Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹92.7 CrAccepted-AOC | ₹92.7 Cr | L1 | Accepted-AOC Bidder qualifies in Technical evaluation and found L1 in Financial evaluation |
| 2 | L2₹99.1 CrRejected-AOC | ₹99.1 Cr | L2 | Rejected-AOC Bidder qualifies in Technical evaluation but found L2 in Financial evaluation |
| 3 | L3₹99.6 CrRejected-AOC | ₹99.6 Cr | L3 | Rejected-AOC Bidder qualifies in Technical evaluation but found L3 in Financial evaluation |
Tender Value
₹84.3 Cr
EMD Value
₹1.1 Cr
Closing Date
11 Jul 2024, 5:00 pmClosed
Superintending Engineer CCP-II
Victoria Cross Vijeta Gabar Singh Urja bhawan Dehradun-248001
Installation of Reactive Power Solution on 33/11kV Substations in Uttarakhand on Turnkey Basis Including AMC for Five Years.
2024_UPCLC_72565_1
CCP-II/3/2024-2025
Open Tender
Electrical Works
365 days
As per Tender specification
Please refer Tender documents.
5 documents required · 5 mandatory
₹29,500
Yes
Executive Engineer Electricity store division UPCL
₹1.1 Cr
Yes
19 Oct 2024
22 Jun 2024
12 Jul 2024
22 Jun 2024
11 Jul 2024
23 Jun 2024
Amount
12.65 kV, 4800 kVAr, 3-Phase, 50 Hz housed in Outdoor Type IP 5X CRCA Panel, Capacitor bank having four Variable steps of 1200 KVAr, 1200 KVAr, 1200 KVAr & 1200 kVAr OR six variable steps of 300+600+600+900+1200+1200Kvar (to be installed at substations where space for installation of 6 step capacitor bank is available). Bank shall be complete with Capacitor units of 400/300/200/100 kVAr, Aluminium busbars, Pin & Post insulators, HRC fuses etc. Outdoor Type CRCA Panel shall be accomodating capacitors,Series Reactor,Vacuum contactor, Surge suppressor, Fuses, RVT etc.
12.65 kV, 3600 kVAr, 3-Phase, 50 Hz housed in Outdoor Type IP 5X CRCA Panel, Capacitor bank having four Variable steps of 600 KVAr, 600 KVAr, 1200 KVAr & 1200 kVAr . Bank shall be complete with Capacitor units of 400/300/200/100 kVAr, Aluminium busbars, Pin & Post insulators, HRC fuses etc. Outdoor Type CRCA Panel shall be accomodating capacitors,Series Reactor,Vacuum contactor, Surge suppressor, Fuses, RVT etc.
12.65 kV, 3000 kVAr, 3-Phase, 50 Hz housed in Outdoor Type IP 5X CRCA Panel, Capacitor bank having four Variable steps of 300 KVAr, 600 KVAr, 900 KVAr & 1200 kVAr . Bank shall be complete with Capacitor units of 400/300/200/100 kVAr, Aluminium busbars, Pin & Post insulators, HRC fuses etc. Outdoor Type CRCA Panel shall be accomodating capacitors,Series Reactor,Vacuum contactor, Surge suppressor, Fuses, RVT etc.
Indoor Type Automatic Power Factor Controller
Vacuum Circuit Breaker along with C&R Panel for Automatic Capacitor Bank (Indoor/ Outdoor) 11kV, 630 Amps indoor/outdoor VCB, C&R Panel, CT unit with mounting structure
Allied Equipments for Automatic Capacitor Bank 11kV, 630 Amp, Off Load Isolator with earth switch and mounting structure
Allied Equipments for Automatic Capacitor Bank 9kV, 10KA, Station class (III), Lighting Arrester
Control Cables of size 4x2.5sq.mm.
Control Cables of size 6x2.5sq.mm.
Control Cables of size 16x2.5sq.mm.
Power Cables 11 KV XLPE insulated 3x185 mm2 Armoured
Other Works for Automatic Capacitor Bank Lugs/thimble, Junction Box, 2 nos. Cable supportstructure etc.
Heat Shrinkable Jointing kit for 11KV 3x185 sq. mm. XLPE Cable (Indoor termination Kit)
Heat Shrinkable Jointing kit for 11KV 3x185 sq. mm. XLPE Cable (Outdoor termination Kit)
GI Earthing Strip (size 35x6 sqmm)
Pipe Electrode
Cable Trench for lying of Power/control cables
Cable box of 2MM thick CRCA sheet of dimension 1000X600X500MM with associated acessories like bus bar. Insulator, Holding clamps for clamps for cable etc. to connect with existing 11KV Panel
Steel (Reinforcement)
Description of Work / Item(s)
Amount
12.65 kV, 4800 kVAr, 3-Phase, 50 Hz housed in Outdoor Type IP 5X CRCA Panel, Capacitor bank having four Variable steps of 1200 KVAr, 1200 KVAr, 1200 KVAr & 1200 kVAr OR six variable steps of 300+600+600+900+1200+1200Kvar (to be installed at substations where space for installation of 6 step capacitor bank is available). Bank shall be complete with Capacitor units of 400/300/200/100 kVAr, Aluminium busbars, Pin & Post insulators, HRC fuses etc. Outdoor Type CRCA Panel shall be accomodating capacitors,Series Reactor,Vacuum contactor, Surge suppressor, Fuses, RVT etc.
12.65 kV, 3600 kVAr, 3-Phase, 50 Hz housed in Outdoor Type IP 5X CRCA Panel, Capacitor bank having four Variable steps of 600 KVAr, 600 KVAr, 1200 KVAr & 1200 kVAr . Bank shall be complete with Capacitor units of 400/300/200/100 kVAr, Aluminium busbars, Pin & Post insulators, HRC fuses etc. Outdoor Type CRCA Panel shall be accomodating capacitors,Series Reactor,Vacuum contactor, Surge suppressor, Fuses, RVT etc.
12.65 kV, 3000 kVAr, 3-Phase, 50 Hz housed in Outdoor Type IP 5X CRCA Panel, Capacitor bank having four Variable steps of 300 KVAr, 600 KVAr, 900 KVAr & 1200 kVAr . Bank shall be complete with Capacitor units of 400/300/200/100 kVAr, Aluminium busbars, Pin & Post insulators, HRC fuses etc. Outdoor Type CRCA Panel shall be accomodating capacitors,Series Reactor,Vacuum contactor, Surge suppressor, Fuses, RVT etc.
Indoor Type Automatic Power Factor Controller
Vacuum Circuit Breaker along with C&R Panel for Automatic Capacitor Bank (Indoor/ Outdoor) 11kV, 630 Amps indoor/outdoor VCB, C&R Panel, CT unit with mounting structure
Allied Equipments for Automatic Capacitor Bank 11kV, 630 Amp, Off Load Isolator with earth switch and mounting structure
Allied Equipments for Automatic Capacitor Bank 9kV, 10KA, Station class (III), Lighting Arrester
Control Cables of size 4x2.5sq.mm.
Control Cables of size 6x2.5sq.mm.
Control Cables of size 16x2.5sq.mm.
Power Cables 11 KV XLPE insulated 3x185 mm2 Armoured
Other Works for Automatic Capacitor Bank Lugs/thimble, Junction Box, 2 nos. Cable supportstructure etc.
Heat Shrinkable Jointing kit for 11KV 3x185 sq. mm. XLPE Cable (Indoor termination Kit)
Heat Shrinkable Jointing kit for 11KV 3x185 sq. mm. XLPE Cable (Outdoor termination Kit)
GI Earthing Strip (size 35x6 sqmm)
Pipe Electrode
Cable Trench for lying of Power/control cables
Cable box of 2MM thick CRCA sheet of dimension 1000X600X500MM with associated acessories like bus bar. Insulator, Holding clamps for clamps for cable etc. to connect with existing 11KV Panel
Civil work (including foundation of Capacitor Cubical etc. as per requirement) Earth Work
Brick work 1:6 Sub Structure
Brick work 1:6 Super Structure
Cement plaster 1:6(12mm thick) on plinth
Steel (Reinforcement)
Annual Maintenance Charges for 5 years Annual Maintenance Charges per Unit ( 12.65kV, 3000 kVAR, 3- Phase Automatic Power Factor Correction Panel and all other associated equipment) per year
Annual Maintenance Charges for 5 years Annual Maintenance Charges per Unit (12.65 kV, 3600 KVAr, 3-Phase Automatic Power Factor Correction Panel and all other associated equipment) per year.
Annual Maintenance Charges for 5 years Annual Maintenance Charges per unit (12.65 kV, 4800 KVAr, 3-Phase Automatic Power Factor Correction Panel and all other associated equipment) per year.
Century Infrapower Private Lmited
Shreem Electric Ltd
Century Infrapower Private Lmited
Shreem Electric Ltd
Shreem Electric Ltd
Century Infrapower Private Lmited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid