 700.00 Mtr. 47.00
SITC of 24 x 10/100/1000BASE-T ports
4 x Gigabit RJ45/SFP Combo ports
Advanced L2 switching and security features
L2+ Static Routing RS: Fifteen Thousand
306 Optional “standard mode” or “surveillance mode” management user interface 3.00 Each 15247.00 Two Hundred Forty Seven
[Approved by Competent only
Authority i.e. not Below the rank of Executive Engineer ]
Supply, Installation, testing and commissioning of 24 port Cat 6 19" Toolless Patch Panel ( fully loaded) enable
all possible combinations of the various types of cable mounted on the same panel by using various toolless
connector blocks/modules. Have a metal structure enabling them to be durably fixed to the uprights of the 19”
chassis and assuring automatic grounding between toolless RJ-45 connectors, the panel, and the 19” uprights of
the enclosure. Include rear cable support with plastic cable guides to hold cable without need for cable ties. RS: Four Thousand
307 Include quick mounting system to mount the panel into the 19” rails without use of cage-nuts. These may be 3.00 Each 4357.00 Three Hundred Fifty
used to secure the connections of wifi access points, IP cameras, servers, or other critical devices. Front Seven only
Removal IO's option for maintenance and trouble shooting with 6 Different Colours Labels for Labelling &
Identification of Individual Ports. & as per attached details specification. (CAT 6 )
SITC of company fabricated Patch cords shall conform to Cat- 6 & conductor shall be stranded for better
flexibility Shall support network line speeds up to 1 Gbps Shall have RJ-45 jacks. For 1 Mtr.[Make and model RS: One Hundred
approved by EIC as per specification] Fifty Five only
SITC of company fabricated Patch cords shall conform to Cat- 6 & conductor shall be stranded for better
flexibility Shall support network line speeds up to 1 Gbps Shall have RJ-45 jacks. For 2 Mtr. [Make and model RS: One Hundred
approved by EIC as per specification] Ninty Nine only
Supply and installation of 9U steel rack for installing 4 nos. Ethernate switches/Hubs. The Rack should be fully
enclosed steel housing fabricated with 14 SWG sheet and powder coated with glass doors and having wire
RS: Eleven Thousand
management systems. The rate includes the Exhaust Fan, 2 nos. 4 socket and 1 switch power strip and all the
310 3.00 Each 11441.00 Four Hundred Forty One
wiring in the rack. (Rittal, Valrack, APC, Legrand Make and model approved by EIC as per specification)
Supplying & erecting Delton or approved make Telephone Cable electrolytic copper conductor PE insulation
twisted in two pairs, & wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable
for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of RS: Four Hundred
311a pairs. With necessary connections. For Conductor Size 0.5 mm armoured Fifty Pairs.[make and model approved 150.00 Mtr 463.00
Sixty Three only
by EIC strictly as per tender specification]
For Conductor Size 0.5 mm armoured Twenty Pairs.[make and model approved by EIC strictly as per tender
RS: One Hundred
311b specification] 100.00 Mtr 198.00
Ninty Eight only
Providing & erecting main Distribution (MDF) indoor type, back mounted frame as per DoT standard approved RS: One Thousand
312a with krone strips For Suitable For Suitable for 20 pair 2.00 Each 1355.00 Three Hundred Fifty Five
For Suitable for 50 pair RS: One Thousand
312b 2.00 Each 1730.00 Seven Hundred Thirty
Supply, Installation testing and commissioning of 16 Gauge M.S. Powder coated floor raceway Access outlet
/ service junction box with 16 Gauge M.S. Powder coated Cover plate with duct entry 25 mm / 38 mm size
having epoxy powder coated trap lead with corrosion & rust free with adjustable levelling screw of following size.
for 300 mm x 300 mm x 50 mm depth. (M.k, legrand, OBBO) RS: Seven Hundred
Forty Nine only
150 mm x 150 mm x 50 mm depth (M.k, legrand, OBBO) RS: Six Hundred
Seventy Two only
Supplying and erecting approved make Octagonal pole made from HR sheet steel. The pole should be made as
per IS. and shall be coated with hot dip galvanizing as per IS 2629/2633/4759, suitable suspend local wind
speed with integral Junction box with Hot Deep Galvanised door having 2 nos. 180° operated hinges & 2 nos. Ln
key locking with silicon rubber gasket. Consist of terminal plate of min 6mm Hylam sheet, standard profile
mm X 7.5 mm Din-Rail & MCB, Brass stud type terminal and arrangement for cable termination to be erected on
RS: Six Thousand
RCC foundation as per details given by manufacturer and EIC considering site requirement. Foundation Details:
314 14.00 Each 6917.00 Nine Hundred Seventeen
(1) Grade of RCC 1:2:4, (2) Grade of steel rainforcement of RCC FE 415, (3) Clear cover to rainforcement
50mm, (4) Concrete vibrated, (5) use suttering / farma, (6) Hot deep galvanized average 70 Micron, (7) Detail
drawing will be given by corporation
For 5 Mtr. Long 70 mm Top X 130 mm bottom dia, 3 mm thickness with 200 mm X 200 mm X 12 mm base
plate, 4-M16 Bolts and 600 mm long hot deep galvanized J-Bolt, nuts, washers with 800 mm under ground and
200 mm above ground level and Foundation in 1:2:4 proportion as per details given by manufacturer and EIC
considering site requirement. Approx Pole weight 46 kg.(Make:- Bajaj, Valmont, Transrail, Ambica Only) (Test
certificate to be submitted)
Supplying & erecting approved make SMC press moulded composite FRP. loop-in, loop-out approx. 2mm thick
box complete with Bakelite connector strip 5way(3P+N+E), DIN rail for mounting mob & hinged doors as per
requirement having locking arrangements with mounting clamp with nuts, bolts & washers suitable for erection RS: Eight Hundred
315a on pole with cable clamps& earth bolt of following size of box. For 300mm x 200mm x 100mm 16.00 Each 890.00
For 250mm x 200mm x 100mm [deep]
RS: Five Hundred
For 140mm x 140mm x 100mm [deep]
RS: Two Hundred
Ninty Five only
Supplying and making Coil type earthing, coil made from 8 SWG galvanised iron wire with 50 mm OD and
turns (length of turns approx. 200 mm) and having additional continuous streight length of 3.00 mtr at open end
and should be connected to earthing bolt and burried in 1.5 mtr deep specially prepared earth pit complete with
salt and charcoal/coke as required for coil type earthing.(Approx weight of coil 1.0 to 1.1 Kgs) RS: Three Hundred
Sixty Nine only
Supplying and erecting Fabricating terminal box for street light pole made from 16 SWG M.S. sheet having
following size complete with fixing arrangement for terminal board, with necessary hole for wire entry and exit
from the box. The box shall be provided with cover and hinges on one side and bolting at other end The box
shall be fixed by clamps fabricated from 25mm x 6mm flat.The box shall be painted with one coat of red oxide
and two coats of paint having following box size 330 mm x 260 mm x 140 mm (depth). Providing and fixing RS: Seven Hundred
Terminal board of size 5.0 x 127 x 152.4 mm.bakelite sheet with 15 Amp. kitkat pattern porcelain fuse unit with Two only
suitable brass studs with nuts, washers and clamps of size 25 mm x 3 mm suitable for pole painted with one
coat of red lead paint.
Providing & erecting bracket consisting of ISI mark "B" class G.I. Pipe 4.2 cm outside diameter complete with
suitable G.I. Sleeve tubing of 2 mm. thick and required size and length suitable for 76.5 / 80 mm. required size of
pole top or pipe in pipe surface for terrace as per instruction of EIC or wall bracket as per instruction of EIC
having nuts and bolts for fixing the brackets and having spread of Upto 0.50 mtr. length with suitable rise as per
site condition and suitable welded stiffner reducer and nipple with check nut complete painted with one coat of RS: Four Hundred
318a yellow zinc and two coats of alluminium paint for Single arm bracket suitable for pole or terrace as per design 22.00 Each 487.00
Eighty Seven only
given by EIC. For single arm bracket. (Jindal / Asian / Tata / Surya Prakash make Only) (Fabricators:- Bajaj,
Valmont, Transrail, Ambica, RR Ispat Only) (Test certificate to be submitted)
For Double arm bracket. (Jindal / Asian / Tata / Surya Prakash make Only) (Fabricators:- Bajaj, Valmont,
Transrail, Ambica, RR Ispat Only) (Test certificate to be submitted) RS: Six Hundred
SITC of Outdoor aesthetically designed LED Street Light Luminaire with total consumption of Max. 45 W with
single piece die cast aluminium housing, high power LED shall be mounted on high quality metal core PCB with
extremely precison designed heat sink complete with IP66 protection Class with polycarbonate / thoughened
glass cover the fixture should be suitable for pole/bracket mounting. The fixture to comply both LM79 and LM
guidelines with LED module min. 130 lumen/watt with toughen Glass L70 at 50,000 hrs, provided with high
quality polycarbonate lenses for better light distribution. The watt capacity of Each LED must be >=4W in street
light fitting. The Fixture Should be able to be Pole Mounted and also bracket mounted, provided with high quality RS: Three Thousand
319 driver for protection against high and low Voltage cut Off, opertional for high amibient and high humid 18.00 Each 3512.00 Five Hundred Twelve
envirnoments, THD of driver should be less than 10% and P.F > 0.95. Also the Fixture should meet the following only
technical criterias Oprating range Voltage 160 to 270 V, system efficiency >= 110 lm/w, and total lumens not less
then 4950, CCT > 5000K, CRI > 65, beam angle 120 deg, surge immunity level at least 4 KV integral and 10 KV
non integral (Note:- The manufacturer / authorized Channel partner of the manufacturer has to submit 5yrs free
replcement Guarantee for complete Fixture)
SITC of Outdoor aesthetically designed LED Street Light Luminaire with total consumption of Max. 90W with
single piece die cast aluminium housing, high power LED shall be mounted on high quality metal core PCB with
extremely precison designed heat sink complete with IP66 protection Class with polycarbonate / thoughened
glass cover the fixture should be suitable for pole/bracket mounting. The fixture to comply both LM79 and LM
guidelines with LED module min. 130 lumen/watt with toughen Glass L70 at 50,000 hrs, provided with high
quality polycarbonate lenses for better light distribution. The watt capacity of Each LED must be >=4W in street
light fitting. The Fixture Should be able to be Pole Mounted and also bracket mounted, provided with high quality RS: Six Thousand
320 driver for protection against high and low Voltage cut Off, opertional for high amibient and high humid 16.00 Each 6117.00 One Hundred Seventeen
envirnoments, THD of driver should be less than 10% and P.F > 0.95. Also the Fixture should meet the following only
technical criterias Oprating range Voltage 160 to 270 V, system efficiency >= 110 lm/w, and total lumens not less
then 9900, CCT > 5000K, CRI > 65, beam angle 120 deg, surge immunity level at least 4 KV integral and 10 KV
non integral (Note:- The manufacturer / authorized Channel partner of the manufacturer has to submit 5yrs free
replcement Guarantee for complete Fixture)
SITC of Outdoor aesthetically designed LED Flood Light Luminaire with total consumption of maximum 120 W
with single piece die cast aluminium housing, high power LED shall be mounted on high quality metal core
based PCB with extremely precison designed heat sink, complete with IP66 protection Class, with polycarbonate
/ Toughened glass cover. The fixture should be suitable for pole/bracket mounting. The fixture to comply both
LM79 and LM 80 guidelines with LED minimum 130 lumen/watt with L70 at 50,000 hrs, provided with high
quality polycarbonate lenses for better light distribution. The Fixture Should be able to be Pole Mounted and also
bracket mounted, provided with high quality potted driver for protection against, high and low Voltage cut Off, RS: Seven Thousand
321 opertional for high amibient and high humid envirnoments, THD of driver should be less than 10% and P.F > 2.00 Each 7395.00 Three Hundred Ninty Five
0.95. Also the Fixture should meet the following technical criterias. Operating range Voltage 160 to 270 V, only
system efficiency >= 110 lm/w, CCT > 5000K, CRI >65, beam angle 120 deg, surge immunity level at least 4KV
integral & 10 KV nonintegral. Flood Light lumens shall be not less than 13200 (Note:- The manufacturer /
authorized Channel partner of the manufacturer has to submit 5 yrs free replcement Guarantee for complete
SITC of Outdoor aesthetically designed LED Flood Light Luminaire with total consumption of maximum 90 W
with single piece die cast aluminium housing, LED's mounted on high quality metal core based PCB with
extremely precison designed heat sink, complete with IP66 protection Class, with polycarbonate / Toughened
glass cover. The fixture should be suitable for pole/bracket mounting. The fixture to comply both LM79 and LM
80 guidelines with LED minimum 110 lumen/watt with L70 at 50,000 hrs, provided with high quality
polycarbonate Seperate lenses for better light distribution. The watt capacity of Each LED must be >=4W in
street light fitting. The Fixture Should be able to be Pole Mounted and also bracket mounted, provided with high RS: Six Thousand
322 quality potted driver for protection against, high and low Voltage cut Off, opertional for high amibient and high 2.00 Each 6228.00 Two Hundred Twenty
humid envirnoments, THD of driver should be less than 10% and P.F > 0.95. Also the Fixture should meet the Eight only
following technical criterias. Operating range Voltage 160 to 270 V, system efficiency > 110 lm/w, CCT > 5000K,
CRI >65, beam angle 120 deg, 4kV integral & non integral surge immunity level at least 10 KV non integral...
Flood Light lumens shall be more than 9900. (Note:- The manufacturer / authorized Channel partner of the
manufacturer has to submit 5yrs free replcement Guarantee for complete Fixture)
supplying & erecting 30 W LED POST TOP LATTERN fitting with high power white LEDs wattage of 1 ww and
above assebled on single MCPCB's effiency more than 130 lumens per watt and corrosion free high pressure
diecast alluminium housing with smooth finish powder caoted and heat sink extruded alluminium with difuser and
poly carbonate optics/ lences with compny mark / name /engraved or embossed 120 to 300 volt, power factor
more than 0.95, THD < 10%, CCT 5000K to 5700K , Uniformity ratio > 0.45, Luminure efficency Min 110 lumens
per watt. LED Driver efficency > 85%. Cree/osram/philips Lumileds/Nichia /Seoul/Bridge Lux (USA) make LED RS: Four Thousand
used for luminare ( Each Fitting required LM 79 and LM-80 certificates) (B) Flood Light(IP-65)Surge- Fifty Two only
10KV.(E)Post Top Latern LED Fitting Comprises of 650 MM TOP diameter 120 degree beam angle with 3 Nos
supporting ribs proposed for garden & Promenade. maximum 40 WATT, (Note:- The manufacturer/authorized
Channel partner of the manufacturer has to submit 5yrs free replcement Guarantee for complete Fixture)
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single
MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming to IS:
513/CRCA/aluminium pressure die cast powder coated and high U.V. & corrosion resistance with diffuser
housed in aluminium casted body with company mark/name
160V to 270V,Power Factor more than 0.95, THD < 15 %,
CCT 3000 K to 6500K,
RS: Eight Hundred
324 Luminaire efficacy> 85 lumens/watt , 100 Each 805.00
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity
of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.)(F) Spot
Light 5 Watt 425 Lumens, Surge-2KV ( For Police Station Outside elivation Light)
Providing , erecting , testing and commissioning Insu Intelligent Streetlight Controller specially design for energy
saving in conventional streetlight system ( Cat. No. SLC-03-1Ph-7.5KVA-20Amp/Cat NoSLC-03-1 ph-15 KVA
amp per phase) having technial specification ,1 phase 2 wire, 230 V AC/ph +/- 25% R Y B N 2 Wire supply
System.50 Hz (+ / - 10 %), 2 W (Stand By) to 4 W (at street light operation)consuption, Advance 8 bit micro
controller, switching on longitude and latitude base, accaracy of +- 1 minute per month. with inbuilt battery, with
battery life of more than 8 years, with speicial device which hold the parameter for more then 10 years without
any power and password protected. 16 character and two line LCD display with backlight, 4 keys user friendly
RS: Twenty Thousand
keyboard system, 7500 VA feeder pillar capacity, 63/100 amps isolator ,3 Outpus with termination 40/63 Amps
325 1.00 Each 20255.00 Two Hundred Fifty Five
2/3 pole contactor , 3X16 Amps with F R cable provision to by pass by way of relay operation through
auto/manual switch, 2 to 55 centigrade and humidity 90 % non condensing Outdoor type installation on pole with
clamps.(Provided with clamps and nut bolt) or wall or floor, three locking system flush type internal panel lock,
external pad lock and internal U clamp locking systems for against theft of panel. having 17/25 Kg weight ,16/18
guage MS weather proof with industrial exterior powder coated with 7 tank process RAL
Providing & Erecting Universal Astro 5 KVA intelligent streetlight control system insu with weather proof box for
RS: Twelve Thousand
outdoor application. (As per specification attached separately) (Make and model approved by EIC)
326 1.00 Each 12895.00 Eight Hundred Ninty Five
Providing & erecting XLPE (IS : 7098) (I)-88 ISI marked armoured Aluminium conductor cable for 1100 volt to be
laid 90 cms. Under ground or to be laid on wall with suitable G.I. heavy guage 1.0mm thick cable clamp or in
existing DWC pipe underground or road crossing or floor.For 3*1/2 core 70 Sq. mm (35 Sq. mm * 1/2 core) ( RS: Three Hundred
Ele Room Power Supply) Seventy Five only
For 3*1/2 core 50 Sq. mm (25 Sq. mm * 1/2 core)
RS: Two Hundred
Eighty Two only
Providing & erecting XLPE (IS : 7098) (I)-88 ISI marked armoured Copper cable for 1100 volt to be laid 90 cms.
Under ground or to be laid on wall with suitable G.I. heavy guage 1.6mm thick cable clamp or in existing DWC
pipe underground or road crossing or floor. For 4 core x 4 sq.mm. (For Street Light cable and Barrack Power RS: Three Hundred
Supply) Sixty One only
Providing & erecting XLPE (IS : 7098) (I)-88 ISI marked unarmoured Copper cable for 1100 volt to be laid
cms. Under ground or to be laid on wall with suitable G.I. heavy guage 1.0mm thick cable clamp or in existing
DWC pipe underground or road crossing or floor. For 4 core x 10 sq.mm. (From ACDB to Solar Meter)(For 20 RS: Five Hundred
KW) Sixty Eight only
Providing & fixing Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size
evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts
330a in an approved manner. For 16/25 Sq.mm. 6.00 Each 15.00 RS: Fifteen only
For 35/50 Sq.mm
330b 6.00 Each 20.00 RS: Twenty only
For 70 sq.mm RS: Twenty Five
Providing & fixing Solderless crimping type Copper lugs conforming to IS suitable for cable of following size
evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts
331 300.00 Each 8.00 RS: Eight only
in an approved manner. For 1.5/2.5 to 6 Sq.mm
Providing & fixing double compressed heavy duty flange type brass cable gland with rubber ring for P V C
insulated armoured cable complete with outgoing tails, insulating tape etc. For following size cables.For 2 to 4 RS: Forty Three
core x 4.0 Sq. mm (Sigma, MCI, Comet Make Only) only
For 3*1/2 core x 35.0/50.0 Sq. mm (Sigma, MCI, Comet Make Only) RS: Seventy Five
For 3*1/2 core x 70.0 Sq. mm (Sigma, MCI, Comet Make Only) RS: One Hundred
For 2 to 4 core x 10.0 Sq. mm (Sigma, MCI, Comet Make Only) RS: Forty Eight
Providing & fixing PVC cable gland with rubber ring for P V C insulated unarmoured cable complete with
outgoing tails, insulating tape etc. For following size cables. For 2 to 4 core x 6.0 to 10Sq. mm For Solar System RS: Twenty Five
Supplying following size of Light duty “A” Class G.I. Pipe & erecting as directed by Engineer-in-charge. For
mm dia. RS: One Hundred
Seventy One only
Providing & Erecting Flexible PVC insulated multistrand multicore 1.1 kv grade ISI marked copper wires of
following size to be erected as directed. For 3 core 2.5 sq.mm. PVC insulated round copper wire ISI mark. RS: Seventy Seven
For 3 core 1.5 sq.mm. PVC insulated round copper wire ISI mark.
Providing & laying HDPE Double walled corrugated pipes (DWC) (conforming to IS: 16205 (part 24) 2018)) with
minimum load required of 450N capacity with anti rodent and ultra violet material properties with necessary
connecting accessories of same material at required depth to be laid 90 cms. under ground for laying of cable
below ground / road surface for enclosing cable and back filling the same to make ground as per original. For RS: One Hundred
Outer dia. 50 mm and Inner dia. 38 mm. (Test Certificate to be Submitted) Seventeen only
For Outer dia. 90 mm and Inner dia. 75 mm. (Test Certificate to be Submitted)
RS: One Hundred
Providing & laying. R.C.C. Hume pipe for cable to be laid 90 cms. below ground across the road crossing or on
floor with necessary material in an approved manner and making the ground as per original. For 150 mm Dia RS: Two Hundred
Supplying and erecting Fully Automatic hydro pneumatic booster system with cast iron housing Enclosure class
IP44 minimum , with built in PTO motor protection and stainless steel impeller pump, pump model GRUNDFOS
CMB 5-46 series or equivalent with 24 Liter hydro pneumatic pressurized tank capacity : 5 m3/hr,Rated head
:30 mtr, motor rating : 1.2 H.P. includes pressure switches, Non Return Valve, Pressure Gauge, 5 way Brass RS: Forty Five
338 connector, with necessary Plumbing work which includes all required size of pipes, Joints valves, Bypass valve, 2.00 Each 45679.00 Thousand Six Hundred
labor all accessories required for installation of pressure pump ( Foundation work and base stand and Control Seventy Nine only
Panel cost included)
Providing & erecting ISI make medium duty (B class) galvanized MS pipe with coupling, bend, union, reducer, RS: Two Hundred
339 tee, MS flange etc. with plumbing charges.For 50 mm dia 10.00 Mtr. 260.00
Supplying and erecting C.I. Swing check type non-return (reflux) valve ISI marked with packing, flange, nuts and
bolts etc.suitable for following pipe size. For 50 mm dia. (SANT,KIRLOSKAR,LEADER,ZOLOTO) RS: One Thousand
Ten Hundred Ten only
Supplying Water tight M.S.Box of size 20 x 15 x 15 cms. to erect suitable kitkat fuse / MCB to be . erected on
polished wooden board inside the box with hinged/sliding door with rubber rings and erected on pole with RS: Two Hundred
suitable pole clamp, all duly painted with one coat of red oxide and two coats of paints. Thirty Two only
Providing and erecting ISI marked PVC insulated PVC Sheathed Flat flexible Submersible copper cable RS: One Hundred
342 approved make of following Size. For 3 Core x 2.5 Sq. mm. 20.00 Mtr. 103.00
Providing Water proof straight Joint in PVC insulated flat flexible copper cable by using insulating material, water RS: One Hundred
343 proofing material, & making the joint complete. Up to 10Sq. mm 2.00 Each 188.00
Eighty Eight only
Supplying, Installation, Testing & commissioning of Electric driven Main Fire Pump suitable for automatic
operation and consisting of following, complete in all respects, as required: (a) Horizontal type, Single stage,
centrifugal, End Suction Long Coupled Pump of cast iron body & bronze impeller with stainless steel shaft,
mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous
speed 2900 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for
enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.
(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)
Suitable Cement Concrete Foundation duly plastered with anti vibration pads. (e) cost include foot valve of
suitable size CI body heavy duty. (f) Discharge :- minimum 1620 LPM. Note: The head of the pump shall be RS: One lac Eighty Six
344 selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. Agency has to 1.00 Each 186556.00 Thousand Five Hundred
calculate the total head required for getting minimum 3.5kgf/cm2 pressure at the farthest & highest point of Fifty Six only
building of wet riser fire system. For that agency has to calculate total pump head by considering vertical head (
Total Building height+ Sump depth+3.5kgf/cm2 pressure & Total equivalent vertical head due to frication losses
of total length of pipe + bend number, Elbow number, Tee, Valve etc.) Agency must have to select pump model
having required head & discharge( asper fire department rules) at duty point. No Extra payment shall be done
for head variation due to site situation & fire rules. The panel shall be design according to motor H.P
Supplying, installation, testing and commissioning of Diesel engine driven Main Fire Pump suitable for automatic
operation and consisting of following, complete in all respects, as required: [Diesel driven pump]
(a) Horizontal type, Singlestage, centrifugal, End suction Long Coupled pump of cast iron body & bronze impeller
with stainless steel shaft, mechanical seal conforming to IS
(b) Suitable HP 2900 RPM water cooled with radiator diesel conforming to relavant IS standard complete with
auto starting mechanism 12/24 Volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 M
outside pump house duly insulated with 50 mm thick glass wool with 1.00 mm thick aluminium sheet cladding, RS: Four lac Fifty Six
345 residential silencer, instrument and protection as per standard specification, stop solenoid for auto stop in the 1.00 Each 456202.00 Thousand Two Hundred
event of fault with auto indications painted with post office red color etc. as required. Two only
(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
(d) Suitable cement concrete foundation duly plastered with anti vibration pads.
(e) Cost include providing, erecting req. size copper XLPE Armound cable with GI cable tray, support etc. as per
EIC instruction (app. cable lenth 15 mtr.)
(f) Cable from pump to panel will be laid in cable tray or fixed on G.I./M.S. strip / channel as per instructions
given by EIC as per site requirement.
(g)Cost include foot valve of Suitable size CI body heavy duty (SANT,Kirloskar, Kartar, Zoloto make)
(h)Discharge:- minimum 1620 LPM. Note: The head of the pump shall be selected in a manner so as to give a
minimum 3.5kgf/cm2 pressure at the highest/farthest point.
[The all require Technical specification & Test certificate shall be submitted to Local fire Authority for approval]
(Factory inspection will have to carried out by agency with G.S.P.H.C.L. engineer)
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for
automatic operation and consisting of following, complete in all respects, as required: (Jockey Pump).
(a) Horizontal type, Singlestage, centrifugal, End suction Long Coupled pump of cast iron body & bronze impeller
with stainless steel shaft, mechanical seal conforming to IS
(b) Suitable HP Squirrel cage induction motor, TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz
AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F'
insulation,conforming to IS :
(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
(d) Suitable cement concrete foundation duly plastered and with anti vibration pads. RS: Seventy Three
346 (e) Required size 3 core flat cable from pump to panel for connection should be provided with pump. 1.00 Each 73821.00 Thousand Eight Hundred
(f) Cable from pump to panel will be laid in cable tray or fixed on G.I./M.S. strip / channel as per instructions Twenty One only
given by EIC as per site requirement.
(g) Cost include foot valve of suitable size CI body heavy duty.(SANT,Kirloskar, Kartar, Zoloto make)
(h) Discharge:- minimum 180 LPM. Note: The head of
the pump shall be selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest
(Factory inspection will have to carried out by agency with G.S.P.H.C.L. engineer)
Fabrication, supply, installation and commissioning of electrical control panel of cubical construction, floor
mounted type, fabricated out of 2 mm thick CRCA sheet, compartmentalised with hinged locable doors, dust and
vermin proof, power coated of approved shade after 7 tank treatment process, cable alley, inter connection with
suitable size copeer conductor cable/solid copper strip having switchgear and accessories, mounting and RS: Two lac Seventeen
347 internal wiring, earth terminals, numbering etc. complete in all respect suitable for main fire pump, pressurisation 1.00 Each 217623.00 Thousand Six Hundred
pump and diesel pump set complete as per specification with following incoming and outgoings suitable for Twenty Three only
operation on 415 V, 3 phase 50 Hz AC supply with enclosure protection class IP 42 as required.
250A, 50 KA 4 Pole MCCB Ics=100% Icu rating.
Digital voletmeter 0-500 V with selector switch
Digital ammeter 0-250 A with selector switch and CT's etc.
LED type RYB phase indicating lamp, ON, OFF, TRIP indicationg lamps.
Set of copper busbar 300 A.
[Note:- All outgoing feeder for pumps should have digital ammeter with selector switch and LED type ON, OFF
and TRIP indicating lamps.)
MAIN FIRE PUMP:
250 A 50kA TPN MCCB Ics=100% Icu with fully automatic star/delta starter suitable for 60 HP pump with
overload protection current sensing type single phase preventor complete with all accessories and internal wiring
required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.
63 A 50kA TPN MCCB Ics=100% Icu with suitable HP fully automatic Star/Delta starter with overload protection,
current sensing type single phase preventor complete with all accessories and internal wiring required for
automatic operation, selector switch for local/remote, auto/manual/OFF operation.DIESEL ENGINE CONTROL:
1) Automatic/Manual selector switch and 3 attempt starting device, timers and relay as required, push buttons,
start/stop in manual mode.
2) Indicating lamp for high/low lub oil pressure, high water temperature and engine ON indication.
3) Battery charger suitable for 12/24 V DC with boost and trickle selector switch 0-30 V DC Volt meter and 0-20
4) All standard relays and accessories for autoamtic operation of diesel engine.
SYSTEM CONTROLLER:
Design, supply, installation, testing and commissioning of system controller to control operation of main electric
fire pump, Pressurisation (Jockey) Pump, Diesel pump and terrace pump in sequence as per specification
consisting of relays, timers, sensors, annunciation window for fault indication complete as per specification.
Supplying, installation, testing and
commissioning of electric driven terrace pump
conforming to IS 12469: 2019 suitable for automatic
operation and consisting of following, complete in all
respects, as required: (Terrace Pump)
(b) Horizontal type, multistage, centrifugal, split
casing pump of cast iron body & bronze impeller
with stainless steel shaft, mechanical seal as
required. RS: Seventy Seven
348 (c) Suitable HP squirell cage induction motor TEFC 1.00 77438.00 Thousand Four Hundred
type suitable for operation on 415 volts, 3 phase, 50 Thirty Eight only
Hz, AC supply with IP55 class of protection for
enclosure, horiziontal foot mounted type with Class-
'F' insulation, conforming to IS-12615:
(d) M.S.fabricated common base plate, coupling,
coupling guard, foundation bolts etc.as required.
(e) Suitable cement concrete foundation duly
plastered and with anti vibration pads. 450 LPM at 35m head
Supplying & erecting approved make motor control cubical panel (Direct - on - line) made from 16 G. CRCA
sheet duly epoxy powder painted inside and outside with hinged doors and locking, arrangement consisting of
suitable size of ON- OFF isolator (AC - 3/23duty) main fuses, single phasing preventer, indicating lamps for R- Y -
B phases, overload relay, Automatic water level controller, Ammeter, Voltmeter each with two way selector RS: Eight Thousand
349 switch incoming, wires duly socket crimped, main contactor & overload relay, start - stop push buttons, to be 1.00 8624.00 Six Hundred Twenty Four
erected on angle iron frame grouted on wall as directed. The isolator, overload relay & contactors will be of L & only
T, Siemens or BCH make only. (B) DOL for 7.5 H.P.
Providing and fixing of Dial type Pressure Gauge having 100 mm dial & range of 0-14 Kg/cm2 with isolation ball
RS: One Thousand
valve. (Make:- Hguru, Fiebig,General Instrument) (Test certificate must be submitted)
350 3.00 Each 1539.46 Five Hundred Thirty Nine
and Paise Forty Six only
Providing and fixing of Pressure switch with Needle valve ( Indfos,Honeywell,System Sensor make and Model
RS: One Thousand
Instruct by EIC (Only)
351 3.00 Each 1415.00 Four Hundred Fifteen
Providing and fixing of Air Release Valve including Ball Valve 25 mm dia. (Approved ISI make & model
RS: One Thousand
352 approved by EIC strictly as per specification) 3.00 Each 1601.00
Six Hundred One only
Supply, Installation, Testing and Commissioning of Pump On-Off switch (with all mounting accessories
complete with Junction Box for mooting on Surface, Cable lugs at Ends, cable compression glands, cable tags
and Ferruling.)for remote operation from each floor of the building. (Approved by EIC) (Test certificate must be RS: Eight Hundred
submitted) Ninty only
Supply and laying of 3C x 6 sq.mm PVC Copper Flat cable with all require accessories for Main Pump. (Make :
Mecab, Darshan,Rimcab) RS: One Hundred
Seventy One only
Supply and laying of 3C x 16 sq.mm PVC Copper Flat cable with all require accessories for Main Pump. (Make :
Mecab, Darshan,Rimcab) RS: Four Hundred
Eighty Four only
Executing comprehensive (All-in-All) service & maintenance with spare parts as per terms & condition of tender
for Fire terrace pump with fire hydrant agency for defect liability period and copy of this contract will be submitted
before final bill. Agency has to quote rate accordingly. Agency has to also provide the fitness certificate from
system agency and submit to G.S.P.H.C.L. Agency has to submit FDR of Rs.56584.00+GST or quoted rate
whichever is higher to G.S.P.H.C.L,for minimum maturity period of Four years in favour of G.S.P.H.C.L Which
will be released after successful completion of A.M.C. & at the completion of defect liability period. Fire System
agency has to maintain written record of service & maintenance during defect liability period duly sign by police RS: Fifty Six Thousand
356 dept. and submit regularly to G.S.P.H.C.L. Agency has to give minimum three services and demonstration per 1.00 Per Tower 56584.00 Five Hundred Eighty Four
year and testing and training of pump during defect liability period and obtain necessary certificate from police only
department and submit to G.S.P.H.C.L. Agency has to do maintenance as per terms & condition alternative in
tender.Agency has to give One live demonstration of fire Mock drill for fire fighting with minimum 01 no. CO2 and
01 no. ABC type fire extinguisher at the time of handing over this system to the Police department and another at
the time of releasing final Security deposit. The necessary certificate / photographs for that must be submitted.
Executing comprehensive (All-in-All) service & maintenance with spare parts as per terms & condition of tender
for Fire terrace pump with fire hydrant agency for defect liability period and copy of this contract will be submitted
before final bill. Agency has to quote rate accordingly. Agency has to also provide the fitness certificate from
system agency and submit to G.S.P.H.C.L. Agency has to submit FDR of Rs.5342.00+GST or quoted rate
whichever is higher to G.S.P.H.C.L,for minimum maturity period of Four years in favour of G.S.P.H.C.L Which
will be released after successful completion of A.M.C. & at the completion of defect liability period. Fire System
agency has to maintain written record of service & maintenance during defect liability period duly sign by police
dept. and submit regularly to G.S.P.H.C.L. Agency has to give minimum three services and demonstration per RS: Five Thousand
357 year and testing and training of pump during defect liability period and obtain necessary certificate from police 1.00 Per Tower 5342.00 Three Hundred Forty Two
department and submit to G.S.P.H.C.L. Agency has to do maintenance as per terms & condition alternative in only
tender.Agency has to give One live demonstration of fire Mock drill for fire fighting with minimum 01 no. CO2 and
01 no. ABC type fire extinguisher at the time of handing over this system to the Police department and another at
the time of releasing final Security deposit. The necessary certificate / photographs for that must be
submitted.(For Terrace Pump)
Supply ,Installation , testing & Commissioning of heavy duty meduim voltage cable as per specficification & IS
7098 part I , 4C X 1.5 SQ.,MM ARMOURED CABLE (CU.) FRLS,RED colour with approved make , with require
support , cable tie, cable tagging , hardare are etc to complete the work.(As per BIS standard) RS: One Hundred
Supplying and erecting Flexible PVC insulated multistrand multicore 1.1 kv grade ISI marked copper wires of
following size to be erected as directed.For 1.50 Sq.mm 2 core round PVC sheathed. having insulation colour RS: Thirty One
359 RED and BLACK for Fire Alarm System. 330.00 Mtr. 31.00
SITC of Microprocessor based Net-workable Analogue Addressable Fire Alarm Control Panel. The Panel shall
be compliant with EN54-2, EN54-4 and approved by LPCB. The Fire Alarm Control Panel shall have inbuilt one
loop. The Panel must have large graphic display. The Panel must also have the capability to take Addressable
Intelligent Wired and Wireless Devices on same loop. Each loop shall have a capacity of 127 analogue
RS: Ninty Three
360 Addressable devices and 127 Base sounders/Base Sounder Beacons. The Panel shall have 240 V AC power 2.00 Each 93005.00
Thousand Five only
supply along with automatic Battery Charger. Non-Networkable
Approved by LPCB (Including Five year free maintenance with guarantee)
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector having
RS: Two Thousand
IS-11360-1985 or BS 5446 Part I-1977 & Part VII –1985 (VdS approved) or NFPA72 (UL/ULC/FM approved)
361 97.00 Each 2,415.38 Four Hundred Fifteen and
with Latest ammendment complete with mounting base complete as required. (Morley / GST/ cooper / ASES /
Paise Thirty Eight only
HUCHIKI make and model approved by EIC as per specification) [Test certificate must be submitted]
Supplying, installation, testing & commissioning of addressable manual call point having IS or BS (EN 54)
RS: Three Thousand
(Vds approved) or NFPA 72 (UL/ULC/FM approved) with Latest Amendment complete as required. (ASES
362 8.00 Each 3271.00 Two Hundred Seventy
/ravel/morley or approved by EIC as per Tender specifications) (Test certificate must be submitted)
Supplying, installation, testing & commissioning of addressable horn cum strobe having IS or BS (EN 54)
RS: Two Thousand
(Vds approved) or NFPA 72 (UL/ULC/FM approved) with Latest Amendment complete as required. (ASES
363 8.00 Each 2966.00 Nine Hundred Sixty Six
/ravel/morley or approved by EIC as per Tender specifications) (Test certificate must be submitted)
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two
LED, metallic cover complete with all connections etc as required.(Make:GST,Siemens,Morley,Copper, RS: Two Hundred
Honeywell) Twenty Nine only
Providing and fixing of ABC Type Store Pressure Fire Extinguisher Having capacity 6 kg Filled with Mono
RS: One Thousand
Ammonium Phosphate Powder 50% confirms to IS 4308, Stored Pressure Type, UGTS Pressure Gauge, Can
365 5.00 Each 1991.00 Nine Hundred Ninty One
Height 530 mm, Diameter 150 ± 10mm, Discharge Time 24 Sec, Controllable discharge mechanism, Jet Range
5 Meters, Average Discharge is 92%, applicable on Class A,B & C and electrically started Fire, Fire Rating
Providing Construction
and fixing of CO2: type
drawn & CO2 Mig
Pressure welded,
Portable 4.5 EPDM(Ethylene Propylene
kg Fire Extinguisher, Diene
filled with Monomer)
Co2 Gas as per IS
RS: Six Thousand
15222, Control discharge mechanism fitted with 1 Meter Wire Braided Hose & Electrical non-conductor
366 5.00 Each 6526.00 Five Hundred Twenty Six
Polyethylene Flat Horn with Diffuser Nozzle for dispersed discharge of CO2, Discharge Time 12 Sec, Average
Discharge is 95%, Applicable on Class B, C and electrically started Fire, Fire Rating 55B, Internal coating is not
Providing & External
fixing ofcoating is of enamel
Automatic type 5spray
kg painting, Powder Coated
Fire Extinguishers Mono Handle,
AmmoniumValvePhosphate
Confirm to powder
RS: Five Thousand
Confirms to IS 4308, Applicable fire classes A,B & C, UGTS Pressure Gauge, Can Height 370mm, Diameter
367 3.00 Each 5240.00 Two Hundred Forty
230 ± 10mm, Made up from 2 mm thick sheet, Body Construction Deep Drawn with MIG Welding technology,
Brass forged sprinkler valves with Nozzle is specially designed to give more than 99% discharge. Together with
SITC characteristic
3LCD Lamp to cover
basedadequately
projectorfire risks with
having wxgascattering coneorof better
(1280x800) 40 to 45° Angle. External
resolution Pure
with minimum white
RS: Thirty Three
brightness of 3800 lumens and color brightness of 3800 lumens. The projector should have minimum
368 1.00 Each 33560.00 Thousand Five Hundred
1HDMI,1VGA input. Having contrast ratio of 15000:1 or more. the projector should have auto vertical key stone
correction of +/- 30 degree and Manual Horizontal of +/-30 degree. the projector should have optical lens, throw
of 120 inch Zoom Factor
Self Lock MW of 1.2.
(8 x Lens focus Manual
6) Instalock having focal
Slow Retraction length Aspect
Screen, 16.9mmRatio-4:3
to 20.28mm. projector
RS: Five Thousand
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ].[Make: Da-lite / draper / liberty
369 1.00 Each 5282.00 Two Hundred Eighty Two
Supply, Installation Testing & Commissioning 15 Mtr. HDMI Interface Cable as per the detailed Specifications
supports transmission of 4K Signals as per the detailed Specifications .[Make: Kramer / Extron / Crestron] RS: One Thousand
370 1.00 Each 1760.00 Seven Hundred Sixty
SITC of universal Projector mounting kit, with necessary grouting, fasteners etc. with adjustable height and
suitable for all types of projectors. [Approved by Competent Authority i.e. not Below the rank of Executive RS: Six Thousand
371 Engineer ] 1.00 Each 6781.00 Seven Hundred Eighty
Providing and erecting water cooler having storage capacity 80 Ltr. & cooling capacity 40 Ltr.per hour @ an
ambient temp of 45˚ C. The outlet temp. of the water should drop by 15˚C within a hour, The water cooler should
be comprising of hermetically sealed compressor Reciprocating compressor with R134A gas , fan motor,
Copper Condensing unit, fan motor, water tank surrounded by evaporating, coil, thermostats, relay etc.complete
with necessary inlet & outlet connection. The body of water cooler will be made from Stainless Steel, CP brass
push cock, inlet float valve, with all plumbing and electrical accessories, inlet, outlet, overflow and PVC drain out
connection to FD complete as required With 20 Amp. 3 pin plug Top with indicator. (This item including
372 2.00 Each 49069.00 Thousand Sixty Nine
comprehensive service & maintanance including Spare Parts & consumable item during warranty period of one
year. Maintanance & service must be carried out by OEM dealer/distributer who has executed the work. Service
& Maintance must be as per OEM guid line.) (Agency has to give AMC to water cooler OEM / authorized dealer
upto defect liability period] [Voltas, Bluestar, Usha model approved by EIC as per specification]
Supplying & erecting 5 stage single reverse osmosis water purification system with M.S. powder coated frame,
prefilter housing with 'O' ring presediment filter GAC filter, carbon filter suitable buster DC pump capacity 80 psi,
mention with 40 psi inline type post carbon filter auto low & high pressure switches with following size of storage
tank & LPH capacity & erected as directed [B] 25 Ltr / Hr with 30 Ltr. Storage Tank [ ION EXCHANGE,
AQUAGUARD, KENT, EUREKA FORBES, RAIN DROP, Make- Power H2O, Blue mount appliances Pvt. Ltd.]
RS: Fifteen Thousand
373 2.00 Each 15466.00 Four Hundred Sixty Six
The purpose of RO plant is cater the portable and drinking water 24X7 to beneficiary.So we have taken
comprehensive maintenance contract item in this tender. Agency has to give All in All maintenance contract to
OEM of RO plant and submit AMC copy to GSPHCL at the time of final bill.Agency has to compulsory submit
FDR of Rs 27,838.00+ GST or quoted amount whichever is higher to GSPHCL. Which will be released after
successful completion of AMC & at the and of defect liability period. AMC consist of general service & Filter shall
be replaced at every 3 months.Membranes & booster pump shall be repaired/ replaced whenever RS: Thirteen
374 required.Agency has to stick maintenance schedule on the RO plant and date of service, TDS of water, 2.00 Each 13919.00 Thousand Nine Hundred
discharge of water etc. shall be written on this.Agency has to receive certificate from beneficiary every year and Ninteen only
submit at the time of releasing SD.For 25 Ltr RO plant
Supply, Installation, Testing & Commissioning of following size of Grid Tied Solar Power Plant with Solar Panels
(ALMM approved): Frame Material : Anodized Aluminum alloy Frame With Twin Wall Profile, Front Cover : High
Transmission Low-Iron Tempered Glass (AR Coated), High efficency and positive power tolerance Pmax: 0/+5,
Module Efficiency should be approx. 18%-21%, Normal operating temperature 45'C, Junction Box with
Waterproof IP67 & MC4 Compatible and Enclosed with Bypass diodes, 100% Electroluminescence test to
ensure error free Modules, Thep. temp. co-efficient of the PV module shall equal or better than -0.45%/degree C. RS: Forty Two
375 Solar PV modules of minimum fill factor 75% to be used. Unit Production:- 4 to 5 Unit /kw /day (Actual)(1Year 20.00 Per KW 42035.00 Thousand Thirty Five
Avg) With 10 year Product warranty and 25 year Linear Power Warranty., only
Solar Inverter: MPPT Range: 80-1000 V, Max efficiency: 97.5% - 98.9%, O/p Frequency: 50/60Hz, Operating
Altitude (m) ≤4000, O/p Power Factor: ~1, O/P THDi: <3%, Operating Tempreture Range: -25~60°C, Anti-
islanding Protection:
Integrated, Input Reverse Polarity Protection Integrated, Insulation Resistor Detection Integrated, Residual
Current Monitoring Unit Integrated, Output Over Current Protection Integrated, Output Short Circuit Protection
Integrated, Output Over Voltage Protection Integrated, Protection Degree: IP65, User Interface LCD &
APP,Datalogger & Communication: GPRS / Wi-Fi, Module Mounting Structure: Seamless Box Pipe / 'C' Channel
of suitable size for rooftop solar installations with good stability agaist wind & weight load., Hot Dipped
Galvanized steel coils. suitable arrangement for base plate for foundation , solar panel mounting, the structure
should be suitable for carry the load of solar panel,wiring, sprinkler system etc. with necessary foundation
work/wall mount, j bolt, anchor fastner etc. the nut bolt used for installtion of stucture should be (SS 304) quality.
and Balane of System with necessary Swithgears (Suitabel size and protection of ACDB & DCDB), inter
connecting wiring, earthing system, lightining arrester system, all liasoning work with various gov. department
like state nodal agency,DISCOM & CEIG is included in agency scope
Grid Tied Solar Power System: For 20kW (3 - phase)
Executing Com of solar Pv Modules, Inverter, wiring,earthing,switchgears, etc with material and labour cost including
preventive maintanance.The cost covers entire installation. AMC also includes monthly site visit and inspection of project
with submission of inspection and solar generation report. All parts should be replaced/repaired if found faulty within
specified time. Agency has to provide necessary liasoning work for warranty,power,Bidirectional meter etc of following
Capacity as per terms & condition of tender for defect liability period.Agency has to compulsory submit FDR of approved
bank as per clause 2.0 section 3 Rs. 305100.00+ GST or quoted rate which ever is higher to GSPHCL,for minimum maturity RS: Fifteen Thousand
376 period of four years in favour of GSPHC .Which will be released after succesfull completion of AMC & at the end of defect 20.00 Per KW 15255.00 Two Hundred Fifty Five
liability period.Solar Agency has to maintain record of service & maintenance during defect liability period duly sign by only
Benificiaries and submitted regularly to GSPHCL & also get satisfactory certificate from beneficiaries at the time of Defect
liability period and copy of maintenance contract must be submitted during final bill. For 20KW
Supply, Installation, Testing & Commissioning of following size of Grid Tied Solar Power Plant with Solar Panels
(ALMM approved): Frame Material : Anodized Aluminum alloy Frame With Twin Wall Profile, Front Cover : High
Transmission Low-Iron Tempered Glass (AR Coated), High efficency and positive power tolerance Pmax: 0/+5,
Module Efficiency should be approx. 18%-21%, Normal operating temperature 45'C, Junction Box with
Waterproof IP67 & MC4 Compatible and Enclosed with Bypass diodes, 100% Electroluminescence test to
ensure error free Modules, Thep. temp. co-efficient of the PV module shall equal or better than -0.45%/degree C. RS: Forty Three
377 Solar PV modules of minimum fill factor 75% to be used. Unit Production:- 4 to 5 Unit /kw /day (Actual)(1Year 10.00 Per KW 43645.00 Thousand Six Hundred
Avg) With 10 year Product warranty and 25 year Linear Power Warranty., Forty Five only
Solar Inverter: MPPT Range: 80-1000 V, Max efficiency: 97.5% - 98.9%, O/p Frequency: 50/60Hz, Operating
Altitude (m) ≤4000, O/p Power Factor: ~1, O/P THDi: <3%, Operating Tempreture Range: -25~60°C, Anti-
islanding Protection:
Integrated, Input Reverse Polarity Protection Integrated, Insulation Resistor Detection Integrated, Residual
Current Monitoring Unit Integrated, Output Over Current Protection Integrated, Output Short Circuit Protection
Integrated, Output Over Voltage Protection Integrated, Protection Degree: IP65, User Interface LCD &
APP,Datalogger & Communication: GPRS / Wi-Fi, Module Mounting Structure: Seamless Box Pipe / 'C' Channel
of suitable size for rooftop solar installations with good stability agaist wind & weight load., Hot Dipped
Galvanized steel coils. suitable arrangement for base plate for foundation , solar panel mounting, the structure
should be suitable for carry the load of solar panel,wiring, sprinkler system etc. with necessary foundation
work/wall mount, j bolt, anchor fastner etc. the nut bolt used for installtion of stucture should be (SS 304) quality.
and Balane of System with necessary Swithgears (Suitabel size and protection of ACDB & DCDB), inter
connecting wiring, earthing system, lightining arrester system, all liasoning work with various gov. department
like state nodal agency,DISCOM & CEIG is included in agency scope
Grid Tied Solar Power System: For 10kW (3 - phase)
Executing Com of solar Pv Modules, Inverter, wiring,earthing,switchgears, etc with material and labour cost including
preventive maintanance.The cost covers entire installation. AMC also includes monthly site visit and inspection of project
with submission of inspection and solar generation report. All parts should be replaced/repaired if found faulty within
specified time. Agency has to provide necessary liasoning work for warranty,power,Bidirectional meter etc of following
Capacity as per terms & condition of tender for defect liability period.Agency has to compulsory submit FDR of approved
bank as per clause 2.0 section 3 Rs. 165270.00+ GST or quoted rate which ever is higher to GSPHCL,for minimum maturity RS: Sixteen Thousand
378 period of four years in favour of GSPHC .Which will be released after succesfull completion of AMC & at the end of defect 10.00 Per KW 16527.00 Five Hundred Twenty
liability period.Solar Agency has to maintain record of service & maintenance during defect liability period duly sign by Seven only
Benificiaries and submitted regularly to GSPHCL & also get satisfactory certificate from beneficiaries at the time of Defect
liability period and copy of maintenance contract must be submitted during final bill. For 10KW
Total Of Electrical item Amount in Rs.
Total Electrical Say Amount In Rs.
Assistant Engineer (Ele.) Dy. Ex. Engineer (Ele.)(S.P) Executive Engineer (Ele.)
Ahmedabad Gandhinagar Gandhinagar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
ALL CONDITIONS NALSAROVAR.pdf
ATTACHED SPECIFICATIONS NALSAROVAR.pdf
cement consumption nalsarovar.pdf
DMO_2941_01-Apr-2026_744.pdf
ELE 01 Schedual B Ele Nalsarovar 01072026.pdf
ELE 02 Tender Condition 01072026.pdf
ELE03.Specifications BookletNAL SAROVAR.pdf
FINAL MAKE LIST- EOI 2026.pdf
Genral Techinal Specification B S BOOK_ 24-3-23.pdf
SBD VOLUME 1 NALSAROVAR.pdf
SBD VOLUME 2 NALSAROVAR.pdf
SBD VOLUME 3 NALSAROVAR.pdf
SBD VOLUME 4 NALSAROVAR.pdf
SCHEDULE B 01.07.2026 Civil and Ele Club.pdf
Special Condition.pdf
STANDARD SPECIFICATIONS NALSAROVAR.pdf
arc nal sarovar police station and srp block.pdf
srp str_compressed (1).pdf
str police station 1.pdf
str police station 2.pdf
Important changes In SBD CLAUSES.pdf
CORRIGENDUM
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .