Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.5 LAccepted-AOC | L1 | Accepted-AOC Competent committee approved the tender in favour of Ist Lowest Bidder | |
| 2 | L2₹19.8 L+₹2.1 L (12.1%)Rejected-AOC CHANDAN NAGAR OPP IOCL PERTROL PUMP RAMPUR ROAD BAREILLY UP 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | L2 | Rejected-AOC Competent committee rejected the file due to higher rates | |
| 3 | L3₹24.0 L+₹6.4 L (36.1%)Rejected-AOC | L3 | Rejected-AOC Competent committee rejected the file due to higher rates | |
| 4 | Not Admitted-Fee | - | Not Admitted-Fee Insufficient Fee amount | |
| 5 | Not Admitted-PreQual/Technical | - | Not Admitted-PreQual/Technical Not Complied with technical specification |
Tender Value
₹37.5 L
EMD Value
₹37,520
Closing Date
16 Dec 2022, 5:00 pmClosed
SUPERINTENDING ENGINEER
ELECTRICITY DISTRIBUTION CIRCLE, KATJU MARG, BAREILLY
Giving Connection of 200 KVA to Project Manager, Toll Palza Faridpur fed from 33/11 KV S/S Andharpura under EDD-II, Bareilly
2022_MVVNL_754903_1
65/EDCB/2022-23
Open Tender
Electrical Works
Item Rate
90 days
WORK
AS PER TENDER FORM
3 documents required · 3 mandatory
₹3,540
SE,EDC
₹37,520
18 Jul 2023
30 Nov 2022
17 Dec 2022
30 Nov 2022
16 Dec 2022
30 Nov 2022
Amount
The work of safe carriage of the following material from CB Ganj store center to work site under the jurisdiction of EDD-II, Bareilly. Approx. distance upto 45 Km. Including safe loading and unloading.
ST Pole 11 Mtr
11 KV Incoming Panel (VCB)
11 KV Outgoing Panel (VCB)
11 KV XLPE Cable 3x185 Sq mm
Outdoor Cable Box for 11 KV XLPE Cable 3x185 Sq mm
Straight Through Cable Jointing Kits for 11 KV XLPE Cable 3x185 sqmm
ACSR Raabbit Conductor
ACSR Dog Conductor
11/0.4 KV 3 Phase 250 KVA T/F
11 KV Pilfer proof Metering cubical and CT PT Unit
Other Line material i.e., 33 KV & 11 KV pin insulater/stay/earthing complete/Disc Fitting/Disc Insulators/Dropper Channel/Crossing Bracing/ Top Channel/Binding Wire/Danger Board/Barbed Wire/numberplate/stone pad/Control Cable etc
Construction of T/F plinth 1.5x1.5x2 m3 for mounting 250 KVA T/F including foundation work (below ground 0.5 M), Brick work, RCC slab of 4” thickness and plastering in 1:6 ratio with 02 Nos channel pieces of 1.5 mtr long of size 100x50x6 mm compete in all respect
Cage fencing of 250 KVA Plinth mounted transformer in Town areas to avoid electrical human/cattle accidents by fabrication of cage (1 Inch Sq wiremesh) made of 10 No gauge in suitable size angle iron frame of size 7.5'(L)x5'(W)x8’(H) by strenghtening of wire mesh 20x3 mm M.S. flat haorizentally as well as vertically, Grouting the panel with 1:2:4 cement/coorse send/brick ballast. The Frame should be bolted on angles at the four corners so that frame may be un-bolted/bolted at the time of replacement of the transformer. Provision of 1 gate should be there for maintenance of the transformer. Painting (1 coat of red oxide + 2 coat of Bus green enamel paint). The wire mesh should be earthed with 50x6 mm MS earthing strip with existing earthing of Transformer Body. All men, material and T&P provided by the contractor to complete the fabrication, transportation and installation.
Mounting of 250 KVA T/F Transformers as per norms complete in all respect -
Erection/Installation of following new panel (VCB) in control room including grouting of Anchor bolt of Panel and making/repairing of pocket for cable to insert in panel from trench and fixing, taping of bus bar with wiring for PT. AC, DC connection including providing of AC & DC Supply.
11 KV Incoming Panel (VCB)
11 KV Outgoing Panel (VCB)
Providing cutting, fixing and welding of MS Strip from existing, earthing to new 11 KV VCB Complete in all respect, all material shall be arranged by the Contractor.
Pipe Earthing of VCB & Transformer (By boring of 4 inch diameter 20 m deep, 40 mm diameter A class GI pipe is inserted to a depth of 20 m and a holed pipe of 1.5 m length is inserted at the bottom. Tighten one end of the MS strip of size 50x6mm with the nut bolt with the neutral of the converter and weld the other end with the GI pipe inserted in the boring for earthing. Putting a socket on the upper part of the pipe (mouth) so that water can be poured into it to retain moisture. To complete the work Contractor will provide all material, Manpower, T&P, safe carriage of material to worksite. Above work will be carried out under supervision of concerned JE/SDO/EE)
Supply and Installation of Battery Charger 24 Volt with Battery Set 24 Volts complete in all respect (Exide Make Only)
Erection of Single/Double pole in H.T/L.T lines including fitting of all accessories as per RESSPO Norms
ST Pole 11 Mtr long (Single)
ST Pole 11 Mtr long (Double)
Grouting of following Pole with 1:4:8 mixture in size(450x450x1500mm.) including cost of cement/BB & sand Required as per RESSPO Norms
ST Pole 11 Mtr long (Single)
ST Pole 11 Mtr long (Double)
The work of Driving the earthing electrode and making connections with 6 S.W.G. GI wire as per RESSPO Norms
Laying, Stringing & Sagging of Following Conductor complete in all respect
ACSR Rabbit Conductor
ACSR Dog Conductor
Under ground laying of 11 KV XLPE 3x185 sq mm cable in Single circuit complete in all respect Along with road restoration
Hoisting of 11 KV XLPE Cable (3x185 Sqmm) on double pole bote with GI pipe of size 6" dia 4 Mtr long including the jumpering complete with clamps , nut and bolts
Supply & Laying of 6" dia G Pipe at various places i.e road crossing & Hoisting etc. complete in all respect ((ISO certified GI pipe 150 NB 3 mm thick dia 6" would be Provided by contractor through approved vendors of Discom at his own cost)
Fixing of Outdoor11 KV Cable Boxes for 3x70 sqmm XLPE Cable complete in all respect
Fixing of 11 KV Straigh through Jointing Kits for 3x185 sqmm XLPE Cable complete in all respect
The work of digging of pits, erection of Stay Clamp, Insulator etc.
Grouting of stays, 1:4:8 cc ratio (600x600x300mm.) as per RESPO norms.
Supply and Fixing of Following Material as per RESPO norms complete in all respect (would be Provided by contractor through approved vendors of Discom at his own cost)
Stone Pad 300x300x75 mm
X-Arm M.S. Angle 65x65x6 mm V-Type
Cross Arm Holding Clamp
11 KV Pin Insulator
11 KV Pin with Nut
F Bracket
Aluminium Tape
Jointing Sleev For ACSR Rabbit
Danger Board With Clamp
Barbed Wire
Number Plate
G.I Holding Clamp for G.I. Pipe
Cable Holding Clamp for 11 KV XLPE Cable 3x185 Sq mm
Off Size Nut & Bolts with washer
Top Channel 100x50x2240mm 9.6 KG/Mtr
M.S. Channel 100x50x2028mm @ 9.6 KG/Mtr for Dropper Channel
M.S. Angle Iorn 65x65x6 (2700 mm)
Aluminium Lug 240 sqmm with Nut&Bolt
Painting Number Mark with Pains
Aluminium Paint
Red Oxide Paint
Dropper Channel (100x50x2028mm)
Holding Clamp for Top Channel, TPMO & Fuse Set etc With Nut & bolts
Top Channel 125x65x2240mm
11 KV Disc Fitting with Insulator 45 KV (T &C Type)
11 KV Pin Insulator with Nut & Bolt
11 KV TPMO
11 KV Fuse Set
Danger Board Barbed wire inscluding Jumper
T-Off Channel (125x65x1300 mm)
Clamp for LT T-Off with Nut & Bolts
Cross Bracings M.S. Angle
11 KV Disc Insulator B&S Type
11 KV Disc Fittings
PG Clamp
Dropper Channel (100x50x2000 mm)
Clamp With Nut & Bolt
After Mounting of CT PT unit on double pole, laying of 50 Mtr 11 KV 3cx70 sq mm cable in single circuit on river sand form Double Pole to metering room complete in all respect. Alongwith filling of cable jointing kits
Installation of 11 KV Pilfer Proof Metering Cubicle in metering room complete in all respect
BHARAT ELECTRICAL TRADERS
M/S MEGHA ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .