| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹61.9 LAccepted-Finance FLAT NO C 401 LORD KRISHNA GREEN OPPOSITE DOON SCHOLAR SCHOOL KEDARPUR DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹61.9 L | L1 | Accepted-Finance Ok |
| 2 | L2₹64.8 L+₹2.9 L (4.74%)Accepted-Finance 24 A RAGHBIR MARG NEAR 22 NO PHATAK PATIALA 147001 PB | PATIALA | PATIALA | PUNJAB | 147001 | ₹64.8 L+₹2.9 L (4.74%) | L2 | Accepted-Finance Ok |
| 3 | L3₹65.9 L+₹4.0 L (6.49%)Accepted-Finance 4578 STREET 15 15A AGGARWAL ROAD DARYAGANJ CENTRAL DELHI DELHI 110002 UDYAM DL 01 0031798 | CENTRAL DELHI | DELHI | 110002 | ₹65.9 L+₹4.0 L (6.49%) | L3 | Accepted-Finance Ok |
| Sl No | Description | Qty | Unit | MAHESH KUMAR SINGLA CONTRACTOR L2 | Ansh Enterprises L1 | M/s Kamal Traders L3 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of transformer 315 KVA as per manfacturer standard ratings, 11/0.433 KV, 3 phase, 50 Hz, Dyn11, outdoor ONAN type, copper wound, oil immersed naturally cooled, step down transformer with OFF circuit tap changing arrangement on HV side (tapping range + 7.5% in steps of 2.5% each) with Vector group Dyn11 and having cable end box on HV & LV side. The cable box at LV/HV side shall be suitable to house for proper size and capacity of incoming/outgoing aluminium cable and to be provided with gland and gland plate. The transformer shall be provided with all standard accessories and first filling of filtered dehydrated transformer oil of IS: 335 complete as per specification and confirming to Energy efficiency level -3 of IS: 1180(Part-I) -2014 with amendment No 4. The Transformer shall be having following standard accessories complete all as specified and directed:-
(a) Name rating & diagram plate - 01 Nos
(b) Off circuit tap changing switch - 01 Nos
(c) Earthing Terminals - 02 Nos
(d) Lifting lugs - 02 Nos
(e) Oil level indicator (flush tube) - 01 Nos
(f) Oil drain valve with plug - 01 Nos
(g) Oil temperature gauge- 01 Nos
(h) Aluminium body breather - 01 Nos
(j) Vent pipe - 01 Nos
Note:- Cost of any other accessories as per manufacturers instructions/ IS provision shall be inclusive in the quoted rates. | 2 | Each | 13,00,000 ₹26,00,000 Lowest | 14,05,000 ₹28,10,000 | 15,70,000 ₹31,40,000 |
| 2.00 | All as per item No 1 above but capacity 500 KVA or next higher capacity as per manfacturer standard ratings. | 1 | Each | 19,00,000 ₹19,00,000 | 18,45,765 ₹18,45,765 Lowest | 22,00,000 ₹22,00,000 |
| 3.00 | All as per item No 1 above but capacity 200 KVA or next higher capacity as per manfacturer standard ratings. | 1 | Each | 10,50,000 ₹10,50,000 | 11,50,339 ₹11,50,339 | 10,00,000 ₹10,00,000 Lowest |
| 4.00 | M&L for earthing complete with copper earth plate electrode 600x600x3.15m thick burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to copper earth strip 20x3mm by means of bolts, nuts, check nuts and washers of GI or steel all as shown in respective electrical plate of SSR Part-I 2009 connected to earthing test point/ transformer/ panel and testing on completion as directed including necessary excavation & earth work in any type of soil, funnel, PCC chamber (1:3:6) type C1, RCC pit cover, charcoal, salt including provision of earth lead protection pipe 40mm dia light grade GI and 20mm dia medium grade GI Pipe for watering complete all as specified and directed.
Note:
(i) If the desired earth resistance is not found within permissible limit of less than 2 Ohm, earthing shall be redone by contractor without any extra cost.
(ii) Cost of copper earth strip upto 7.5 mtr, 40mm dia light grade GI pipe and 20mm dia medium grade GI Pipe for watering is included in the rate quoted for this item. | 16 | Each Set | 51,000 ₹8,16,000 | 17,650 ₹2,82,400 | 12,000 ₹1,92,000 Lowest |
| 5.00 | Supplying, installing and testing gang operated air break switch 12 insulator type, HT 11 KV, AC 50 C/S, Triple pole, vertical mounting type, mechanically operated from ground, mounted on 12 silicon rubber insulators 11 KV grade and steel frame, current rating upto 200 Amps complete with fuse mounting, fuse carriers and fuse elements of required capacity fixed on the pole structure on channel/ angle iron/ cross arm with suitable GI nuts, bolts & washers etc complete all as specified and directed. | 4 | Each | 25,000 ₹1,00,000 | 12,000 ₹48,000 Lowest | 12,000 ₹48,000 Lowest |
| 6.00 | Supplying, installing and testing lightning arrestor, station class type of rated voltage 12 KV and discharge current capacity 65 KA suitable for 11000 Volt complete all as specified and directed. | 4 | Each set of three | 4,500 ₹18,000 | 13,500 ₹54,000 | 3,000 ₹12,000 Lowest |
Tender Value
₹61.8 L
EMD Value
₹1.2 L
Closing Date
19 Aug 2026, 6:00 pmClosed
CWE Dehradun
HQ CWE Dehradun
SPECIAL REPAIRS FOR REPLACEMENT OF BER DISTRIBUTION TRANSFORMERS AT GARHI CANTT OF AGE E/M -II UNDER GE DEHRADUN
2026_MES_778633_1
1061/DDN/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Dehradun
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
GE Dehradun
₹1.2 L
Yes
3 Sept 2026
15 Jul 2026
21 Aug 2026
15 Jul 2026
19 Aug 2026
6 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of transformer 315 KVA as per manfacturer standard ratings, 11/0.433 KV, 3 phase, 50 Hz, Dyn11, outdoor ONAN type, copper wound, oil immersed naturally cooled, step down transformer with OFF circuit tap changing arrangement on HV side (tapping range + 7.5% in steps of 2.5% each) with Vector group Dyn11 and having cable end box on HV & LV side. The cable box at LV/HV side shall be suitable to house for proper size and capacity of incoming/outgoing aluminium cable and to be provided with gland and gland plate. The transformer shall be provided with all standard accessories and first filling of filtered dehydrated transformer oil of IS: 335 complete as per specification and confirming to Energy efficiency level -3 of IS: 1180(Part-I) -2014 with amendment No 4. The Transformer shall be having following standard accessories complete all as specified and directed:-
(a) Name rating & diagram plate - 01 Nos
(b) Off circuit tap changing switch - 01 Nos
(c) Earthing Terminals - 02 Nos
(d) Lifting lugs - 02 Nos
(e) Oil level indicator (flush tube) - 01 Nos
(f) Oil drain valve with plug - 01 Nos
(g) Oil temperature gauge- 01 Nos
(h) Aluminium body breather - 01 Nos
(j) Vent pipe - 01 Nos
Note:- Cost of any other accessories as per manufacturers instructions/ IS provision shall be inclusive in the quoted rates. | 2 | Each | - | - |
| 2 | All as per item No 1 above but capacity 500 KVA or next higher capacity as per manfacturer standard ratings. | 1 | Each | - | - |
| 3 | All as per item No 1 above but capacity 200 KVA or next higher capacity as per manfacturer standard ratings. | 1 | Each | - | - |
| 4 | M&L for earthing complete with copper earth plate electrode 600x600x3.15m thick burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to copper earth strip 20x3mm by means of bolts, nuts, check nuts and washers of GI or steel all as shown in respective electrical plate of SSR Part-I 2009 connected to earthing test point/ transformer/ panel and testing on completion as directed including necessary excavation & earth work in any type of soil, funnel, PCC chamber (1:3:6) type C1, RCC pit cover, charcoal, salt including provision of earth lead protection pipe 40mm dia light grade GI and 20mm dia medium grade GI Pipe for watering complete all as specified and directed.
Note:
(i) If the desired earth resistance is not found within permissible limit of less than 2 Ohm, earthing shall be redone by contractor without any extra cost.
(ii) Cost of copper earth strip upto 7.5 mtr, 40mm dia light grade GI pipe and 20mm dia medium grade GI Pipe for watering is included in the rate quoted for this item. | 16 | Each Set | - | - |
| 5 | Supplying, installing and testing gang operated air break switch 12 insulator type, HT 11 KV, AC 50 C/S, Triple pole, vertical mounting type, mechanically operated from ground, mounted on 12 silicon rubber insulators 11 KV grade and steel frame, current rating upto 200 Amps complete with fuse mounting, fuse carriers and fuse elements of required capacity fixed on the pole structure on channel/ angle iron/ cross arm with suitable GI nuts, bolts & washers etc complete all as specified and directed. | 4 | Each | - | - |
| 6 | Supplying, installing and testing lightning arrestor, station class type of rated voltage 12 KV and discharge current capacity 65 KA suitable for 11000 Volt complete all as specified and directed. | 4 | Each set of three | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
1061_Tender.pdf
Tender Documents • 1.25 MB
BOQ_872086.xls
BOQ • 0.50 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .