Executive Engineer ED Bijbehara
Executive Engineer ED Bijbehara
Execution Installation of HT Meter 11/0.433 KV,250 KVA Substation at JNV Aishmuqam
2025_PDD_296933_1
EDB/e-tender/68 of 2025-26
Open Tender
Electrical Works
Turn-key
60 days
Executive Engineer ED Bijbehara
Please refer Tender documents.
6 documents required · 6 mandatory
₹200
Executive Engineer ED Bijbehara
₹3,900
1 Dec 2025
1 Dec 2025
23 Dec 2025
1 Dec 2025
22 Dec 2025
1 Dec 2025
1 Dec 2025 - 20 Dec 2025
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Executive Engineer Electric Division Bijbehara
Name of Work: Execution/Installation of HT Meter 11/0.433 KV,250 KVA Substation at JNV Aishmuqam
Contract No: EDB/e-tender/68 of 2025-26 Dated:-01-12-2025.
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description (As Per Latest REC/ IS Standards) Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder inclusive of all taxes and duties Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT inclsuive of all Taxes & duties Rs. P TOTAL AMOUNT inclsuive of all Taxes & duties Rs. P TOTAL AMOUNT In Words
1 Execution/Installation of HT Meter 11/0.433 KV,250 KVA Substation at JNV Aishmuqam
11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No G.I channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door. BI01010001010000000000000515BI0100001114 1 job 101 Excess(+) Full Conversion INR
Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5 The CT ratio shall be as under: 20/5 for 250kVA DT BI01010001010000000000000515BI0100001115 1 job 102 Excess(+) Full Conversion INR
11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase and accuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23kV pf for one minute. BI01010001010000000000000515BI0100001116 1 job 103 Excess(+) Full Conversion INR
Bus Bar details: CTs bus bar:- 40x6 mm copper strip or adequate size PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size duly insulated by the monoplast tape BI01010001010000000000000515BI0100001117 1 job 103 Excess(+) Full Conversion INR
d)1 lot PVC copeer wire flexible multi-standard of required size for secondary connections . For CT size the minimum wire size should be 4mm Sq (RYB) and for the PT wiring minimum size shall be 2.5mm Sq (RYB). CT and PT wiring routed through separate rigid G.I Conduit. BI01010001010000000000000515BI0100001118 1 job 104 Excess(+) Full Conversion INR
PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm² (RYB) and for PT wiring minimum wire size shall be 2.5 mm² (RYB). BI01010001010000000000000515BI0100001119 1 job 105 Excess(+) Full Conversion INR
Copper Lugs preferably ring type duly crimped for termination of wires and tapes BI01010001010000000000000515BI0100001120 1 job 106 Excess(+) Full Conversion INR
DLMS compactable HT, trivector meter 3-phase 4-wire 5amp and 110/63.5 volts. BI01010001010000000000000515BI0100001121 1 job 106 Excess(+) Full Conversion INR
Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm² BI01010001010000000000000515BI0100001122 1 job 107 Excess(+) Full Conversion INR
3Ph3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS 232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. BI01010001010000000000000515BI0100001123 1 job 105 Excess(+) Full Conversion INR
3 Core 11 kV Aluminium cable XLPE armoured 35 mm2 including cost of clamp for its fixing where ever required. BI01010001010000000000000515BI0100001124 20 Mtr 107 Excess(+) Full Conversion INR
Supply and fixing of Heat shirinkable outdoor cable termination kit suitable for 3*35 mm Sq 11kv cable BI01010001010000000000000515BI0100001125 4 No 108 Excess(+) Full Conversion INR 2 Construction of chamber for 100mm sluices valve item3 10 Nos
Earthing by way of 40 mm Dia G.I pipe or 20 mm G.I Rod , 2.5 meter and 25 *25* mm iron plate as per standards for grounding of metering unit. BI01010001010000000000000515BI0100001126 1 Job 111 Excess(+) Full Conversion INR
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
SBD.pdf
Tender Documents • 1.02 MB
StandardDrawings.pdf
Other Document • 36.45 MB
technicalspecifications.pdf
Additional Documents • 5.25 MB
BOQ_962310.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .