Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.5 LAccepted-AOC 149 5 A PILKHANA ROAD BERHAMPORE DIST MURSHIDABAD | BERHAMPORE | MURSHIDABAD | WEST BENGAL | L1 | Accepted-AOC AOC | |
| 2 | L2₹11.6 L+₹1.1 L (10.7%)Rejected-Finance 131 NILMONI BHATTACHARJEE LANE KADAL BERHAMPORE MURSHIDABAD W B PIN 742102 | BERHAMPORE | MURSHIDABAD | WEST BENGAL | 742102 | L2 | Rejected-Finance L2 | |
| 3 | L3₹12 L+₹1.5 L (14.5%)Rejected-Finance 13 RAMLAL MUKHARJEE LANE P O KHAGRA P S BERHAMPORE DIST MURSHIDABAD | BERHAMPORE | MURSHIDABAD | WEST BENGAL | L3 | Rejected-Finance L3 | |
| 4 | Rejected-Technical 2 BOSE PARA ROAD BARISHA KOLKATA WEST BENGAL 700008 | KOLKATA | WEST BENGAL | 700008 | - | Rejected-Technical Reject due to Tender withdrawal request Received form Bidder. |
Tender Value
Refer Docs
EMD Value
₹21,000
Closing Date
2 Feb 2024, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
O/o The Executive Engineer Murshidabad Electrical
O/o The Executive Engineer Murshidabad Electrical Division P.W.Dte. 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Construction of a new 2 pump fire station at Jangipur under Raghunathganj police Station in Murshidabad District --- SITC of UPS.
2024_WBPWD_648728_1
WBPWD/EE/MsdED/54/e-Q of 23-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Murshidabad
Please refer Tender documents.
5 documents required · 5 mandatory
₹21,000
28 Aug 2024
17 Jan 2024
5 Feb 2024
17 Jan 2024
2 Feb 2024
19 Jan 2024
Amount
Topology, IGBT BASED DSP CONTROLED
Make: Switching AVO,Legrand,Emerson,Schneider,PowerOne)
Input Frequency: 45 to 55 Hz
Isolation Transformer: Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided at output
Back feed Protection: UPS should have back feed protection
Charging: Autometic float cum Boots Charging Capability with setteble flote & boost charging voltages and current levels and boots charger timer
Output Voltage: 415 VAC
Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3%
Output Frequency: 50 Hz +/- 0.1%
Output Power Factor: 0.8
Crest Factor: 3:1
THDu: < 2% (linear load), < 5%(non linear load)
Waveform: Pure Sine Wave
Birdge: Microprocessor based and IGBT Technology
Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 30 sec
Static By Pass: 100 % rated static switches with fuse protection overload on Bypass: 100% for 10 ms
Overall Efficiency: 92%
Battary Rack: With power coated MS angle with suiteble dimention and gadge.Useing Nyvin cable with proper rating for interlink cables and battery input and necessary acessiress.
Battery : 12 V, Mono Block batteries. SMF VRLA
DC Bus : Minimum 192V or above, 30 mim back up required Battery. Battery Make: Exide/Amar Raja(Quanta)
Protection: Multi Protection-Over Temperature Protection with 8 Sensors, Overload, Battery Under Voltage, Fan Failures ,Short Circuit. Four Circuit Breakers, Providing Full Protection When Fault, Strong Overload Capability. Surge Protector at Panel Input & EB Input. PV Reverse Polarity, Input Low & High Voltage, Output Low & High Voltage cut off. Glass cartridge Fuse on Control Circuits MCB at Input Panel,
Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip
Metering: Graphical LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current
Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current
Termination: Input, Battery, Output & Bypass
Enclosure: IP 20
Operating Temp: 0 to 40 Deg C
Humidity: Upto 95% Rh (non-condensing)
Cooling: Forced Air
Noise: < 55 dB
Cold Start : Provided
CE Certification:IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture)
ISO 9001: 2015, ISO 14001: 2015, ISO 45001:2018,ISO 50001;2018 , ISO:20000-1:2011,ISO:27001:2013, ROHS
15 KVA UPS of above mentioned specification
Warranty:One Year on UPS & two yers on batteries on site against any Manufacturing defects(after commissioning)
SANJIB GHOSH
BHATTACHARYYA ENTERPRISE
technical_1398994.pdf
PDF • 0.76 MB
techsummary_1398994.pdf
PDF • 0.61 MB
finance_1398994.pdf
PDF • 0.62 MB
BOQ Comparative Chart
xlsx • 0.01 MB
finsummary_1398994.pdf
PDF • 0.62 MB
File0023.PDF
PDF • 0.64 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .