Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.0 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹33.0 L+₹2.0 L (6.45%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical Not enlisted in Category b(ii) | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlisted in Category b(ii) |
Tender Value
Refer Docs
EMD Value
₹64,000
Closing Date
21 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) Chandigarh
HQ CWE(AF) Chandigarh PIN-160003
AUGMENTATION OF POWER SUPPLY TO CATER NEW PROJECTS/UPGRADATION AT AF STN KASAULI
2023_MES_598093_1
CWE/AF CHD/CHD/T-54/2022-23
Open Tender
Civil Works
Item Rate
180 days
Chandigarh
As per NIT
7 documents required · 7 mandatory
₹500
GE(AF) Chandigarh
₹64,000
7 Aug 2023
24 May 2023
28 Jun 2023
24 May 2023
21 Jun 2023
7 Jun 2023
Amount
EXTERNAL ELECTRIFICATION
Dismantling of existing Transformer 250 KVA by mechanical means i.e. Crane etc and depositing to MES Store yard complete all as specified and directed by Engineer-in-Charge
Supply , installations, testing and comissioning of indoor type oil immersed naturally cooled (ONAM) transformer copper wound type of capacity 500 KVA as per IS 1180 level 2 and IS-2026 with off load changer on primary side to vary secondary voltage with in limit (+) 5% to (-) 7.5% in steps of 2.5%. The transformer shall be provided with cable termination box to terminate indoor type termination of sutiable size on HT side 11KV & LT side 1100 V Transformer step down ratio 11000 Volts/433 Volts, 3 Phase 4 wire, impendance as per IS. Oil type ONAM cooled suitable for indoor installation and double wound core type with cold rolled grain oriented silicon shell insulated laminations and clamped to minimize vibrations and noise. The winding shall be copper and shall be designed for full load current and withstand the thermal and electro magnetic stresses arising due to the through fault current vector groups shall be DYn 11 including supply of all standard fittings/ fixture and comprising of the following all as specified and directed: (a) HT cable termination box (b) LT cable termination box (c) Rating and diagram plate (d) Earthing terminals (e) Lifting lugs (f) Oil level indicator with minimum level marking (g) Thermometer pockets (h) Conventional conservator with oil filling hole with cap and drain plug (j) Air release plug (k) Silica gel breather (l) Off circuit tap changer (m) Bi-directional rollers (n) Jacking pads (o) Radiators/ fins (epoxy painted) Note : Pre dispatch inspection of transformer shall be carried out by the Rep of Accepting officer. All factory inspeection arrangments will be co-ordinated by the contractor
Supply, laying and testing PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq. mm 3.5 Core, complete all as specified and directed by Engr- in-charge .
Supply, laying and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 120 sq. mm 3 Core, complete all as specified and directed by Engr- in-charge .
Supply and laying GI Tubing light grade 80 mm bore of pipe for cable protection, complete all as specified and directed by Engr- in-charge .
Supply and laying GI Tubing light grade 50 mm bore of pipe for cable protection complete all as specified and directed by Engr- in-charge .
Supply, fixing tetsing and commissioning Voltage stabilizer for automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 1% and speed of correction 50 Volts per second and of capacity 500 KVA, complete all as specified and directed by Engr-in-Charge.
Supply, fixing tetsing and commissioning Voltage stabilizer for automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 1% and speed of correction 50 Volts per second and of capacity 50 KVA, complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel with including 40mm dia bore GI tubing light grade as protection pipe complete all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion, complete all as specified and directed.
Supply and installations of LT Cubical panel indoor type ( C.P.R.I Approved) made out of 2mm Thick sheet, front and back openeable, 3 Phase, 415 V, AC Supply, 50 HZ, dust weather and vermin proof, Bus bar Aluminum 1200 Amp, 4 pole, mounted on SMC supports in seperate compartement covered from all sides. Incoming and outgoing MCCB links shall be powder coated seamen's grey shade RAL 7032. Power Control wiring shall be copper conductor, L. T. Panels shall be SMS Panels & Switchgears are Followings: (a) ACB 800A, 4P, 50KA-01 or equivalent model of make specfied here-in-after. (b) ACB 250A 4P, 35KA -03 or equivalent model of make specfied here-in-after. (C) R.Y.B Indicating Lights -03. (d) Digital volt meter in built seleactor switch-01 (e) Digital amp. meter in built seleactor switch-01 (f) MCB 6 amp.SP 10 KA -03. (g) C.T.s 0-400 amp-03 .
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sq mm, complete all as specified and directed and as per direction of Engr-in-Charge..
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable, complete all as specified and directed by Engr in charge.
M&L for Cable jointing kit for 1100V (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable 120, complete all as specified and directed by Engr in charge.
Ayushmat Contractors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .