Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.1 LAccepted-AOC R O SUJANPUR TEHSIL DISTT HAMRIPUR | L1 | Accepted-AOC accept | |
| 2 | L2₹32.0 L+₹1.9 L (6.30%)Rejected-AOC BELOW SLAUGHTER HOUSE KRISHNA NAGER SHIMLA | SHIMLA | SHIMLA | HIMACHAL PRADESH | L2 | Rejected-AOC accept | |
| 3 | L3₹35.4 L+₹5.3 L (17.7%)Rejected-AOC VILLAGE P O MANSIMBLE TEHSIL PALAMPUR DISTRICT KANGRA HP | KANGRA | HIMACHAL PRADESH | 175013 | L3 | Rejected-AOC accept | |
| 4 | Rejected-Technical | - | Rejected-Technical reject | |
| 5 | Rejected-Technical NOT AVAILABLE | NA | NA | 121004 | - | Rejected-Technical reject |
Tender Value
Refer Docs
EMD Value
₹31,200
Closing Date
23 Nov 2020, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
O/O Engineer JSV Division Thural
O/O The Executive Engineer JSV Division Thural
Providing LWSS Andarana bandhan Under Jal Jeevan Mission in Tehsil Jaisinghpur Distt Kangra H.P
2020_HPIPH_42484_1
THL-KNG05-729 (14080-14145 dated 16.11.2020)
Open Tender
Civil Works - Others
Item Rate
180 days
Providing LWSS Andarana bandhan Under Jal Jeevan M
Please refer Tender documents.
10 documents required · 10 mandatory
₹400
₹31,200
Yes
12 Apr 2021
16 Nov 2020
24 Nov 2020
16 Nov 2020
23 Nov 2020
16 Nov 2020
120 days
Amount
Excavation in foundations and trenches(for pipes and pits in all depths etc.) in all lifts and in all kinds of soils such as pick work, jumper work, blasting in soft/hard rock, chiseling/wedging out of rock (where blasting is prohibited)and saturated soils, stacking the excavated earth within all leads and lifts, clear from the edge of excavation and then returning the stacked soil in 15 cms. layers when required into plinths, sides of foundation and trenches etc., consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated earth as directed by Engineer-in-charge within all leads and lifts including uprooting of trees, dressing of beds and sides and preparation of sub-grade, restoration of unmetalled/metalled/paved surfaces to its original conditions including soring, strutting, timbering and dewatering , where ever required, providing diversion for traffic, fixing night signals, fixing caution boards, crossing over trenches for access to houses complete and to the entire satisfaction of the Engineer-in-charge.
Laying, jointing & testing of GI pipe with circumfrential butt welded joints by electrical arc welding ( welding thickness shall be equal to pipe wall thickness) steel flanged pipes after every 100 mtr of pipe of following diameter Conforming to IS 1239-1990 (Part-II), having wall thickness as specified below capable of withstanding required test pressure, including manufacturing and febrication of reducers/ tapers , all short pieces, etc. as per site requirement made from parent tubes . The laying of pipe shall also include flanged joints duly welded in three layers (Two inner & one outer), where ever required as per direction of the Engineer-in-charge (Earth work in trenches and the cost of providing flanges i/c nut & bolts, gasket will be measured and paid for separately) and all operations such as cutting, welding, jointing, fabrication of tees i.e. lowering and laying in excavated trench to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the entire satisfaction of the Engineer in charge. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The damaged portion of the pipes and all the specials ( If damaged during laying & jointing operation of pipe) made form the parent tube shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing, D.P. test of butt welded joints complete in all respect and to the best satisfaction & direction of Engineer in charge with in all leads and lifts.
1st stage G.I. ( M. Class) pipe 80mm dia with wall thickness 4.80 mm of , (FT-5) outer dia 89.50 mm , at every 100 mtr pipe flanged from RD 0 to 220 = 220 Rmt
2nd stage G.I. ( M. Class) pipe 80mm dia with wall thickness 4.80 mm of , (FT-5) outer dia 89.50 mm , at every 100 mtr pipe flanged from RD 0 to 1800 = 1800 Rmt
2nd stage G.I. ( M. Class) pipe 80mm dia with wall thickness 4.80 mm of , (FT-28) outer dia 89.50 mm , at every 100 mtr pipe flanged from RD 1800 to 2820 = 1020 Rmt
2nd stage G.I. ( M. Class) pipe 80mm dia with wall thickness 4.80 mm of , (FT-17) outer dia 89.50 mm , at every 100 mtr pipe flanged from RD 2820 to 3860 = 1040 Rmt
Stage-1st - Percolaction Well:- Supply of submersible pumping set of (KSB /Kalama/Kirloskar/Johnston/Cromption/BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with uptodate ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-5.00 HP each
I,Total Head 46.04 Mtrs,ii,Discharge required from each pump 3.46 LPS for each pump ( One Will act as stand by),iii,No. of pump required 2.00 Nos. One act as stand by,iv,Location of the site of installation of machinery.The site is located at a distance of 65 Kmts from Palampur.,v,The Altitude of installation.The altitude of place is 700 mtrs above MSL,vi,Type of current.AC Three phase supply with,vii,Rate Voltage 415+ 10%,viii,Type of water and its source P/Well,ix,Charactristics of water.a)Ambient Temperature dig.c 20 dig. C,b)Turbidity NTU,c)Hardness260Mg/Ltrs(as CaCO3),d) PH 7.5,e)total solid Mg /Ltrs f)Other,x,Depth of S/Well 10 mtrs,xi,LWL in S/ well mtrs.,xii,Dia of Bore,xiii,Maz draw down,xiv,Static water level in S/Well mtrs, XV,Center line level of Pump ,912.40 mtrs,Xvi,Discharge level of highest point 950.00 mtrs,Xvii,Static head in Mrs 37.60 mtrs.,XViii,Length of R/Main 220 mtrs.,XIX,Dia of Rising main ,XX,No of working hours per day 16 Hours,xxi,Limit of pump operation.(-) 15 % (+) 10% of total head,xxii,R.P.M. of pumping set.2900 RPM ( or to be specified by the tenderer),xxiii,Test run.8 Hours continueously for 7 days
Supply , installation, testing and commissioning of PLC (Programmable Logic Controller) based Fully Automatic LT Panel for submeresible pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos. pump automatically as per site requirement along with sluice valve automatically as per design timing which can be acted as and when required one at a time or together as per requirement through PCL panel (CPRI approved , with 50 KA Short Circuit and IP-55 protection duly insulated with heat shrinkable sleeve as per colour, supported on epoxy insulator 01 set, common earth bus of 25mm x 4 mm at bottom inside panel 1 No. board with two earth tereminal out side panel board, cable alley cable gland with independent plate at bottom and complete panel board painted with powder coating in gray colour all as spcified & directed, Make of panel board : dvepl / aspl / tricolite. The pannel board should also have following items ( i to xviii).
PLC (Programmable Logic Controller),1.00 Nos
ICTP switch with HRC fuses L&T / Standard / Havells make & having capacity 30 % extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB.1.00 Nos
MCB /MCCB suitable capacity of Schneider/Siemens/ABB make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.1.00 Nos
Y-D starter of suitable capacity for submersible pump Make - L&T / ABB/ Schneider.1.00 Nos
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.1.00 Set
Star delta timer.1.00 Nos
Single phase parventer of reputed make Minillic / L & T / Standard & Suitable capacity.1.00 Nos
Automatic Phase Sequnce Corrector with prevention against, phase revarsal protection, under / over load protection Make ABB/ L&T / Siemens/GIC.1.00 Nos
Control MCB 6A -SP,1.00 Nos
On / Off indicator and push button, Set of 1each
Control and power wiring,LS
Power capacitor of suitable capacity,1.00 Nos
Control terminal, Bus Bar, i.e.Bolt, insulator, etc.LS
LED 5 Watt.1.00 Nos
Cooling fan 230 VAC 1.00 Nos
Hour run Meter.1.00 Nos
Supply of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast Iron double flanged sluice valve 80 mm dia class PN1.0 confirming to BIS-780-1984 (to be provided on R/main side) capable of with standing nominal seat test pressure of 16 kg/cm².
Supply of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast Iron double flanged swing check type reflux valve 80 dia class PN 1.0 vconfirming to BS 5312-1984 having bye pass arrangement (to be provided on R/main side) and shall be suitable for withstanding nominal seat pressure of 16 kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type, size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 2.5 mm^2 ( From HPSEB Meter to Switch &Starter).
On motor side 3 core flat joint less copper cable of size 2.5 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Supply & errection of floor power shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments of GEC/Siemen/ Havells L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of requirement KVAR according to BHP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including Standard/ L&T/Kilburn/Indo asian make ICTP switches conforming to BIS 4064- 4064-1978 or latest with HRC fuses.
Supply of standarad make 80 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
P/Laying Column assembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. Column assembly =80 mm dia G.I.flanged pipe(medium grade) NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Errection of all equipments i/c cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
Stage-2nd:-Supply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir Sabar make conforming to BIS: 1520-1980 (latestwith upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. and shall be suitable for operation as per data given below.20 HP Each (2x 20 HP= 40 HP)
I,Total Head 204.80 Mtrs.,ii,Discharge required from each pump.3.46 lps,iii,No. of pump required 2.00 Set (One act as stand by),iv,Location of the site of installation of machinery The site is located at a distance of 65 Km from Palampur.v,The altitude of installation.700 MSL.,iv,Type of current.AC three phase supply with freqduency of 75cycle per second.,v,Rate Voltage 415V + 10%,vi,Type of water and its source,Clear water.Shaft level,945.4,Level of discharge point 1092,Static Head 146.6,vii,Charactristics of water.a)Ambient Temperature dig.c,b)Turbidity NTU,c)Hardness260Mg/Ltrs(as CaCO3),d) PH 7.5,e)total solid Mg /Ltrs,f)Other Depth of well assembly,xvi,No. of working hours per day 16.00Hours.xvii,Length of Rising main 3860 Rmts.,xviii,Dia of Rising main 80 mm,xix,Limit of pump operation.In the completem Range of (-)75% .xx,R.P.M. of pumping set. 2900 RPM (or to be specified by the tenderer).xxi,Test run.8 Hours contineously for 7 days.
Supply , installation, testing and commissioning of PLC (Programmable Logic Controller) based Fully Automatic LT Panel for centrifugal pump made out of 16 Gauge sheet powder coated dust and veremin prof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos. pump automatically as per site requirement along with acctuator sluice valve automatically as per design timing which can be acted as and when required one at a time or together as per requirement through PCL panel (CPRI approved , with 50 KA Short Circuit and IP-55 protection duly insulated with heat shrinkable sleeve as per colour, supported on epoxy insulator 01 set, common earth bus of 25mm x 4 mm at bottom inside panel board with two earth tereminal out side panel board, cable alley cable gland with independent plate at bottom and complete panel board painted with powder coating in gray colour all as spcified & directed, Make of panel board : dvepl / aspl / tricolite. The pannel board should also have following items ( i to xviii).
PLC (Programmable Logic Controller), 1.00 Nos
ICTP switch with HRC fuses L&T / Standard / Havells make & having capacity 30 % extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB.1.00 Nos
MCB /MCCB suitable capacity of Schneider/Siemens/ABB make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.1.00 Nos
Y-D starter of suitable capacity for centrifugal pump Make - L&T / ABB/ Schneider.1.00 Nos
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.1.00 Set
Star delta timer.1.00 Nos
Single phase parventer of reputed make Minillic / L & T / Standard & Suitable capacity.1.00 Nos
Automatic Phase Sequnce Corrector with prevention against, phase revarsal protection, under / over load protection Make ABB/ L&T / Siemens/GIC.1.00 Nos
Control MCB 6A -SP,2.00 Nos
On / Off indicator and push button, Set of 2 each
Control and power wiring,LS
Power capacitor of suitable capacity,1.00 Nos
Control terminal, Bus Bar, i.e.Bolt, insulator, etc.LS
LED 5 Watt.1.00 Nos
Cooling fan 230 VAC,1.00 Nos
Hour run Meter.1.00 Nos
Supply of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast steel double flanged accutated sluice valve of class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 52 kg/cm².
NOTE:-The Cast steel sluice valve shall conform to BIS:780-1984 for 50 to 300mm dia & BIS:2906-1984 for 350 to 1200mm dia ( latest edition). However if seat pressure exceeds the limits prescribed in above mentioned BIS, then it shall be of cast steel conforming to class ASA-150 for seat pressure upto 52 Kg/cm² or class ASA-300 for seat pressure 52 Kg/cm² as per BS 1414 (API 600) .
Supply of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of class ASA-300 confirming to BS 1868(API-600) (latest edition)to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 52kg/cm².
Supply of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of class ASA-300 confirming to BS 1868(API-600) (latest edition)to be provided on Rising main) of 80 mm and shall be suitable for withstanding nominal seat pressure of 52 kg/cm².
NOTE:- The Cast steel reflux valve shall conform to BIS: 5312-1984- Part-I ( latest edition). However if the seat pressure exceeds the limits prescribed in BIS 5312 then it shall be of cast steel conforming to class ASA-150 for seat pressure upto 21 Kg/cm² or class ASA-300 for seat pressure 52 Kg/cm² as per BS 1868 (API 600)
Supply of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make C.I double flanged sluice valve class PN-I confirming to BIS 780-1984 to be provided on Suction side of size one dia higher then the suctrion size of pump capable of withstanding nominal seat pressure of 10.20 kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/Grandlay/Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 16 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 6 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Supply & errection of floor/wall mounted power shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments of GEC/Siemen/ Havells L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of requirement KVAR according to BHP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including Standard/ L&T/Kilburn/Indo asian make ICTP switches conforming to BIS 4064- 4064-1978 or latest with HRC fuses. (range to be specified by the tenderer.)
Supply of standarad make 80 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
P/L G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe XXX mm dia = to be specified by the Tenderer
Delivery pipe XXX mm dia = to be specified by the Tenderer
Common header = XXX mm dia
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Providing and lying double loop earthing with coper plate 600x600 x3 thick electrode and copper strip of 25x3 complete including providing of material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, Copper /GI wire/ Strips of required capacity conforming to BIS 8034-1978 latest with upto date ammendments for above motor & other electriacl equipments including all civil works. (for both machineries).Note. The strip size shall be 20x3 upto 18.5 KW . 25x3 for 18.5 to 37 KW to 55 KW and 32x5 beyond 55 KW.
Errection of all equipments including cost of tees,bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
SUNIL KUMAR
SANJAY SAINI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .