Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.0 LAccepted-AOC | L1 | Accepted-AOC LOA | |
| 2 | L2₹12.8 L+₹1.8 L (16.5%)Rejected-Finance AGGARSAIN CHOWK VILLAGE BHOJPUR POST OFFICE FETEHPUR SAHARANPUR ROAD YAMUNANAGAR HARYANA 135101 | YAMUNANAGAR | HARYANA | 135101 | L2 | Rejected-Finance Highest | |
| 3 | L3₹13.0 L+₹2.0 L (18.3%)Rejected-Finance VILLAGE DHAND KAITHAL 136020 R24 | KAITHAL | KAITHAL | HARYANA | 136020 | L3 | Rejected-Finance Highest | |
| 4 | L4₹14.0 L+₹3.0 L (27.3%)Rejected-Finance | L4 | Rejected-Finance Highest |
Tender Value
₹14.8 L
EMD Value
₹29,680
Closing Date
2 Jan 2025, 5:00 pmClosed
NAVEEN RATHEE
ED - Ambala
Const. of the proposed stadium at village Thol in Distt. Kurukshetra (Pdg. Lighting Arrangement Only ).
2024_HRY_420235_1
2024A35A3264 3DA9 41EE 9574 F76158CC0B6F663BAR
Open Tender
Civil Works
Works
360 days
Ambala Cantt
Const. of the proposed stadium at village Thol in Distt. Kurukshetra (Pdg. Lighting Arrangement Only ).
2 documents required · 2 mandatory
₹1,000
₹29,680
Yes
2 Apr 2025
26 Dec 2024
3 Jan 2025
27 Dec 2024
2 Jan 2025
27 Dec 2024
Amount
[23.22.1.9]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.9. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 6 amp to 100 amp , 25 KA [Through Rate]
[23.22.2.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 2.1. MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 125 A FP [Through Rate]
[23.22.4.10]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.10. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. Vertical TPN DB Double Door 6 way ( 8 incoming 3phase*6 outgoing) [Through Rate]
[23.22.5.5]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.5. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp MCBs TRIPLE POLE [Through Rate]
[23.24.1]MS STAND, BUS BAR CHAMBER AND PANELS 1. Supply and erection of M.S. angle iron frame duly welded for housing M.S. sheet & main switches etc. on it, fixed on wall by means of suitable size of rag bolts with cement concrete, duly painted with three coats of approved paint including one coat of red oxide. [Through Rate]
[23.27.5]Supply and erection of Godrej Almirah typeM.S. pedestal made of 50 mm x 50 mm x 6 mm angle iron frame with 3.00 mm thick M.S. sheet covering including shutters with suitable hinges and locking arrangement with Godrej type handle including round bars . The top covering should have downward overhang of 75 mm on all sides of pedestal , having two sets of water proof ventilation holes of suitable size on the sides , at top and bottom , each set containing four Nos. holes to discharge the heat produced by the current . The shutters fixed with rubber gasket of superior quality and of suitable size to make it water proof . The pedestal duly painted both inside and outside with two coats of approved paint and primary coat and its legs are embeded upto the entire depth in 1:2:4 cement concrete block , projected 75 mm all around the pedestal and and 200 mm above the ground level including the cost of all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work:- 5. M.S. pedestal of size 1200 mm wide ,1500 mm high ,450 mm deep and bottom totally open , duly embeded in cement concrete block of size 1350 mm x 600 mm x 200 mm above ground level , having a base of size 1500 mm x 750 mm x 250 mm below ground level . 0 0 [Through Rate]
[23.5.6.2]COPPER WIRING IN EXISTING PVC/MS CONDUIT PIPE SURFACE/RECESSED FOR ELECTRICAL POINTS 6.2. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in existing MS/PVC Conduit etc as required. 1 run of Size 2.50 Sqmm(1.1.80mm) [Through Rate]
[24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. [Through Rate]
[24.1.13]EARTHING AND LIGHTENING ARRESTOR 13. Providing and fixing 4.00 mm dia G1. Wire on surface or in recess for loop earthing as required. [Through Rate]
[24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. [Through Rate]
[24.13.24]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 24. 16 Sq mm 4 core (Arm.) [Through Rate]
[24.2.7.2]LT CABLE 7.2. Supply and erection of suitable compression type brass cable glands for underground Cable :- 10 sqmm to 16 sqmm Cable 2 to 4 Core [Through Rate]
[24.4.15.1]STREET LIGHT 15.1. B.S.E.N. 10025 High Masts "Supply, installation, testing and commissioning of 12.5 mtr. long High Mast manufactured from B.S.E.N. 10025 or equivalent grade material in, 2 (two) section hot dip, galvanized inside and outside in single dip, suitable for wind velocity as per IS 875 Part-3 suitable for 6 nos. luminaire loading fully motorized (power tool) with starter & cable complete along with standard accessories supplied by the manufacturer with 3 nos. steel wire rope double drum system and twin dome aviation light with LED without foundation but including cost of set of foundation nut and bolts, installation at site complete in all respect upto entire satisfaction of Engineer -in-Charge Thickness of Top and Bottom Section = 3 mm (minimum) Top Dia = 150 mm and Bottom Dia = 360mm Thickness of Galvanization - Top = 65 micron (minimum) and Bottom = 85 micron (minimum)" [Through Rate]
[24.5.2.3]MISCELLANEOUS ITEMS 2.3. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 63/50 mm outer dia/inner dia [Through Rate]
[24.9.1]RCC FOUNDATIONS FOR HIGH MAST OCTAGONAL POLES 1. Providing RCC foundation of M25 grade (1 Cement:1 Stone aggregate: 2 Coarse sand) i/c excavation, steel reinforcement (Fe 500) @ 75 kg/cum of concrete contents, concrete cover 50mm, anchor bolts etc. over a bed of PCC 1:5:10 of required dimensions for high mast octagonal poles of various heights as per following specifications complete in all respects and as per directions of Engineer-in-charge 12.5 m high mast pole [Through Rate]
`SITC of LED Flood light 250 watt of Makes Hevells (JETA IRIS MAX) and model No. JETAIRISMAXFL250WLED757PWBLTG Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lighting and accessories required to complete the job in all respect including erection on existing pole for fixing including connection of the same upto the entire satisfaction of Engineer in Charge of the work ( Make as per list attached ). `
`Supply and erection of 32 Amp. 3 Pole/230V Astronomical automatic time switch of Havells make Cat No. IHXTS0306A alongwith contactor of required capacity movement controlled by precisaty quartz osciliation operation on main supply of continue to run on built in rechargeable nickel cadium cell for 150 hours in the event of power failure including cost of contractor complete in all respect upto the entire satisfaction of Engineer-in-charge of the work ( Make as per list attached ). `
Radhey Krishan Enterprises (BID ID -1194367)
MS Tiger Solar Light Trading Co. (BID ID -1194318)
M/s Sania Power System (BID ID -1194098)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .