Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹6.4 Cr
EMD Value
₹6.4 L
Closing Date
12 Nov 2024, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Construction New Central Medical Store at JLNH and RC, Sector-9, Bhilai Steel Plant (BSP), Chhattisgarh.
NBCC/SBG/OD/CG/NIT/24-25/22
NBCC/SBG/OD/CG/NIT/24-25/22
Open Tender-Domestic
Civil Works General
Ludhiana, Punjab
₹11,800
₹6.4 L
12 Nov 2024
29 Oct 2024
12 Nov 2024
12 Nov 2024
17 Dec 2024
ABSTRACT OF COST
CONSTRUCTION OF (G+2) CENTRAL MEDICAL STORE AT JLNH & RC, SECTOR 9,
BHILAI STEEL PLANT AT BHILAI ( CHHATTISHGARH)
SL.NO. PARTICULARS TOTAL AMOUNT
SL.NO. PARTICULARS TOTAL AMOUNT
1 Central Medical Store
1.1 Civil Works 2,47,91,841
1.2 Internal & External Plumbing Works 6,18,822
1.3 Internal & External Fire Fighting System 1,91,25,548
1.4 HVAC Works 99,03,053
1.5 Electrical & ELV System 92,17,662
SubTotal [D] :- 6,36,56,926
SubTotal Including GST [D] :- 6,36,56,926
Digitally signed by Rakesh
CG SOR DSR-2023
Sl. No. SOR DESCRIPTION UNIT QTY. SOR AMT. DSR Amount
2015 RATE RATE
B 1.00 EARTH WORKS
1 1.1 Excavation for all types and sizes of foundations, trenches and drains or
for any other purpose including disposal of excavated stuff upto 1.5 m lift
and lead upto 50m (at least 5m away from the excavated area), including
dressing and leveling of pits.
1.3 1.1.4 In hard rocks where blasting in prohibited. Cum 111.89 949.62 1,06,252.18
3 1.17 Filling from available excavated stuff (Excluding rock) in trenches, plinth,
sides of foundation etc. in layers not exceeding 20cm in depth
consolidating each deposited layer by ramming and watering with a lead
upto 50 M. and lift upto 1.5 M. Cum 573.22 77.35 44,338.28
4 1.18 Providing and filling in plinth with sand/ Crusher dust and hard moorum
under floor in layers not exceeding 20cm in depth consolidating each
deposited layer by ramming and watering, including dressing etc.
5 1.2 Surface dressing of the ground including removing vegetation and making
up undulations and in-equalities not exceeding 15 cms in depth/ height
including disposal of rubbish upto 1.5 m lift and lead upto 50m (at least 5m
away from the dressed area). Sqm 564.30 8.57 4,836.05
6 1.22 Supplying chlorpyrifos/ Lindane emulsifiable concentrate of 20% in sealed
containers including delivery as specified. Litre 598.67 247.52 1,48,183.29
i 1.23.1 Along external wall where the apron is not provided using diluted chemical
emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a
depth of 300 mm including excavation channel along the wall & rodding
etc. complete: Metre 1194.24 10.83 12,933.62
8 1.25.1 Surface treatment by spreading emulsion under floor, over the plinth area
before laying base concrete @ 5 litres / sqm Sqm 274.24 368.96 1,01,183.59
a 3.1.4 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40mm
b 3.1.3 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm
nominal size). Cum 27.81 3534.30 98,281.81
3 3.13 Providing and laying damp proof course (upto 50mm thick) with plain
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded crushed
stone aggregate 20mm nominal size) including form work. Cum 1.83 5042.03 9,232.90
4 3.14 Providing and mixing water proofing material in PCC/ RCC work in the
proportion recommended by the manufacturer. Per 50 kg cement 12.00 51.77 621.24
5 3.15 Applying a coat of hot bitumen VG-10 using @ 1.7kg/ sqm on damp proof
course after cleaning the surface with brushes and finally with a piece of
cloth lightly soaked in kerosene oil. Sqm 36.62 111.27 4,075.12
6 3.16 Making 50mm thick plinth protection of plain cement concrete 1:3:6 (1
cement : 3 coarse sand : 6 graded crushed stone aggregate 20mm
nominal size) over 75mm bed of dry brick ballast 40mm nominal size well
rammed and consolidated and grouted with sand including finishing the
1.1 2.1.1 Foundations, footings, bases of columns plinth beam, curtain wall in any
shape and size and all type of wall below plinth level. Sqm 53.76 165.41 8,892.44
1.2 2.1.2 Wall of any thickness including attached pilasters, buttresses etc. in super
1.3 2.1.7 Suspended floors, roofs, access platform, balconies (plain surfaces) and
shelves (cast in situ) Sqm 1338.22 279.65 3,74,232.20
1.4 2.1.8 Beams, lintels, cantilevers & walls Sqm 1110.36 240.38 2,66,907.74
1.5 2.1.5 Columns, Pillars, Piers and likes- rectangular or square in shape Sqm 904.24 353.43 3,19,585.54
1.6 2.1.15 Stair cases of all types excluding spiral and folded plate type, including
risers and landings Sqm 205.64 273.70 56,284.35
1.7 2.1.4 Edge of slab, breaks in floor and walls upto 200mm. Metre 313.30 40.46 12,676.12
1.8 2.1.13 Weather shade, chhajja, Cornices and mouldings Sqm 125.28 349.86 43,830.46
i 3.12.2 Thermo-Mechanically treated bars FE 500D Kg 113989.55 64.86 73,93,362
2 5.35 Add for using extra cement in the items of design mix over and above the
specified cement content therein. quintal 54.33 872.87 47,424.16
i 7.1.4 Cement Mortar 1:6 (1 Cement : 6 Coarse Sand) Cum 37.96 4546.99 1,72,592.37
2.1 7.5.4 Cement Mortar 1:6 (1 cement : 6 coarse sand) Cum 3882.97
3 7.11.2 Half brick thick brick masonry with fly-ash lime bricks (FaLG Bricks)
confirming to IS:12894-2002 of class designation 4.0 in superstructure
above plinth level upto plinth level: Cement Mortar 1:4 (1 cement : 4 coarse sand)
3.1 7.12 Extra for half brick work in superstructure above plinth level for every story
or part thereof in addition to rate for upto plinth level: Sqm 31.81 13.09 416.39
4 7.20 Extra for providing and placing in position hopping 25x1.60 mm or 2 Nos
6mm dia MS bars reinforcement at every third course of half brick
13.4.3 Granite stone lakha red/ shahi red Sqm 2.00 5067.02 10,134.04
2 13.5.3 8mm thick Granite tile work (machine cut, table rubbed & mirror polished)
for wall lining (veneer work) in cement mortar 1:3 (1 cement : 3 coarse
sand) including pointing with cement mortar 1:2 (1 white cement : 2
marble dust) mixed with matching pigment.
Granite stone lakha red/ shahi red Sqm. 47.34 2879.80 1,36,342.69
3 12.7.2 Providing and fixing ceramic glazed wall tiles conforming to IS : 15622
of approved make, colours, shades and size on wall and dados over 12
mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and
jointing with grey cement slurry @ 3.3kg per sqm including pointing in
white cement mixed with matching pigment complete.
1.1 8.1.2 Sal, bijasal, benteak, khair, haldu Cum 0.60 72650.69 43,939.14
3.01 8.19.1 Rectangular or square Each 12.00 82.11 985.32
4 8.18.3 Providing and fixing lipping with second class teak wood lipping on all
edges of shutters. (35 x 6 mm size) Rmt 75.60 550.20 41,595.12
Digitally signed by Rakesh
CG SOR DSR-2023
Sl. No. SOR DESCRIPTION UNIT QTY. SOR AMT. DSR Amount
2015 RATE RATE
6 9.15 Providing and fixing M.S. grill of approved pattern made of M.S. flats or
square or round bars welded to steel frame of windows etc. including
applying a priming coat welded to frame with all necessary fitting complete
including applying a priming of red oxide zinc chromate primer.
7 8.159 Providing and fixing IS: 3564 marked aluminium extruded section body
tubular type universal hydraulic door closer with double speed adjustment
with necessary accessories and screws etc complete. Each 4.00 1253.07 5,012.28
35 8.125.1 Providing and fixing aluminium door mounted door stopper with necessary
nickel plated iron screws etc complete. 100 mm long Each 24.00 53.55 1,285.20
2 9.11 Providing and fixing in position collapsible steel shutters with vertical
channels 20x10x2mm and braced with flat iron diagonals 20x5mm size
with top and bottom rails of T-iron 40x40x6mm with 38mm steel pulleys
complete with bolts, nuts, locking arrangement stoppers, handles
including applying a priming coat of red oxide zinc chromate primer. sqm 8.16 3962.70 32,336.00
a 9.6.1 In stringers, treads, landings etc. of stair cases including use of chequered
plate wherever required, all complete. KG 100.00 83.30 8,330.00
b 9.6.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar
1 12.49 25 mm thick KOTA stone slab flooring over 20mm (Average) thick base
of cement mortar 1:4 laid over and jointed with grey cement slurry
mixed with pigment to match the shade of the slab including grinding
rubbing and polishing etc. complete (Area of slab to be over 0.20 sqm
2 12.50 KOTA stone slab 25mm thick in risers and treads of steps, skirting
dado and pillar laid in 12mm (Average) thick cement mortar 1:3 (1
cement : 3 coarse sand) and jointed with grey cement slurry mixed with
pigment to match the shade of the slab including rubbing and polishing
complete. (single stone is to be used for riser and treads of steps and
the width of stone for skirting and dado shall be equal to the height of
skirting/ dado up to length of 1.0 M.) Sqm 26.97 1178.10 31,771.00
3 12.53 Extra for nosing in steps and treads of red or white fine dressed sand
4 12.50 Extra for necessary grinding and polishing to get mirror finish on KOTA/
Marble Stone flooring/ steps/ treads instead of normal grinding and
12.46.3 Granite stone lakha red/ shahi red sqm 1139.76 5084.87 5795506
1 10.41 Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 stone aggregate 10mm and down grade) including finishing with
cement mortar 1:3 (1 cement : 3 fine sand) as per standard design : rmt. 83.00 80.92 6716
i 11.2.4 In Cement Mortar 1:6 (1 cement : 6 fine sand) Sqm 1621.20 108.89 176533
2 11.7 Providing and making 18 mm thick cement plaster with under layer of
12mm thick cement plaster 1:5 (1 cement : 5 fine sand) finished with a
top layer of 6mm thick cement plaster 1:3 (1 cement : 3 fine sand). Sqm 2145.21 193.97 416106
5 11.9 Extra for providing and mixing water proofing materials in cement per bag of 50KG
plaster work in proportion as recommended by manufacturer. Cement Used in
Digitally signed by Rakesh
CG SOR DSR-2023
Sl. No. SOR DESCRIPTION UNIT QTY. SOR AMT. DSR Amount
2015 RATE RATE
i 14.16.1 New work (Two or more coats applied @ 1.43 ltr/10 sqm
over and including priming coat of exterior primer applied
1.2 9.47.2 For shutter of doors, windows & ventilators including providing and making
provision for fixing of fitting wherever required including the cost of PVC/
neoprene gasket required (Fittings shall be paid for separately). KG 313.20 431.38 1,35,108.22
2 9.48 Extra for powder coated (minimum 50 micron) aluminium sections instead
i 9.51.2 With float glass panes of 5 mm thickness Sqm 93.75 842.52 78,986.25
9.50.2 With decorative lamination on both side Sqm 33.60 1119.20 37,605.12
i) First layer of slurry of cement @ 0.488 kg/sqm mixed with water
proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to
air cure for 4 hours. ii)
Second layer of slurry of cement @ 0.242 kg/sqm mixed with water
proofing cement compound@ 0.126 kg/sqm. This layer will be allowed to
air cure for 4 hours followed with water curing for 48 hours.
The rate includes treatment and sealing of all joints, corners, junctions of
pipes and masonry with polymer mixed slurry.
iii) After two days of proper curing applying a second coat of cement
slurry using 2.75kg/ sqm of cement admixed with water proofing
compound conforming to IS : 2645.
iv) Finishing the surface with 20 mm thick jointless cement mortar of mix
1:4 (1 cement :4 coarse sand) mixed with water proofing compound
conforming to IS : 2645 including laying glass fibre cloth of approved
quality in top layer of plaster and finally finishing the surface with trowel
with neat cement slurry and making pattern of 300x300 mm square 3mm
v) The whole terrace so finished shall be flooded with water for a
minimum period of two weeks for curing and for final test. SQM 449.12 727.09 3,26,548.08
TOTAL (Carried Over to Summary of Civil Works) 3,34,357.95 0.00
ALL SUB-HEAD TOTAL 2,29,57,309.16 18,34,532.07
GRAND TOTAL 2,47,91,841.23
GRAND TOTAL 2,47,91,841.23
Digitally signed by Rakesh
DETAILED PLUMBING ESTIMATE
SI.No. DSR-2023/ Description of Item UNIT MEDICAL STORE TOTAL SSR RATE DSR RATE NS RATE SSR AMOUNT DSR AMOUNT NS AMOUNT
NON DSR QUANTITY
A) SANITARY INSTALLATION
1.01 18.4 Providing and fixing vitreous china water closet (European type W.C.
pan) with white ISI marked plastic seat and lid, 10 litre low level white
P.V.C. flushing cistern (same colour), conforming to IS : 7231, with all
fittings and fixtures complete including cutting and making good the
walls and floors wherever required :
18.4.1 White pedestal type Each 2 2 3429.58 6859.16 0.00 0.00
1.02 DSR 2023 17.8 Providing and fixing white vitreous china battery based infrared Each 2 2 7979.20 0.00 15958.40 0.00
sensor operated urinal of approx. size 610 x 390 x 370 mm having pre
& post flushing with water (250 ml & 500 ml consumption), having
water inlet from back side, including fixing to wall with suitable
brackets all as per manufacturers specification and direction of
Engineer-in-charge.
1.03 12.48 8 mm thick Table rubbed polished Granite stone tile in risers and
treads of steps skirting dado and pillars laid on 12mm (Average) thick
base of cement mortar 1:3 (1 cement : 3 coarse sand) and jointed
with grey cement slurry including rubbing and polishing etc.
12.48.2 Granite stone black Sqm 1 1 1668.38 1668.38 0.00
1.04 18.10.2 Providing and fixing 15 mm nominal bore uplasticised PVC connection Each 8 8 79.14 633.08 0.00
pipe with PTMT nuts and PVC bush of approved quality and colour:
1.05 18.17 Providing and fixing vitreous china wash basin with C.I. brackets, 32
mm C.P. brass waste of standard pattern, including painting of
brackets, cutting and making good the walls wherever required :
1.06 18.29 Providing and fixing 600x450 mm beveled edge 4mm mirror of Each 4 4 712.81 2851.24 0.00
superior glass (of approved quality) complete with 6 mm thick hard
board ground fixed to wooden cleats with C.P. brass screws and
washers complete.
1.07 19.14 Providing and fixing 15 mm nominal bore C.P. brass fittings of
approved make and conforming to IS:8931 including C.P. brass
extension if required:
19.14.13 Toilet paper holder Each 2 2 295.12 590.24 0.00
1.08 DSR-2023 17.71 Providing and fixing PTMT liquid soap container 109 mm wide, 125 Each 2 2 168.35 0.00 336.70 0.00
mm high and 112 mm distance from wall of standard shape with
bracket of the same materials with snap fittings of approved quality
and colour, weighing not less than 105 gms.
1.09 19.14 Providing and fixing 15 mm nominal bore C.P. brass fittings of
approved make and conforming to IS:8931 including C.P. brass
extension if required:
19.14.2 Bottle trap set with extension pipes Each 4 4 562.87 2251.48 0.00
1.10 19.14 Providing and fixing 15 mm nominal bore C.P. brass fittings of
approved make and conforming to IS:8931 including C.P. brass
extension if required:
1.11 NS Providing and fixing Coat Hook. Each 2 2 926.00 0.00 1852.00
1.12 NS Providing ,Fixing of straight / offset type flexible single body push fit Each 2 2 946.00 0.00 1892.00
type WC pan connector of with integral single mould sealing fins
made of flexible EVA body to be fixed with manufacture supplied
grease, including rubber bush / adaptor for use with uPVC pipe as
supplied with the pan connector.
1.13 19.14 Providing and fixing 15 mm nominal bore C.P. brass fittings of
approved make and conforming to IS:8931 including C.P. brass
extension if required:
19.14.5 Two way bib cock (800 grams) Each 2 2 842.52 1685.04 0.00
1.14 19.14 Providing and fixing 15 mm nominal bore C.P. brass fittings of
approved make and conforming to IS:8931 including C.P. brass
extension if required:
19.14.19 Health foscet (hand jet) with flexible connection pipe (for WC) Each 2 2 921.06 1842.12 0.00
1.15 19.14 Providing and fixing 15 mm nominal bore C.P. brass fittings of
approved make and conforming to IS:8931 including C.P. brass
extension if required:
19.14.3 Long body bib cock (500 grams) Each 1 1 506.94 506.94 0.00
1.16 19.14 Providing and fixing 15 mm nominal bore C.P. brass fittings of
approved make and conforming to IS:8931 including C.P. brass
extension if required:
19.14.7 Angle valve for basin mixer and geyser points (450 grams) Each 8 8 454.58 3636.64 0.00
TOTAL FOR SANITARY INSTALLATION 29831.00 16295.00 3744.00
B) WATER SUPPLY
Digitally signed by Rakesh
DETAILED PLUMBING ESTIMATE
SI.No. DSR-2023/ Description of Item UNIT MEDICAL STORE TOTAL SSR RATE DSR RATE NS RATE SSR AMOUNT DSR AMOUNT NS AMOUNT
NON DSR QUANTITY
2.01 19.5 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply including all CPVC
plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00
m spacing. This includes jointing of pipes & fittings with one step
CPVC solvent cement and the cost of cutting chases and making good
the same including testing of joints complete as per direction of
Engineer in Charge.
Concealed work, including cutting chases and making good the
a) 19.5.1 15 mm nominal outer dia .Pipes. Mtr. 22 22 158.27 3481.94 0.00
b) 19.5.2 20 mm nominal outer dia .Pipes. Mtr. 13 13 198.73 2583.49 0.00
c) 19.5.3 25 mm nominal outer dia .Pipes. Mtr. 13 13 253.47 3295.11 0.00
d) 19.5.4 32 mm nominal outer dia .Pipes. Mtr. 2 2 337.96 675.92 0.00
2.02 19.4 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply including all CPVC
plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00
m spacing. This includes jointing of pipes & fittings with one step
CPVC solvent cement and testing of joints complete as per direction
of Engineer in Charge.
Internal work - Exposed on wall
a) 19.4.1 15 mm nominal outer dia .Pipes. Mtr. 0 0 130.90 0.00 0.00
b) 19.4.3 25 mm nominal outer dia .Pipes. Mtr. 0 0 236.81 0.00 0.00
b) 19.4.4 32 mm nominal outer dia .Pipes. Mtr. 22 22 322.49 7094.78 0.00
2.03 NS Providing and fixing Forged Brass Ball Valve (Screwed). with setting
and gland of superior quality having minimum working pressure of 16
a) 15 mm nominal bore Each 1 1 927.00 0.00 927.00
b) 25 mm nominal bore Each 3 3 1662.00 0.00 4986.00
c) 32 mm nominal bore Each 2 2 2570.00 0.00 5140.00
2.04 DSR 2023 18.62 Providing and fixing PTMT Ball cock of approved quality, colour and
make complete with Epoxy coated aluminium rod with L.P./ H.P.H.D.
a) 18.62.3 25 mm nominal bore, 152mm long, weighing not less than 440 gms Each 1 1 523.80 0.00 523.80 0.00
TOTAL FOR WATER SUPPLY 17131.00 524.00 11053.00
C) INTERNAL DRAINAGE
Providing and fixing soil, waste and vent pipes
3.01 DSR 2023 17.35 Providing and fixing soil, waste and vent pipes
17.35.1.3 Hubless centrifugally cast (spun) iron pipes epoxy coated inside & Mtr 36 36 1169.30 0.00 42094.80 0.00
outside IS:15905
3.02 DSR 2023 Providing and fixing bend of required degree with access door,
17.38 insertion rubber washer 3 mm thick, bolts and nuts
17.38.1.3 Hubless centrifugally cast (spun) iron pipes epoxy coated inside & Each 5 5 567.20 0.00 2836.00 0.00
outside IS:15905
3.03 DSR 2023 Providing and fixing plain bend of required degree.
17.39.1.3 Hubless centrifugally cast (spun) iron pipes epoxy coated inside & Each 5 5 368.00 0.00 1840.00 0.00
outside IS:15905
3.04 18.60 Providing fixing and push on jointing sand cast iron S&S heel rest
sanitary bend as per IS: 3989 including EPDM rubber gasket
3.05 18.63 Providing fixing and push on jointing sand cast iron S&S single equal
junction with access door of required degree as per IS: 3989,
insertion rubber washer 3 mm thick, bolts and nuts including EPDM
rubber gasket complete:
3.06 DSR 2023 Providing and fixing single equal plain junction of required degree :
17.44.1.3 Hubless centrifugally cast (spun) iron epoxy coated inside & outside Each 5 5 581.45 0.00 2907.25 0.00
as per IS:15905
3.07 18.40 Providing and fixing sand cast iron S&S single equal plain junction of
required degree as per IS : 1729
3.08 DSR 2023 Providing and fixing terminal guard.
17.56.1.3 Hubless centrifugally cast (spun) iron epoxy coated inside & outside Each 4 4 427.80 0.00 1711.20 0.00
as per IS:15905
3.09 DSR 2023 Providing and fixing shielded coupling for Hubless centrifugally cast
17.57A iron pipe.
a) 17.57A.1 100mm dia
17.57A.1.1 SS 304 grade coupling with EPDM rubber gasket Each 5 5 432.05 0.00 2160.25 0.00
3.10 18.54 Providing lead caulked joints to sand cast iron/ centrifugally cast
(spun) iron pipes and fittings of diameter:
Digitally signed by Rakesh
DETAILED PLUMBING ESTIMATE
SI.No. DSR-2023/ Description of Item UNIT MEDICAL STORE TOTAL SSR RATE DSR RATE NS RATE SSR AMOUNT DSR AMOUNT NS AMOUNT
NON DSR QUANTITY
3.11 18.56 Providing and fixing sand cast iron S&S trap of self cleansing design
with screwed down or hinged grating with or without vent arm as per
IS: 1729 complete, including cost of cutting and making good the
walls and floors :
3.12 18.79 Painting sand cast iron/ centrifugally cast (spun) iron soil, waste vent
pipes and fittings with paint of any colour over a coat of primer (of
approved quality) for new work :
3.13 18.81 Providing and fixing M.S. holder bat clamp of approved design to
sand cast iron/ cast iron (spun) pipes comprising of M.S. flat brackets
made of 50x5mm flat of specified shape, projecting 75mm outside
the wall surface and fixed on wall with 4nos, 6mm dia expansion hold
fasteners including drilling necessary holes in brick wall/ CC/ RCC
surface and the cost of bolts etc. The pipes shall be fixed to the
already fixed brackets with the help of 30mm x1.6mm galvanised
M.S. flats of specified shape and of total length 420mm and shall be
fixed with M.S. nuts, bolts, & washers of size 25x6mm, one bolts on
each side of the pipe.
18.81.2 Total bracket length 810mm of approved shape and design (for two, Each 4 4 205.87 823.48 0.00
100mm dia pipes).
3.14 NS Providing and fixing cast brass Floor Clean Out plug 100mm with
suitable insert keys for opening, male threaded joint with G.I. socket
lead caulked to soil pipe / waste pipe of C.I. and C.I.(LA) pipe as
required complete as per instruction of the Engineer in charge.
3.15 19.7 Providing and fixing on wall surface G.I. pipes medium class complete
with G.I. fittings and clamps, including cutting, making good the walls
etc. and testing of joints complete:
3.16 19.21 Painting G.I. pipes and fittings with synthetic enamel white paint over
a red oxide zinc chromate priming coat, both of approved quality for
3.17 NS Providing and fixing 125 mm dia, 3 mm thick Stainless steel grating
with frame for floor traps or drains of required pattern including
cutting and making good the floors complete.
TOTAL FOR DRAINAGE 22564.00 53550.00 17289.00
D) RAIN WATER WORK
4.01 18.76 Providing and fixing on wall face or under floor UV stabilized
Unplasticised Rigid PVC pipes (single socketed) having 3.2mm wall
thickness conforming to IS : 13592 (4kg/sqcm) including required
couplers, jointing with seal ring conforming to IS : 5382 leaving 10
mm gap for thermal expansion etc complete.
4.02 18.77 Providing and fixing on wall face UV stabilized Unplasticised - PVC
moulded fittings/ accessories having 3.2mm wall thickness for Rigid
PVC pipes conforming to IS : 13592 (heavy) jointing with seal ring
conforming to IS : 5382 leaving 10 mm gap for thermal expansion.
a) 18.77.1 Tee/ Tee with door/ Bend 45°/ Bend 90°
b) 18.77.3 Vent covel
4.03 18.78 Providing and fixing UV stabilized Unplasticised -PVC pipe clips of
approved design to Rigid PVC pipes by means of 50x50x50mm hard
wood plugs, screwed with M.S. screws of required length including
cutting brick work and fixing in cement mortar 1:4 (1 cement : 4
coarse sand) and making good the wall etc. complete.
4.04 10.42 Making khurras 45x45 cm with average minimum thickness of 5 cm Each 5 5 243.95 1219.75 0.00
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate of 20 mm nominal size) over P.V.C. sheet 1mx1mx650
micron thick (0.65mm), finished with 12mm cement plaster 1:3 (1
cement : 3 coarse sand) and a coat of neat cement rounding the edge
sand making and finishing the outlet complete.
TOTAL FOR RAIN WATER WORK 22913.00 0.00 0.00
E) EXTERNAL WATER SUPPLY WORK
5.01 19.9 Providing and laying in trenches G.I. pipes medium class complete
with G.I. fittings including excavation of trenches, refilling the same
and testing of joints complete:
a) 19.9.3 25 mm dia. nominal bore Metre 12 12 264.18 3170.16 0.00
Digitally signed by Rakesh
DETAILED PLUMBING ESTIMATE
SI.No. DSR-2023/ Description of Item UNIT MEDICAL STORE TOTAL SSR RATE DSR RATE NS RATE SSR AMOUNT DSR AMOUNT NS AMOUNT
NON DSR QUANTITY
5.02 19.23 Painting G.I. pipes and fittings with two coats of anti-corrosive
bitumastic paint of approved quality:
a) 19.23.1 25 mm diameter pipe Metre 12 12 7.02 84.25 0.00
5.03 19.24 Providing and filling fine sand or coarser grade all-round the G.I. pipes
in external work.
5.04 19.10 Making connection of G.I. distribution branch in G.I. main of following
sizes by providing and fixing tee, including cutting and threading the
pipe etc. complete: (dia of main line to be measured)
TOTAL FOR EXTERNAL WATER SUPPLY WORK 3985.00 0.00 0.00
F) EXTERNAL SEWER WORK
6.01 DSR 2023 2.10 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, anddressing of sides, ramming of bottoms,
depth up to 1.5 m, including getting out the excavated soil, and then
returning the soil as required, in layers not exceeding 20 cm in depth,
including consolidatingeach deposited layer by ramming, watering,
etc. and disposing of surplus excavated soil as directed,within a lead
2.10.1 All kinds of soil
2.10.1.2 Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia metre 40 40 352.15 0.00 14086.00 0.00
6.02 1.1 Excavation for all types and sizes of foundations, trenches and drains
or for any other purpose including disposal of excavated stuff upto
1.5 m lift and lead upto 50m (at least 5m away from the excavated
area), including dressing and leveling of pits.
1.1.1 In all types of soils. cum 11 11 220.15 2421.65 0.00
6.03 NS Supplying and laying of following size DWC SN8 pipe ISI marked along
with all accessories like socket, bend, couplers etc. conforming to IS
16098, Part II complete with fitting and cutting,jointing etc.direct in
ground (75 cm below ground level) including excavation and refilling
the trench but excluding sand cushioning and protective covering
etc., complete as required.
6.04 20.2 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse
sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W.
pipes including bed concrete 150mm thick as per standard design:
6.05 20.3.1 Providing and fixing square-mouth S.W. gully trap grade 'A'’ complete Each 2 2 1593.41 3186.82 0.00
with C.I. grating brick masonry chamber with well burnt modular clay
bricks crushing strength not less than 35kg/cm2, water tight C.I. cover
with frame of 300 x300 mm size (inside) the weight of cover to be not
less than 4.50 kg and frame to be not less than 2.70 kg as per
standard design : 100x100 mm size P type
6.06 20.7 Constructing brick masonry manhole with well burnt modular clay
bricks crushing strength not less than 35kg/cm2 in cement mortar 1:4
( 1 cement : 4 coarse sand), R.C.C. top slab with 1:2:4 mix (1 cement :
2 coarse sand : 4 graded stone aggregate 20 mm nominal size),
foundation in cement concrete 1:4:8 mix (1 cement : 4 coarse sand :
8 graded stone aggregate 40mm nominal size) inside plastering
12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand)
finished with floating coat of neat cement and making channels in
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20mm nominal size) finished with a floating coat of neat
cement complete as per standard design :
20.7.1 Inside size 90x80 cm and 45 cm deep including C.I. cover with frame Each 4 4 7976.57 31906.28 0.00
(light duty) 455x610 mm internal dimensions total weight of cover
and frame to be not less than 38 kg (weight of cover 23 kg and weight
of frame 15 kg) :
6.07 20.8 Extra for depth for manholes:
6.08 19.9 Providing and constructing brick masonry circular arch type manhole
upto 1.67m depth, 0.91m internal dia at bottom and 0.56m dia at top
having brick masonry wall 190mm thick with well burnt modular clay
bricks crushing strength not less than 35kg/cm2 in cement mortar 1:4
(1 cement : 4 coarse sand), in side cement plaster 12 mm thick with
cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating
coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3
coarse sand : 6 graded stone aggregate 40mm nominal size), and
making necessary channel in cement concrete 1:2:4 (1 cement : 2
coarse sand : 4 graded stone aggregate 20mm nominal size) finished
with a floating coat of neat cement, providing and fixing S.F.R.C.
cover and frame (heavy duty, HD- 20 grade designation) 560mm
internal diameter conforming to I.S. 12592, total weight of cover and
frame to be not less than 182kg, in cement concrete 1:2:4 (1 cement
: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) all
complete as per standard design (excavation and foot rests shall be
paid for separately) :
Digitally signed by Rakesh
DETAILED PLUMBING ESTIMATE
SI.No. DSR-2023/ Description of Item UNIT MEDICAL STORE TOTAL SSR RATE DSR RATE NS RATE SSR AMOUNT DSR AMOUNT NS AMOUNT
NON DSR QUANTITY
6.09 20.10 Providing and constructing extra depth for circular type manhole Meter 0.6 0.6 3602.13 2161.28 0.00
0.91m internal dia (at bottom) beyond 0.91m and upto 1.67m
6.10 11.2 Providing and making 12mm thick cement plaster of mix:
11.2.1 In cement Mortar 1:3 (1 cement : 3 fine sand) Sqm 10 10 136.85 1395.87 0.00
6.11 20.12 Providing orange colour safety foot rest of minimum 6 mm thick Each 20 20 203.49 4069.80 0.00
plastic encapsulated as per IS : 10910, on 12 mm dia steel bar
conforming to IS: 1786, having minimum cross section as 23 mmx25
mm and over all minimum length 263 mm and width as 165 mm with
minimum 112 mm space between protruded legs having 2 mm tread
on top surface by ribbing or chequering besides necessary and
adequate anchoring projections on tail length on 138 mm as per
standard drawing and suitable to with stand the bend test and
chemical resistance test as per specifications and having
manufacture's permanent identification mark to be visible even after
fixing, including fixing in manholes with 30x20x15 cm cement
concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
6.12 20.19 Making connection of drain or sewer line with existing manhole
including breaking into and making good the walls, floors with
cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) cement plastered on both sides with
cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating
coat of neat cement and making necessary channels for the drain etc.
20.19.1 For pipes 100 to 230 mm diameter Each 1 1 246.33 246.33 0.00
TOTAL FOR EXTERNAL SEWER WORK 86458.00 14086.00 43200.00
G EXTERNAL STORM WATER WORK
7.01 DSR 2023 2.10 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, anddressing of sides, ramming of bottoms,
depth up to 1.5 m, including getting out the excavated soil, and then
returning the soil as required, in layers not exceeding 20 cm in depth,
including consolidatingeach deposited layer by ramming, watering,
etc. and disposing of surplus excavated soil as directed,within a lead
2.10.1 All kinds of soil
2.10.1.2 Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia metre 75 75 352.15 0.00 26411.25 0.00
7.02 1.1 Excavation for all types and sizes of foundations, trenches and drains
or for any other purpose including disposal of excavated stuff upto
1.5 m lift and lead upto 50m (at least 5m away from the excavated
area), including dressing and leveling of pits.
1.1.1 In all types of soils. cum 18 18 220.15 3918.67 0.00
7.03 DSR 2023 19.6 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes
with collars jointed with stiff mixture of cement mortar in the
proportion of 1:2 (1 cement : 2 fine sand) including testing of joints
etc. complete :
For storm water pipe
7.04 DSR 2023 19.3 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse
sand : 10 graded stone aggregate 40 mm nominal size) up to
haunches of RCC. pipes including bed concrete as per standard design
7.05 20.7 Constructing brick masonry manhole with well burnt modular clay
bricks crushing strength not less than 35kg/cm2 in cement mortar 1:4
( 1 cement : 4 coarse sand), R.C.C. top slab with 1:2:4 mix (1 cement :
2 coarse sand : 4 graded stone aggregate 20 mm nominal size),
foundation in cement concrete 1:4:8 mix (1 cement : 4 coarse sand :
8 graded stone aggregate 40mm nominal size) inside plastering
12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand)
finished with floating coat of neat cement and making channels in
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20mm nominal size) finished with a floating coat of neat
cement complete as per standard design :
20.7.1 Inside size 90x80 cm and 45 cm deep including C.I. cover with frame Each 4 4 7976.57 31906.28 0.00
(light duty) 455x610 mm internal dimensions total weight of cover
and frame to be not less than 38 kg (weight of cover 23 kg and weight
of frame 15 kg) :
7.06 20.8 Extra for depth for manholes:
Digitally signed by Rakesh
DETAILED PLUMBING ESTIMATE
SI.No. DSR-2023/ Description of Item UNIT MEDICAL STORE TOTAL SSR RATE DSR RATE NS RATE SSR AMOUNT DSR AMOUNT NS AMOUNT
NON DSR QUANTITY
7.07 19.9 Providing and constructing brick masonry circular arch type manhole
upto 1.67m depth, 0.91m internal dia at bottom and 0.56m dia at top
having brick masonry wall 190mm thick with well burnt modular clay
bricks crushing strength not less than 35kg/cm2 in cement mortar 1:4
(1 cement : 4 coarse sand), in side cement plaster 12 mm thick with
cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating
coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3
coarse sand : 6 graded stone aggregate 40mm nominal size), and
making necessary channel in cement concrete 1:2:4 (1 cement : 2
coarse sand : 4 graded stone aggregate 20mm nominal size) finished
with a floating coat of neat cement, providing and fixing S.F.R.C.
cover and frame (heavy duty, HD- 20 grade designation) 560mm
internal diameter conforming to I.S. 12592, total weight of cover and
frame to be not less than 182kg, in cement concrete 1:2:4 (1 cement
: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) all
complete as per standard design (excavation and foot rests shall be
paid for separately) :
7.08 20.10 Providing and constructing extra depth for circular type manhole Meter 2.0 2 3602.13 7204.26 0.00
0.91m internal dia (at bottom) beyond 0.91m and upto 1.67m
7.09 11.2 Providing and making 12mm thick cement plaster of mix:
11.2.1 In cement Mortar 1:3 (1 cement : 3 fine sand) Sqm 20 20 136.85 2668.58 0.00
7.10 20.12 Providing orange colour safety foot rest of minimum 6 mm thick Each 18 18 203.49 3662.82 0.00
plastic encapsulated as per IS : 10910, on 12 mm dia steel bar
conforming to IS: 1786, having minimum cross section as 23 mmx25
mm and over all minimum length 263 mm and width as 165 mm with
minimum 112 mm space between protruded legs having 2 mm tread
on top surface by ribbing or chequering besides necessary and
adequate anchoring projections on tail length on 138 mm as per
standard drawing and suitable to with stand the bend test and
chemical resistance test as per specifications and having
manufacture's permanent identification mark to be visible even after
fixing, including fixing in manholes with 30x20x15 cm cement
concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
7.11 20.26.1 Providing and constructing brick masonry road gully chamber Each 7 7 3583.09 25081.63 0.00
45x45x77.5 cm with well burnt modular clay bricks crushing strength
not less than 35kg/cm2 in cement mortar 1:4 (1 cement : 4 coarse
sand ) with precast R.C.C. vertical grating complete as per standard
7.12 20.19 Making connection of drain or sewer line with existing manhole
including breaking into and making good the walls, floors with
cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) cement plastered on both sides with
cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating
coat of neat cement and making necessary channels for the drain etc.
20.19.1 For pipes 100 to 230 mm diameter Each 2 2 246.33 492.66 0.00
TOTAL FOR EXTERNAL STORM WATER WORK 106035.00 170164.00 0.00
ALL SUB-HEAD TOTAL 288917.00 254619.00 75286.00
GRAND TOTAL 618822.00
GRAND TOTAL 618822.00
Digitally signed by Rakesh
PACKAGE - INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
S.No SSR 2015/DSR Description Unit TOTAL QTY RATE SSR-2015 RATE DSR- MARKET AMOUNT SSR AMOUNT DSR AMOUNT MR
2022/ MR E&M 2022 RATE
1.00 DSR E&M 2022 Supplying, installation, testing and commissioning of electric driven terrace pump
18.4 suitable for automatic operation and consisting of following, complete in all respects,
as required: (Terrace Pump)
(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body &
bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520
b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415
volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal
foot mounted type with Class-'F' insulation, conforming to IS-325.
(c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts
etc.as required.
(d) Suitable cement concrete foundation duly plastered and with anti vibration pads.
2.0 23.32 Supplying and fixing 2 way Fire Brigade Connection of cast iron body with 2 Nos. Gun Each 1 10956.33 10956.33 0.00 0.00
metal male instantaneous inlet couplings complete with cap and chain conforming to
IS: 904 including connection to existing MS pipe line complete as required.
3.00 23.11 Providing and fixing pressure switch with suitable for 1-10 Kg/cm2 including 12/15 mm Each 2 1491.07 2982.14 0.00 0.00
Ø isolation valve, G.I. nipple, elbow, electrical connections setting of Cut-In and cut-Off
pressure complete in all respects and in an approved manner.
4.00 23.18 Supplying and fixing single headed internal hydrant valve with instantaneous Gun Each 4 7995.61 31982.44 0.00 0.00
metal couplings of 63 mm dia with cast iron wheel ISI marked conforming to IS: 5290
(Type - A) with blank Gunmetal cap and chain as required
5.00 23.24 Supplying & fixing 63 mm dia Stainless Steel IS: 3444 Grade-1 branch pipe with 20 mm Each 4 3549.77 14199.08 0.00 0.00
dia (nominal internal) Gun Metal nozzle conforming to IS: 903, suitable for
instantaneous coupling connection to connect hose pipe coupling as required.
6.00 23.22 Supplying and fixing 63 mm dia, 15 mtr long RRL hose pipe with 63 mm dia Male and Each 8 4197.13 33577.04 0.00 0.00
Female Stainless Steel-IS: 3444 Grade-1 couplings duly binded with GI wire, rivets etc.
conforming to IS: 636 (Type -A) as required.
7.00 23.14 Supplying and fixing swinging type First-Aid Hose Reel drum with MS construction spray Each 4 5247.90 20991.60 0.00 0.00
painted in Post office Red colour, conforming to IS: 884 with upto date amendments,
complete with brackets for fixing on wall, connections from riser with 25 mm dia MS/GI
pipe and GM gate valve but excluding hose reel.
8.00 23.16 Supplying and fixing 19mm dia 30 metre long high pressure polypropylene First-Aid Each 4 2303.84 9215.36 0.00 0.00
8.00 23.1 Supply, erection, jointing, testing & commissioning of "C" Class MS pipes (as per IS:
1239) including necessary specials such as tees, bends, flanges reducers etc., complete
on wall/ ceiling. The pipes to be erected on wall or suspended from beams, RCC roof
slabs with suitable size MS bars/ angle irons including painting of metal part except
9.00 23.2 Painting for M.S. pipe with a coat of red oxide primer and two or more coats of
synthetic enamel paint of approved colour and Quality to give an even shade including
surface preparation.
10.00 23.3 Providing and wrapping 4 mm thick of approved make and quality bitumen based anti
rust felt over MS pipe with overlap of 25 mm to make an impermeable layer including
painting with one coat of bitumastic paint before felt complete. (Only on MS pipe to be
laid in soil below ground).
9.00 DSR E&M 2022 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe
18.7 conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees,
flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with
suitable clamp/support frame and painting with two or more coats of synthetic
enamel paint of required shade complete as required :
9.00 23.5 Supplying, fixing, testing and commissioning of flanged butterfly valve PN 1.6, with
Bronze/Gunmetal seat duly ISI marked complete with Nuts, Bolts, washers, gaskets,
conforming to IS: 13095 of following sizes as required.
10.00 23.4 Providing, installation, testing and commissioning of dual plate non-return valve of
following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts,
washers etc. as required.
11.00 23.7 Providing and fixing brass GM/ ball valve (full bore type) with plastic coated lever and
screwed female ends tested to 20 Kg/ cm2 of approved quality as specified.
12.00 DSR E&M 2022 Providing, installation, testing and commissioning of stainless steel Y-strainer
18.15 fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia
holes with stainless steel flange.
13.00 23.12 Supplying and installing pressure gauge of 100 mm Ø ., 0-300 PSI or 0-21 kg per cm Each 6 892.50 5355.00 0.00 0.00
square fitted with 12/15 mm Ø . pad cock valve, and G.I. pipe, elbow etc. as per
requirement in approved manner
14.00 23.36 Supplying and installing Air Vessel of 300 mm dia, 1.5m in height made of 5mm thick Set 1 15631.84 15631.84 0.00 0.00
MS sheet including painting with one primer and two finish coats complete as per
15.00 14.18 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as Metre 90 44.63 4016.70 0.00 0.00
16.00 20.1 Supplying and installing following size powder coated, perforated M.S. cable trays with
perforation not more than 17.5% rigidly suspended from the ceiling with M.S.
suspenders at a distance not more than 2.5 metre and near every junction/ joint etc
complete as required.
a) 20.1.2 150 mm width X 50 mm depth X 1.6 mm thickness Metre 30 408.17 12245.10 0.00 0.00
FF 222 Digitally signed by Rakesh
PACKAGE - INTERNAL & EXTERNAL FIRE FIGHTING SYSTEM
S.No SSR 2015/DSR Description Unit TOTAL QTY RATE SSR-2015 RATE DSR- MARKET AMOUNT SSR AMOUNT DSR AMOUNT MR
2022/ MR E&M 2022 RATE
17.00 14.17 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections Metre 50 141.61 7080.50 0.00 0.00
etc. as required.
18 23.25 Supplying and fixing of MS hose cabinet box of made of 2 mm thick MS sheet and 40 x
40 x 5mm angle iron with front openable cover having 6 mm thick glazed glass viewing
window i/c necessary locking arrangement, on existing wall/ brick platform etc
complete as required.
19.00 23.33 Providing and fixing standard fireman's axe (tested for 20000 Volts) with heavy Each 4 2897.65 11590.60 0.00 0.00
insulated rubber handle. (ISI marked)
20.00 23.9 Providing and fixing gunmetal single acting air release valve with screwed inlet 25 mm Each 1 1339.94 1339.94 0.00 0.00
dia and with necessary G.I. coupling, valve to be fitted on top of Air vessel or on wet
riser as per specification.
21.00 MR-1 Providing and fixing reinforced neoprene rubber vibration eliminators / expansion
joints (to provide relief from stresses at pipe flanges) suitable for upto 20 kg/cm2
pressure, complete as per specification.
22.00 17.1 Supplying and laying following sizes one number PVC insulated/ XLPE, PVC sheathed,
steel armoured, aluminium conductor power cable of 1.1 KV grade direct in ground
including excavation, sand cushioning, protective covering and refilling the trench etc
23.00 MR-2 Supply, installation, testing and commissioning ISI marked (IS:15683) Fire Extinguisher, Each 7 6190.00 0.00 0.00 43330.00
Carbon-di-oxide type capacity 4.5 Kg. Flat base including valve, discharge hose of not
less than 10 mm dia, 1M long and complete in all respects including initial fill with CO2
gas conforming to IS:307-1966 and walll suspension braket as required as per
specifications.
24.00 MR-3 Supply, installation, testing and commissioning of 6kg ABC (Powder Type) Fire Each 4 3348.00 0.00 0.00 13392.00
Extinguisher. Mild Steel Cylinders ISI marked fitted with pressure indicating gauge,
internal tube, squeeze lever type valve fully charged with ABC 90 powder (Mono
Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall
suspension bracket and conforming to IS:15683 as required as per specifications.
25.00 MR-4 Providing, fixing, testing and commissioning of control panel for Terrace Booster Each 1 77790.00 0.00 0.00 77790.00
Incoming: MCCB 35A 1 set of Phase indicating lamps, 2 set of 35A Al bus bars, 1No
Ammeter, 1No Voltmeter with phase selector switch Feeder for Booster Pumps - 2 No.
2 No. 32A TP MCCB without releases. DOL starter with over load relay, single phase
preventor and indicating lamps with ON/OFF push buttons. 2 No. Automanual selector
switch. Suitable for booster pumps
26.00 MR-5 Supply & Installation of PESO approved & UL Listed seamless 180 Ltr Cylinder (IS 7285)
assembly with 65- Degree CP Gauge. Clean Agent Fire Suppression System FK-5-1-12
for following room complete with activation control panel, at 70 bar pressure with
pressure gauge, safety burst filled with FK-5-1-12 at 4.5% concentration. Discharge
time should be less than 10 seconds pipe work, heads, valves, control equipment, 2
zone gas release panel, smoke Detector, cables, Hooter, abort switch, manual release
switch, nozzles, all necessary discharge accessories, Electrical actuator, Manual
actuator, Discharge Hose, NRV, Pneumatic Actuator, cylinder clamp and fittings.
Cylinder & valve must have PESO approval. The price shall cover all manpower,
material, piping, fittings, installation etc.
GRAND TOTAL 19125548
GRAND TOTAL 19125548
FF 223 Digitally signed by Rakesh
BILL OF QUANTITIES FOR HVAC SYSTEM
S.No. DSR E&M Description Unit Qty Rate Amount
Supply, Installation, Testing & Commissioning (referred to as
"SITC" here after) of following Equipment; Materials &
Accessories as per specifications including supply,
installation, testing & commissioning of any materials &
accessories required to make the system complete in all
1 MR INLINE FANS:
1.1 Supply, installation, testing and commissioning of
Circular/rectangular Inline exhaust fan with blower and motor.
Motor suitable for continous operations. Casing shall be in sheet
metal as per specifications. The motor shall be suitable for 220 V,
Single Phase, 50 Hz AC supply. The price shall include fan speed
regulator and cowl with bird screen. The electrical wiring from
socket to fan considering 3 m distance between socket and fan.
Motor shall be IP-44 enclosure & complete with motor protection
through built in thermal contact with class F insulation.
Sound level shall not be more than 55dB @3 mtr & Static
pressure = 15 mm.
a) Capacity: 300 CFM Set 2 10000 20000
2 MR AIR COOLED DX TYPE DUCTABLE / HIGH WALL SPLIT TYPE
SPLIT UNITS WITH GREEN REFRIGERENT (NON INVERTER
Supply, Installation,Testing & Commissioning of DX AIR
COOLED DUCTABLE TYPE SPLIT UNITS consisting of outdoor
unit (having compressor condenser coils with fan and motor),
indoor unit (having evaporator coil, filter,fan with motor), cordless
remote, interconnecting, fixing frame for indoor and outdoor unit,
drain piping up to nearest drain point, piping support, Stablizer for
High wall Split AC ,etc. and all other accessories for system
completeness and installation at site as per specifications and
site requirement.
a) Capacity: 2.0 TR / Single phase (High Wall Split AC with Set 9 53000 477000
b) Capacity: 3.0 TR / Three phase (DX ductable Split AC) Set 3 82500 247500
c) Capacity: 11.0 TR / Three phase (Single circuit DX ductable Split Set 16 235000 3760000
3 MR Floor Mounted Tower AC
Supply, Installation,Testing & Commissioning of DX Air cooled
Floor mounted type Tower AC consisting of outdoor unit (having
compressor condenser coils with fan and motor), indoor unit
(having evaporator coil, filter,fan with motor), cordless remote,
interconnecting, fixing frame for indoor and outdoor unit, drain
piping up to nearest drain point, piping support, Stablizer,etc. and
all other accessories for system completeness and installation at
site as per specifications and site requirement.
a) Capacity: 4.0 TR / Three phase Set 3 110000 330000
4 MR REFRIGERANT COPPER PIPING
Supply, Installation,Testing & Commissioning of copper
refrigerant piping complete with copper fittings & charge of
refrigerant gas for the above split units. Piping associated with
DX units to be insulated with 9mm thick closed cell elastomeric
insulation with class 'O' fire retardant properties in tubing form
(K flex / Supreme / Paramount) as required. Piping shall be laid
over duly painted slotted angle trays fixed with GI clamps.
Quoted Price shall be inclusive of UV protection paint for
all exposed pipes of approved make .Price shall be inclusive
of copper piping circuit with insulated sleeves from indoor
to outdoor unit as required.
Pair of Soft refrigerant piping (per Circuit) for Split / Ductable
packages with compressor & minimum thickness of pipe is 0.7
Digitally signed by Rakesh
S.No. DSR E&M Description Unit Qty Rate Amount
a) Capacity: 2.0 TR (High Wall Split AC) RMT / Ckt 150 1300 195000
b) Capacity: 3.0 TR (DX ductable Split AC) RMT / Ckt 50 1500 75000
c) Capacity: 4.0 TR (DX Tower Split AC) RMT / Ckt 50 1700 85000
d) Capacity: 11.0 TR (Single circuit DX ductable Split AC) RMT / Ckt 250 2000 500000
5 MR RIGID cPVC Drain piping with P type trap
Supply & installation of Rigid PVC piping complete with P type
trap fittings, supports as per specifications and duly insulated with
9mm thick closed cell nitrile rubber insulation.
6 MR Angle iron stand installation
Supply & installation of Angle iron Stand with Eproxy paint all
accessories for DX Units
a) Capacity: 2.0 TR (High Wall Split AC) Nos 9 1250 11250
b) Capacity: 3.0 TR (DX ductable Split AC) Nos 3 2500 7500
c) Capacity: 4.0 TR (DX Tower Split AC) Nos 3 3500 10500
d) Capacity: 11.0 TR (Single circuit DX ductable Split AC) Nos 16 8500 136000
7 MR Electrical control cable
Supply & installation of control cum transmission wiring for
copper in suitable conduit between Indoor and Outdoor unit and
for remote control insulation.
a) Capacity: 2.0 TR (High Wall Split AC) RMT / Ckt 165 195 32175
b) Capacity: 3.0 TR (DX ductable Split AC) RMT / Ckt 60 225 13500
c) Capacity: 4.0 TR (DX Tower Split AC) RMT / Ckt 60 235 14100
d) Capacity: 11.0 TR (Single circuit DX ductable Split AC) RMT / Ckt 275 250 68750
8 MR Auto timer cycling Sequencing of Ductable / Split units:
Supply, Installation , Testing and Commissioning of
Auto timer cycling Sequencing of Split units with controller
along with enclosure/accessories as per requirement for
sequenced Start/Stop for following split units :
a) Two number DX units including one standby Sets 9 30000 270000
DELHI SOR DUCTING, GRILLS, DIFFUSER AND INSULATION:
9 16.12.1 Supply, installation, balancing and commissioning of factory
fabricated GSS sheet metal rectangular/round ducting complete
with neoprene rubber gaskets, elbows, splitter dampers, vanes,
hangers, supports etc. as per approved drawings and
specifications of following sheet thickness complete as required.
a) 16.12.1.1 Thickness 0.63 mm sheet sq m 500 1148.04 574020
10 16.12.2 Supply, installation, balancing and commissioning of fabricated at
site GSS sheet metal rectangular/round ducting complete with
neoprene rubber gaskets, elbows, splitter dampers, vanes,
hangers, supports etc. as per approved drawings and
specifications of following sheet thickness complete as required.
11 16.13 Supply, installation, testing and commissioning of GI volume sq m 20 7489.90 149797.96
control duct damper complete with neoprene rubber gaskets,
nuts, bolts, screws linkages, flanges etc, as per specifications
12 16.15 Supplying & fixing of powder coated extruded aluminium Supply sq m 6 9678.62 58071.69
Air Grills with aluminium volume control dampers as per
specifications.
Digitally signed by Rakesh
S.No. DSR E&M Description Unit Qty Rate Amount
13 16.16 Supplying & fixing of powder coated extruded aluminium Return sq m 6 6282.33 37693.98
Air Grills with louvers but without volume control dampers
complete as required.
14 16.17 Supplying, fixing testing commissioning of supply air diffusers of sq m 6 12951.59 77709.552
powder coated aluminium with aluminium volume control
dampers with anti smudge ring & removable core.
15 16.18 Supplying, fixing testing commissioning of Return air diffusers of sq m 8 8632.62 69060.984
powder coated aluminium without volume control dampers with
anti smudge ring & removable core.
16 16.19 Supply, installation, testing & commissioning of thermal insulated
flexible duct of following sizes duly supported at regular interval
as per site requirement etc. complete as required as per
specifications.
17 16.21 Supply and fixing of acoustic lining of supply air duct and plenum sq m 225 752.60 169335.9
with 25 mm thick resin bonded glass wool having density of 32
kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600
mm centre to centre covered with Reinforced Plastic tissue paper
and 0.5 mm thick perforated aluminum sheet fixed to inside
surface of ducts with cadmium plated nuts, bolts, stick pins,
CPRX compound etc. complete as required and as per
specifications.
18 16.23 Supplying and fixing of following thickness duly laminated
aluminum foil of mat finish closed cell Nitrile rubber (Class "O")
insulation on existing duct after applying suitable adhesive for
Nitrile rubber. The joints shall be sealed with 50 mm wide and 3
mm thick self adhesive nitrile rubber tape insulation complete as
per specifications and as required.
Make: Supreme / K-Flex / Aerolam
19 4.1 Supplying and installing following size of perforated painted with
powder coating M.S. cable trays with perforation not more than
17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with M.S. suspenders including bolts
& nuts, painting suspenders etc as required.
Make: Slotco / Legrand / MEM
a) 4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness RM 250 642.05 160513
b) 4.1.3 200 mm width X 50 mm depth X 1.6 mm thickness RM 100 732.41 73240.7
c) 4.1.6 450 mm width X 50 mm depth X 2.0 mm thickness RM 30 1208.63 36258.93
d) 4.1.7 600 mm width X 50 mm depth X 2.0 mm thickness RM 100 1452.06 145205.8
20 MR FLEXIBLE CANVASS CONNECTIONS
Supply, Installation, Testing of 125mm deep antivibration flexible Nos 21 2500 52500
joints. Flexible connections shall be constructed using imported
fire retardant fabric with extruded GI frame/flange on both
21 MR UNDERDECK INSULATION
Providing & Fixing thermal insulation of ceiling under deck sq m 375 1500 562500
insulation Aero cell nitrile insulation sheet of thickness 25 mm
meet class O as per BS-476 part 6 & class 1 as per BS476 part
7, density 50+/- 20% kg/m3 & temperature range -40 deg C to
105 deg C fixed to ceiling with metallic cleats (50x50x3mm) @ 60
cm at various elevations with rawl plugs including clips. All
complete as per direction by Engineer in charge.
22 Note: Scope should be part of HVAC BOQ
Digitally signed by Rakesh
S.No. DSR E&M Description Unit Qty Rate Amount
The supplied shall guarantee the material, workmanship and
satisfactory performance of all equipments, and the system too,
as per requirements indicated by the employer and as per
specifications furnished by the supplier. The guarantee of the
complete air-conditioning system for a minimum period of one
year from the date of successful commissioning. The bidder shall
guarantee the performance of the system under peak load
Any defect found during the guarantee period shall be rectify and
defective parts shall be replaced at no extra cost to the employer.
Guarantee test if required in the case shall be repeated with new
parts at no extra cost to the period to ensure trouble free
operation of system.
AC Contractors should visit the site before submission of HVAC
The Contractor Bill shall be given as per actual measurement
All material must be approved by the Consultant/Client technical.
GST will be paid extra as applicable, all others taxes levies etc. to
The contractor to ensure that all waste and debris is collected
and satisfactorily disposed off from site.
All shop drawings will be made on Autocad as per Site
The AC Contractor shall be Authorised dealer partner of
It is the responsibility of the air conditioning contractor to ensure
that the new system works properly.
TOTAL SUMMARY 99,03,053
Digitally signed by Rakesh
PROJECT- CMS BHILAI - ELECTRICAL & ELV BOQ
SCHEDULE OF QUANTITIES
SUMMARY OF PRICES
AMOUNT CG AMOUNT AS AMOUNT AS
S.NO. DESCRIPTION OF ITEMS
SOR PER DSR MR
1 ELECTRICAL & ELV SCOPE
A. POINT WIRING AND SUBMAINS 8,00,750.60 2,95,310.00 37,500.00
B. CABLES & CABLE TRAYS ,RACEWAY 2,89,824.50 0.00 14,50,000.00
C. DISTRIBUTION BOARDS 2,43,916.68 0.00 0.00
D. LIGHT FIXTURES 0.00 0.00 9,46,590.00
E. EARTHING SYSTEM 1,83,211.52 0.00 65,000.00
G. DISTRIBUTION BOARDS & PANELS 0.00 0.00 7,95,000.00
H. SAFETY AND FIRE PROTECTION EQUIPMENTS 0.00 0.00 45,500.00
I. FIRE ALARM AND DETECTION SYSTEM 8,62,513.19 46,452.00 95,500.00
J. CCTV SYSTEM (IP BASED) 19,76,632.84 0.00 3,79,250.00
K. DATA, VOICE & TV CABLING 27,785.37 0.00 3,01,925.00
Digitally signed by Rakesh
SCHEDULE OF QUANTITIES FOR ELECTRICAL SYSTEM
RATE AS PER CG AS PER
Electrical AS MR
S.No. SOR Description of work Unit QTY
A POINT WIRING AND SUBMAINS
Wiring for light/fan point/ exhaust fan point/ call bell point with 1.5sqmm
FRLS PVC insulated copper conductor single core cable in surface/
1 1.70 recessed steel conduit, with modular switch, modular plate, suitable GI box
and earthing the point with 1.5sqmm FRLS PVC insulated copper
conductor single core cable etc as required.
Wiring for light /power plug with 2X4 sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed steel conduit along with 1
No 4 sq. mm FRLS PVC insulated copper conductor single core cable for
loop earthing as required.
Wiring for group controlled (looped) light/fan point/ exhaust fan point/ call
bell point (without independent switch etc.) with 1.5sqmm FRLS PVC
3 DSR 1.54 insulated copper conductor single core cable in surface/ recessed steel
conduit, earthing the point with 1.5sqmm FRLS PVC insulated copper
conductor single core cable etc as required.
Wiring for circuit/ submain wiring along with earth wire with the following
4 1.13 sizes of FRLS PVC insulated copper conductor, single core cable in
surface/ recessed steel conduit (included ) as required
a 1.13.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Meter 267 182 48653
b 1.13.6 2 X 4.0 sq. mm + 1 X 4.0 sq. mm earth wire Meter 75 238 17850
c 1.13.7 2 X 6 sq. mm + 1 X 6 sq. mm earth wire Metre 50 240
d 1.13.8 2 X 10 sq. mm + 1 X 6 sq. mm earth wire Metre 50 342
e 1.13.12 4 X 4 sq. mm + 2 X 4 sq. mm earth wire Metre 50 174 8687
Supplying and fixing of following sizes of steel conduit along with
accessories in surface/recess including painting in case of surface conduit,
or cutting the wall and making good the same in case of recessed conduit
Supplying and fixing following modular switch/ socket on the existing
6 7.40 modular plate & switch box including connections but excluding modular
plate etc. as required.
a 7.4.1 5/6 amps switch Each 41 2142 87822
b 7.4.4 15/16 amps switch Each 32 114 3656
c 7.4.5 3 Pin 5/6 amps socket outlet Each 53 104 5487
d 7.4.6 6 pin 15/16 amp socket outlet Each 32 150 4798
Supplying and fixing following size/ modules, GI box alongwith modular
7 6.40 base & cover plate for modular switches in recess etc as required. (GI box
thickness shall be 1.6mm)
a 6.4.1 1 or 2 Module (75mmX75mm) Each 0 88 0
b 6.4.2 3 Module (100mmX75mm) Each 50 132 6605
c 6.4.4 6 module ( 200mmX75mm) Each 0 161 0
d 6.4.5 8 Module (125mmX125mm) Each 15 238 3570
e 6.4.6 12 Module (200mmX150mm) Each 0 273 0
Supplying & fixing suitable size GI box wih modular plate and cover in front
on surface or in recess including providing and fixing 25A modular socket
outlet and 25 A modular SP MCB "C" curve including connections, painting
etc. as required.
1200mm dia High speed Ceiling fan, 5 Star rating with down rod & regulator
etc, Make_Havells/Crompton etc
Supplying & laying Inner and outer plain surface high density poly ethylene
(HDPE) pipe (PE 63 Grade & PN4) confirming to IS : 4984 latest as on date,
10 M.R. complete with necessary fitting for protection of 1.1 KV Grade U.G. cable at a depth
as shown in Drawing but not more than 750MM including excavation, digging
trenches, dismantling of road if required and refilling the trench etc as required.
Make- Sudhakar/ Dura-line / Supreme/ BEC
a 180/152mm-outer dia/inner dia Meter 150 250 37500
TOTAL FOR POINT WIRING AND SUBMAIN 0 8,00,751 2,95,310 37,500
B CABLES & CABLE TRAYS ,RACEWAY
Supply, loading, transportation unloading at site, storages at site ,shifting
from storage place to site, installation of following sizes of XLPE insulated
1 M.R. PVC sheathed, Aluminium/copper galvanized steel round wire/ flat strip
armoured cable armoured power cable of 1.1 KV grade conforming to IS
amended upto date and as per specifications.
b 4 C x 25 Sqmm Cu Metre 1100 550 605000
Digitally signed by Rakesh
RATE AS PER CG AS PER
Electrical AS MR
S.No. SOR Description of work Unit QTY
c 4 C x 16 Sqmm Cu Metre 150 450 67500
d 4C x 6 sqmm Cu Metre 1200 350 420000
e 3C x 6 sqmm Cu Metre 25 300 7500
f 1 C x 6 Sqmm Cu flexible cable for UPS earthing Metre 40 150 6000
Supplying and making indoor end termination with brass compression
2 17.24 gland and copper lugs for following size of XLPE insulated and PVC
sheathed / XLPE aluminium conductor cable of 1.1kV grade as required.
f 17.24.21 1 C x 6 Sqmm Cu flexible cable for UPS earthing Each 4 114 457
Providing and fixing of fire retardant sealant on wall / floor
crossings/Manholes.
Supplying and installing following size of perforated Hot Dipped Galvanised
Iron cable tray (galvanisation thickness not less than mininmum 70
microns) with perforation not more than 17.5%, in convenient sections,
joined with connectors, suspended from the ceiling with G.I. suspenders
including G.I. bolts & nuts, bends, reducers, tee etc. as required.
a 20.1.1 150 mm width X 50 mm depth X 1.6 mm thickness Metre 200 349 69734
b 20.1.4 300 mm width X 50 mm depth X 1.6 mm thickness Metre 300 587 176001
20.2 Supplying and fixing of following sizes powder coated, perforated, M.S.
cable trays bends (horizontal) turning at 900 in same plane with perforation not
more than 17.5% rigidly jointed with cable tray etc. complete as required.
20.2.1 100 mm width X 50 mm depth X 1.6 mm thick Each 10 464 4641
20.2.4 300 mm width X 50 mm depth X 1.6 mm thick Each 10 1210 12102.3
20.3 Supplying and fixing of following sizes vertical, powder coated, perforated,
M.S. cable trays bends (vertical) turning at 900 in another plane with perforation
not more than 17.5% rigidly jointed with cable tray etc. complete as required.
20.3.1 100 mm widthX50 mm depthX1.6 mm thick Each 10 211 2106.3
20.3.4 300 mm widthX50 mm depthX1.6 mm thick Each 10 495 4950.4
5 GI Raceway & Junction boxes
Providing and fixing of race way made from minimum 1.6 mm thick pre-
galvanised steel sheet, factory fabricated, with internal partition of the
following sizes including providing removable double folded cover of 1.6mm
thick upto 150mm wide raceway and 2mm thick above 150mm wide
raceway, knock out holes and fixing accessories earthing stud for
5.1 terminating 8 SWG copper earth wire complete as required including floor
supports, bends, access boxes, tap off boxes and cross over as per site
requirement. (underfloor / wall mounted recovery & junction boxes
shall be 1.6 mm thick). The pre-galvanised sheet shall be as per IS 277 or
BS 2989 having tensile strength of minimum 500 N/sq.m. and minimum
zinc coating of 275 GSM.
a M.R. 150 mm wide x 40 mm deep RM 100 650 65000
b M.R. 100 mm wide x 40 mm deep RM 80 450 36000
Providing of 2 mm thick pregavanised sheet outlet junction box including
providing cover with provision to adjust overall height, knock outs on four
sides to accept raceways of specified sizes and cutouts to fix required
outlets for following size of race ways.
a M.R. 200 mm wide x 40 mm deep No. 20 700 14000
b M.R. 150 mm wide x 40 mm deep No. 20 500 10000
5.3 Providing and fixing of PVC raceway
TOTAL OF CABLES & CABLE TRAYS ,RACEWAY 2,89,825 - 14,50,000
C DISTRIBUTION BOARDS
11.8 Supplying and fixing following way,horizontal type three pole and
neutral,sheet steel,MCB distribution board, 415 Volts, on
surface/recess,complete with tinned copper busbar,neutral busbar,earth
1 bar,din bar,interconnections, powder painted including earthing , numbering
etc. as required. (But without MCB/RCCB/Isolator)
Digitally signed by Rakesh
RATE AS PER CG AS PER
Electrical AS MR
S.No. SOR Description of work Unit QTY
a 11.8.6 6way (4+18), Double door Each 6 9526 57156
b 11.8.7 8way (4+24), Double door Each 3 10442 31327
Supplying and fixing following way,horizontal type Single pole and
neutral,sheet steel,MCB distribution board, 240 Volts, on
surface/recess,complete with tinned copper busbar,neutral busbar,earth
bar,din bar,interconnections, powder painted including earthing , numbering
etc. as required. (But without MCB/RCCB/Isolator)
Supplying and fixing 5 amps to 32 amps, rating, 240/415 volts, 'C' Curve ,
miniature circuit breaker suitable for inductive load of following poles in the
2 11.11 existing MCB DB complete with connections, testing and commissioning
etc. as required.
a 11.11.2 Single Pole Each 216 183 39584
b 11.12.3 Double Pole Each 3 509 1528
Supplying and fixing following rating, double pole, (single phase and
neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity
3 11.20 current 30 mA in the existing MCB DB complete with connections, testing
and commissioning etc. as required.
Supplying and fixing of following rating, four pole , 415 volts,MCB in the
4 11.21 existing MCB DB complete with connections, testing and commissioning
etc. as required.
TOTAL FOR DISTRIBUTION BOARDS 0 2,43,917 - -
E EARTHING SYSTEM
Supplying and laying 25 mm X 5 mm copper strip including connection/
terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be
1.0 14.90 done by overlapping and with 2 sets of brass nut bolt & spring washer Metre 50 666 33320
spaced at 50mm).
Supplying and laying 25 mm X 5 mm GI strip including connection/
terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be
done by overlapping and with 2 sets of brass nut bolt & spring washer
spaced at 50mm).
3.0 14.18 Providing and Fixing 6 SWG GI wire for DBs etc wherever required RM 300 45 13389
Supply, Installation, Testing & Commissioning of UL listed, CPRI Tested
maintenance free copper coated earth rod of 3 metre having diameter of 25mm
with 250 micron copper coating with clamp made of stainless steel or gun metal for
4.0 14.20.1 terminating cable / flat conductor. Rod shall be short circute tested from CPRI for Nos. 8 14103 112822
minimumof 85 kA peak. Earth enhancing mineral (PROCEM) compound shall be
non-bentonite 25 kg tested for Leaching & TCLP with NABL accredited lab.
Supplying and laying 50 mm X 6 mm GI strip including connection/
terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be
done by overlapping and with 2 sets of brass nut bolt & spring washer
spaced at 50mm).
Rates shall also include the following :
All fixing accessories such as brass saddles, brass screws raw plugs etc.
Jointing by rivetting and brazing after rivetting in case of copper and
welding / bolting in case of GI earthing.
3 Cutting chases holes and making good the same wherever required.
4 Effecting adequate and proper interconnections.
5 Use of copper thimbles.
6 Earthing system shall comply to IS:3043-1987.
7 All earthing pits shall be interconnected.
The systems is conforming to IS 3043, IS / IEC 62305, IEC 61643-5-54, UL
467, the rod has to be tested to for dimension, marking, tensile strength,
salt mist, coating thickness, electrical resistivity test before and after
corresion test etc as per IEC 62561-2. including Heavy Duty chamber with
cover made on polypropylene material with tested to carry 5000 Kg with
pulling hook size approx 300x300 mm.
Note:-Where the earthing pit is to be made if it is of poor resistivity of the
area. So backfilling of natural soil will be required to obtain the required ohm
9 value. The cost will be included in this item. If the contactor wants to test the
resistivity value at site, he can do it but the resultant value should not exceed
one ohm for minimum 3 years.
TOTAL FOR EARTHING SYSTEM CARRIED TO SUMMARY 0 1,83,212 - 65,000
Digitally signed by Rakesh
RATE AS PER CG AS PER
Electrical AS MR
S.No. SOR Description of work Unit QTY
SITC of 5 kVA 1 phase IN & 1 phase Output online UPS with 30 mins back
up. The non-redundant UPS shall comprise a solid state rectifier/ battery
1 M.R. charger, battery, a solid state inverter, static switches and stand-by Nos 1 3,75,000 375000
regulated AC supply, battery racks etc .
TOTAL FOR UPS CARRIED TO SUMMARY - - 3,75,000
G DISTRIBUTION BOARDS & PANELS
DISTRIBUTION PANELS
1.0 M.R. Main LT Panel
1 No. 800 amps 4 pole ACB EDO with O/L, S/C, inbuilt E/F Protection
1 No. Digital Multi-function meter with RS 485 communication port of
accuracy class-1 model no Rish master 3440 or equivalent
1 set of Breaker ON / OFF / TRIP indicating lights with control MCB’s.
1 set of 0-800 Volt digital voltmeter with selector switch 96 x 96 mm sq.
& phase indicating lamps connected through 415 V √ 3 : 110 V √ 3 PT’s,
Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
1 set of 0-800 Amps digital electronic ammeter with selector switch with 3
nos. 800/5A, 15VA, CL-1.0 Current Transformer
1 set of ON / OFF / TRIP indicating lights with control MCB’s.
1000 amps TPN aluminium bus bars (35 kA/sec) with coloured heat
shrinkable insulation sleeve.
1 No Surge protection device Type 1 & 2 ( Class B & C), 4 Mode, MOV
type suitable for 8/ 20 µ s surge,Voltage Protection level Up < 1.8kV,
Operating Temperature -40 deg 'c' - +80 deg 'C', Connected Between
3Nos. phase to neutral and 1Nos. neutral to earth with discharge Current
Imax. ≥ 40KA Per mode & In ≥ 20kA per Mode. Make & Model: Argos-AG-
230-40T2-E or eq. SPD with 63A 4P HRC fuses of 100kA breaking
capacity. For connecting SPD minimum 10sqmm copper wire must be used
& length of connecting leads shall not be more than 500mm for per mode
connection with each busbar including all necessary accessories. The SPD
shall complience with IEC 61643-11 and certified by
TUV,CE,ROHS,UL94V-O.
63 amp 4P MCCB(25kA) 3Nos.& 1No.(SPARE)
40amp 4P MCCB(25kA) 01Nos.& 1No.(SPARE)
32 amp 4P MCCB(25kA) 06Nos.& 1No.(SPARE)
63 amp 4P RCBO with overload, short circuit & earth fault protection (25kA)
and 100mA Sensitivity 16Nos.& 1No.(SPARE)
32amp 4P RCBO with overload, short circuit & earth fault protection (25kA)
and 100mA Sensitivity 6Nos.& 1No.(SPARE)
Main LT Panel as described above Set 1 7,50,000 750000
Note:-All outgoing breaker shall have on,off trip indicating lights.
2.0 M.R. UPS Panel
1Nos. 40amps 2 pole MCB (15kA)
1 Set of Digital Multi-function meter with RS 485 communication port of
accuracy class-1
1 Set of Phase indicating lights
1 Set of Breaker ON / OFF / TRIP indicating lights with control MCB’s.
63 amps TPN aluminium bus bars with coloured heat shrinkable insulation
20 amp DP MCB 5Nos. (C Curve)
20 amp DP MCB 2Nos. (C Curve)(spare)
UPS Panel as described above Set 1 45,000 45000
TOTAL OF DISTRIBUTION BOARDS & PANELS - - 7,95,000
H SAFETY AND FIRE PROTECTION EQUIPMENTS
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made
1.0 M.R of mild steel,atleast 2mm thick,and vitreous enamelled white on both Each 1 300 300
sides,and with inscription in single red colour on front side as required.
Supply and fixing suitable size wooden framed covered with glass for Main
2.0 M.R Panel SLD in electrical room as per IE rules fixed to wall as required. Each 1 2,500 2500
Supply and providing ISI marked electrical 1.1 kV grade 3 mm thick anti-
3.0 M.R skid rubber mat, 2 x 1 mtr as per IS:15652-2006 with up to date Each 5 1,700 8500
Digitally signed by Rakesh
RATE AS PER CG AS PER
Electrical AS MR
S.No. SOR Description of work Unit QTY
4.0 M.R ABC type duly refilled 6 Kg & ready to use Each 4 3,800 15200
Providing & fixing Fire Extinguishers as per IS Dry chemical poweder type -
Providing & fixing of 'No Smoking' and 'No Unauthorized Entry' signboards
in English and Hindi, as per IPR- 1970.
TOTAL OF SAFETY AND FIRE PROTECTION EQUIPMENTS - - 45,500
I FIRE ALARM AND DETECTION SYSTEM
Fire Alarm Panel
SITC of Intelligent Analogue Addressable 2 Loop Fire Alarm Control
Panel having the total panel capacity to acomodate 240 Nos. of detector (at
least) & each loop shall have the capacity to accomodate at least 120
detector & 200 devices (or any other combination as per IS 2189). The
panel shall be able to give pin point location of all Fire /fault and Isolation
conditions of addressable units via the address codes.The panel shall have
the capacity of storing upto 4000 events. Further, the panel must be able to
automatically switch ON /OFF respective control module whenever any
1.0 29.1.2 alarm is triggered. The panel should have inbuilt common Alarm, Fault and Nos 1 131278 131278
monitored sounder output. The panel shall have a minimum of 320
Character LCD/ Touch screen display. The panel shall have a built in power
supply of 170 Watts and battery charger. Battery charger shall be able to
charge the system batteries of up to 33AH capacity for 48 hrs back up. The
Panel shall have the capacity of connecting additional 31 panels or Network
terminals using network card, with redundancy in the network. The panel
shall have RS 485 Network Card.
2.0 29.40 Supply, Installation, Testing & Commissioning of repeater panel Nos 1 69128 69128
Supply, Installation, Testing & Commissioning addressable Multi criteria
Supplying, installation, Testing and commissioning addressable response
Supplying, installation, Testing and commissioning of addressable type
fault isolation module, desired and loose circuits between two successive
fault isolators with automatic resetting arrangement (base Model). Ul Listed
Supply, Installation, Testing & Commissioning of Analogue addressable
Manual Call Point (Resettable Type) with inbuilt isolator and LED
indicator, designed for IP44 requirements and approved to operate in
– 10 ° C to +55 ° C temperature, complies with the essential requirement of
6.0 29.7.1 the EMC Directive to be supplied with Barriers, Junction Box, Glands and Nos 12 3887 46638
other mounting accessories for proper installation. (For Detectors/Device
without inbuilt isolator, Fault Isolator or Isolator base to be provided with
each detector/device). Approval EN54/UL.
Supply, Installation, Testing & Commissioning of Analogue Addressable
loop powered Sounder & Beacon with inbuilt isolator and having Min 15
distinct sound patterns/ multitone to indicate Exit doors and direct
occupants for safe and fast evacuation and 100dB output with minimum
1Hz Frequency flash rate designed for IP65 requirements and approved to
7.0 DSR-17.2.6 operate in – 10 ° C to +55 ° C temperature, complies with the essential Nos 12 3,871 46452
requirement of the EMC Directive to be supplied with Junction Box, Glands
and other mounting accessories for proper installation. (For
Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be
provided with each detector/device). Approval EN54/UL.
Supply, Installation, Testing & Commissioning of Analogue addressable
Monitor module with inbuilt relay and isolator with LED indicator, approved
to operate in – 10 ° C to +55 ° C temperature, complies with the essential
requirement of the EMC Directive to be supplied with Junction Box, Glands
8.0 M.R and other mounting accessories for proper installation. In case of Nos 2 4,000 8000
Manufacturer with single Input or Output module need to supply One
quantity of each for line item. (For Detectors/Device without inbuilt isolator,
Fault Isolator or Isolator base to be provided with each detector/device).
Approval EN54/UL.
Supply, Installation, Testing & Commissioning of Analogue addressable
Control (Input/Output) module with inbuilt relay and isolator with LED
indicator, approved to operate in – 10 ° C to +55 ° C temperature, complies
with the essential requirement of the EMC Directive to be supplied with
Junction Box, Glands and other mounting accessories for proper
installation. In case of Manufacturer with single Input or Output module
need to supply One quantity of each for line item. (For Detectors/Device
without inbuilt isolator, Fault Isolator or Isolator base to be provided with
each detector/device). Approval EN54/UL.
Digitally signed by Rakesh
RATE AS PER CG AS PER
Electrical AS MR
S.No. SOR Description of work Unit QTY
Supplying, installing, testing and commissioning of 2cx1.5 sq.mm fire
survival armoured cable 600/1000 volt rated with class-2 copper conductor
having crosslinkable low smoke zero halogen insulation as per BS EN
50363 and low smoke zero halogen (LSZH) inner & outer sheath. The
10.0 M.R cable should meet fire performance circuit intergrity test as per BS EN mtrs 500 175 87500
50200 PH120 & BS 6387 CWA (950 Deg. C for 3 hours). Outer Sheath
should be in red colour with Anti-rodent & LSZH properties including end
terminators, saddles, clamps with screws etc for fixing on wall/ceiling or on
cable trays complete as required.
TOTAL OF FIRE ALARM AND DETECTION SYSTEM 0 862513 46452 95500
J CCTV SYSTEM (IP BASED)
Supply, Installation, Testing and commissioning of Outdoor Varifocal Bullet
Camera, 2 MP Varifocal Bullet Network Camera- 1/2.8'' Progressive Scan CMOS,
1920 × 1080 at 25fps, 2.7 to 13.5 mm Varifocal Auto iris lens, 0.002 Lux at F1.4, 0
Lux with IR on, ICR, ONVIF (PROFILE S, PROFILE G, PROFILE T), support H.265,
H.264, MJPEG, 120db WDR, BLC, HLC, 3D Digital Noise Reduction, Three
individually configurable stream, 12 VDC & PoE, IR range: 50m, Alarm : 2 inputs &
1 30.20 2 outputs, Audio: 1 input & 1 output, IP67, IK10, Edge Analytics- Line crossing No. 3 40208 120623
detection, intrusion detection, Scene change detection, Motion detection, Face
capture, audio exception detection, Video tampering, Region entrance detection,
Region exiting detection, False alarm reduction through human and vehicle target
classification. UL/BIS, CE, FCC certified.
Micro SD/SDHC/SDXC memory slot (Min.128GB Preloaded) Make: Hikvision-DS-
2CD3626G2T-IZS (C) (2.7 to 13.5mm) / Equivalent
Supply, Installation, Testing and commissioning of Indoor Fixed Dome
Camera, 2 MP IR Fixed Dome Network Camera- 1/2.8″ Progressive Scan
CMOS, 1920 × 1080 at 25fps, 2.8 mm Fixed lens, 0.002 Lux at F1.4, 0 Lux
with IR on, ICR, ONVIF (PROFILE S, PROFILE G, PROFILE T), support
H.265, H.264, MJPEG, 120db WDR, 3D Digital Noise Reduction, Three
individually configurable stream, 12 VDC & PoE, IR range: 30m, IP66/67, IK
2 30.10 10, Edge Analytics- Line crossing detection, Intrusion detection, Motion No. 28 26813 750766
detection, Scene change detection, Face capture, Region entrance
detection, Region exiting detection, Video tampering, audio exception
detection, Focus on human and vehicle targets classification. UL/BIS, CE,
Micro SD/SDHC/SDXC memory slot (Min.128GB Preloaded) Make:
Hikvision-DS-2CD3126G2-IS (C) (2.8mm) / Equivalent
Supply, Installation, Testing and commissioning of Network Video
Recorder (NVR): 16ch Network Video Recorder- Connect Up to 16 IP
Cameras, Dual OS, Up to 12 Megapixels Resolution, HDMI1/VGA1 and
HDMI2/VGA2 outputs provided, atleast one HDMI output of 4K resolution,
atleast 1 VGA output with output upto 1920 × 1080, Support H.265, H.264,
Supports N+1 hot spare system, Supports RAID0, RAID1, RAID5, RAID6
and RAID10, Supports HDD hot swap, ,Incoming Bandwidth 320 Mbps, 8
SATA Hard Disks, 1 eSATA interface, ANR Technology, 8 SATA interfaces
for 8 HDDs and capacity of each HDD upto 10TB, 3 × USB at least 1 ×
USB with 3.0, Alarm I/O 16/4, RS-485, RS-232, 2 RJ-45 10 /100/1000
Mbps self-adaptive Ethernet interface, Multiple network monitoring: Web
viewer, CE, FCC, UL/BIS certified.
Supply, Installation, Testing and commissioning of 10 TB Hard Disc Drive
(CCTV Surveillance) for 30 days storage
Supply,Installation,Testing and Commissioning of Full HD 42" LED
Professional Display Panel.
5 M.R SITC of Cat-6 UTP Unarmourd Cable, Make: Panduit / Equivalent Mtr. 600 35 21000
SITC of MS Conduit, 25mm conduit (Heavy Duty), Make: AKG /
Supply, Installation, Testing and commissioning of 16 port Unmanaged
7 M.R Network PoE Switch: L2, Unmanaged, 16 Gigabit POE ports, 4 SFP Port, No. 3 20,000 60000
Make: Cisco / Equivalent
Supply, Installation testing and commissioning of 19" Modular Patch - 1U
Patch Panel 16, RJ 45 Cat-6 connector.
17U Floor Standing Rack, Fully Loaded,Size-600(F) x 800(D) x 1139(H)
Accessories for CCTV Work, such as 'Connectors, L-band/ T-Band/
Shaddle/ Cable Tie/ Gitti/ Nut bolts/ RJ45 etc.Make - OEM
TOTAL OF CCTV SYSTEM 0 1976633 0 379250
K DATA, VOICE & TV CABLING
Digitally signed by Rakesh
RATE AS PER CG AS PER
Electrical AS MR
S.No. SOR Description of work Unit QTY
Supply, installation, testing and commissioning of 24 Port Network
Switches (2 SFP port for uplink gigabyte) with following feature :- 1)
Indicators - Power, Link/Activity/Speed (per 10/100/1000 Mbps Port),
Link/Activity (per SFP Port), Fan (per Device), Button to Switch LED Display
Mode between PoE and Link/Activity.2) Speed - 10/100/1000 Mbps. 3)
Hardware memory - Packet Buffer Memory: 1 MB per Device. 4) Additional
1 MR feature - Certifications: FCC Class A, CE Class A, ICES-003, VCCI Class No 2 70,000 140000
A, C-Tick, BSMI, Media Interface Exchange: Auto MDI/MDI-X Adjustment
for all Twisted-pair Ports, Transmission Method: Store-and-forward, MAC
Address Update: Upto 256 Static MAC Entries, Enable/disable Auto-
learning of MAC Addresses, Maxim...View More Certifications: FCC Class
A, CE Class A, ICES-003, VCCI Class A, C-Tick, BSMI, Media Inter. 5)
Type - Managed.
Supply, Installation testing and commissioning of 19" Modular Patch - 1 U
Patch Panel 24, RJ 45 Cat-6 connector.
SITC of 19 Inch 42U with PDU and FAN 600X600mm Network Rack with
3 MR PDU 12 Sockets, Server Tray(2 Nos), Cable Organiser 1U Closed, 4 Fan & No 1 25,000 25000
Hardware Kit - Combo Pack
4 MR SITC of duplex white color faceplate. No 15 95 1425
5 7.4.12 SITC of RJ45 Voice outlet with red colour female RJ45 connector No 15 84 1267
6 7.4.14 SITC of RJ45 data outlet with blue colour female RJ45 connector No 15 267 3998
7 7.4.13 SITC of TV coaxial outlet No 2 88 176
8 MR SITC of HDMI port outlet No 2 200 400
Supply, Installation testing and commissioning of patch cord as mentioned
below :- CAT 6 RJ 45 Patch Cord F/UTP 1 Mtr. Color Blue.
Supply, Installation testing and commissioning of patch cord as mentioned
below :- CAT 6 RJ 45 Patch Cord F/UTP 1 Mtr. Color red.
Suppling and drawing 4 pair shielded, 0.5 mm PVC.Insulated copper
conductor un-armoured Cat-6 computer cable FRLS in existing surface /
concealed ,steel / PVC. Conduit/Casing-N-Capping as required.
Supplying and fixing 25mm MS conduit ISI marked alongwith the
accessories in concealed system including painting etc. as required
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper
conductor PE insulated, shielded with fine tinned copper braid and
protected with PVC sheath in the existing surface/ recessed steel/ PVC
conduit as required.
14 MR Supplying and drawing High speed HDMI 2.1 cable Meter 60 1,500 90000
15 MR Testing , commissioning, Cripping & cable ties etc… L/S 1 5,000 5000
16 MR Fluke Test L/S 1 5,000 5000
TOTAL OF DATA, VOICE & TV CABLING 27785 0 301925
Digitally signed by Rakesh
Sr. No. PRODUCT DESCRIPTION PRODUCT IMAGE UNIT QUANTITY SUPPLY LABOUR SUPPLY LABOUR
Supply, loading, unloading at site, installation and commissioning of light fixtures complete in all respects such as all clamps,
D. internal wiring between accessories and earthing terminal etc. All Compact lighting fixtures such as LED shall be provided with
Electronic ballast/ drivers and shall be a part of the lighting fixtures.
SITC of Havells make FLAT ,24W , 2’X2’ recessed Luminaire with housing made up of Powder-Coated Sheet Steel d white after
phosphochromate treatment ,Optics made up of High transmittance dual/multi layer prismatic Decorative PMMA moulded
diffuser contour optics for glare free symmetric light distribution , Powered by an independent, Output electronic LED driver
(SMPS based constant current supply) with Output Short-circuit protection, Surge protection & other reliability test as per
1 24W Recess IP20 2'X2' IS:15885 Part 2/Sec 13.. Power Consumption should not greater than 24W and System Efficacy not less than 120 Nos. 185 3890 100 719650 18500
Lumens/Watt,Depth of the fixture should not exceed 65mm, CCT 5700K PF>0.95, CRI>80 ,THD<10%. Operating temperature: -10
° C to +45 ° C , Operating voltage range: 140 V - 270 V,. Luminaire Should conform to IP20 Classification. Test report to be
submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79 for luminaire and LM80
for led source, Driver and Fixture to be BIS certified
SITC of Havells make VIBE DR ,15W Deep Recess DownLight Luminaire with housing made up of Elegantly designed pressure die-
cast aluminium Optics made up of High quality deep recessed diffuser in opal finish, Powered by an independent, isolated,
output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge Voltage protection
15W Deep Recess & other safety test as per IS:15885 Part 2/Sec 13. Power Consumption not greater than 15W and System Efficacy not less than
DownLight 100 Lumens/Watt, CCT 5700K PF>0.95, CRI>80 ,THD<10%. Operating temperature: -10 °C to +45 °C , Operating voltage range: 140
V - 270 V,. Luminaire Should conform to IP20 Classification. Luminaire Cutout dimension is 110mm and height will not more than
50 mm.Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79
for luminaire and LM80 for led source, Driver and Fixture to be BIS certified
SITC of Havells make VIBE DR ,18W Deep Surface DownLight Luminaire with housing made up of Elegantly designed pressure
die-cast aluminium Optics made up of High quality deep Surfaceed diffuser in opal finish, Powered by an independent, isolated,
output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge Voltage protection
18W Deep Surface & other safety test as per IS:15885 Part 2/Sec 13. Power Consumption not greater than 18W and System Efficacy not less than
DownLight 100 Lumens/Watt, CCT 5700K PF>0.95, CRI>80 ,THD<10%. Operating temperature: -10 °C to +45 °C , Operating voltage range: 140
V - 270 V,. Luminaire Should conform to IP20 Classification. Luminaire Cutout dimension is 145 mm and height will not more than
55 mm.Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79
for luminaire and LM80 for led source, Driver and Fixture to be BIS certified
SITC of Havells make Lumiline XS ,36W LED batten luminaires with housing made of Aluminum Extrusion for thermal
management with an anodized finish. Luminaire should be suitable for Wall/Ceiling mounting with SS clamps. Luminaire shall
deliver excellent illumination & visual comfort with CRI of >80, High transmittance Opal Polycarbonate diffuser for glare-free
36W IP20 Industrial symmetric light distribution. Luminaires should be with 140 lm/W System Efficacy and designed for Avg. LED Life (L70 B50) 50,000
Batten Burning Hours & with high efficient Photobiologically safe LEDs. Luminaire should be Powered by an integral electronic constant
current Potted driver offering THDi<15% , compliance, Output Short-circuit protection, Surge Voltage protection, and other
reliability tests as per IS:15885 Part 2/Sec 13. Luminaires should be provided with 4kV surge protection. Luminaires manufacturer
to have an in-house NABL-accredited Laboratory for testing Photometric parameters.
SITC of Havells make Lumiline Plus ,10W LED 2ft batten luminaires with housing made of Aluminum Extrusion for thermal
management with an anodized finish. Luminaire should be suitable for Wall/Ceiling mounting with SS clamps. Luminaire shall
deliver excellent illumination & visual comfort with CRI of >80, High transmittance Opal Polycarbonate diffuser for glare-free
10W IP20 2ft Mirror symmetric light distribution. Luminaires should be with 100 lm/W System Efficacy and designed for Avg. LED Life (L70 B50) 50,000
Light Burning Hours & with high efficient Photobiologically safe LEDs. Luminaire should be Powered by an integral electronic constant
current Potted driver offering THDi<15% , compliance, Output Short-circuit protection, Surge Voltage protection, and other
reliability tests as per IS:15885 Part 2/Sec 13. Luminaires should be provided with 4kV surge protection. Luminaires manufacturer
to have an in-house NABL-accredited Laboratory for testing Photometric parameters.Cat: Havells Lumiline Plus 10W
Unidirectional Exit Supply, Installation, Testing and Commissioning of 3W LED Unidirectional Exit Signage Light with inbuilt 2hours battery back up.
Total For- LIGHTING FIXTURES 918490 28100
Digitally signed by Rakesh
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT01.pdf
Tender Document
BOQ.pdf
Tender Document
CMS BHILAI_ Specification.pdf
Tender Document
CMS scope of work.pdf
Tender Document
DBR-CMS Bhilai.pdf
Tender Document
Drawings.pdf
Tender Document
Final_LIST_OF_MAKES.pdf
Tender Document
GCC2022.pdf
Tender Document
Physical Milestone.pdf
Tender Document
SCCBhlai.pdf
Tender Document
Singed IP.pdf
Tender Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .