2ND IN COMMAND ELECETIRCAL
2ND IN COMMAND ELECETIRCAL FTR HQ GUJ
Repair and replacement of MFP OR SFP feeder pillars in AOR of 194 Bn BSF under SHQ BSF Gandhinagar
2023_BSF_784899_1
19/2IC(EL)/NIT/FTR-GUJ/2023-24
Open Tender
Electrical Works
Item Rate
60 days
DIG SHQ BSF GNR
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹42,932
28 Dec 2023
12 Dec 2023
20 Dec 2023
12 Dec 2023
19 Dec 2023
12 Dec 2023
Amount
Fabrication, supplying, installation, testing and commissioning of CPRI approved outdoor type double door, 700 mm x 600 mm x 450 mm deep fabricated out floor mounted electric panel cubical type fabricated with minimum 14 SWG CRCA sheet of size steel sheet with intermediate membes of same material and guage as required. having 400 amps, 4 nos. insulated aluminium bus bars, interconnection from bus bar to MCCB through aluminium strip and to accommodate following accessories, front and back openable door The box should be supported by 700 mm x 450 mm x 600 mm legs and frame made by 50 mm x 50 mm x 6 mm thick MS angle iron at the base and individual leaf hinged door with, detachable gland plate made of 3 mm thick MS sheet at the bottom, water drip proofing arrangement at the top, air ventilation grooves at sides dust and vermin proof design, earthing studs. Having following accessories in Panel (A) 125 Amp Four pole MCCB ICS=ICU=100% , 18 k, 415 Vac Model No-CM90677OOLO Make-L&T or equivalent Havells/HPL/Legrand/C&S- 02 Nos (B) 80 Amp Four pole MCCB ICS=ICU=100% , 18 k, 415 Vac Model No-CM90677OOLO Make-L&T or equivalent Havells/HPL/Legrand/C&S- 03 Nos (C) Pilot Neon lamp (R,Y,B) model RB2-BVL03,RB2-BVL04,RB2-BVL05 Make-C&S or Equivalent Havells/HPL/Legrand-03 Nos Make-Havells or equivalent HPL/Legrand/C&S including making of provision of inlet outlet of cable, connection interconnetion etc, errection,testing, commissioning of panel which includes civil foundation etc. as required.
Supplying ,installation,testing and commissioning of cubical type padestal mounted outdoor Junction Feeder Pillar of size 500mmX500mmX400mm made out of 2.0 mm. thick MS sheet and mounted on 35mm x 35mm x 5mm thick angle iron frame i/c same size of angle 04 nos. legs 500mm lenght erected in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation & refilling,hinged front & back doors with locking arrangements,with provision of fixing of glands at the bottom, antirust design, air ventilation grooves, water drop proofing arrangement ,insluators,earthing studs & connection with 25mm x 5 mm 2 mtr GI strip,nuts bolts etc.as required including connections,interconnetions , painting with primer & finish paint with synthetic enamel paint , 04 nos aluminium bus bar strip suitable for 200 A,415 V capacity with suitable insulated support for aluminium bus bar complete as required.
Supplying ,installation,testing and commissioning of weatherproof distribution /jumction box made of 1.6 mm CRCA sheet of size 500mmX600mmX200mm with front openable door having locking arrangment, suitable sloping at top having IP-65 protection, provision of 2 Nos earth stud for earthing, box have to be fitted on existing octagonal poles with help of bracket, necessary nut & Bolt (of GI), provision of 3.5 core x 35 sq mm inlet & outlet cable connection including providing and fixing 4 Nos, 100 amp Al bus bar & 01 Nos 16 Amp DP MCB & 4 Nos 6 Amp SP MCB for control of existing LED fitting/HPSV fititng with 3 nos surge protection device(SPD) of 10 KV, 5KV(Dm/cm)/04 Nos Ballst 250 watt,-04 Nos Ignitor and 04 Nos Capacitor b/w busbar and pole wiring by 4 way connector etc including dismental of existing CG box, connection testing & commisioning etc. as required.
Providing and fixing 1.42 mtr x.53 mtr of 2 mm CRCA Sheet door with stainless door hinges hevy duty-03 Nos,steel handle-02 Nos and door lock arrangement with 10 mm stainless steel/MS lenth 7 inch-01 Nos in existing SFP and remove existing hinges , etc as required.
Providing and fixing 0.72 mtr x1.12 mtr of 2 mm CRCA Sheet door with stainless door hinges hevy duty-03 Nos,steel handle-02 Nos and door lock arrangement with 10 mm stainless steel/MS lenth 7 inch-01 Nos in existing SFP and remove existing hinges , etc as required.
Providing and fixing 0.53 mtr x1.12 mtr of 2 mm CRCA Sheet door with stainless door hinges hevy duty-03 Nos,steel handle-02 Nos and door lock arrangement with 10 mm stainless steel/MS lenth 7 inch-01 Nos in existing SFP and remove existing hinges , etc as required.
Providing and fixing 0.34 mtr x 0.64 mtr of 2 mm CRCA Sheet door with stainless door hinges/Bolted screw hevy duty-03 Nos, remove existing hinges , etc as required.
Providing and fixing 0.66 mtr x 0.45 mtr of 2 mm CRCA Sheet door with stainless door hinges/Bolted screw hevy duty-03 Nos, remove existing hinges , etc as required.
Providing and fixing 0.75 mtr x 0.46 mtr of 2 mm CRCA Sheet door with stainless door hinges/Bolted screw hevy duty-03 Nos, remove existing hinges , etc as required.
Providing and fixing 1.5 mtr x 0.53 mtr of 2 mm CRCA Sheet door with stainless door hinges/Bolted screw hevy duty-03 Nos, remove existing hinges , etc as required.
Providing and fixing .25 mtr x 0.38 mtr of 2 mm CRCA Sheet door with stainless door hinges/Bolted screw hevy duty-03 Nos, remove existing hinges , etc as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed I XLPE aluminium conductor cable of 1.1 kV grade as required. Make- Jainsons/VIB/ Dowells
3.5 x 35 sqmm(32 mm)
3.5 x 95 sqmm(45 mm)
Supplying and Laying of one number 3.5 x 35 SQ mm PVC sheathed XLPE power Aluminum cable of 1.1 KV grade in the 63 mm dia DWC HDPE pipe as required. ( Make - havells/ polycab /KEI/FINOLEX/ANCHOR)
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
Applying priming coat:With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade at Existing Panel sheet on both side. Two or more coats
Earthing with GI earth pipe 4.5 mtr. Long 40mm dia including accessories & providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. (But without charcoal / coke and salt) as reqd.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing door lock arrangement with 10 mm stainless steel/MS lenth 7 inch-01 Nos,03 Nos Hinges with 02 Nos Handle in existing SFP/MFP and remove existing hinges , etc as required.
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Providing and fixing following rating and breaking capacity MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
100 Amp, 30 KA 4 Pole
200 Amp, 36 KA 4 Pole
Providing and fixing following rating and breaking capacity MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.63 Amp, 25 KA 4 Pole(50%)
shivalaycorporation
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .