| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.5 LAccepted-AOC H NO 199 W NO 6 NEAR OLD SDM OFFICE DISTT HAMIRPUR HP 177001 | HAMIRPUR | HAMIRPUR | HP | 177001 | L1 | Accepted-AOC award issued being L1 contr | |
| 2 | L2₹12.0 L+₹52,660 (4.60%)Rejected-Finance | L2 | Rejected-Finance REJECTED BEING L2 FIRM | |
| 3 | Rejected-Technical HOUSE NO 214 WARD NO 2 TEHSIL SUJANPUR DISTT HAMIRPUR HP | HAMIRPUR | HIMACHAL PRADESH | 174304 | - | Rejected-Technical bid responsive but disqualified | |
| 4 | Rejected-Technical C O DEVNAR ENTERPRISES NERCHOWK DISTRICT MANDI H P | UNA | HIMACHAL PRADESH | 174301 | - | Rejected-Technical BID RESPONSIVE BUT DISQUALIFIED | |
| 5 | Rejected-Technical | - | Rejected-Technical bid responsive but disqualified |
Tender Value
₹14.7 L
EMD Value
₹29,400
Closing Date
4 Mar 2023, 10:00 amClosed
Executive Engineer, Electrical Division, HP.PWD Ma
Executive Engineer, Electrical Division, HP.PWD Mandi
Providing UPS 40KVA IGBT basis instead of Faulty UPS adjusted in 5th floor for 2 Nos. OT Pediatric ICU Ward of Hospital in Shri lal bahadur shastri Govt. Medical college and Hospital Nerchowk District Mandi HP
2023_PWD_69449_1
PW/MED/TA/NIT/ e-notice/22-23-8391-02 dt 15.02.23
Open Tender
Electrical Works
Item Rate
180 days
Nerchowk
PLZ REFER TO BID DOC
11 documents required · 11 mandatory
₹500
₹29,400
8 Jul 2024
25 Feb 2023
4 Mar 2023
25 Feb 2023
4 Mar 2023
25 Feb 2023
Amount
SITC of 40 KVA/40 KW online pure sine wave UPS with enclosure suitable for (3 phase AC input and 3 phase AC output) with Inbuilt/External Isolation Transformer of same OEM Make compatible with external battery bank ( of minimum VAH= 46,800 VAH) for one hour backup . The UPS should be of Microprocessor control double conversion, PWM/ IGBT based invertor and rectifier with touch screen display & Multi Colour led Bar for monitoring of its status with Advanced 3 Level IGBT based technology and provided with Battery Rack and Connected wires between UPS and battery Bank and with advanded battery Management system. The job includes the cost of carriage, erection, installation, commissioning and testing charges including rack, connecting cables, and other petty material required to complete the job. The UPS should be of Emerson -Vertiv / Eaton / APC Schneider and Legrand-Numeric make only.
The UPS should have following Technical specification.
Inbuilt Manual by-pass and automatic /Static bypass Facility with Emergency Power Off (EPO) facility.
Switching device shall be IGBT. At rectifier & inverter both.
Input : 380/400/415 V AC 3 ph + N with Voltage Range 400VAC(-20%/ +15%) on Full Load
Output : 380/400/415V AC (± 1%)
Operating Temp. -00C to +400 C (at rated voltage, rated load)
Operating humidity: 20 to 95% RH (Non condensing)
Input THDi: < 5%
Output Voltage harmonics distortion at output: <2 % for Linear Load, and <5% for (Non-Linear Load
Efficiency: AC-AC efficiency (upto 96%)
Out Put Power Factor: Unity (40KVA/40KW)
Overload Capacity: upto 125% load Continue for 10 min with no bypass , upto 150% load Continue for 1 min with no bypass.
Frequency 50/60 Hz
Frequency accuracy ±0.01% (At Self-oscillation)
Protection Class: 1P20
Alarm & Alerts : Alarm for battery low-voltage, mains abnormal, UPS fault, output overload & Multi Colour led Bar for monitoring of its status from distance.
Protection functions: Poterction for battery under-voltage, overload, short-circuit, over-temperature, input over-voltage, communication abnormal.
Audible Noise Level (dB) - <60 dBA
UPS should be with Inbuilt Phase sequence protection & correction feature along with inbuilt Backfeed protection.
UPS should be with inbuilt Battery temperaturesensor and with remote Panel alarm.
Certifications & Standarard Compliances: Safety: IEC62040-1, EMC: IEC62040-2, Performance IEC62040-3 , along with CE/UE and ISO 9001 & 14001 certification. Product should be ROHS/ PEP certified.
Communications & Management :- USB & RS 232Ports with optional SNMP .
UPS should be compatible for Parallel option upto 6 Units for future expansion of power .
Warranty: 2 year onsite for UPS.
SERVICE & Support : OEM should have service centers /network in the town/Distt for better services & support and need to furnish service centre address along with atleast two enginerrs contact details, considering the critical nature of application load.
Battery Bank for 60 min Backup on 40KVA UPS Load
1Set of Battery Bank of 12 V SMF VRLA Type with suitable AH for 60 min backup on 40KVA UPS at 0.8 load PF , Min VAH of Battery Bank requried is 46,800VAH,
Warranty: 2 year onsite for batteries.
pankaj saini
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .