Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
31 Aug 2026, 3:00 pm7d left
Sudipta Bose (EE/EL)
nbdd uttarkanya
Infrastructural development of the auditorium and conference rooms of Uttarkanya, Branch Secretariat Jalpaiguri - Air Condition Works.
2026_NBDD_1038264_9
NBDD/BS/EE /NIQ-16- (EL) of 2026-2027(SL No. 01 to 10)
Open Tender
Electrical Work/ Equipment
Item Rate
120 days
Jalpaiguri
Please refer Tender documents.
6 documents required · 6 mandatory
₹70,000
Yes
14 Aug 2026
14 Aug 2026
3 Sept 2026
14 Aug 2026
31 Aug 2026
14 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with
Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell
elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to
ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original 242 DELHI SCHEDULE OF RATES (E&M)-2025
Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical
cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730,
hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per
CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient
temperature). Inverter Type - Cooling only (Make- Hitachi/Blue-Star/Voltas/Daikin) 1.5 TR with 5 Star BEE Rating | - | Nos | - | - |
| 2 | Supplying, Installation, Testing and Commissioning of Air Cooled Floor standing Tower type split Air conditioners
complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with
insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5 Mtr (IDU to ODU), copper power cable upto 5.5 Mtr (IDU to ODU), i/c drain pipe of suitable length and size. R-32/R-410/R-407C Green Refrigerant, wireless
Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC
supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary with min 5 year Original Equipment Manufacturer (OEM) warranty 245 DELHI SCHEDULE OF RATES (E&M)-2025
both compressor and Printed Circuit Board (PCB). as specified. The system shall be able to deliver 100% of the
rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National
Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International
Electrotechnical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/ Electrical
Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as
per CPWD specification and as per IS: 1391 as required. [ Make-Carrier/Voltas/Blue Star/O General/Hitachi/ DIAKIN] 4.6 TR BEE 5 Star Rating ( Only Cooling) | - | Nos | - | - |
| 3 | Wiring for circuit/ submain wiring along with earth wire
with the following sizes of FRLS/HFFR PVC insulated
copper conductor, single core cable in surface/
recessed steel conduit as required. 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC | - | MTR | - | - |
| 4 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire | - | MTR | - | - |
| 5 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire | - | MTR | - | - |
| 6 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire | - | MTR | - | - |
| 7 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire | - | MTR | - | - |
| 8 | Supplying and fixing of following sizes of medium
class PVC conduit along with accessories in
surface/recess including cutting the wall and making
good the same in case of recessed conduit as required.20 mm Dia | - | MTR | - | - |
| 9 | 25 mm Dia | - | MTR | - | - |
| 10 | Supplying and fixing following way, single pole and
neutral, sheet steel, MCB distribution board, 240 V,
on surface/ recess, complete with tinned copper bus
bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing
etc. as required. (But without MCB/RCCB/Isolator) | - | EACH | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.47 MB
Tendernotice_2.pdf
PDF • 0.51 MB
BOQ_2550568.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].