Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹56.8 LAccepted-AOC UPPER BAZAAR BHAWARNA TEHSIL PALAMPUR DISTT KANGRA H P | ₹56.8 L | L1 | Accepted-AOC Lowest Amount |
| 2 | L2₹57.1 LRejected-Finance VILLAGE KALEHALI PO BAJAURA THE BHUNTAR DISTT KULLU HP | BHUNTAR | KULLU | HIMACHAL PRADESH | ₹57.1 L | L2 | Rejected-Finance Higher rate |
| 3 | L3₹82.5 LRejected-Finance NIL | ₹82.5 L | L3 | Rejected-Finance Higher rate |
| Rank | Bidder | Quote | Total Amount |
|---|---|---|---|
| - | Novelty Enterprises Bid ID 593099 | 15% above | ₹87,31,176.33 |
| - | VINAY ENTERPRISES Bid ID 592038 | 8.62% above | ₹82,46,785.85 |
| - | DILE RAM Bid ID 593353 | 13.05% below | ₹66,01,528.54 |
| - | Bidder Name | - | - |
| L2 | VINAY ENTERPRISES ( Bid ID 592038 | - | ₹82,46,785.85 |
| L3 | Novelty Enterprises ( Bid ID 593099 | 56,77,528% above | ₹87,31,176.33 |
| L1 | DILE RAM ( Bid ID 593353 | 57,10,528% above | ₹66,01,528.54 |
Tender Value
₹75.9 L
EMD Value
₹75,923
Closing Date
12 Dec 2025, 12:00 pmClosed
CE Operation M. Zone HPSEBL Mandi.
O/o CE Operation M. Zone HPSEBL Mandi.
Tender for, Reconstruction of 11 KV Malana spur of 11 KV Jari feeder from Chowki to Dam site washed away due to flash flood ( Cloud Burst ) during July 2023 under ESD ,HPSEBL, Jari .
2025_HPSEB_122715_1
HPSEBL/CEOMZ/MM/NIT-32/2025-26
Open Tender
Electrical Works
180 days
Mandi
Please refer Tender Documents
11 documents required · 11 mandatory
₹1,180
₹75,923
27 Jan 2026
5 Dec 2025
15 Dec 2025
5 Dec 2025
12 Dec 2025
5 Dec 2025
11KV HT Line (Supply Part)
Supply of 9.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980 (Part-'A') as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-47
Supply of 10.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980 (Part-'A') as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-47
Supply of RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if any
Supply of ACSR conductor of size 6/1/3.35 mm (50mm2) conforming to IS-398 (Part-II)/1996 with upto date amendments
Supply of 11 KV Disc insulator B&S type conformimg to IS-731/1971 all latest version thereof for suspension & tension string ball and socket type having pin ball. The minumum and maximum creepage distance with diameter of insulator- 225 mm & having electromechanical strength 90KN. The insulator shall have W type phosphors bronze security clips for ball socket porcelain conforming IS: 2486-1971 (90KN) complete in all respect. Moderately polluted atmospheres Creepage distance 320mm
Supply of 11 kV Pin Insulator Brown Glazed Porcelain insulator alongwith GI Pin confirming to IS-731/1971 or latest version thereof with minimum and maximum creepage distance & duly fitted with lead/zinc thimble suitable for use with GI forged pin having small steel head as per IS:2486 (Part-I & II) of 1993 & latest amendment if any. Moderately polluted atmospheres Creepage distance- 320mm
Supply of MS Channel 100x50x6 mm Cross Arm: Fabrication and supply of Cross arms suitable for 11 KV made of only TATA/SAIL/RASHTRIYA ISPAT M.S. Channel Iron 100x50x6 mm Cross Arm, suitable for fixing on both Steel and PCC Poles whatever is required single/double pole structure of 11KV line with holes at suitable places wherever required to adjust 5/8” dia nuts and bolts, pin insulators, ball cleaves, eye socket and washers. The weight of MS channel should be strictly 9.56 Kg per meter with a variation of +/-5%. The Cross Arm should be duly painted with two coat red oxide paint of superior quality:
2340 mm long
1500 mm long
1270 mm long
Supply of MS Channel 75x40x6 mm Cross Arm: Fabrication and supply of Cross arms suitable for 11 KV made of only TATA/SAIL/RASHTRIYA ISPAT M.S. Channel Iron 75x40x6 mm Cross Arm, suitable for fixing on both Steel and PCC Poles whatever is required single/double pole structure of 11KV line with holes at suitable places wherever required to adjust 5/8” dia nuts and bolts for supporting GO Switch / DO Fuse units. The weight of MS channel should be strictly 7.14 Kg per meter with a variation of +/-5%. The Cross Arm should be duly painted with two coat red oxide paint of superior quality:
2800 mm for G.O. Switch and D.O. Fuse Unit
Supply of 11KV 400 A, 25kA G.O. switches complete with manually operated equipment and accessories required for their satisfactory operation for their use on distribution sub-station and tapping /sectionalizing points of 11 KV lines.
Supply of 11KV, outdoor, open, dropout (D.O.) explusion type fuse units, complete with manually operated equipment and accessories required for their satisfactory operation for their use on distribution sub-station and tapping /sectionalizing points of 11 KV lines.
Supply of HT Stay Set complete including, Guy Assembly, Helically fitting & stay wire @ 10.00 kg per stay set (Supply of Galvanized Stay Strand conforming to ISS-2141/1992 Edition 2002-05 (with upto date amendments) with heavy coating Zinc hot Dip Galvanized as per ISS-4826/1979 (2001-06) (latest)of following grade and size:- Grade -4 Size 7/3.15mm (7/10SWG) )
Supply of Knee bracing set 2(750x50x50x6) mm
Supply of Cross bracing set for DP 2(2125x50x50x6) mm
Supply of Belt set for DP 2(1800x50x50x6) mm
Supply of Earthing set suitable for HT line/Earthing of metering unit made of GI pipe 40 mm dia (internal dia) wall thickness 3.25 mm medium quality pipe of standard make conforming to IS: specifications 2500 mm long with GI Socket closed at top pipe shall have holes of 12 mm dia every 150 mm apart throughout the length and staggered diameterically. Full clamps of MS Flat 40x3 mm fitted at top end of the pipe along with bolts and nuts size 50x12 mm and washers for fixing the clamp on the pipe. The bottom end of the pipe shall be tapered cut at 45 degree.
Supply of eye hook for earth wire
Supply of Galvanised Mild Steel wire conforming to ISS-280/1978/2006 (with up to date amendments ) for general engineering purpose, having fine finish, hot dip galvanised, with heavy coating of Zinc as per ISS-4826/1979 (2001-06)(latest) in soft condition and of size 4.06 mm (8 SWG).
Supply of Danger Plate Size: 250x200x1.6 mm made of mild steel plates 1.6 (minimum) thick vitreous enameled white letter figure, conventional skill and X-Boxes and signal red colour on front side for use in HPSEBL. The rear side of the plate shall be black enameled and conforming to IS specifiction no. IS-1351/1982 suitable for 11KV
Supply of M.S. Hexagon Bolts and Nuts with washers conforming to ISI-1363-1992 off size
Supply of Galvanised steel barbed wire of 9.8 kg /100metre
Supply of Top Clamp
Supply of Half Clamp (MS Flat 50x6mm)
Supply of Full Clamp (MS Flat 50x6mm)
Supply of Aluminium Paint for all poles and steel fitting
11KV HT Line (Erection Part):-
Manual Carriage of material (AVERAGE LEAD=0.500Km), Qty=0.500x6.815= 3.408Km
Erection of steel tubular pole (Single pole str) digging of pit, Drilling of holes in X-arm, Erection of pole, Fixing of insulator X-arm, Fixing of barbed wire danger plate , Concreting of RCC Muff, Filling of pit+ramming, painting of pole and all steel items (Punching of the poles is stricitly not allowed)
Erection of steel tubular pole (double pole str) digging of pit, Drilling of holes in X-arm, Erection of pole, Fixing of insulator X-arm, Fixing of barbed wire danger plate , Concreting of RCC Muff, Filling of pit+ramming, painting of pole and all steel items (Punching of the poles is stricitly not allowed)
Erection of steel tubular pole (Triple pole str) digging of pit, Drilling of holes in X-arm, Erection of pole, Fixing of insulator X-arm, Fixing of barbed wire danger plate , Concreting of RCC Muff, Filling of pit+ramming, painting of pole and all steel items (Punching of the poles is stricitly not allowed)
Erection of ACSR Conductor of size 6/1/3.35 mm (Laying, Stringing, sagging & Binding with Insulator)
Erection of GI wire
Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
Erection of GO switch
Erection of DO fuse unit
Erection of Stay Set HT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.33 MB
SBDNIT32.rar
Tender Documents • 5.14 MB
Tecspc.rar
Tender Documents • 32.56 MB
GuidelineforERA.pdf
Additional Documents • 2.33 MB
BOQ_180078.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid