Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.1 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹24.7 L+₹2.2 L (9.92%)Rejected-AOC UPPER SARTHI VIHAR AJABPUR KALAN PO NEHRUGRAM HARIDWAR ROAD DEHRADUN 248001 UK | DEHRADUN | UTTARAKHAND | 248001 | L2 | Rejected-AOC R | |
| 3 | L3₹29.8 L+₹7.4 L (32.8%)Rejected-AOC | L3 | Rejected-AOC R | |
| 4 | Rejected-Technical 5 DARSHANI GATE DEHRADUN PIN 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | - | Rejected-Technical No in WLR |
Tender Value
Refer Docs
EMD Value
₹78,000
Closing Date
26 Sept 2020, 6:00 pmClosed
GE IMA DEHRADUN
GE IMA DEHRADUN
REPAIR MAINT OF CENTRAL AC PLANT INSTALLED AT KHETRAPAL AUDITORIUM AT IMA DEHRADUN
2020_MES_370183_1
GE/IMA/37/2020-21 8980/E8
Open Tender
Street Lighting
Item Rate
334 days
GE IMA DEHRADUN
Refer NIT
8 documents required · 8 mandatory
₹500
Yes
GE IMA DEHRADUN
₹78,000
Yes
12 Dec 2020
18 Aug 2020
28 Sept 2020
19 Aug 2020
26 Sept 2020
3 Sept 2020
Amount
Preventive maintenance written report in each month diagnosis of trouble,adjustment,minor repair or reseting of control as well as maintenance of central air conditioning plant chiller unit of capacity 2x125 TR comprising and other connected installed machineries & accessories (Mainly screw type compressor 2x125TR (Make-M/s Trane) 2 No & pumping sets, condensing pumping sets 2 nos, FRP cooling tower 01 Nos , monoblock pump sets -2 nos, Air handling units -04 nos with belt driven motor, air blower fittings, shaft assembly cooling coil expansion valve etc by autorized service Engineer complete with descaling of condenser and chillers, compressure and connected moters etc completely cleaning, removing the dust particles, servicing, replacement of all minor parts , greasing, oiling, charging of refrigerant as per manufacturers recomendation through out contract period all required for the efficient, smooth & satisfactorily functioning throughout contact period including routine maintenance whenever required minimum four periodic servicing of the entire plant & equipments as per manufacturers instruction complete for eleven months. Note: spare parts required for maint/servicing will be measured and paid separately
Notes:- (a) Preventive and comprehensive maintenance each month shall be got done from authorised service Engineer and cerfificate to to this effects shall be submitted by firm dealing with AC Plant complete contract period for the entire AC plants including replacement of Refrigerant & compressor oil etc (b) The tenderers shall have to submit a copy of proof to carry out the preventive/routine maintenance including overhauling servicing of complete AC plant.
(c) All maint service shall be carried out by authorised service Engineer to each chilling machine / plants 2 Nos during the contract period. The contractor shall submit the record of periodical /preventive /annual maint service carried out along with documentary evidence for claiming payment. The contractor shall produce the "purchase order" issued to auth dealer for comprehensive maint (all inclusive part and labour contact.) (d ) Contractors quoted rates shall be deemed to be inclusive of any miscellaneous minor spares such as wires, toggle switch, lugs,nuts,cable gland,connector,thimbles,gland packing etc when required or as ordered by EIC for smooth and uninterrupted operation of the complete system except spares such as mentioned here in after in relevant items of this schedule. (e) M&L for de-scaling of condensers by dismantling in original position all as required at site for shell and tube type condenser unit of Central AC Plant including supply and replacement of gaskets and worn out nuts etc all as required complete during throughout contract period as specified and directed by Engineer-in-charge.
Daily Routine maintenance (Contains cleaning, oiling, greasing, replacement of motar bearings, nuts bolts , moterpump set coupling, electric cable connection thimbles, pipes joints,packing materials, gland packing etc as required) checking and minor maintenance, repair shall cover the following components of AC plant. (i) Condensing pump set with motor 30 HP capacity -02 Nos. (ii) Chiller Motor pump set with motor 30 HP capacity- 02 Nos (iii) FRP cooling tower 2 x 125 TR capacity with electric motor- 01 Nos, (iv) Condenser water piping various sizes up to 300 mm with butter fly valve 50 mm to 200mm dia Non return valve, Y/ pot strainer/globe valve/Thermometer & balancing valve & connected accessories etc. (v) AHU complete-2 Nos and FCU-02 units with accessories i.e blower with casing , chiller water coil, , filter & filter frame, drive motor humidification kit motorised motor control panel 2 nos (vi) Refrigerant /condenser including drain water piping of various sizes up to 200 mm dia pipe with butterfly valve, balancing valve, globe valve, Non return valve, Pot Y/strainer up to 200 mm dia including thermometer, Auto air vent & including other connected accessories etc. (vii) Make up water tank /expansion tank of and chilled water circuit, installed at the roof of the plant room . (viii) LT central panel board with aluminium armoured cable of all sizes of cable tray from main panel to machinery in main room. (ix) LT panel board including all accessories and control wiring LT cable of various sizes for exhaust blower central industrial type installed at main AC plant room including blower fan heavy duty, MS impeller, Blower fan and blower shaft with electric motor (x) Butterfly valve with actuator Gate etc.
Repair/maint.of expension valve including opening refixing after repairing nitrogen pressure test vaccumising during re-commissioning including testing of oil internal parts and testing of A.C. plant complete all as specified and directed.
S&F / replacement of oil filter water cooled screw chillers Model No RTHB 1 x 125 TR
S&F / replacement of 'O' ring 3.600 IDX210 RD, Neoprene
S&F/replacement of compressor oil 300 SUS, 1 Gal container
S&F/ replacement of of high pressure switch cut out with conduit adaptor, 120/240 V AC SPDT
S&F/ replacement of low pressure cut out switch 260P/39CL
S&F replacement of sensor T-10 to 150F, 25DIX x 2.0 LG 156 IN Jacketed cable
S&F / replacement of T-32 to 201F, 25 D, dia x 2.00 LG, 240 IN Jacted cable
S&F/ replacement T-15 to 140F, 25 DIAX 2 LG, 288 IN Jacketed cable machined pair
S&F/ replacement of sensor temp, thermisotr, 15-140F, 25DIAX 2 LG, 216" Jacked cable
S&F/ replacement of differential pressure control (FD-113-SNBAA-07404)
S&F/replacement of resitor transition, 5 ohms, 365W 27A
S&F/ replacement o of module starter UCP2
S&F / replacement of mnx -70 contactor Make- L&T
S&F / replacement of micro filter 610 x 610x50 mm cap 2000 CFM Box Type non woven synthetic media supported by aluminium mess on one side and finished with HDPE ess on the other side.
All as per srl item No 16 above but of size 457mm x 457mm x 50mm of cap 1125 CFM
M&L for dismantling blower shaft of AHU upto 125 TR by removing the belt and pully, blower drum, dismantling the shaft with welding, turning, grinding to have its original dimension balancing the shaft and refitting in AHU including reassembling the blower,m pulley etc with new bearing of existing size, testing and commissioning the AHU for satisfactory operation complete all as specified and as directed
S&F in resplacement gun metal butter fly valve dia 150 mm with side handle operated complete with packing/gasket material complete all as specified and directed, Make- Sant/Castel/Unique/Kirloskar
S&F in replacement of PVC nozzle assembly 045, suitable for cooling tower complete all as specirfied and directed Make- Paharpur
S&F in replacement motorised valve 2 way/3 way 100mm dia for chilled water pipe line with complete accessories required as per site requirement incl packing material and commissioning, testing upto entire satisfaction of EIC, Make-Honeywell
S&F in replacement brass NRV/check valve 200mm materila complete as per existing make size and type including packing material, gasket all as pecified and as directed Make- Zoloto/Castle
S&F in replacement of push botton as per existing type complete Make- L&T
S&F in replacement of ammeter 0-30/0-40/0-60 amp range square type 440 volt AC 50 Hz Make- L&T
Sub main wiring with four single core PVC insulated unsheathed FR cable 1100 Volt grade, 10.0 Sqmm size with multi stranded copper conductor drawing into conduit in surface/concealed as required including two run single core PVC insulated unsheathed 10 Sqmm cable with multi stranded copper conductor colour code as a earth continuity and connected upto DB including taking down old unserviceable submain wiring complete all as directed. Make of wire : Finolex, Plaza, Havells, Polycab NOTE: (i) Four run of single core PVC cable with two run of earth conductor and conduit shall be measured as one unit.
S&F in replacement electronic timer 0-30 sec all as specified and directed Make-L&T
Cleaning of condesoner coil and cooling tower through max clean/treat-05 solution complete all as specified and directed
Servicing of air curtains unit upto 2.0 M long each, AC single phase 230 volts 50 Hz velocity 15 to 16 amps airthrough 2.5 M as in preventive maint alongwith blower assembly and components to the entrie satisfaciton of EIC complete all as specified and directed.
All as per srl item No 28 above but 1.50 mtr long
Taking down carefully electric motor 3 phase, 415 V, by disconnecting all electric connections, nut, bolts of foundation all as per site requirement and transporting to workshop for repair complete opening of motor, taking out rotor from starter, cutting of winding, extraction of all burnt wire from stator ,cutting of winding extraction of all burnt wire from stator shaft and rewinding with supper enameled insulated copper wire of suitable size or gauge varnished twice and then dry in electric oven complete with all insulating winding material, glass wool sleeves fasteners and terminal plate of required size and installation and testing at site of following capacity motors complete all as specified and directed. :-
Replacement of strip heater made of Gp sheathing having terminal at one end and two holes for installation 240 volt,3000 watt, complete all as specified and directed. Make DASS PASS and equivalent as approved.
All as per srl item No 34.00 above but 3500 watt
M&L for replacement of water flow switch type, IPS industrial pressure switch complete all as specified and directed. make : INDFOSS or equivalent as approved.
All as per sl item No.11.00 above but contactor MN x45 complete all as specified and directed. Make : L&T or equivalent as approved.
All as per sl item No 11.00 here-in-above but contactor MN X 12 Make- L&T or equivalent as approved.
M&L for replacement of over load relay 20 to 33 A, make : L&T or equivalent as approved.
M&L for replacement of over load relay 4.5 to 7.5A, complete all as specified and directed. Make-L&T or equivalent as approved.
MCB TPN 32 Amps, 415 volts 'C' Curve 10 KA, including connection with suitable size copper lugs complete fixed in repair all as directed. Make Protect :- Legrand/ABB/Schneider/L&T
MCB TPN 63 Amps, 415 volts 'C' Curve 10 KA, including connection with suitable size copper lugs complete fixed in repair all as directed. Make Protect :- Legrand/ABB/Schneider/L&T.
M&L for replacement of MCCB, 3 phase 415 volt 100 A 25 KA frame TM 125 complete all as specified and directed. Make- GE Power Control or equivalent.
Replacement of 'V' belt of size B-100 complete all as specified and directed.
All as per item No 20 above but B-46 complete all as specified and directed.
M&L charging of refrigerant gas (Make R-22) including leakage testing of complete plant with nitrozen gas and repairing leakage portion all as specified and directed.
S&F in replacement amp meter 0-50 Amp Make - CE/AE complete all as specified and directed
S&F in replacement amp meter 0-150 Amp Make: CE/AE complete all specified and directed
Complete removing of paint from old painted surfaces of steel and preparation of steel surfaces of AC plant 2x125 TR complete including all pipe lines of any dia or size with accessories, and applying two coasts of synthetic enamel paint over a coat of red oxide primer by spray painting to protect extra spreading paint from manufacturers stickers and plates complete all as specified and directed.
Complete removing of paint from old painted surfaces of steel and preparation of steel surfaces of AC plant cooling tower of 250 TR complete including all pipe lines of any dia or size with accessories, and applying two coasts of synthetic enamel paint over a coat of red oxide primer by spray painting to protect extra spreading paint from manufacturers stickers and plates complete all as specified and directed.
Repair, maintenance and serving to 1X125 Ltr TR compressor make trane dismantling and opening and removing unservicable defective parts inclusing cleaning, oiling and refilling of R-22 Gas etc and replacement of unserciceable parts with new one, overhauling/servicing and testing of compressor complete by authorised service engineer all as specified and directed
S&F of replacement Filter, Element, Requires ring 1157 Refrigeration element
S&F pf replacement Gasket- Adapter, suction service valve , non--asbestos R-123 compatible Lakjk, .06 THK X 2.84 OD X 2.28
S&F of replacement Gasket, .031 X 3.22 X 2.53 Chloroprent (Non- asbestos) W/Anti-Stick Coating one side
S&F Gasket, 4IN. Flange -300#
S&F of replacement of RING O, 4.234 ID X .139 RD
S&F of replacement of RING O, 2.234 ID X .139 RD
S&F of replacement of RING O, 2.859 ID X .139 RD
S&F of replacement of RING O, 3.359 ID X .139 RD
S&F of replacement of RING O, 3.984 ID X .139R
S&F of replacement of RING O, 4.609 ID X .139 RD
S&F of replacement of RING O, 5.109 ID X .139 R
S&F of replacement of RING O, 6.234 ID X .139R
S&F of replacement Filter, ASM, 1.31 SAE O-Ring, Hydraulic.Service
S&F & Replacement Filter, Permanent .080/ .100T X .31 Dia Bronze
S&F replacement Gasket, Solenoid vlave, 2.00 ODX .031 Thik
S&F replacement Gasket, 2050 OD X 18.90 BC R-123 Compatible
S&F replacement Heater, oil compressor, 100 watts, 120 volt
S&F of replacement Kit, pisotn chha, R150 without piston
S&F of replacement Ring, Sealing O-Ring 1.16 OD X .18 W
S&F of replacement Ring, O 18.955 ID X 0.275 RD, For use with refrigerant only
Dismantling and taking out unserviceable, S&F of replacement of RING O, 1.859 ID X.139 RD
Dismantling and taking out unserviceable, S&F of replacement of RING O, 3.225 ID X.210
Dismantling and taking out unserviceable, S&F of replacement of RING O, 17.455 ID X.275
Dismantling and taking out unserviceable, S&F of replacement of RING O, 1.237 ID X.103 RD NEOPRENE SIZE#124
Dismantling and taking out unserviceable, S&F of replacement of GASKIT, TEFLON SIZE 1", (Fitting Size 1.25-12)
Dismantling and taking out unserviceable, S&F of replacement of SEAL, LABRYNTH 6.00 INCH DIA 6061 ALUM
Dismantling and taking out unserviceable, S&F of replacement of TERMINAL, HEREMETIC .035 X .25W, 1/8 NPT
Dismantling and taking out unserviceable, S&F of replacement of TERMINAL, MOTOR, INCLUDES ALUMINA INSULATORS
Dismantling and taking out unserviceable, S&F of replacement of RING, O 18.955 ID X.275 RD
Dismantling and taking out unserviceable, S&F of replacement of RING, SEAL PISTON 4.030 OD X.232T
Dismantling and taking out unserviceable, S&F of replacement of RING, WEAR 4.00 OD X.50T GLASS FILLED NYLON
Dismantling and taking out unserviceable, S&F of replacement of RING, Gaskit, 0.031 x 4.16 x 3.38, Chloroprene (Non- Asbestor) W/Anti Stick coating one side
Dismantling and taking out unserviceable, S&F of replacement of Bearings for CHHA140 compressor (set of 9 bearings)
Dismantling and taking out unserviceable, Opening the condenser replacement of Copper Tube condenser .75 OD x .026 x 91.812 in long inciuding installation charge completed all as specified and directed
M&L for replacement of water temp gauge dial type 0-120 degree F make H Guru or equivalent of approved make complete all as specified and directed
M&L for replacement of solenoid valve1/4NPTE Maleunloader B-14 S2 Make- TRANE as approved complete all as specified and directed
S&F in replacement of spiral veval gear box suitable for cooling tower 250 TR make Paharpur Model T-82-449, series 10P, with rotating shaft and bearing set 14131 and 501314 Make- NBC including filling of synthetic lubricant
Material and labour for earthing with galvanised steel earth plate electrode 60cmX60cmX 6mm thick burried directly in ground (earth pit not less than2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below ground level connected to 25 x 4mm thick GI strip protected by 40 mm bore light grade galvanised iron pipe and other end connected to test point as directed including funnel with wire mesh and watering pipe 20 mm bore medium grade galvanised iron pipe with charcoal and common salt in alternaterlayers of 15 cm thickness all around the GI plate electrode with concrete pit in PCC 1:3:6 type C-1 with cast iron frame including cast iron cover10mm thick hinged to CI frame and 6mm MS rod for handle, necessary excavation and earth wok in hard/dense soil and disposal of spoil to a distance n exc 50 m and necessary testing complete all as shown in electrical plate No 3 of SSR part-I all as specified and directed.
S&F in replacement power indicating LED lamp with holder assembly (R, Y, & B ) 230 volt AC complete all as specified and directed Make- L&T
S&F / replacement of PVC cooling tower fins for supperior quality bluish shading having thickness 0.2mm for suitable Paharpur cooling twoer of central type AC plant
Electronic schematic diagram alongwith design condition (Temp and Humidity) of AC plant to be displayed in the plant room all as specified and directed.
Marking on all chiller & condenser pipes with colour code at flow of gases on Chillar plant all as specified and directed.
Repair and maintenance of Chillar water pipe line including supply and fixing insulation materials complete all as specified and directed.
Supply only sling psychrometer for measuring temp all as specified and directed. Make :- Bellstone
Shifting/change mode of AC plant system from cooling to heating at winter change/ heating to cooling at summer as per direction of users or engineer in charge withing 5 days by draining out complete water from system by changing all valves, cleaning of pipes, replacing of NRV/ cut off valve position etc and reclaiming of refrigerent, replacement of parts, pressure testing with Nitrogen, Vacummizing gas charging complete plant complete all as specified and directed.
M/S Garhwal Enterprises
MAHADEV ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .