| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.2 LAccepted-AOC | L1 | Accepted-AOC Reasonable rate | |
| 2 | L2₹27.2 L+₹50,334.40 (1.88%)Rejected-Finance | L2 | Rejected-Finance Quoted amount higher than L1 | |
| 3 | L3₹31.9 L+₹5.2 L (19.3%)Rejected-Finance | L3 | Rejected-Finance Quoted amount higher than L1 | |
| 4 | Rejected-Technical | - | Rejected-Technical Not having appropriate category, hence rejected |
| Sl No | Description | Qty | Unit | M/S NIYATI NETWORK L1 | M/S Ajoy Acharjee L2 | PERFECT BUILDERS AND SUPPLIERS L3 |
|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation of poles,cables etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil etc complete all as specified and as directed. | 48 | Cum | 390 ₹18,720 Lowest | 420 ₹20,160 | 420 ₹20,160 |
| 2.00 | All as per item No 01 above but depth exc 1.5m but n.exc 3m complete all as specified and as directed. | 7 | Cum | 360 ₹2,520 Lowest | 400 ₹2,800 | 420 ₹2,940 |
| 3.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cms thick in soils complete all as specified and as directed. | 25 | Cum | 159 ₹3,975 Lowest | 175 ₹4,375 | 250 ₹6,250 |
| 4.00 | Removing excavated material to a distance n.exc 50M and deposited/ spreaded where directed at a level n. exc 1.5 M above the starting point complete all as specified and as directed . | 30 | Cum | 190 ₹5,700 Lowest | 195 ₹5,850 | 260 ₹7,800 |
| 5.00 | Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cable including spreading and punning down to 18 cm thickness complete all as specified and as directed.(Compacted thickness shall be measured) | 6.24 | Cum | 2,290 ₹14,289.6 Lowest | 2,300 ₹14,352 | 2,500 ₹15,600 |
| 6.00 | Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1, with peak, size 300mm x 180mm x 40mm in trenches on cable as cable protection across the length of the cable (width wise)complete all as specified and as directed. | 250 | Each | 112 ₹28,000 Lowest | 120 ₹30,000 | 160 ₹40,000 |
| 7.00 | Material and labour for PCC (1:4:8) type D2 (using 40 mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and as directed. | 30 | Cum | 6,000 ₹1,80,000 Lowest | 6,200 ₹1,86,000 | 9,000 ₹2,70,000 |
| 8.00 | Materials and labour for providing cement concrete Type B1 1:2:4 ( 20 mm graded aggregate) as in coping of poles including weathering, slightly rounded or chamfered angles and throating including necessary form work complete all as specified and as directed. | 6 | Cum | 9,900 ₹59,400 | 9,500 ₹57,000 Lowest | 11,000 ₹66,000 |
| 9.00 | Dismantling old unservicable steel tubular poles/struts, any size including breaking up PCC foundation and removal of rubbish complete all as specified and as directed. | 39 | Each | 490 ₹19,110 Lowest | 500 ₹19,500 | 600 ₹23,400 |
| 10.00 | Supply and fixing steel tubular swaged pole, type 410 SP 55 (Overall length 11.00 meter) conforming to IS-2713 (Part 1 to 3) 1980 complete with cast iron base plate, finial taper plug, bolts, nuts and washers, screws. Pole shall be painted with two coat of black bituminous throughout internally and externally upto planting depth and the remaining external portion shall be painted with two coats of aluminum paints over a coat of red oxide primer including painting from bottom to 1.2m height alternative with 30cm red and white strip and writing pole no with black paint on yellow background complete all as specified and as directed.
Note:
(a) Earth work and PCC shall be measured and paid separately under relavent items of schedule 'A'/BoQ.
(b) Design / drawing of HT pole and dimension is to be obtained from OEM/auth dealer/supplier and same is to be got approved from AGE(I) before placing order to the manufacturer. | 39 | Each | 23,900 ₹9,32,100 Lowest | 24,000 ₹9,36,000 | 27,000 ₹10,53,000 |
Tender Value
₹27 L
EMD Value
₹54,000
Closing Date
22 Dec 2025, 10:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
COL AMIT CHAUBEY
HQ 137 Wks Engr PIN 914137 c/o 99 APO
SPL REPAIR/ REPLACEMENT OF OLD VINTAGE HT POLE, TWO POLE, THREE POLE, FOUR POLE STRUCTURE AND ALLIED WORKS AT MILITARY STATION AGARTALA
2025_MES_742246_1
8107/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Agartala
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
AGE (I) Agartala
₹54,000
Yes
17 Feb 2026
1 Dec 2025
29 Dec 2025
1 Dec 2025
22 Dec 2025
15 Dec 2025
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation of poles,cables etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil etc complete all as specified and as directed.
All as per item No 01 above but depth exc 1.5m but n.exc 3m complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cms thick in soils complete all as specified and as directed.
Removing excavated material to a distance n.exc 50M and deposited/ spreaded where directed at a level n. exc 1.5 M above the starting point complete all as specified and as directed .
Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cable including spreading and punning down to 18 cm thickness complete all as specified and as directed.(Compacted thickness shall be measured)
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1, with peak, size 300mm x 180mm x 40mm in trenches on cable as cable protection across the length of the cable (width wise)complete all as specified and as directed.
Material and labour for PCC (1:4:8) type D2 (using 40 mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and as directed.
Materials and labour for providing cement concrete Type B1 1:2:4 ( 20 mm graded aggregate) as in coping of poles including weathering, slightly rounded or chamfered angles and throating including necessary form work complete all as specified and as directed.
Dismantling old unservicable steel tubular poles/struts, any size including breaking up PCC foundation and removal of rubbish complete all as specified and as directed.
Supply and fixing steel tubular swaged pole, type 410 SP 55 (Overall length 11.00 meter) conforming to IS-2713 (Part 1 to 3) 1980 complete with cast iron base plate, finial taper plug, bolts, nuts and washers, screws. Pole shall be painted with two coat of black bituminous throughout internally and externally upto planting depth and the remaining external portion shall be painted with two coats of aluminum paints over a coat of red oxide primer including painting from bottom to 1.2m height alternative with 30cm red and white strip and writing pole no with black paint on yellow background complete all as specified and as directed. Note: (a) Earth work and PCC shall be measured and paid separately under relavent items of schedule 'A'/BoQ. (b) Design / drawing of HT pole and dimension is to be obtained from OEM/auth dealer/supplier and same is to be got approved from AGE(I) before placing order to the manufacturer.
Taking out existing old damaged / unserviceable HT UG cable of any size from trench /duct /pipe including jointing kit complete all as specified and as directed. Note:- Earth work shall be measured and paid separately.
Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured HT electric power UG cable (heavy duty with stranded aluminum conductor) of size 95 Sqmm, 3 core, 11000 Volts(Earthed) grade, conforming to IS-7098 (Part-II) laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs complete all as specified and as directed. Note : Earth work, precast cable cover protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Material and labour as in replacement of HT 11 KV (Earthed) grade heat shrinkable end termination jointing kit outdoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed.
Material and labour as in replacement of HT 11 KV (Earthed) grade heat shrinkable jointing kit straight through complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed.
Dismantling of old unserviceable air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism of any size or any type complete all as specified and directed.
Dismantling old unserviceable D.O. fuse assembly complete including insulators complete all as specified and directed.
Dismantling old unserviceable lightening arrestor 11/33KV complete all as specified and directed.
Dismantling of old rusted Cross Arms bracing support, clamps and back plate of any sections from poles setting aside complete all as directed at site.
Dismantling of broken, cracked, unserviceable HT pin/disc type insulator of any make and any size insulator complete all as directed.
Material and Labour for cross arms. Bracings, support channel, backplate hooks etc fabricated from structural steel, sections (MS Channel) of required size and shape including nuts, bolts,washers, welding, bending , cutting cold or hot, drilling holes for inserting bolts as indicated and directed including painting with one coat of red oxide primer and two coats of silver aluminium paint complete all as specified.
Supply and fixing Pin type insulator, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade confirming to IS 1445-1977 & IS 731-1971 complete all as specified and as directed. .
Supply and fixing Disc type insulator, porcelain, vitreous 145 mm high and 255mm dia ball and socket type, white, brown or green, Single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts grade conforming to IS-731 & IS-3188 complete all as specified and as directed.
Material and labour for Loop type insulator, vitreous porcelain, white, brown or green, large size with overall dimension 90x140mm clearance of hole 25.5mm complete all as specified and as directed.
Supply and fixing triple pole mechanically operated air break isolator (GOD), vertical mounting, rotating type, mounted on insulator and steel frame with operating mechanism worked from ground level complete in all respect such as gun metal moving contacts and spring loaded gun metal fixed jaws, knife copper jumper strip etc, suitable for 11000 Volts grade, 50 Hz, with 9 insulator of rating upto 400 Amps including taking down existing GOD complete all as specified and as directed.
Material and labour for expulsion type drop out fuse single pole mounted on insulator for 11000 volt and current rating upto 25 Amps including taking down existing unservicable DO fuse complete all as specified and directed.
Material and labour for HT outdoor expulsion type lightening arrestor with mountings accessories complete fixed on cross arms of two pole structure/GI flat strip and connect with same size of ACSR conductor with all fittings connected to earth strip with nut, bolt, washer transmission class having discharge capacity of 65 kilo Amps and suitable for working pressure 11 KV complete all as specified and directed.
Supply and fixing as in replacement for Danger notice plate of 25x20cm size and 1.6mm thick mild steel sheet, vitreous enamelled white, with letters(Local & Hindi language), figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT pole complete all as specified and as directed.
Supply and laying GI tubing 80mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables including taking down old unserviceable pipes complete all as specified and as directed. .
Supply and laying GI tubing 100mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables including taking down old unserviceable pipes complete all as specified and as directed.
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 25x4mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
8107tenderdocu.pdf
Tender Documents • 1.46 MB
BOQ_831158.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .