Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹9.0 LAccepted-AOC VELLAPLACKAL HOUSE VARANDARAPPILLY PO THRISSUR 680303 | THRISSUR | THRISSUR | KERALA | 680303 | ₹9.0 L | 1 | Accepted-AOC First lowest hence agreement executed |
| 2 | 2₹10.1 LRejected-AOC | ₹10.1 L | 2 | Rejected-AOC Second lowest hence rejected |
| Sl No | Description | Qty | Unit | BINSON JOSEPH L1 | SHARJAS A L2 |
|---|---|---|---|---|---|
| 1.00Appendix 1:Electrification of Labours Rest Room at DAF, Chelakkara, Thrissur | |||||
| 1.00 | 1.10.3: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C | 20 | point | 1,689.22 ₹33,784.40 | 2,500 ₹50,000 |
| 1.00 | OD316012/2025-2026 : Wiring combined plug point together with the light point/ fan point/ exhaust fan point/ call bell point including 6 A 5 pin modular socket controlled by 6A one way modular switch in the existing switch board and giving connection to thephase,neutral and earth terminal with 1.5sq.mm.FRLS PVC insulated copper conductor single core cable ( Green wire for earthing) etc as required. | 6 | point | 388.76 ₹2,332.56 | 388.76 ₹2,332.56 |
| 1.00 | 90.3.19.3 : Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture | 8 | each | 1,245.56 ₹9,964.48 | 1,245.56 ₹9,964.48 |
| 1.00 | 90.4.1: Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required | 4 | each | 187.07 ₹748.28 | 187.07 ₹748.28 |
| 1.00 | OD316005/2025-2026 : Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required: | 4 | each | 3,142.89 ₹12,571.56 | 3,142.89 ₹12,571.56 |
| 1.01 | OD316022/2025-2026 : Supply ,installation,testing and commissioning of 700lm pressure die cast housing Bulk head with IP66 protection & IK 08 having efficacy not less than 105lm/W and giving connection with 3 core flex wire as required. | 2 | each | 1,012.96 ₹2,025.92 | 1,012.96 ₹2,025.92 |
| 1.01 | 90.15.4.2 : Supply Conveyance, installation, testing and commissioning of 36/40W LED street
light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chipmake Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) | 4 | each | 4,665.37 ₹18,661.48 | 4,665.37 ₹18,661.48 |
| 1.01 | 90.3.18.2 : Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps | 6 | metre | 716.71 ₹4,300.26 | 716.71 ₹4,300.26 |
| 1.01 | 90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required | 2 | each | 519.1 ₹1,038.20 | 519.1 ₹1,038.20 |
Tender Value
₹9.0 L
EMD Value
₹22,600
Closing Date
13 Mar 2026, 4:00 pmClosed
PROJECT ENGINEER
PROJECT ENGINEERS OFFICE KLDC VADAKARA
Electrification of works 1- Labours Rest Room , 2- Poultry Shed, 3- strorage room , 4- Bore well Pump set and Accessories
2026_KLDC_843944_1
KLDC/ VTK/2025-26/10(2)
Open Tender
Electrical Works
180 days
DAF Chelakkara in Thrissur District
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,150
₹22,600
26 May 2026
5 Mar 2026
17 Mar 2026
5 Mar 2026
13 Mar 2026
5 Mar 2026
5 Mar 2026 - 13 Mar 2026
Appendix 1:Electrification of Labours Rest Room at DAF, Chelakkara, Thrissur
1.10.3: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD316012/2025-2026 : Wiring combined plug point together with the light point/ fan point/ exhaust fan point/ call bell point including 6 A 5 pin modular socket controlled by 6A one way modular switch in the existing switch board and giving connection to thephase,neutral and earth terminal with 1.5sq.mm.FRLS PVC insulated copper conductor single core cable ( Green wire for earthing) etc as required.
90.3.19.3 : Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture
90.4.1: Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required
OD316005/2025-2026 : Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required:
OD316022/2025-2026 : Supply ,installation,testing and commissioning of 700lm pressure die cast housing Bulk head with IP66 protection & IK 08 having efficacy not less than 105lm/W and giving connection with 3 core flex wire as required.
90.15.4.2 : Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chipmake Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.2 : Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required
OD316015/2025-2026 : Supply,conveyance, installation , testing and commissioning of 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.24.3: Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5: Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.21.1: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
2.3.4 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1: Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.10.1: Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
OD316032/2025-2026: SITC of Single Phase Energy meter enclosure with hinged door environment friendly recyclable anti acid and anti-corrosive IP65 in accordance with IEC 60259 SINTEX make GSMB 2525/EQUIVALENT
OD316006/2025-2026: Supplying and fixing 32A, HRC Fuse Base with HRC Fuse link with connections, in existing meter board etc as required.
OD316009/2025-2026: Supply and installation of 32 A, 2 Way neutral links mounted on DMC/SMC base
5.4: Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.2.2 : Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class)
90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD316014/2025-2026 : Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required.25 x 6 mm brass bolt & nut
OD316017/2025-2026 : Supply and providing iron hook for binding service wire
OD316010/2025-2026 : Supply and laying of Nylon transparent string for supporting service cable.
Appendix 2: Electrification of Poultry Shed at DAF, Chelakkara, Thrissur
1.10.3: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
90.3.19.3: Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
OD315990/2025-2026: Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required:
90.15.4.2: Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.2 : Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
1.27.2: Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.24.3: Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switc
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.21.1: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X1.5 sq.mm
1.17.4: Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm
1.17.12: Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21: Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
2.3.4: Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door
2.12.1: Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.10.1: Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
OD315992/2025-2026: SITC of Single Phase Energy meter enclosure with hinged door environment friendly recyclable anti acid and anti-corrosive IP65 in accordance with IEC 60259 SINTEX make GSMB 2525/EQUIVALENT
OD315995/2025-2026 : Supplying and fixing 32A,HRC Fuse Base with HRC Fuse link with connections, in existing meter board etc as required.
OD315988/2025-2026: Supply and installation of 32 A, 2 Way neutral links mounted on DMC/SMC base
5.4: Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.1.2: Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.2: Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.2.2: Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class)
OD315994/2025-2026: Supply and providing iron hook for binding service wire
OD315989/2025-2026: Supply and providing the following sizes of bolt and nut with washers on the existing MS box /earth bus etc. as required including drilling necessary holes as required. 25 x 6 mm brass bolt & Nut.
Appendix 3: iElectrification of Storage Room at DAF, Chelakkara, Thrissur
1.10.3: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD315981/2025-2026: Wiring combined plug point together with the light point/ fan point/ exhaust fan point/ call bell point including 6 A 5 pin modular socket controlled by 6A one way modular switch in the existing switch board and giving connection to the phase,neutral and earth terminal with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable ( Green wire for etc as required.
90.3.19.3: Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture.
90.15.4.2: Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.2: Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
90.4.1: Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
OD315984/2025-2026: Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required:w
90.4.8: Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
OD315985/2025-2026: Supply,conveyance, installation , testing and commissioning of 380 mm sweep, 900 rpm Heavy Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
1.27.2: Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.24.3: Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5: Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.21.1: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3: Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12: Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21: Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
2.3.4: Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door
2.12.1: Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1: Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.10.1: Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Appendix 4: Borewell Pump set and Accessories Thrissur
OD356649/2025-2026: Supply, conveyance, installation, testing and commissioning of 3 phase 415V, 15 HP/11KW, oil cooled bore well submersible pump set with a discharge rate of 530/100 LPM against the head range of 64 to 176M, 12 no of stages, 65MM delivery with required accessories- Kirloskar model no. KU6i HHN 350-1512 or equivalent make
90.6.6.4: Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.6 sqmm
OD356650/2025-2026: Supply and laying 10 mm or nearest size stainless steel rope
OD356651/2025-2026: Supply and fixing 63mm dia 4 Kgff/cm2 PVC pipe including fixing the pipe accessories with clamp/clips at 60cm spacing. etc as required
OD356652/2025-2026: Supply and providing 50mm dia 6kg/cm2 HDPE pipe [ISI]
OD356653/2025-2026: Supply and providing 50 mm dia Cast iron Non return Valve( Heavy duty)
OD356655/2025-2026: Supply and providing 50mm G.I.Barrel nipple
OD356668/2025-2026: Supply and providing 50mm Full way wheel Valve (GM)
OD356669/2025-2026: Supply and providing 50mm dia PVC Adaptor-Male
90.14.28.6: S & F Motor starters of the following ratingsFully automatic star delta starter for 15HP motor
90.14.24.5: Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor suitable for direct connection to motors.
90.14.1.1: Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame).
2.1.3: Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N
90.14.5: Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD356675/2025-2026: Supply and installation of dust and vermin proof,3 phase syntax meter board(GS MB- 6535) and to fix KSEB meters, fuse units , CT etc as required including fixing it on wall, making good the damages colour washing etc. as required
OD356677/2025-2026: Supplying and fixing 100A, HRC Fuse Base with HRC Fuse link with connections, in existing meter board etc as required.
OD356678/2025-2026: Supply and installation of 63 A, 2 Way neutral links mounted on DMC/SMC base
2.13.3: Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
5.4: Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.1.3: Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3: Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.6.4.54: Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 4 Run
90.16.2.2: Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class)
OD360819/2025-2026: Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required. 25 x 6 mm brass bolt & nut
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1424736.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
SBDchelakkaraELECTRIFICATION.pdf
Tender Documents • 1.24 MB
BOQ_1424736.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid