Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.7 LAccepted-AOC B 5 117 KALYANI NADIA 741235 | KALYANI | NADIA | WEST BENGAL | 741235 | L1 | Accepted-AOC Lowest Bidder Rate | |
| 2 | L2₹3.8 L+₹5,599.08 (1.50%)Rejected-Finance 71 3 VIDYASAGAR PATH MADRAL NAIHATI 743165 | NAIHATI | 24 PARAGANAS NORTH | WEST BENGAL | 743165 | L2 | Rejected-Finance L2 | |
| 3 | L3₹3.8 L+₹7,118.62 (1.90%)Rejected-Finance B 17 175 KALYANI NADIA | KALYANI | NADIA | WEST BENGAL | L3 | Rejected-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹7,712
Closing Date
25 Jul 2025, 11:00 amClosed
The Assistant Engineer, EMSD-II,PHE Dte.
Office of the Assistant Engineer.Eastern Mechanical Sub Division - II, P.H. Engineering Directorate.A2 Market, Rail Gate, Shiv Mandir, P.O.- Kalyani, Dist.- Nadia.
Supply delivery and installation of Voltage Corrector Device and other allied works at Saguna PH-II water supply scheme under Eastern Mechanical Sub-Division-II , PHE Dte.
2025_PHED_875664_3
WBPHED/AE/EMSD-II/NIET_08 of 2025-2026
Open Tender
MECHANICAL
Item Rate
30 days
Kalyani
Please refer Tender documents.
5 documents required · 5 mandatory
₹7,712
Yes
25 Sept 2025
14 Jul 2025
28 Jul 2025
14 Jul 2025
25 Jul 2025
15 Jul 2025
Amount
Supply and delivery at site of 30KVA, 3phase, oil cooled type Servo Motor operated copper wound line voltage corrector conforming to IS-9815 (Pt.-1)- 1994 suitable for un-balanced input voltage with following specification including first filling oil as per IS-335 where applicable.(Make : Approve make of P.H.E. Dte.)
Input Voltage:- 3 phase, Main supply may or may not be balanced with respect to Phase to Phase?225V-500V Phase to Neutral-144V-290V
Output voltage:-3 phase balanced output voltage. Phase to Phase- 400Vor 415V± 1%, Phase to Neutral?230V-240V ± 1% (Provision should be made to adjust the Variation of output voltage per phase by a variable pot oil within ± 5% of output).
Line regulation:- Out put voltage should remain well with ±1% of set voltage (From Minimum to Maximum i.e. either 400V. or 415V. supply variation).
Load regulation : Output voltage should remain neutral well within ±1% of set voltage be ( From no load to full load ) i.e. either 400V. or 415V.
Correction speed:- Better than 35 Volt / Second.
Efficiency:- Better than 95% on full load.
Cut off limit (minimum &maximum ) by limit switch with Audio & Visual.
Lamp Indication :- For Input & Output should be provided. ( 3 lamps per side ).
MCCB Protection: For Input side.
Load protection : MCCB on each output phase should be available
Output over shoot:- Beyond 210V to . 255V /phase in case of “ MANUAL MODE” & voltage protection :AUTO MODE” operation.
VISUAL Indication for under voltage & over voltage of output.
Manual Mode:- Up & Down correction with O / P voltage over shoot protection. Beyond 210 V-255 V. per phase.
Nature of cooling:- Oil cooled system.
Electric current over load protection .
Circuit for delay output
Input high voltage cut-off above 500 V.
Mode of Operation:- AUTO/MANUAL with a provision to restore the normal working of the unit “STANDBY OPERATION” should be available in case of any Electronic failure in auto mode.
Auto Mode:- Normal * Standby.( Manufacturing test certificate should be Provided at the time of delivery).
Supply and Delivery of foollowing materials at site
100 Amp. 4 pole on load change over switch (Make:Approve make of P.H.E. Dte.)
100 Amp. Re-wireable type TPN main switch (Make: Approve make of P.H.E. Dte.)
100 Amp. 4 way Copper busbar chamber box by 16 SWG sheet steel enclosure including porcelain Chair etc. with painting complete as per direction of the EIC. (Approved make)
25 sqmm. 3 ½ core PVC insulated 1.1KV, AI., Ar. cable(Make: Approve make of P.H.E. Dte.)
Making brick built foundation with supplying of all required materials suitable for the above Voltage stabilizer by (4:1) cement mortar including holding down foundation bolts(If required) and plaster with neat cement finish as per direction of E.I.C.
Fitting, Fixing and connection of above supplied changeover switch, bus-bar and Main Switch as in item no 2/2.01 to 2/2.03 on the wall by supplying all necessary materials to complete the job as per direction of E.I.C
Installation of the above voltage stabilizer of item no. 1 on the foundation including all connection complete as per direction of E.I.C
Drawing and connection of cable on wall as in item no. 2/2.04 and all connection complete with all equipment as per requirement and as per direction
Making joints of the cable by supplying compression type gland thimple, socket etc.as per requirement and as per direction of EIC.
Earthing with 50 mm dia. G.I. pipe, 3.65 mm thick & 3mtrs long (2 sets) and conn. by 25x 6 mm G.I. strip ( for reqd length) upto the earth bus-clamp with the equipments on wall/floor with staplesburied inside as reqd. at site and with 25 mm x 6mm GI flat strip to earth electrode pipe,fastening with 13mmx80mm G.I bolts,nuts,washers, including all f & f of materials & filling & restoring the surface by ramming &making suitable earthpit with brick structure & MS lid on top as per direction.
Add GST @ 18%
Add LWC @ 1%
M/S. G. P. ENTERPRISE (BID ID -6734850)
STANDARD ENGINEERING (BID ID -6739964)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .