Loading…
Loading…
Tender Value
Refer Docs
Closing Date
26 Jul 2022, 3:00 pmClosed
Ajay Trimbake
Hazira Depot, Bharat Petroleum Corporation Limited
Bidder has to download, sign and upload ann-A- Scope of work and Specific terms and conditions, ann - B -TECHNICAL SPECIFICATION FOR LABORATORY GAS DISTRIBUTION SYSTEM and ann III - Bid Security Declaration
3951
1000389216
Limited Tender
Works
Hazira Depot
27 Jul 2022
11 Jul 2022
26 Jul 2022
11 Jul 2022
26 Jul 2022
11 Jul 2022
12 Jul 2022 - 26 Jul 2022
TECHNICAL SPECIFICATION FOR
LABORATORY GAS DISTRIBUTION
SL. CHAPTER NAME DESCRIPTION
1 CHAPTER-03 LABORATORY GAS DISTRIBUTION SYSTEM
1 SCOPE OF SUPPLY /WORK
1.1 General Requirements:
The gas distribution system has two independent types of systems namely Bottled
gas system and Compressed air system. The bottled gas system feeds the process
fluids from the gas banks to the laboratory utility points whereas the compressed
air is fed from the compressor room.
The gas system consists of the following from the gas yard; main isolation valve,
floor isolation valves, branch isolation valves, pressure gauges, tubes & tube
fittings, point of use regulators, gas purifiers, supports, clamps etc.
2 TECHNICAL REQUIREMENTS
It is the intent of this specification to provide a high quality gas distribution
System for the laboratory usage.
2.2. Gas Tubing:
2.2.1. Tubing sizes 1/4” up to 1” OD should be made of SS 316 seamless tube.
2.2.2. Tubing should have a minimum of 8% Nickel
2.2.3. Tubing should have carbon content < 0.040%.
2.2.4. The tubing should be supplied with plugged ends.
2.2.5. Tubing hardness should have a max HRB
2.2.6. Tubing supplied has MOC of SS
2.3. Tube Fittings:
2.3.1. The fittings shall be of “Flareless” design and consist of primarily four
components, i.e. body, front ferrule, rear ferrule and nut.
2.3.2. Tube to tube joints and braches are joined by the way of compression.
2.3.3. The fittings shall be capable of holding the maximum working pressure of
the tubing without any leak after only one and a quarter turn pull up of the
2.3.4. The rear / back ferrule on Stainless Steel Tube Fittings shall have a
machined recess on the inside diameter and shall have complete surface
hardening to substantially reduce the required pull up torque. Both the
requirements i.e., complete surface hardness and machined recess shall be
met for all rear ferrules of sizes ranging from 1/4” to 1” OD
2.3.5. Nuts for SS fittings shall have silver plated threads to act as a lubricating
agent to avoid galling and to reduce tightening torque.
2.3.6. All the fittings end connections shall be compatible to tube of hardness
less than or equal to RB
2.3.7. Stainless Steel Tube Fittings made from bar stock (straight configurations)
should meet ASTM A269 / ASTM A269M standards and those made from
forgings (including elbows, crosses and tees) should meet ASTM A182 /
ASME SA182 standards. For Brass fittings the standards are respectively
ASTM B16 / ASTM B453 & ASTM B283.
2.3.8. HDPE Drainage: HDPE pipes and fittings thermal weld type, 4mm thick.
2.3.9. Moisture trap: Inline type, Clear acrylic / glass tube, regenerable, with
1/4" ferrule fittings at both ends with all SS 316/316 fittings inside. Make:
Reputed Valves manufacturer (Panel mounted).
2.4. PRIMARY CONTROL MODULES
2.4.1. Supply of Gas Primary control modules along with pig tails, bull noses,
cylinder brackets, restraining chains, support brackets and necessary fittings
for connecting cylinders in the gas banks.
2.4.2. Performance testing of the manifolds with respect to the purity, flow rate
and leakage of gases.
2.4.3. Material of construction for the manifold will be SS 316L and working
pressure rating shall be 250 bar. The manifold should have been tested for
2.4.4. The gases used for this application shall be high purity analytical grade so
it is intended to have the complete primary control module pre-cleaned and
certified for 5.0 purity gas application.
2.4.5. Only SS 316 double braided bellow hoses, heavy wall construction.
2.4.6. The braided hoses shall be tested for 300 bar and certificate produced.
2.4.7. The primary control module shall be supplied with the following
specifications.
(a) The Body of the primary control module is Brass
(b) The regulator shall be provided with an inlet (0-300 bar)and an outlet
gauge (0-10 bar)
(c) The regulators shall be provided a back mounting support which shall
be mounted on a Powder coated MS profile.
(d) Inlet and outlet port size is 1/4” Female NPT connections.
(e) The regulator shall be provided with an integrated relief vent to blow
at 1.5 times the outlet pressure.
(f) Helium leak tests shall be performed on all the regulators and
certification used by the manufacturer.
2.4.8. Mild steel cylinder holding brackets to hold both 9” dia and 15” dia
cylinders, powder coated with restraining chains with locking arrangements.
2.5. ISOLATION VALVES
2.5.1. Stainless Steel 316 SS, ¼”, ½”. 1” ferrule type
2.5.2. Teflon gland packing with Silicone base lubricant
2.5.3. The valves shall be factory tested at 1000 PSIG and certification shall be
2.5.4. The factory leak test shall be performed to a maximum allowable leak rate
of 1 X 10-3 cc / sec He
2.5.5. Operating pressure 0-150 Bar.
2.6. PRESSURE GAUGES
2.6.1. Bourdon type, centre back connection for dropper gauge and bottom
connection for Regulator gauge.
2.6.2. Inlet size ¼” MNPT with dial size of 60 mm
2.6.3. Bourdon and socket material SS
2.6.4. Casing is SS
2.6.5. Accuracy shall be +/- 1% of FSD.
2.6.6. Factory Calibration Certificate required along with supply.
Flanges will be as per ANSI B 16.5 class
Flanges will be socket weld type.
3. SUMMARY OF MATERIAL OF CONSTRUCTION
Tube fittings : SS
Primary Control Modules : SS
Tubing Supports : Mild Steel
Piping Supports : GI
Tube support clamps : Polypropylene
Cylinder Bracket : Mild steel
Pressure Gauge : SS Bourdon and BLACK Zinc body
Gas fixtures : Brass Powder Coated
4.0 INSPECTION AND TESTING
4.1 Performance Test for Gas System:
4.1.1 Installation Purging Procedures:
4.1.1.1 The sealed tubes after starting the process of cutting and deburring has to
be purged with general purity nitrogen.
4.1.1.2 Connect the tubes to the flexible hose of the regulated supply (at 2 bars)
and blow the debris for 5 min.
4.1.1.3 To ensure the purging is totally complete, blow the tubes intermittently
holding the pressure for few seconds at the end of the tube.
4.1.1.4 Now use the tube to swage the fitting. And install the tube with the fitting
at the required place.
4.1.2 Pre Testing Purging Procedure
4.1.2.1 Once the main header and the sub header installation is complete, check
for the misalignment or improper fitting connections
4.1.2.2 Connect the regulated pressure from the Nitrogen cylinder and
blow the system for 15 mins non stop.
4.1.2.3 Start the process again after a 15 mins duration and blow the system for
another 10 mins.
4.1.2.4 Reconnect the needle valves and open the port fully.
4.1.2.5 Start the purging process one more time with the valve open blow the
whole system for 30 mins.
4.1.2.6 Now the system is completely purged and now ready for handing over
after the pressure test.
4.1.2.7 Please note purged air must be directed to outside of Lab.
4.1.3 Pressure Testing Procedure
4.1.3.1 Ensure complete piping is purged with prior to pressure test. Use Nitrogen
for leak check. Please note purged air must be directed to outside of Lab.
4.1.3.2 Ensure the system point is not hooked up to the lab equipment.
4.1.3.3 Shut-off point of use valve and pressurize system through the cylinder
4.1.3.4 Increase pressure slowly to maintain 30 psi and shut-off the cylinder
valve. Observe the pressure gauge for evidence of pressure drop.
4.1.3.5 If the pressure drops, trouble-shoot leaking joints by using “Snoop” liquid
leak detector rectify as necessary.
4.1.3.6 Proceed to increase pressure to 100 psi if no leak is detected after 15 mins.
of pressurization at 30 psi.
4.1.3.7 Repeat item (a) if leak is detected.
4.1.3.8 Proceed to increase pressure to 1.5 times the working pressure of the
system. (Normally system with same procedure as above.
4.1.3.9 Maintain pressure for 12 hours and check for evidence of pressure drop.
4.1.4 Preliminary Testing
4.1.4.1. Preliminary Leak testing will be carried out in two phases:
- Pressure decrease method (Pressure testing: 1.5 times the maximum working
Necessary formats will be used and all relevant data will be recorded during the
test. GDS vendor and Management staff of Watson Pharma will jointly witness
the test and certify the same.
- TIFF leak detection.
Necessary formats will be used and all relevant data will be recorded during the
test. GDS vendor and Management staff of Watson Pharma will jointly witness
the test and certify the same.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
BUDGETDOC_3951.pdf
pdf • 0.51 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .