Arrangement of pre commissioning testing of equipment for 220 KV Newly constructed Bay for Tanakpur feeder at 220 KV S/S C.B. Ganj, under E.T.D. Bareilly
2020_UPTCL_471183_1
Short Term E-Tender No. 01 ETD (B) / 2020-21
Open Tender
Electrical Works
20 days
Bareilly
Please Refer in Tender Documents
3 documents required · 3 mandatory
₹590
Yes
Ac No 0043002100037996, IFSC PUNB0004300
₹2,000
Yes
23 May 2020
16 May 2020
22 May 2020
16 May 2020
22 May 2020
16 May 2020
Amount
Arrangement of pre commissioning testing of following equipment of 220 newly constructed bay for 220 KV Tanakpur feeder including all cost, cost of men, Special T&P, consumables, Crane / Hydra etc. required for completion of work.
Testing of C.B.
1. Measurement of Circuit Breaker Operating Timings Including PIR Timings. 2. DCRM Contact Travel Measurement /DC Injected Current and Trip/Close Coil Currents. 3. Operational lockout Checking for EHV Circuit Breakers. 4. Measurement of Static Contact Resistance 5. Checking the Anti-Pumping Feature 6. Checking the Anti-Condesation Heaters 7. Pole Discrepancy Relay Testing
Testing of C.T.
1. Tan Delta & Capacitance measurement of CT 2. Polarity Test for CT 3. Magnetization Characteristics of CT 4. Ratio Test on CT 5. IR Measurement of CT (Primary & Secondary Winding) 6. DGA Test for CT Oil
Testing of CVT
1. Tan Delta & Capacitance measurement of CVT & each Slack CVT. 2. CVT each Polarity, Ratio Test 3. Insulation Resistance Measurement of Primary and Secondary Winding
Testing of Isolator
1. CRM Test 2. IR Test 3. Timing Test
Testing of Lightning Arrestor
1. Third Harmonic Resistive Current (THRC) for Surge arrestors 2. IR Measurement of each slack of LA 3. Tan Delta Test