Loading…
Loading…
Tender ID
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical 1696 VICTORY BUILDING KADAMPAZHIPPURAM PALAKKAD 678633 | PALAKKAD | PALAKKAD | KERALA | 678633 | Accepted-Technical Accepted |
| 2 | Accepted-Technical KAKKADAMPOYIL NILAMBUR MALAPPURAM 673604 | MALAPPURAM | MALAPPURAM | KERALA | 673604 | Accepted-Technical Accepted |
| 3 | Accepted-Technical 2 SBC 1 THEJASWINI BUILDING PHASE 1 TECHNOPARK THIRUVANANTHAPURAM 695581 | THIRUVANANTHAPURAM | THIRUVANANTHAPURAM | KERALA | 695581 | Accepted-Technical Accepted |
| 4 | Rejected-Technical 9 8 B THENGUMTHARAVIL MLA ROAD PANANGAD PO KOCHI 682506 | KOCHI | ERNAKULAM | KERALA | 682506 | Rejected-Technical Rejected |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
25 May 2026, 3:00 pmClosed
MANAGING DIRECTOR
UNITED ELECTRICAL INDUSTRIES Ltd,REGD OFFICE,PALLIMUKK KOLLAM 691010
SITC OF FIRE FIGHTING SYSTEMS AT BEYPORE PORT-SUPPLY INSTALLATION TESTING AND COMMISSIONING OF FIRE FIGHTING SYSTEMS INCLUDING FIRE TANKS AT BEYPORE PORT
2026_UNILE_851642_1
PMC/MARKETING/006/2026-2027
Open Tender
Electrical Works
Item Wise
45 days
BEYPORE PORT
REFER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹8,850
Yes
₹1 L
Yes
4 Jun 2026
18 May 2026
26 May 2026
18 May 2026
25 May 2026
18 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Supplying, Installing, Testing & Commissioning of Electric Driven Main Fire Pump suitable for automatic operation consisting of Horizontal, End Suction Centrifugal Fire pump with cast iron casing & cast-iron impeller, stainless steel shaft to deliver 1620 Ltrs/Min at 60 MWC (Meter of Water Column). Pump coupled to Squirrel cage type TEFC (totally Enclosed Fan Cooled) induction motor suitable for operation on 415 v, 3 phase 50hz system with Common base plate for pump and motor and coupling, coupling guard and other accessories accessories standard mounting accessories. (RCC foundation & Cabling shall be provided by others) | 1 | Nos | - | - |
| 1.02 | Supplying, Installing, Testing & Commissioning of Electric Driven Jockey Pump suitable for automatic operation consisting of Horizontal End Suction Centrifugal Fire pump with cast iron casing & cast- iron impeller, stainless steel shaft to deliver 180 Ltrs/Min at 60 MWC (Meter of Water Column). Pump coupled to Squirrel cage type TEFC (totally Enclosed Fan Cooled) induction motor suitable for operation on 415 v, 3 phase 50hz system of with Common base plate for pump and motor and coupling, coupling guard and other standard mounting accessories.(RCC foundation & Cabling shall be provided by others) | 1 | Nos | - | - |
| 1.03 | Supply, Installation, Testing and Commissioning of Diesel Engine Driven Fire Pump of approved make suitable for automatic/manual operations End suction type fire pump with CI impeller with CI body should be of grade F.G. 200 to IS : 210 casing shall be designed for 1.5 time of working pressure, capable of delivering of 1620 LPM against a total head of 60 Mtrs while running at minimum of 1600 R.P.M to ensure a minimum pressure of 3.5 Kg per Sq.cm at the farthest outlet; complete with common base plate, coupling, coupling guard and other accessories standard mounting accessories.(RCC foundation & Cabling shall be provided by others) | 1 | Nos | - | - |
| 1.04 | Supply, Installation, Testing and Commissioning of charges for automatic fire hydrant system panel for the main pump, standby pump, terrace pump and jockey pump. Incorporating automatic start delta starter for main and stand by fire pump & automatic direct online starter indications showing the power supply condition ammeter with clear indications of the motor full load current, volt meter with selector switch L&T 9(ISI) etc , the panel shall be duly painted with protective anticorrosive lacquer and be of floor mounted type. | 1 | Nos | - | - |
| 1.05 | Supply, erection, testing and commissioning of Electrical driven Monoblock Terrace pump 450 Lpm@ 3.5 Bar with all the necessary accessories. | 1 | Nos | - | - |
| 1.06 | Supply, installation, testing and commissioning of motor control panel with necessary indication lamps for ON or OFF. | 1 | Nos | - | - |
| 1.07 | Supply, Installation, Testing and Commissioning of 50mm GI 'C' Class Exhaust Pipe for diesel engine pump | 6 | Mtr | - | - |
| 1.08 | S I T C of hydraulically operated Sprinkler control valve, with water motor gong bell and trims as required, pressure gauges, drain valves, ball valves, check valves, strainers etc. complete | 1 | Nos | - | - |
| 1.09 | Supplying, installing, testing and commissioning of Pressure gauges of suitable range for pump sets. Glycerin filled 150mm dia pressure gauges to use on pump discharge & test lines. | 6 | Nos | - | - |
| 1.1 | Supply, Installation, Testing and Commissioning of charges of Pressure switch arrangement for pump room and total system | 4 | Nos | - | - |
stage.html
html • 0.02 MB
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.27 MB
GC.pdf
Tender Documents • 0.39 MB
BOQ_1438967.xls
BOQ • 0.29 MB
CORRI06.pdf
PDF • 0.87 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .